Professional Documents
Culture Documents
O & Manual 8-3-2016 ii(1)
O & Manual 8-3-2016 ii(1)
com
:('27$1.6&20//&
43BODIP4BIVBSJUB#MWE4UF
4BIVBSJUB ";
Introduction To Your
Biological Wastewater Treatment System
For:
6HWUDFR1LJHULD/LPLWHG
6(75$&2%XLOGLQJ3ORW
6KHKX<DU DGXD:D\
$EXMD1LJHULD30%*DUNL
23(5$7,21 0$,17(1$1&(0$18$/
Using The
:XKUPDQ%LRORJLFDO1XWULHQW5HPRYDO3URFHVV
:LWK/ the following components
Equalization Tank (1) Sludge Storage/Digester Tank (1)
Aeration Tank ( $QR[LF7DQN )LQDOClarifier (2) DQG
&KORULQH&RQWDFWWDQN
August 4
Tel: 866.374.2083 Fax: 866.681.7694 E-mail: roger@wedotanks.com
1 | Page
TABLE OF CONTENTS
PAGE NO.
General Description:
The system is designed to create a very favorable condition for the growth of organisms to adsorb and
remove the organic waste in the water. The system utilizes the Wuhrman biological process.
Although the Wuhrman process is classed as a nitrifying/denitrifying (N/D) process, post denitrification in the
secondary anoxic reactor allows only limited removal of nitrate. More complete nitrate removal is often achieved
however through carbon dosing of the anoxic reactor.
The limiting factor for denitrification here is the scarcity of organic carbon in the anoxic zone. Denitrification
requires organic carbon to fuel the process, and in this configuration the only organic carbon available comes from
the slow breakdown of dead and dying bacteria which limits the rate of denitrification by a factor of 6-10 compared
to high rate RBCOD driven denitrification.
This process also commonly uses a flash aeration reactor to clean up ammonia and condition (make aerobic) the
mixed liquor by raising its redox potential prior to secondary clarification. Another function of flash aeration is to
remove any bubbles of nitrogen associated with the floc - an issue often caused by the rapid denitrification arising
with methanol dosing.
The organic waste is measured as BOD (Biochemical Oxygen Demand) or the amount of oxygen the
organisms require to reduce the organic wastes in the water to carbon dioxide, water and an increase in the
amount of organisms.
Starting after the inlet connection and as the wastewater treatment plant is laid out:
Secondary Clarifier:
Inlet Feed from Aeration tank
Effluent Trough and Scum Baffle
Side Slope
Return Sludge Pump (0.54 hp)
Scum Skimmer Pump ( 0 . 5 4 h p )
Chlorine tablet feeder (76-757 M3/day
1. PART 2. Description of the Biological
Wastewater Treatment System
Report Title: ĞĚĂƌƐƚĂƚĞƐ͖ďƵũĂ͕EŝŐĞƌŝĂ Wedotanks.com, LLC
Report Created: July ϴ, 2015 ϭϱϵϵϬ^͘ZĂŶĐŚŽ^ĂŚƵĂƌŝƚĂ͕ůǀĚ͘
Plant Description: BNR (Biological Nutrient Removal ^ƚĞ͘ϭϱϬ͕Box Ϯϭϱ
Author: Roger Haag ^ĂŚƵĂƌŝƚĂ͕ϴϱϲϮϵ
Tel.231.354.7375 Fax. 866.681.7694
www.wedotanks.com/www.sassprov2.com E-mail:roger@wedotanks.com
The Nutrient Removal Flow Through (NRFT) plant is based on the Wuhrman
nutrient removal process modified and adapted to small plant operations by
Wedotanks.com, LLC (fka HTI, Inc.).
Wedotanks has a computer program to design and model the operation of a
NRFT plant (Sasspro-see Basis of Design section for simulation of the process and
description of the process used for this WWTP.)
The Wuhrman process was first suggested in 1964. This process depended upon post
denitrification using a secondary anoxic reactor following the aerobic zone. Numerous plants of
this type supplement the nitrogen removal by the addition of an external carbon source such as
methanol which can rapidly and effectively lower the effluent nitrate concentration in the
process effluent. In this plant, methanol will not be used, we are suggesting the operator use a
product called Micro C, which has a COD value of 1,040,00 mg/l and is non-hazardous or
explosive as methanol. Further description available at
http://www.microc.com/product/microc2000.htm
The equalization tank receives all the wastewater after the wastewater flows
through a screening box and the equalization tank contains coarse bubble diffused
aeration for mixing and providing minimum air per 10 States Standards. The flow
from the equalization tank leaves via two (2) 0.54 HP submersible equalization
pumps and a flow splitter box. The submersible equalization pumps are controlled
by floats and alternate operation. The flow is pumped from the equalization tank up
into the box where the flow to the next process tank is controlled and measured by
the flow's level over a V-Notch Weir with the extra volume overflowing from the flow
splitter box back into the equalization tank.
The wastewater from the aeration tank flows by gravity to the anoxic tank
where all the nitrate in the mixed liquor suspended solids, being returned from the
aeration tank, is converted to nitrogen gas and some of the BOD is converted to
carbon dioxide, water and more organisms. 7KHanoxic tank has a HP
submersible mixer capable of 0PLQ generated flow. This equates to
hp/0 generally only 0. hp/0 is adequate for mixing.
The digester receives the excess activated sludge produced in the wastewater
treatment process from the clarifiers via activated sludge return and waste pumps.
5.Clarifiers. ()
ZĞƉŽƌƚdŝƚůĞ͗ĞĚĂƌƐƚĂƚĞƐ͖ďƵũĂ͕EŝŐĞƌŝĂ tĞĚŽƚĂŶŬƐ͘ĐŽŵ͕>>
ZĞƉŽƌƚƌĞĂƚĞĚ͗:ƵůLJϴ͕ϮϬϭϱ ϭϱϵϵϬ^͘ZĂŶĐŚŽ^ĂŚƵĂƌŝƚĂ͕ůǀĚ͘
WůĂŶƚĞƐĐƌŝƉƚŝŽŶ͗EZ;ŝŽůŽŐŝĐĂůEƵƚƌŝĞŶƚZĞŵŽǀĂů ^ƚĞ͘ϭϱϬ͕ŽdžϮϭϱ
ƵƚŚŽƌ͗ZŽŐĞƌ,ĂĂŐ ^ĂŚƵĂƌŝƚĂ͕ϴϱϲϮϵ
dĞů͘Ϯϯϭ͘ϯϱϰ͘ϳϯϳϱ&Ădž͘
www.wedotanks.com/www.sassprov2.com ϴϲϲ͘ϲϴϭ͘ϳϲϵϰ
ͲŵĂŝů͗ƌŽŐĞƌΛǁĞĚŽƚĂŶŬƐ͘ĐŽŵ
All the solids and organisms settle out and are concentrated in the bottom of
the clarifier. The solids are returned to the h e a d o f t h e aeration tank or wasted
to the aerobic digester via a 0.54 HP Return Activated Sludge/Waste Activated
Sludge Pump on a VFD . A three way PDQXDO controlled valve allows the Activated
Sludge to be either returned to the Anoxic Tank via a flow measurement box or
wasted to the Aerobic Digester. Each Clarifier also contains an airlift Scum pump
(2-pumps 1- in the clarifier proper and 1-behind the inlet baffle) which transfers
scum, which has been collected by the skimmer mechanisms, either to the
Digester or back to the head of the aeration tanks.
%JTJOGFDUJPOUBOL
-PDBUFEJOUIFEJTJOGFDUJPOUBOLJTBUBCMFUDIMPSJOBUPSBOEGJOBMFGGMVFOUGMPXCPYUIBUUIF
FGGMVFOUGMPXCFJOHEJTDIBSHFEJTNFBTVSFEBOESFDPSEFEJOUIFDPOUSPMQBOFMGMPXNFUFS
The heart of the control system is twofold. The primary component is the PLC
(process logic controller.) This industrial hardened controller is designed for rugged
continuous duty operation in harsh environment. It is installed in a NEMA 12
enclosure keeping all of the control components dry, clean, and protected from the
environment. The PLC is an Allen Bradley Compact Logic processor designed to
support multiple programing languages and is e-net communications compliant. This
controller supports several thousands of lines of code, much more than this project
would ever require.
The other major component is the interface to the PLC. The interface being
used consists of a local HMI (LCD 1” Graphical Touch Interface), local H.O.A.
switches used for critical pump controls.
The operator can view active data to monitor and make changes to the
following items to list a few:
(IIOXHQW)ORZ9LHZIORZUDWHWUHQGDQGYLHZWRWDOV
0RQLWRUDOOSXPSVWDWHVDQGYDOXHVEHLQJFRQWUROOHGE\WKH3/&
7KHFRQWUROV\VWHPZLOODODUPRXWLQWKHIRUPRIDWH[WPHVVDJHRQ
FULWLFDODQGQRQFULWLFDODODUPVZLWKDVSHFLILFGHVFULSWLRQRIWKHDODUP
VWDWHV7KHQXPEHURIUHFLSLHQWVLVDGMXVWDEOH
7KHDPRXQWRIUHWXUQIORZVDQG'2LVHDVLO\FDOFXODWHGZLWKWKHDLG
RIWKH6DVV3UR90RGHOLQJVRIWZDUHSURYLGHGZLWKWKHSODQWEDVHGRQ
LQIOXHQWIORZDQGGHVLUHGOHYHORIWUHDWPHQWWRREWDLQPD[LPXPEHQHILW
PART 3. Components & Functions
PART 4. Start up Procedure
Start Up Procedure-Switching flow from old plant (Septic Tanks) to new plant
Listed below is the procedure we would like to follow to when bringing flow to the new plant and start up the
new plant.
1. The best method would be to find an existing plant in the area and haul in approximately ¼ of the contents of
the aeration.
2. Turn on the air to the aeration tank and equalization tank. Wait until the clarifier is about full and start the
return sludge pump operating.
3. When there is four feet of sewage in the equalization tank turn on the air and start pumping sewage to the
aeration tank.
4. Once the aeration tank is full and operating for few hours effluent standards should be met within about a30-45
days.
5. If the aeration tank can not be filled to operating level, the blowers should be cycled and if available oxygen
concentration in the aeration tank should be measured and kept below 3 PPM.
The new plant is started.
10/57
PART 5. START UP - ADJUST EQ FLOW BO
8/3/2016 1/2 HTI, Inc.
The equalization tank is designed even the flow out over a 24 hour period. Design is
based on more than 60% of the flow coming into the plant over an eight (8) hour period
during the mid-day period.
1. Check flowmeter strip chart to determine if there is a period of time when the
chart is showing no flow through the plant. Also record the flow for both time
periods the flowmeter is presently set and add the interval flows for a 24 hour
period. The flowmeter is presently set to record the total flow from 7:00 AM to
7:00 PM and from 7:00 PM to 7:00 AM.
2. E.G, if the sum of the flows for these two (2) intervals is 17,350 gallons. What
you want to do is to be able to spread this flow out over a 24 hour period. The
Equalization flow control box has two (2) 600 V-notch weirs to allow flow to go
the Aeration # 1 or Aeration # 2. If only running one aeration train, for the one
that is not operating, the V-notch weir slide gate should be up so no flow goes to
the train that is not in operation.
3. For the train that is in operation, the gallons per minute (gpm) over a 24 hour
period is determined by the following calculation:
17,350 gallons/day ÷ 1,440 minutes/day = 12.05 gpm
Refer to the 600 V-notch weir chart in the O & Manual (a sample of the chart is
shown below) to determine how many inches of flow should be going over the V-
notch weir to get the 12.05 gpm of flow.
From the chart we can see that we should have approximately 0.21 feet (2 ½
inches) of flow over the V-notch weir.
8/3/2016 2/2 HTI, Inc.
4. If the strip chart on the flowmeter is showing that no flow is recorded for example
two (2) hours, then lower the slide gate (gate that allows the excess flow to drop
back into the Equalization tank) on the side of the flow equalization box 4 turns
counterclockwise for each hour the flow meter shows that no flow is going
through the plant. Wait two (2) days to see what if the flow meter is still off for a
period of time. If it is, make another adjustment as described above. The goal is
to get approximately 2½ inches of flow over the V-notch weir for the determined
24 hour period.
5. When more people are being brought into the plant for the shutdown, adjustments
will need to be done on a regular basis to equalize the flow. Once the shutdown is
over and you get back to normal operation. Once the flow box is adjusted; only
minor adjustments will need to be made.
PART 6. SPECIAL MAINTENANCE DURING
START-UP PERIOD
Special Maintenance during Start-up
Common Problems
The purpose of the clarifier is to settle out the MLSS and return the sludge to the aeration tank. One of the
characteristics of activated sludge is it is likely to be stringy and sticky during the early weeks of operation. As it
settles toward the bottom of the clarifier, the operator should keep a close eye to make sure that the solids do not
build up in bottom, of clarifier. If this happens, the RAS return rate should be increased by the return sludge
pump (RAS) by VFD in control panel.
In a few days, the build up of sludge will completely fill the lower half of the clarifier. After a short time
this spongy mass will form gas and break up into chunks of sludge that float to the surface of the clarifier and
may be discharged with the treated water. This solid sludge condition prevents the clarifier from performing
properly. This sludge may also give off a very strong odor.
It is possible for the return sludge pump discharging clear water while there is three or four feet of sludge
in the hopper. This occurs when soft sludge packs solid above the hopper bottom except for a narrow clear
channel running down through the sludge mass to the return sludge pump intake. Clear surface water is pulled
down through this channel and up through the pump without disturbing the sludge mass. It is very important to
always visual check return sludge pump discharge.
Every day during the first few weeks of operation, the plant must be visited to see that all equipment is
running and to check the clarifier and return sludge pump discharge.
After the plant begins to develop a stable culture, this maintenance procedure may be reduced to a weekly
or even bi-weekly practice.
Another common condition is a plugged return sludge pump. The sludge is heavier than water and will
normally settle to the hopper bottom. If the return sludge airlift pump is not returning at least at “one-third of a
full pipe” in the aeration tank, the slower movement of sludge will tend to allow the sludge to pack in the square
area at the hopper bottom at the return sludge air lift pump intake. Finally the sludge begins to build up inside the
pump tube until it is blocked completely. This condition may be remedied by opening running the pump at
maximum speed in the VFD valve to return sludge airlift sludge pump.
If the blockage isn’t removed, then the pipe plug at the “tee” (top of pump) must be removed, and the
horizontal discharge pipe closed off at the tee with a shop rag or plumber’s stopper to divert the air downward
through the vertical pump tube to back flush the pump. This great volume of air should break up the solid mass
which has built up. The chunks that rise to the top must be dipped back into the aeration tank or broken up into
small pieces to be returned by the scum skimmer air lift pump.
During construction and starting, very often mud is allowed to flow into the plant. When mud gets into a
plant, the part that gets into the clarifier will naturally sink to the hopper bottoms. Here it mixes with the sludge
and forms a heavier and more solid mass than sludge alone.
15/57
The sludge return pump will not pump heavy mud. If mud is present, its depth or density may be
determined by this probing action with the scraper. If the mud is not too heavy, it may be removed by stirring
the hopper bottom, trying to mix mud with tank water. The return sludge pump may pump it out as muddy water.
However, if the mud is too deep or too heavy, the clarifier may have to be pumped with a power pump and the
mud cleaned out by hand. If the vertical pump tube becomes clogged with mud it may be necessary to remove
the two inch pipe plug at the “tee” and rod out the tube. Care should be taken to see that air lines to the pumps
do not become clogged or restricted by sludge or mud that might back up through the pump tube. If this occurs
the fittings must be removed and cleaned out. After any cleaning or unstopping operation, be sure to set VFD for
normal operations.
Please call us we will be glad to discuss any problems and help you learn how to properly operate and
care for the plant.
Remember:
A clean, properly cared for plant means fewer repairs, more efficient operation and meeting
effluent limits.
16/57
WITHOUT MAINTENANCE WITH PROPER MAINTENANCE
Floating No Floating
Sludge Solids Sludge Solids
Clarifier Clarifier
Aeration Aeration
Tank Tank
FIGURE 1 FIGURE 2
Sludge accumulation as shown in left hand view must be gently scraped toward hopper bottom so that sludge return pump will pick it
up as in right hand view. Watch discharge pipe to determine correct flow. Pipe should run about “1/2 of a pipe full” in most cases.
Continue scraping procedure at short intervals to allow sludge to be picked up by the pump. Sludge break-up must be done gently or it
will rise to surface in chunks. If this occurs, the floating chunks must be broken up with a stick or paddle into small pieces for the
skimmer to pick up and return to aeration tank. When scrapping the clarifier, open the air line valves to the skimmer and sludge return
pump.
16/101
PART 7. MOST COMMON PROBLEMS AND
PRACTICAL SOLUTIONS
Most Common Problems and Practical Solutions
2. Excessive foaming:
a. Spray pump motor not running - check power supply and push reset buttons
b. Spray pump motor running but not pumping - pull pump and clean pump screen
c. Spray pump pumping but sprays not operating properly - remove spray nozzles and clean.
a. Return sludge air lift pump not operating or at too low of a rate. Check air lines and pump tube for
blockage.
b. Plant overloaded - check sewage flow and volume and have raw sewage analyzed for BOD and
suspended solids.
Note: Refer to equipment manufacturers bulletins for more specific maintenance and operating instructions.
17/101
ITEM 8. PLANT MAINTENANCE SCHEDULES
Plant Maintenance Schedules
General
1. Be sure that top of tank walls are always sufficiently above finished grade to prevent surface
water from entering plant.
2. It is recommended that fence, grating, railing or other safety devices be installed around the plant.
3. Keep tanks completely free of debris, such as sand, gravel, rocks, leaves, etc.
4. Check oil level in blower before starting up. (Blower shipped without oil.)
5. Be sure that pump rotation is in correct direction before starting up pumps.
6. Scum skimmer air lift pipe in clarifier should be adjusted so that water will be about 3/8” to 1/2”
deep in the skimmer notch. Adjust air valve so that water is drawn down about 3” in the skimmer
pipe for maximum skimming so a minimum water volume is returned to the aeration tank.
1. Make a daily visual inspection of the plant to be sure that all mechanical equipment is operating.
2. Rake bar screen and dispose of the screenings.
3. Check to see that there is equal air distribution along entire length of aeration tank.
4. Check to see that return sludge pumps are returning sludge to the aeration chamber.
5. Check to see that scum skimmer pump skimmer is working.
6. Check chlorine table dispenser for proper operation. Add chlorine tables when needed.
7. Check and break up scum, in settling tank to insure proper return through scum skimmer pump.
1. Thirty minute settling test (Activated Sludge Volume Test) - collect one sample from
aeration tank and one from the effluent from the clarifier. (Follow Easy To Operate
Instructions)
2. Clean accumulated solids from inlet.
3. Clean the grease and floating solids from walls and water surface of aeration tank and clarifier.
4. Checks all equipment to see if it is operating properly and if any fuses are blown or circuit breakers
opened.
5. Clean the growths and accumulated solids from weirs and pipe inlets.
6. Check to see if diffusers all working properly and not plugged.
7. Check to see if return sludge pump or scum skimmer pump for clogging.
8. Refill chlorine table dispenser.
9. Run pH and residual chlorine test; run dissolved oxygen test.
10.Scrape wall and hoppers of settling tank (See Special Maintenance Section)
ITEM 9. MICROSCOPIC EXAMINATIONS
21/80
22/80
ITEM 11. VISUAL AND OPERATING CHECKLIST
Visual and Operating Check List
1. All equipment Air bubbles rising. Surface clear to a Clear, sparkling. All good - continue same
operating Chocolate color. depth of 18 or No solids. operation.
properly Little or no foam. more inches. More than 1 PPM.
20% - 50% solids. DO
More than 1PPM
DO
2. Same Few or no air Dark and murky Murky, Odor, Check for major air
bubbles rising. High Solids. leaks. When
Black color. corrected aerate
No DO continuously until
brown color and DO
return.
Then return to time clock
operation.
4. All equipment Air bubbles rising. Murky, no visible Murky high solids Overaeration- plant is
operating Light muddy color sludge blanket. running too much.
too much foam .5%- Floating sludge in Reduce running time to
15% solids Murky some areas. minimum necessary to
supernatant poor maintain brown color
separation of liquids common during start-up
and solids. period. Use commercial
defoamer if necessary.
5. All equipment Air bubbles rising Murky large Murky High solids Probably due to
operating Chocolate or gray chucks of floating inadequate sludge return-
properly color 10%- 25% sludge scrape tank more often-
solids 1-3 PPM DO check return pump
(should be returning 1/3
pipe full)(See special
Maintenance
Section)Also, See item 4
on check list
6. Same Air bubbles rising. Clear at surface Not murky May be due to excessive
Chocolate color visible sludge Excessive solid sludge return and/or
23/80
20-50% solids blanket 12" or so particles, DO skimming (See Special
1-3 PPM DO below surface. approximately 1 Maintenance
PPM Section).Possibly due to
inadequate return (See
item 5). Also may check
BOD and flow -plant
may be overloaded.
7. All equipment Same Much floating Clear, no solids. May be due to clogged
operating material C.0. more than l or improperly set
properly except PPM. skimmer-adju st or
skimmer unclog. (see special
maintenance section)
8. All equipment Same Same as item 5 Same as item 5 Probably due to clogged
operating sludge return – lower
properly except skimmer(See Special
sludge return Maintenance Section)
pump
9. Equipment same as item 2 Same as item 2 Same as item 2 Possible failure of PLC
will work on time clock -have
manual but not electrician check.
on automatic Overload may be
released-push reset
11. All Air bubbles rising Murky, Brownish- Murky, excessive Possible excessive
equipment Light muddy color. yellow floating solids. amounts of grease
operating Yellow foam, grease greasy sludge, coming into plant -check
properly balls, No DO excessive grease grease trap-remove
grease before it gets to
the plant.
24/80
ITEM 13 & 14. SIMPLE CALCULATIONS W/
FLOW DIAGRAM AND V-NOTCH WEIR
TABLES
Simple Calculations:
• Flow=24,000 GPD
• 24,000/1440 = 16.67 gpm
• Go to V-notch weir table (at end of this section)
for 90 deg. Weir=2.25” flow over weir.
• Flow = 50,000 GPD
• 50,000 gal/1440 min/day=34.72 gpm
25/57
RAS/WAS Flow Boxes
26/57
ITEM 15. OPERATION THE “EASY WAY”
27/80
28/80
29/80
AARELL
AARELL T HE A ARELL C OMPANY
1100 EAST BIG BEAVER ROAD, TROY, MICHIGAN 48083-1934
Phone: 248-649-3810 Fax: 248-649-3845
www.aarell.com
WeDoTanks.com, LLC
15990 S. Rancho Sahuarita, Blvd.
Ste. 150, Box 215
Sahuarita, AZ 85629
Contents:
INTRODUCTION ......................................................................................................................................1
PLANT DESIGN .......................................................................................................................................2
1. EQUALIZATION TANK (30.57 M3).........................................................................................................2
2. AERATION TANK (125 M3) ..................................................................................................................3
3. ANOXIC TANK (44.5 M3) .....................................................................................................................3
4. RE-AERATION TANK (10.5 M3) ............................................................................................................3
5. CLARIFIER TANK (13.37 M3) ...............................................................................................................3
6. DISINFECTION TANK (8.83 M3)............................................................................................................4
7. AEROBIC DIGESTER (33.3 M3) ............................................................................................................4
CONTROLS AND INSTRUMENTATION .................................................................................................5
INFLUENT SCREENING BOX .....................................................................................................................5
CHEMICAL FEED TANKS ..........................................................................................................................5
VARIABLE FREQUENCY DRIVES (VFD) ....................................................................................................5
ACROSS THE LINE STARTERS (ATL) .......................................................................................................5
FLOAT SWITCHES (TEAR DROP) ..............................................................................................................5
MOTORIZED DIVERTING VALVE ................................................................................................................5
EFFLUENT WEIR FLOW MONITOR ............................................................................................................6
MANUAL FLOW BOXES............................................................................................................................6
TABLET CHLORINATOR ...........................................................................................................................6
OPERATOR INTERFACE SCREENS......................................................................................................7
MAIN OVERVIEW SCREEN........................................................................................................................7
SYSTEM SECURITY ..................................................................................................................................8
MOTOR AND VALVE STATUS SCREEN ......................................................................................................8
EFFLUENT FLOW MONTHLY TOTALS SCREEN ........................................................................................10
TYPICAL AERATOR MOTOR POP-UP SCREEN .........................................................................................11
TRANSFER PUMPS MOTOR POP-UP SCREEN..........................................................................................12
ANOXIC MIXER MOTOR POP-UP SCREEN ...............................................................................................13
TYPICAL CHEMICAL FEED PUMP MOTOR POP-UP SCREEN .....................................................................14
TYPICAL CHEMICAL TANK MIXER MOTOR POP-UP SCREEN ....................................................................15
ALARM LIST.......................................................................................................................................16
ALARM TEXT NOTIFICATIONS ................................................................................................................16
ALARM STATUS SCREEN .......................................................................................................................17
ALARM HISTORY SCREEN .....................................................................................................................18
ABOUT SCREEN ....................................................................................................................................19
INTRODUCTION
The Aarell Company is a ‘Control Systems Solution Provider’ located in Troy, Michigan, USA. Aarell
has designed this custom control system for Roger Haagg from ‘WeDoTanks, LLC’ in cooperation with
Goyette Mechanical. This system is specifically designed for control and monitoring of the wastewater
treatment plant that has been designed for Cedar Estates in Abuja, Nigeria.
The control system is designed using an Allen Bradley ‘CompactLogix’ Programmable Logic Controller
(PLC) that supports multiple languages to include; Ladder Logic, Function Block, Structured Text,
Instruction List and Function Chart. A combination of Ladder Logic and Function Block has been used
for this systems control logic. A 10 Inch Color Graphic Touch Screen Human Machine Interface (HMI)
known as the Allen Bradley PanelView has been used to provide the operator interface to the controls
and monitoring. The control panel is built to NEMA 12 standards for mounting in the control room and
provides protection for the environment to the controls clean, cool and dry. The Control Panel includes
hardwired selector switches and status pilot lights to supplement the control functionality included on
the HMI screens. The HMI Screens can be viewed remotely over the facility Ethernet network and a
‘Netbiter’ modem will provide text messages that can be sent to specific cell phones on alarm
conditions.
The Waste Water Treatment system is designed as a Nutrient Removal Flow Through (NRFT) system
design based upon the Wuhrman nutrient removal process as modified and adapted to small plant
operations by Wedotanks.com, LLC. Wedotanks utilizes their specialized computer program to design
and model the operation of an NRFT plant (Sasspro – Refer to WeDoTanks’s Basis of Design
document for simulation and description of the process used for this WWTP).
The Wuhrman process was first suggested in 1964. This process depended upon post denitrification
using a secondary anoxic reactor following the aerobic zone. Numerous plants of this type supplement
the nitrogen removal by the addition of an external carbon source such as methanol which can rapidly
and effectively lower the effluent nitrate concentration in the process effluent. In this plant, methanol will
not be used, we are suggesting the operator use a product called Micro C, which has a COD value of
1,040,00 mg/l and is non-hazardous or explosive as methanol. Further description available at
http://www.microc.com/product/microc2000.htm
The following sections of this narrative provide a guide to the controls and settings that are provided
through the control panel and the Color Graphic HMI Operator Interface.
PLANT DESIGN
Four (4) float switches are provided in the equalization tank for pump control and alarming. As the level
rises the bottom float will allow the pumps to operate. The next float will cause the ‘lead’ pump to start.
If the level continues to rise the third float will be actuated and start the ‘lag’ pump. If the level
continues to rise the fourth float is triggered and a high Level Alarm will be annunciated. As the level
begins to drop down the pumps will continue to run until the level reaches the lowest float and then both
pumps are shutoff.
If Auto Rotate is selected (see the Pump Control pop-up screen) then when both pumps are off the
Lead and Lag selections will rotate so that the pumps start in the opposite order. This rotation function
can be disabled if it is desired to have the Lead/Lag selection remain consistent.
The submersible equalization pumps are controlled by Variable Frequency Drives (VFD) for smooth
operation and speed setting. The flow is pumped from the equalization tank up into the flow box where
the flow is split to the Aeration Tank and to the Anoxic Tank. The flow is measured and adjusted by the
level over a V-Notch flow Weir with the extra volume overflowing from the flow splitter box back into the
equalization tank.
In the aeration tank all of the ammonia is converted to nitrate and all the remaining BOD is converted to
carbon dioxide, water and other organisms. The flow then continues on by gravity to the Anoxic Tank.
The Clarifier Tank has both a Scum Return Pump and a Sludge Return Pump. The scum pump is
operated to transfer surface scum back to the Aeration Tank as Return Activated Sludge (RAS) or to
the Aerobic Digester as Waste Activated Sludge (WAS). The flow path is manually selected by the
operator through hand valves. The Sludge Return Pump draws from the bottom of the clarifier and
transfers solution through an automatic diverting valve. The flow path is configured by using the on/off
timer functions in the PLC settable through the HMI. The ON Time returns the sludge as RAS and the
OFF Time diverts as WAS based on the time cycles. This time cycle will likely be set to divert to
wasting for six minutes (360 seconds) out of every four hours (14,400 seconds). As an example:
4 hours
240 60 minutes 6 minutes
14,400 60 seconds 60 seconds
360 Minus OFF Time 360 OFF Time
14,040 ON Time
The amount of return flow is easily calculated with the aid of the SassProV2 Modeling software
provided with the plant.
The flow through the tank will overflow to the Disinfection Tank.
A High Level alarm float is provided to alert the operator that the pump out schedule is overdue.
A chemical feed pump is provided for each tank and is also equipped with an on/off cycle timer in
addition to the local volume adjust on the feed pump.
This motorized actuator is powered by 120Volts A.C. to open and to close. Without power to the
actuator it will remain in its last position. This actuator is designed to operate in harsh environments.
The weir is provided with a 30 degree ‘V’ Channel discharge baffle. The level transmitter is
characterized to an output flow range of from 0 to 110 GPM (30 M3/HR) based on the height of the
effluent in the channel leading to the 30 Degree ‘V’ baffle.
IN CM GPM M3/HR
8.00 20.320 110.00 29.98
7.80 19.812 103.30 23.46
7.20 18.288 84.60 19.21
6.60 16.764 68.06 15.45
6.00 15.240 53.63 12.18
5.54 13.716 41.21 9.36
4.80 12.192 30.70 6.97
4.20 10.668 21.99 4.99
3.60 9.144 14.96 3.40
3.00 7.620 9.48 2.15
2.40 6.096 5.43 1.23
Tablet Chlorinator
Though the is a significant contributor to the quality of the effluent there are no automated controls
provided or required for this.
The System Overview screen is the screen that would normally be displayed since it presents the most
complete view of the system and the equipment status. Motor running states are shown as green
motors. Off state is grey. Fault status is red.
The status of the float switches is animated and self explanatory. The flow path for the Sludge Transfer
Diverting valve is shown with the green status being the flow path. The present effluent flow rate is
displayed.
Keys in the lower right corner provide additional screen navigation while ‘hot key’ target zones in the
overview will provide pop-ups for additional operational intervention. More on this in following sections.
If a fault occurs a banner will display at the top of the screen as shown below. The alarm can be
silenced and acknowledged from the banner.
System Security
The graphic screens are accessible by any one who can gain access to the control house. The building
should be secured to prevent entry by unqualified personnel. From a system security standpoint there
are certain functions that we don’t want un-trained visitors to the graphic screen changing and therefore
these functions are disabled without the correct Login user name and password entered. If you are
reading this document you are deemed to be at a sufficient level that access to these functions would
not adversely effect the overall operation of the system. Please use both the user name and the
password as op1 to gain access to those features such as clearing runtime accumulators and setting
on/off cycle times.
A screen is provided that summarizes all of the motor and valve status and on/off time cycle
configurations in one place. The complete Configuration for any device can be accessed by pressing
the SETUP key associated with it.
An Effluent Flow monitoring and diagnostic screen is provided which shows the configuration for the
transmitter, the present flow rate, totalized data and access to log files, along with a flow trending
window.
Effluent flow logs can be accessed from the Effluent Flow Screen. This provides a twelve month log file
showing the daily flow totals for the previous twelve months. These are non-resettable registers but
they are written over with the current months data.
The picture above shows the ‘Pop-up’ that will display when the screen is touched in the area of an
aerator motor. Complete control and monitoring is provided through this pop-up. The motor can be
placed in manual to run or disable. Runtime hours are displayed in both a resettable register and
totalizing register. The On/Off Cycle timer settings and progress indicator is shown as a bar graph.
Light green is the On Time Setting while grey is the Off Time Setting. The darker green bar that
displays below the graph represents the accumulating time and the resulting status. The cycle timer is
the sum of the On Time and the Off Time. For example; If it was desired to operate a motor for ten
seconds out of every minute then the On Time would be set to 10 seconds and the Off Time would be
set to 50 Seconds for a total cycle time of 60 seconds.
Note that an Off Time setting of zero will cause the device to be ON continuously no matter what the
On Time setting is. The runtime accumulator, resettable totalization and on/off cycle time settings
require the user to be correctly logged-in in order to reset or modify the settings.
The Pop-up for the Equalization pumps is shown. HMI Manual functions are provided. Runtime hours
are displayed. The ‘Lead’ and ‘Lag’ selections are provided and can be rotated from this screen. The
pump controls will normally rotate the lead and lag pump selections each time both of the pumps are
off. If this is not desired for any reason the Auto Rotate can be Disabled. This will cause the Lead and
Lag selections to stay fixed as selected.
The runtime accumulator, resettable totalization and on/off cycle time settings require the user to be
correctly logged-in in order to reset or modify the settings.
The picture above shows the ‘Pop-up’ that will display when the screen is touched in the area of the
mixer motor. Complete control and monitoring is provided through this pop-up. The motor can be
placed in manual to run or disable. Runtime hours are displayed in both a resettable register and
totalizing register. The On/Off Cycle timer settings and progress indicator is shown as a bar graph.
Light green is the On Time Setting while grey is the Off Time Setting. The darker green bar that
displays below the graph represents the accumulating time and the resulting status. The cycle timer is
the sum of the On Time and the Off Time. For example; If it was desired to operate a motor for ten
seconds out of every minute then the On Time would be set to 10 seconds and the Off Time would be
set to 50 Seconds for a total cycle time of 60 seconds.
Note that an Off Time setting of zero will cause the device to be ON continuously no matter what the
On Time setting is. The runtime accumulator, resettable totalization and on/off cycle time settings
require the user to be correctly logged-in in order to reset or modify the settings.
The chem. Pumps also have a time cycle adjustment but it will be preferable to first set the flow rate at
the pump head. The runtime accumulator, resettable totalization and on/off cycle time settings require
the user to be correctly logged-in in order to reset or modify the settings.
The Chem Tank Mixers are the same for time cycle control.
ALARM LIST
The following alarm messages can be triggered by the system based on actual conditions for the
equipment and the response to a control request.
The unit is tested with a local service providers SIM chip during the Factory Acceptance Testing in
Troy, Michigan. A local SIM chip will need to be installed after delivery to the final destination. The
configuration for the text messaging is a cloud based service provided through Argos. An annual
subscription will be required and text messaging is purchased in 75 message bundles. Refer to the
Netbiter section of the manual for further information.
The alarm status screen shows all of the faults the are currently active in the system. Acknowledged
faults that are no longer active will be removed from the list.
The alarm History Screens is a retentive listing of the faults that have occurred. This is useful for
scrolling back to see what was happening with the system previously.
About Screen
The ‘About Aarell Screen’ is an introduction to the companies involved in bringing this system together.
In addition to that the Date and Time settings for the HMI are displayed and can be modified if
necessary.
R. PERFORM A HOT TEST FOR INPUTS. VERIFY OUTPUTS, CHECK ALL ANALOG
MODULES COMPLETE TO DATA TABLES
S. OPERATE ALL ON/OFF DEVICES, STROKE ALL ANALOG VALVES, AND CHECK ALL
DISCRETE INPUT SWITCHES
V.
W.
B.
C.
D.
E.
F.
G.
H.
J.
K.
L.
D. PANELS ARE CLEAN FROM INSTALLATION DEBRIS, ENSURE ALL PANEL PANDUIT
COVERING AND WIRING IS DRESSED FOR FINAL ACCEPTANCE
E.
F.