AquaForce Greenspeed Water

Cooled Screw Chiller

Unit Information
Tag Name .......................................... Untitled2
Model Number:................................ 30XWV200
Condenser Type......................... Water Cooled
Compressor Type.................................... Screw
Nameplate Voltage:............................. 380-3-60 V-Ph-Hz
Quantity ........................................................... 1
Manufacturing Source ............... Canoas, Brazil
Refrigerant: ............................................. R134a
Minimum Capacity:..................................... 20,0 %
Shipping Weight: ....................................... 4386 kg
Operating Weight: ..................................... 4210 kg
Unit Length:............................................... 3288 mm
Unit Width: ................................................ 1215 mm
Unit Height: ............................................... 1949 mm

Performance Information
Cooling Capacity: ..................................... 823,2 kW
+Heating Capacity:................................... 964,1 kW
Total Unit Power:...................................... 149,5 kW
Cooling Efficiency (COPR): .................... 0,1817 ikW/kW
+Heating Efficiency (COPH):.................... 6,449 kW/kW

Acoustics Information
A-Weighted Sound Pressure Level: .............. 83 dbA

Evaporator Information
Fluid Type .....................................Fresh Water
Fouling Factor: ....................................... 0,0176 (sqm-K)/kW
Leaving Temperature: ................................ 6,67 °C
Entering Temperature: ............................. 12,22 °C
Fluid Flow:................................................ 35,32 L/s
Pressure Drop: ........................................... 37,5 kPa

Condenser Information
Fluid Type .....................................Fresh Water
Fouling Factor: ....................................... 0,0440 (sqm-K)/kW
Leaving Temperature: .............................. 34,61 °C
Entering Temperature: ............................. 29,44 °C
Fluid Flow:................................................ 44,89 L/s
Pressure Drop: ........................................... 61,0 kPa
Electrical Information
Unit Voltage: ....................................... 380-3-60 V-Ph-Hz
Connection Type ........................... Single Point
Minimum Voltage: ....................................... 342 Volts
Maximum Voltage: ...................................... 418 Volts

Electrical Electrical
Amps Circuit 1 Circuit 2
Max Unit Current 363,0 ---
Draw(RLA)
Nominal Unit 251,0 ---
Current Draw (A)
Nominal StartUp 251,0 ---
Current (ICF)

Accessories and Installed Options


Flange / Victaulic Adapters
BACnet Translator

Integrated Part Load Value (ARI)


IPLV.IP: 0,1035 ikW/kW

Unit Performance
Percent Full Load Cooling Capacity, % 100 75 50 25
Percent Full Load Power, % 100,0 53,2 24,9 11,9
Unloading Sequence Default Default Default Default
Cooling Capacity, kW 823,2 617,4 411,6 205,8
Total Unit Power, kW 149,5 79,60 37,30 17,84
Efficiency (COPR), kW/kW 5,505 7,756 11,03 11,53
Efficiency, ikW/kW 0,1817 0,1289 0,09063 0,08671
Evaporator Data
Fluid Entering Temperature, °C 12,22 10,83 9,44 8,05
Fluid Leaving Temperature, °C 6,67 6,67 6,67 6,67
Fluid Flow Rate, L/s 35,32 35,32 35,32 35,32
Fouling Factor, (sqm-K)/kW 0,0176 0,0176 0,0176 0,0176
Condenser Data
Fluid Entering Temperature, °C 29,44 23,89 18,33 18,33
Fluid Leaving Temperature, °C 34,61 27,59 20,72 19,52
Fluid Flow Rate, L/s 44,89 44,89 44,89 44,89
Fouling Factor, (sqm-K)/kW 0,0440 0,0440 0,0440 0,0440

Non-Standard Part Load Value


NPLV.IP: 9,662 kW/kW
NPLV.IP: 0,1035 ikW/kW

Unit Performance
Percent Full Load Cooling Capacity, % 100 75 50 25
Percent Full Load Power, % 100,0 53,2 24,9 11,9
Unloading Sequence Default Default Default Default
Cooling Capacity, kW 823,2 617,4 411,6 205,8
Total Unit Power, kW 149,5 79,60 37,30 17,84
Efficiency (COPR), kW/kW 5,505 7,756 11,03 11,53
Efficiency, ikW/kW 0,1817 0,1289 0,09063 0,08671
Evaporator Data
Fluid Entering Temperature, °C 12,22 10,83 9,44 8,05
Fluid Leaving Temperature, °C 6,67 6,67 6,67 6,67
Fluid Flow Rate, L/s 35,32 35,32 35,32 35,32
Fouling Factor, (sqm-K)/kW 0,0176 0,0176 0,0176 0,0176
Condenser Data
Fluid Entering Temperature, °C 29,44 23,89 18,33 18,33
Fluid Leaving Temperature, °C 34,61 27,59 20,72 19,52
Fluid Flow Rate, L/s 44,89 44,89 44,89 44,89
Fouling Factor, (sqm-K)/kW 0,0440 0,0440 0,0440 0,0440

Load Line

Unit Performance
Percent Full Load Cooling Capacity, % 100,0 75,0 50,0 80,0
Percent Full Load Power, % 100,0 55,9 28,2 47,9
Unloading Sequence Default Default Default Default
Cooling Capacity, kW 823,2 617,4 411,6 658,5
+Heating Capacity, kW 964,3 696,0 451,0 725,6
Total Unit Power, kW 149,5 83,66 42,21 71,65
Cooling Efficiency (COPR), kW/kW 5,505 7,380 9,751 9,191
Cooling Efficiency, ikW/kW 0,1817 0,1355 0,1026 0,1088
+Heating Efficiency (COPH), kW/kW 6,449 8,319 10,69 10,13
Evaporator Data
Fluid Entering Temperature, °C 12,22 10,83 9,44 11,10
Fluid Leaving Temperature, °C 6,67 6,67 6,67 6,67
Fluid Flow Rate, L/s 35,32 35,32 35,32 35,32
Fouling Factor, (sqm-K)/kW 0,0176 0,0176 0,0176 0,0176
Condenser Data
Fluid Entering Temperature, °C 29,44 25,28 21,11 18,50
Fluid Leaving Temperature, °C 34,61 29,00 23,52 22,38
Fluid Flow Rate, L/s 44,89 44,89 44,89 44,89
Fouling Factor, (sqm-K)/kW 0,0440 0,0440 0,0440 0,0440