Professional Documents
Culture Documents
WXR Evaporative Condenser Operation Maintenance
WXR Evaporative Condenser Operation Maintenance
2 Start-up
(1) Start fan, to observe whether ammeter needle points right.
(2) Start pump, check for the proper rotation indicated by the arrow on the pump cover and confirm condenser has provided water normally and
check spray nozzles spray water equally.
(3) Fill the water basin with fresh water to the overflow level.
(4) Set the make-up valve float so the water shuts off at the overflow level.
Leading Heat Transfer
(5) All things are normal then start refrigeration compressor and other refrigeration equipment.
5 Extended Shutdown
(1) The water basin should be drained and be flushed and cleaned with the suction strainer screens in place.
(2) The suction strainer screens should be cleaned and re-installed.
(3) The cold water basin drain should be left open.
(4) The casing of the unit should be inspected. Clean and refinish if necessary.
2 Maintenance of Fan
①Before putting through the fan power, check whether the wire is broken or if there is creepage or other dangerous factors.
②After installing fan, keeps it running 1 hour then stop motor to check it whether in good running and whether electric motor is heat.
③The external surface of the motor must be cleaned quarterly during running to ensure the cooling of the motor.
④In normal operation, regularly check the space between fan impeller and ventilating duct wall is necessary. To observe whether there is colliding,
otherwise adjustment should be made.
⑤When following cases have happened, stop motor immediately and overhaul.
a. Temperature of fan bearing increased over 95 ℃
b. Electric current in overload operation
c. Smoking in motor
d. Strong shake or big noise of scuffing
⑥The insulation performance of the motor should be checked by ohmmeter before restart motor if don’t use for a long time.
3 Maintenance of Pump
3.1 Maintenance in Operation
①Inlet branch must in great seal with no water and air leakage
②Prohibit long-term running if pump under condition of cavitation erosion
③Specialized person should take charge of the pump avoid occurring accidents
④For long-term running there will be wear in machine. If noise and shake become greater, motor should be stopped. If necessary, replace the
wearing parts. Generally speaking, unit needs to be checked every year.
3.2 Maintenance of Mechanical Seal
①Lubricating fluid should be cleaned with no solid particles
②Dry grinding operating is forbidden.
Leading Heat Transfer
③Before starting pump (electric motor) should running several circles, in order to avoid breakage of seal ring for sudden starting.
Nozzle
it may lead to coil scale and damage both evaporative and dry mode.
may cause corrosion, scale and sludge accumulations. It will reduce heat transfer efficiency and increase operating costs, even shorten the
service life of the equipment.
The concentration of dissolved solids in the circulating water can be reduced by discharging a small amount of circulating water from the system
to control the concentration cycle. Automatic conductivity controller can also be used to maximize the water efficiency of system. In this device,
the discharge rate can be adjusted by the valve on the drain line. Water quality should be checked regularly to ensure effective control of water
quality.
2) Treatment of corrosion and scale
A proper water treatment program, administered under the supervision of a competent water treatment specialist, is an essential part of routine
maintenance to ensure the safe operation and longevity of evaporative cooling equipment, as well as other system components.
The operation principle of evaporative condenser is evaporating the circulating water that flows through the surface of the coil or plate, it takes
the heat to make refrigerant condensing. When the water evaporating, the original impurities still in the water, it makes the concentration of
solid solute dissolved in water rapidly increase and may reach a high level. The impurities in the air continues to flow into the water and makes
the problem serious. If these impurities and contaminants cannot be controlled effectively, it may cause scale, corrosion and accumulation, thus
reducing the efficiency of heat transfer and increasing operating costs and damaging equipment potentially.
• Operating galvanized evaporative cooling equipment with a water pH below 6.0 for any period may cause removal of the protective zinc
coating.
• Operating galvanized evaporative cooling equipment with a water pH above 9.0 for any period may destabilize the passivated surface and
create white rust.
• Scale not only reduces heat transfer and system efficiency, but also may lead to deposit corrosion. If scale is not controlled, it may continue
building on critical components such as fill and severely impact heat transfer performance.
Therefore, the concentration of solid soluble in circulating water such as chloride and sulfide must be controlled within the parameters listed in
Table below:
Table Guidelines for circulating water quality
Parameter Galvanized steel sheet 304 Stainless steel
PH 7.0~9.0 6.5-9.0
Hardness as CaCO3 30-500 ppm 50-500 ppm
Leading Heat Transfer
protection system.
4) Biological Control
The methods of controlling corrosion and scale whether the chemical treat or not are not suitable for controlling biological impurities. The
growth of algae and other microbes may reduce the heat transfer efficiency of the system. Therefore, when the system is filled for the first time,
the sterilization process of biological growth should be used. Liquid fungicides can be added directly to the water basin. If solid fungicides are
used, they must be added by a crucible feeder. If ozone water treatment is used, the concentration of ozone cannot exceed 3~4 ppm for the
maximum service life of the equipment.
One of simple, easy to apply, low-maintenance method to control microbe, IOBIO bacteria and algae is to add low concentration of iodine to the
drain tube. This method is easy, utility, high effective and less maintenance.
sump, the recirculating water pump is mounted remotely at the sump and whenever the pump is shut off, all recirculating water drains back
to the sump.
On applications with a remote pump, the water flow and pump head should meet the requirement. Regulating value must be mounted to
adjust the flow of water on the drain line.
2. Basin Heaters: If a remote sump cannot be used, heat must be provided to the water basin. However, the basin heater will not prevent the
external water lines, pump or pump piping from freezing.
3. Heat Tracing: The make-up water supply, overflow and drain lines, as well as the pump and pump piping up to the overflow level must be
heat traced and insulated to protect them from damage.
4. Dry operating: In winter, both cooling load and ambient temperature below the design conditions. The evaporative condenser can operate
without recirculated water in dry mode. At the moment, the recirculated water is completely drained from the water basin.
Attention: Start/stop pump should not be used to adjust the energy. The condensing capacity is greatly affected by whether to use
recirculated water or not.
Troubleshooting
Item Fault Probably Cause Solutions
Inlet and outlet valve doesn’t open, or blockade in inlet and outlet branch or in
Check, get rid of the blockade
impeller flow passage
Wrong running direction of motor or Slow rotate speed dues to lacking electric
Adjust direction, fix wires
No water from phase
1 Steam leakage of suction tube Tie up every sealing face, remove air
pump
Fluid not filled the pump, air in pump chamber Open vent valve, remove air
not enough water supply on entry, suction path too high, water leakage at bottom
Motor stoppage, adjustment
valve
Over resistance in pipeline, inadequate choice of pump Reduce curve in pipeline, re-choose pump
Leading Heat Transfer