Hotels ,Motels ,Design Criteria, Guestrooms Control Systems
Boilers
Easy Install &
Building .Managament Maintain. Low
Systems ..BMS Energy
Burners www.airandwatersyst…
Guest Rooms
Chillers
Cooling Towers McQuay Parts
Guest Room heating and cooling units shall be fan coil type. Self contained terminal air conditioning units or heat pumps may not
Cooling Load Savings
Calculation be used. Learn how you can
save money on all
Cryogenics
If horizontal concealed fan coil units are used, they shall be located over the foyer ceiling, with filter access doors as return grills. your McQuay
Energy Saving parts needs. Call
Duct Today
If vertically stacked fan coil units are used, air outlets shall be located so as not to cause drafts and to minimise sound levels at AirDistributors.com
Duct ,Smacna
the bed location.
Dampers ,Air
Dust Collection
The fan coil units shall be sized to maintain desired room temperature at no higher than medium speed. Manual J
Fans
calculations
Fire Dampers Done by a Pro, the
Individual Guest Room thermostats shall be provided. The thermostat shall be a combination heating cooling type with colour
Glass Selection essence of a
Heating coded graduated temperature adjustment, on off switch and multiple 3 speed fan control. comfortable home.
Heat Exchangers,water 1-877-316-3960
Thermostat shall be adjustable through 5oK by the guest. Control valves shall be two way type. The thermostat shall throttle the www.ComfyHouse.com
Heat Recovery
Heat Tracing Systems control valve only; fan control is not acceptable. Isolation of the fan (off position) will disable the thermostat and drive control
Hepa Filters valves closed. Water
Temperature
Hvac Applications
Control
Humidifiers / A minimum of fifty (50) cfm must be exhausted from each bathroom. Door grills in bathroom doors are not acceptable. Undercut Intelligent &
Dehumidifiers door to achieve free air space for toilet exhaust air. innovative
Insulation , Duct solutions that
Insulation , Pipe Room ambient design conditions: meet your hot
Insulation , Sound water needs.
www.armstrongintern…
Nano Tech.,In Building Heating: 22oC, dry bulb
Occupancy Sensors
Pneumatic Conveying Cooling: 24oC, dry bulb, 55 percent R.H. Hotels
Piping
Enviroment
Pool Ventilation Fresh air make up shall be introduced to the Guest Room fan coil units ducted directly into the Guest Room. Ducts shall be fitted Legionnare Disease
Process Piping with fire dampers where they penetrate walls, or otherwise suitably designed to prevent smoke ingression in the event of fire. Energy Saving
Psychrometry
Control Software
Pumps All fan coil units shall have (min.) 25mm filters (disposable or washable type) on the intake side of the coil(s). Hotel Design Books
Radiant Heating
Hotel Design
Refrigerant Systems Ensure that condensate pipes are correctly graded to fall and are fully insulated.
Solar Collectors
Sound Provide cut off switch to FCU from balcony door or windows, to isolate cooling/heating valve when opened. Ads by Google
Steam Generation
HVAC Duct
Tables & Charts Gnr. Fan coil unit is to be accessible through a hinged access panel secured by budget locks. Opening to give unobstructed access to
VAV Sytems Suite Hotel
isolation valves, drains and controls.
Valves Furnace HVAC
Ventilation
Supply and return grills shall be aluminium and finished as required by the Architect or Interior Designer, Supply grills are to be
VRV Systems
double deflection type. Return air grills to be hinged with filter fixed in slide rail for maintenance.
STORE
Solar Collectors
Flat Plate Collectors
Evacuated Tube
Collectors
Concentrating
Collectors
Transpired Collectors
Solar Control Systems

Solar Electric
Systems
Standalone Systems
Grid Connected
Systems
Hybrid Systems
Back-up Systems
Fan coil units shall include the following:
Solar Cells
Solar Arrays
Centrifugal fan, direct drive.
Inverters
Change Controller
Motor, three speed permanent split capacitor type with oil cups and overload protection.
Water coil, copper tubes/aluminium fins, three rows minimum. Use two coils or double circuit type for 4 pipe system. Include
Wind Turbines drain and vent connections integral with coil.
T bi
Turbines
Hybrid Systems Include primary and auxiliary insulated drain pans. Drain pans shall be coated on the inside to prevent leakage and corrosion.
Grid Systems Unit casing shall be insulated with 15mm heavy density glass fibre, 18 gauge steel bonded and baked enamel finish (where
Water Pumping finished cabinet is used).
Using Wind Energy
Enviromental Aspects Units shall be UL listed.
Buyer's Guide
Unit sound pressure levels shall not exceed an NC 35 curve in all octave bands at medium speed.

Save Energy Thermostats shall control modulating valves and not fan motor.
Solar Water Heating
Solar Electric Systems Self contained terminal air conditioning units or heat pumps shall include:
Wind Turbines
Passive Solar Heating Centrifugal evaporator and condenser fans, direct connected.
Passive Solar Cooling
Building Material Motor, three speed permanent split capacitor type with oilers.
Water Conservation
Ground Source Heat- Condenser and evaporator coils, electric heating element or hot water coil.
Pumps
Green Hotels Hermetic compressor.
Glass &Windows
Selection Unit casing shall be 18 gauge steel top and sides, 16 gauge steel base zinc coated phosphatised and finished in enamel.

Discharge grill, four way adjustable.

Aluminium outdoor air louvre with adjustable damper. Aluminium shall be clear anodised, 1 hour in accordance with Alcoa Spec.
215R1.

Integral temperature and fan speed control.

Sizing: Base peak cooling loads for selection of guestroom fan coil units on peak exterior loading with sheers closed, two people
per room and 250 watts per room electric load. Select capacity of fan coil unit to maintain room thermostat setting at medium fan
speed. • Supply Air: Quantity equals 102 m3/hr (60 cfm) per
guestroom.

Back to Hotels
Back to Hvac Expert Main Page

HVAC Technician Training Learn refrigeration and air conditioning technology at home. www.PennFoster.edu
FlatPlate Heat Exchangers Compact, High Performance, Heating, Refrigeration & Process Made in USA www.FlatPlate.com
Honeywell Distributor Allied Has the Honeywell Parts You Need. Order Today! AlliedElec.com/Honeywell

Search

Web www.iklim.com

Discuss on the Message Board

http://www.iklimnet.com

You might also like