0. ALL HVAC Drwgs. in one pdf - 3.17.23 with Dispatch Changes

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

DUCTWORK LEGEND ABBREVIATIONS MECHANICAL GENERAL NOTES HVAC DRAWING LIST

SHEET TITLE
SINGLE LINE DESCRIPTION DOUBLE LINE AC
ACC
AIR CONDITIONING
AIR COOLED CONDENSER 1. REFER TO ARCHITECTURAL CONTRACT DOCUMENTS FOR PROJECT PHASING, 6. RUN DUCTS AND PIPING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND
H0.1 HVAC - COVER SHEET
AD ACCESS DOOR DEMOLITION REQUIREMENTS, CUTTING, PATCHING AND CEILING AIR DEVICES. CLEAR OF CEILING INSERTS. ALL DUCTWORK SHALL BE INSTALLED AS CLOSE
NEW WORK
AHU AIR HANDLING UNIT CONTRACTOR SHALL REVIEW ALL TRADES CONTRACT DOCUMENTS TO AS POSSIBLE TO WALL AND UNDERSIDE OF BEAMS AND JOISTS. H2.1 HVAC - NEW WORK PLANS - AREA A
BTU/H BRITISH THERMAL UNITS PER HOUR DETERMINE ALL COORDINATION REQUIREMENTS. OFFSETS IN PIPING AND
EXISTING WORK TO REMAIN DUCTS (INCLUDING DIVIDED DUCTS) AND TRANSITIONS AROUND 7. VERIFY ALL EQUIPMENT CONNECTIONS AND CLEARANCE REQUIREMENTS WITH
CD CEILING DIFFUSER H2.2 HVAC - NEW WORK PLANS - AREA B
CFM CUBIC FEET PER MINUTE OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER. MANUFACTURER'S CERTIFIED DRAWINGS/INSTALLATION MANUAL. VERIFY AND
EXISTING WORK TO BE REMOVED CRAC COMPUTER ROOM AIR CONDITIONING UNIT PROVIDE DUCT TRANSITIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND H2.3 HVAC - ENLARGED FLOOR PLAN - OFFICE DUCTWORK
CU CONDENSING UNIT 2. DRAWINGS ARE DIAGRAMMATIC, THEREFORE DETERMINE EXACT LOCATIONS COORDINATE ALL DIMENSIONS BEFORE FABRICATION.
CW COLD WATER OF EQUIPMENT, SYSTEMS AND COMPONENTS IN THE FIELD. CONTRACTOR H2.4 HVAC - ENLARGED FLOOR PLAN - REMOTE OFFICE DUCTWORK
DUCT UP SHALL NOTIFY ENGINEER IN WRITING OF ANY DISCREPANCIES BETWEEN 8. PROVIDE FLEXIBLE CONNECTIONS ON ALL DUCTS CONNECTING TO FANS AND
°F DEGREES FAHRENHEIT
D DRAIN EXISTING CONDITIONS AND CONTRACT DOCUMENTS PRIOR TO START OF AIR HANDLING UNITS. H2.5 HVAC - ROOF PLAN
DWG. DRAWING WORK.
9. THE INSIDE OF ALL UNLINED DUCTWORK VISIBLE THROUGH A GRILLE OR H3.3 HVAC - ENLARGED FLOOR PLAN - OFFICE PIPING
DUCT DOWN (E) EXISTING
EA EXHAUST AIR 3. WHERE PIPING AND DUCTWORK IS INDICATED TO BE REMOVED, REMOVE DIFFUSER SHALL BE PAINTED FLAT BLACK.
H5.1 HVAC - DETAILS
EF EXHAUST FAN PORTIONS INDICATED AND CAP OR PLUG WITH SAME OR COMPATIBLE
EG EXHAUST GRILLE MATERIAL. WHERE EQUIPMENT IS INDICATED TO BE REMOVED AND/OR 10. SMOKE DETECTORS SHALL BE FURNISHED AND WIRED TO THE FIRE ALARM
H7.1 HVAC - SCHEDULES
VOLUME DAMPER (VD) F FILTER RELOCATED, DISCONNECT AND CAP SERVICES WHERE NECESSARY, REMOVE, SYSTEM UNDER THE ELECTRICAL SECTION. UNDER THE MECHANICAL SECTION,
FD FIRE DAMPER CLEAN, AND STORE EQUIPMENT. WHEN APPROPRIATE, REINSTALL, CONTRACTOR SHALL MOUNT THE DETECTORS IN DUCTWORK, WHERE H9.1 HVAC - SPECIFICATIONS
FPM FEET PER MINUTE RECONNECT, AND REPAIR EQUIPMENT AS REQUIRED TO MAKE OPERATIONAL. REQUIRED BY CODE, AND SHALL WIRE THE DETECTORS TO THE ATC SYSTEM
FIRE DAMPER (FD) FT. FEET WHERE ARCHITECTURAL WALL, CEILING, FLOOR, ROOF, ETC. PENETRATIONS AND FAN STARTERS FOR SHUTDOWN.
FC FLEXIBLE CONNECTION OCCUR, PATCH WITH SAME OR COMPATIBLE MATERIAL.
GA GAGE 11. WORK WILL OCCUR IN AND AROUND OWNER OPERATIONS. PROVIDE MINIMUM
GPM GALLONS PER MINUTE 4. IF PIPE, DUCT, INSULATION OR EQUIPMENT TO REMAIN IS DAMAGED IN ONE WEEK NOTICE FOR SHUTDOWNS TO ANY SYSTEMS. WHERE PARTS OF
COMBINATION FIRE/SMOKE DAMPER (FSD) APPEARANCE OR IS UNSERVICEABLE, REMOVE DAMAGED OR UNSERVICEABLE EXISTING SYSTEMS BEING REMOVED REQUIRE CONTINUOUS OPERATION,
HP. HORSEPOWER
HX HEAT EXCHANGER PORTIONS AND REPLACE WITH NEW PRODUCTS OF EQUAL CAPACITY AND INSTALL AND MAKE OPERATIONAL NEW SYSTEMS PRIOR TO REMOVAL OF
IN. INCHES QUALITY. EXISTING SYSTEMS.
RADIUSED ELBOW KW KILOWATT
LB POUNDS 5. ALL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER, 12. WHEN ITEMS ARE TO BE DEMOLISHED, RETURN ALL ITEMS TO BE SALVAGED
LD LINEAR DIFFUSER RECTILINEAR TO BUILDING STRUCTURE. SUPPORT ALL EQUIPMENT, PIPING FOR THE OWNER'S USE. WHEN THE OWNER DOES NOT REQUIRE THE ITEMS TO
LPR STEAM CONDENSATE RETURN AND DUCTWORK FROM BUILDING STRUCTURE TO PROVIDE A VIBRATION FREE BE SALVAGED, DISPOSE OF ALL DEMOLITION AND CONSTRUCTION WASTE FROM
LPS STEAM SUPPLY INSTALLATION. NOTIFY ARCHITECT AND STRUCTURAL ENGINEER OF ALL THE PROJECT SITE IN A LANDFILL OR INCINERATOR ACCEPTABLE TO
45° BRANCH TAKE-OFF
LR LINEAR RETURN WEIGHTS AND METHODS OF SUPPORT. AUTHORITIES HAVING JURISDICTION. FOLLOW ALL LOCAL ORDINANCES FOR
MAX. MAXIMUM DISPOSAL AND RECYCLED MATERIALS.
MBH 1000 BTU/H
MIN. MINIMUM
BULL HEAD SPLIT TEE MOD MOTOR OPERATED DAMPER
NC NORMALLY CLOSED
NO NORMALLY OPEN
OA OUTDOOR AIR
O.C. ON CENTER
OED OPEN END DUCT
PC PUMPED CONDENSATE
45° ROUND BRANCH TAKE-OFF TEE WITH PSIG POUNDS PER SQUARE INCH
VOLUME DAMPER AT TAKE-OFF QTY. QUANTITY
RA RETURN AIR
REL. HUM. RELATIVE HUMIDITY
RF RETURN FAN
FLEXIBLE DUCTWORK
RG RETURN GRILLE
RHC REHEAT COIL
RL REFRIGERANT LIQUID
LINED TRANSFER AIR DUCT RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
SA SUPPLY AIR
SD SMOKE DAMPER
SDET SMOKE DETECTOR
SF SUPPLY FAN
SG SUPPLY GRILLE
SYMBOLS & EQUIPENT TAGS STL STEEL
TA TRANSFER AIR
TDH TOTAL DYNAMIC HEAD
TEMP. TEMPERATURE
CONNECT NEW TO EXISTING STANDARD 4-WAY BLOW SUPPLY DIFFUSER TG TRANSFER GRILLE
TYP. TYPICAL
UH UNIT HEATER
BLANKED FOR 3-WAY BLOW SUPPLY DIFFUSER UON UNLESS OTHERWISE NOTED
DEMOLISH UP TO THIS POINT VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
# SHEET NOTE DESIGNATION OR BLANKED FOR 2-WAY BLOW SUPPLY DIFFUSER W.G. WATER GAGE
WMS WIRE MESH SCREEN

# DEMOLITION NOTE DESIGNATION BLANKED FOR 1-WAY BLOW SUPPLY DIFFUSER

# SECTION DESIGNATION RETURN/EXHAUST GRILLE OR REGISTER


DWG SHEET NUMBER

LINEAR DIFFUSER
# DETAIL DESIGNATION
DWG SHEET NUMBER
TYPE (SEE SCHEDULE)
CFM
1 REVISION NUMBER
CD1-12(300) DIFFUSER/ REGISTER/ GRILLE CALL OUT

TEMPERATURE SENSOR OR THERMOSTAT NECK


SIZE (INCHES)
HUMIDITY SENSOR OR HUMIDISTAT

SMOKE DETECTOR RETURN OR EXHAUST AIR FLOW


PROJECT:

UC 1/2"
UNDERCUT DOOR
SUPPLY AIR FLOW
MARCUS PARTNERS
XX
XX
EQUIPMENT DESIGNATION (ELECTRIC SERVICE REQUIRED)
EQUIPMENT NUMBER
WAREHOUSE BUILDING
XX EQUIPMENT DESIGNATION (ELECTRIC SERVICE NOT REQUIRED) 5 MANLEY ST.
XX EQUIPMENT NUMBER
WEST BRIDGEWATER, MA
CONSTRUCTION MANAGER:

633 DIVISION ST. ELIZABETH, NJ 07201


ARCHITECT:

rkb architects, inc.


zero campanelli drive, braintree, ma 02184
p 781.848.6600 f 781.848.6660 w rkbarch.com

COPYRIGHT © BY RKB Architects Inc. ALL RIGHTS RESERVED


NO PART OF THIS DOCUMENT MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY
FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE, WITHOUT
THE EXPRESS WRITTEN CONSENT OF RKB Architects Inc. ANY MODIFICATIONS MADE TO THIS DOCUMENT WITHOUT
THE WRITTEN PERMISSION OF RKB Architects Inc. SHALL RENDER IT INVALID AND UNUSABLE.

MEP ENGINEER:

1 03.17.2023 TENANT CHANGES


- 9.9.2022 PERMIT SET
REVISIONS
PROJECT NO: 2216
APPLICABLE CODES STONERIDGE SCALE: AS NOTED
CODE TITLE
ENGINEERING DRAWN BY: RAA
BUILDING 780 CMR MASSACHUSETTS STATE BUILDING CODE 9TH EDITION 1583 LIVINGSTON AVENUE, SUITE #4 ISSUE DATE: 9.9.2022
(2015 IBC W/ MASS AMENDMENTS) NORTH BRUNSWICK, NJ 08902 SHEET TITLE:
Tel. (732) 658-6302
MECH. 780 CMR MASSACHUSETTS STATE BUILDING CODE 9TH EDITION
SRE PROJECT NUMBER 22067
& 2015 INTERNATIONAL MECHANICAL CODE (IMC)

PLUMB. 248 CMR MASSACHUSETTS STATE FUEL GAS AND PLUMBING ENGINEER'S SEAL: HVAC
CODE

ELECT. 527 CMR 12.00 MASSACHUSETTS ELECTRICAL CODE, ROBERT D. CIOFFI


COVER SHEET
2017 NATIONAL ELECTRICAL CODE PROFESSIONAL ENGINEER
MA LICENSE No. 53898
ENERGY 2020 MASSACHUSETTS ENERGY CODE
(2018 IECC W/ MASS AMENDMENTS)
H0.1
6 7 8 9 10 11

1
H2.4

E
Office

Office

42x16 OED W/WMS

SD COORDINATE BOTTOM OF
DUCT ELEVATION WITH
ARCHITECT/TENANT
42x24 UP
(TYP)

MAU THERMOSTAT/CONTROLS.
COORDINATE LOCATION WITH
ARCHITECT/TENANT. 1
H3.3
26x24 UP
1 D
H2.3

1 2 3 4 5 6 7 8 9 10 11

N
E E
PROVIDE WITH 4-WAY
DISCHARGE DIFFUSER
D D
ASSEMBLY & DUCT Production Sales
EXTENSION TO DISCHARGE
Ops Manager Flex Office
C C
BELOW STRUCTURE Flex Office PreViz
B B

A A

1 2 3 4 5 6 7 8 9 10 11

Cubicle Cubicle
PROJECT:

Storage
Cubicle Cubicle
MARCUS PARTNERS
Flex Office Systems Elec.

Cubicle Cubicle C WAREHOUSE BUILDING


Flex Office
5 MANLEY ST.
Cubicle Cubicle
Flex Office
Cubicle Cubicle
WEST BRIDGEWATER, MA
Demo Room
CONSTRUCTION MANAGER:
Flex Office

Flex Office
Cubicle Cubicle Accounting GM Office

633 DIVISION ST. ELIZABETH, NJ 07201


ARCHITECT:
Server
Rental Cubicle Cubicle
Demo Storage
Men's rkb architects, inc.
Women's
B zero campanelli drive, braintree, ma 02184
Janitor p 781.848.6600 f 781.848.6660 w rkbarch.com
Sales
SALES COUNTER

SALES AREA COPYRIGHT © BY RKB Architects Inc. ALL RIGHTS RESERVED


PRODUCT NO PART OF THIS DOCUMENT MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY
FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE, WITHOUT
DISPLAY
THE EXPRESS WRITTEN CONSENT OF RKB Architects Inc. ANY MODIFICATIONS MADE TO THIS DOCUMENT WITHOUT
THE WRITTEN PERMISSION OF RKB Architects Inc. SHALL RENDER IT INVALID AND UNUSABLE.

MAIN MAIN
SPRINKLER ELECTRIC BREAK ROOM Conf. Room
ROOM ROOM Vestibule
Reception

MEP ENGINEER:

G A
1 03.17.2023 TENANT CHANGES
- 9.9.2022 PERMIT SET
REVISIONS
PROJECT NO: 2216
STONERIDGE SCALE: AS NOTED

ENGINEERING DRAWN BY: RAA


1583 LIVINGSTON AVENUE, SUITE #4 ISSUE DATE: 9.9.2022
NORTH BRUNSWICK, NJ 08902 SHEET TITLE:
Tel. (732) 658-6302
SRE PROJECT NUMBER 22067

ENGINEER'S SEAL: HVAC


6 7 8 9 10 11
ROBERT D. CIOFFI
NEW WORK PLANS - AREA A
PROFESSIONAL ENGINEER
1 MA LICENSE No. 53898
H2.1 SCALE: 1" = 10'-0"
H2.1
1 2 3 4 5

1
H2.4

E SHOWER SHOWER

Break Room
WOMEN'S MEN'S

42x16 OED W/WMS

SD COORDINATE BOTTOM OF
DUCT ELEVATION WITH
ARCHITECT/TENANT
42x24 UP
(TYP)

26x24 UP
D
MAU THERMOSTAT/CONTROLS.
COORDINATE LOCATION WITH
1 2 3 4 5 6 7 8 9 10 11
ARCHITECT/TENANT.

E E
PROVIDE WITH 4-WAY
DISCHARGE DIFFUSER
D D
ASSEMBLY & DUCT
EXTENSION TO DISCHARGE C C
BELOW STRUCTURE
B B

A A

1 2 3 4 5 6 7 8 9 10 11

PROJECT:

MARCUS PARTNERS
C WAREHOUSE BUILDING
5 MANLEY ST.
WEST BRIDGEWATER, MA
CONSTRUCTION MANAGER:

633 DIVISION ST. ELIZABETH, NJ 07201


ARCHITECT:

rkb architects, inc.


B zero campanelli drive, braintree, ma 02184
p 781.848.6600 f 781.848.6660 w rkbarch.com

COPYRIGHT © BY RKB Architects Inc. ALL RIGHTS RESERVED


NO PART OF THIS DOCUMENT MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY
FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE, WITHOUT
THE EXPRESS WRITTEN CONSENT OF RKB Architects Inc. ANY MODIFICATIONS MADE TO THIS DOCUMENT WITHOUT
THE WRITTEN PERMISSION OF RKB Architects Inc. SHALL RENDER IT INVALID AND UNUSABLE.

MEP ENGINEER:

A
2 03.17.2023 TENANT CHANGES
1 10.3.2022 OWNER CHANGES
- 9.9.2022 PERMIT SET
REVISIONS
PROJECT NO: 2216
STONERIDGE SCALE: AS NOTED

ENGINEERING DRAWN BY: RAA


1583 LIVINGSTON AVENUE, SUITE #4 ISSUE DATE: 9.9.2022
NORTH BRUNSWICK, NJ 08902 SHEET TITLE:
Tel. (732) 658-6302
SRE PROJECT NUMBER 22067

ENGINEER'S SEAL: HVAC


1 2 3 4 5
ROBERT D. CIOFFI
NEW WORK PLANS - AREA B
PROFESSIONAL ENGINEER
1 MA LICENSE No. 53898
H2.2 SCALE: 1" = 10'-0"
H2.2
9 10 11

OPS FLEX OFFICE FLEX OFFICE PRE VIZ PRODUCTION SALES


HVAC GENERAL NOTES:
1. RUNOUTS TO ALL DIFFUSERS/GRILLES SHALL BE THE NECK SIZE OF THE
MANAGER CD1-8(130)
DIFFUSER/GRILLE.
2. COORDINATE ALL TEMPERATURE SENSOR LOCATIONS WITH ARCHITECT
AND FURNITURE.
CD1-8(200) CD1-8(200) CD1-8(200) CD1-8(200) 3. TRANSITION TO ALL UNIT CONNECTIONS.
CD1-8(140)

RG1-8(110) RG1-8(120)

12x8

12x8
RG1-10(200) RG1-10(200) RG1-10(200) RG1-10(160)

20x10
HP
RG1-6(35) 12x10 16x10 10x10
9 HP
CD1-10(340)
8
(TYP-3)

20x10
CD1-8(175)
(140) (80)
12x10 8"Ø

FLEX RG1-8(85) RG1-8(85)


SYSTEMS 6"Ø STORAGE
OFFICE
RG1-10(150)
OPEN
OFFFICE
CD1-6(50) RG1-6(50)
CD1-6(115)
ELECTRICAL
ROOM
CD1-8(150)
C
CD1-6(115)
RG1-18x18(885)

8x8
FLEX 16x10
16x10 FLEX

20x10
DEMO HP OFFICE
OFFICE
ROOM 10

10x8
HP
CD1-6(125) 6
FLEX
OFFICE

20x10
8"Ø
14x10 HP 20x10 (130)
20x10 11
RG1-8(95)

OPEN
(140)
OFFFICE
8"Ø
FLEX CD1-8(200)
OFFICE (TYP-2)
RG1-18x18(870) RG1-12(270)
RG1-8(95) (120)
GM OFFICE
RG1-8(90)
(TYP-5)

12x8
BRANCH BOX
CONTROLLER CD1-10(300)
CD1-6(125)

12x8
8"Ø

CD1-6(115) PROJECT:
(TYP-5)

MARCUS PARTNERS

18x10
ACCOUNTING
EG1-12x12(250) EG1-12x12(250)

12x10
SERVER
ROOM
CD1-8(175) HP
7 WAREHOUSE BUILDING
DEMO
WOMEN'S MEN'S

18x10
STORAGE 14x8 HP 10"Ø 5 MANLEY ST.
5
OPEN WEST BRIDGEWATER, MA

8"Ø
8x8
RENTAL (125) (30) OFFFICE CONSTRUCTION MANAGER:
CD1-6(125) CD1-8(125) 5"Ø B
CD1-6(50) CD1-6(125) RG1-14(500)
12x10

CD1-14(500)
14x10 (TYP-2)

6"Ø
SALES
EG1-8x8(100) CD2-6(30)
10x8 8x8 (80) HP
20x10 20x10
4 633 DIVISION ST. ELIZABETH, NJ 07201
JANITOR
16x12

16x12

8"Ø

ARCHITECT:
VRF SYSTEM
CONTROLLER
SALES
(120V / 1PH) COUNTER
rkb architects, inc.
14x14 OED W/WMS ERU 6"Ø zero campanelli drive, braintree, ma 02184
INTO ELECTRIC ROOM 1
p 781.848.6600 f 781.848.6660 w rkbarch.com
AT 12" BELOW CEILING
CD1-8(200)
SALES
14x14 UP
14x14 UP
EG1-12x12(200) 8"Ø AREA PRODUCT
14x14

MOD ERC
20x10

1
(150)
DISPLAY COPYRIGHT © BY RKB Architects Inc. ALL RIGHTS RESERVED
RG1-8(195) CD1-8(275) NO PART OF THIS DOCUMENT MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY
FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE, WITHOUT
THE EXPRESS WRITTEN CONSENT OF RKB Architects Inc. ANY MODIFICATIONS MADE TO THIS DOCUMENT WITHOUT
EUH
16x12

THE WRITTEN PERMISSION OF RKB Architects Inc. SHALL RENDER IT INVALID AND UNUSABLE.
HP
2
22x22 UP 2
EUH
1
22x22 OED W/WMS
INTO FIRE PUMP ROOM EG1-12x12(250)
AT 12" BELOW CEILING RG1-16(500)

(75)
18x10

MAIN
22x22 MAIN CD1-10(300)
(100)

18x10
14x12

RG1-16(550)
ELECTRIC (TYP-2) CONFERENCE RG1-12(275) RG1-12(300)
SPRINKLER 14x14 UP
ROOM HP ROOM
ROOM 3
HP
MEP ENGINEER:

1
18x10

CD1-12(350)
MOD
18x10

(TYP-2) CD1-10(325) 1 03.17.2023 TENANT CHANGES


- 9.9.2022 PERMIT SET
REVISIONS
COORDINATE ALL PROJECT NO: 2216
ADDITIONAL SPRINKLER
ROOM CONTROLS
BREAK ROOM CD1-10(325) STONERIDGE SCALE: AS NOTED
REQUIREMENTS/EQUIPMENT
WITH SPRINKLER/FIRE
ENGINEERING DRAWN BY: RAA

ALARM CONTRACTOR. 1583 LIVINGSTON AVENUE, SUITE #4 ISSUE DATE: 9.9.2022


RECEPTION VESTIBULE NORTH BRUNSWICK, NJ 08902 SHEET TITLE:
24" DEEP OAI Tel. (732) 658-6302
24" DEEP OAI SRE PROJECT NUMBER 22067
PLENUM W/MOD
PLENUM W/MOD
ENGINEER'S SEAL:
HVAC
MOD L
1
MOD ENLARGED FLOOR PLAN
L ROBERT D. CIOFFI
OFFICE DUCTWORK
2
A PROFESSIONAL ENGINEER
MA LICENSE No. 53898

H2.3
1
1
H2.3 SCALE: 1/4" = 1'-0"
5 6 HVAC GENERAL NOTES:
1.

2.
RUNOUTS TO ALL DIFFUSERS/GRILLES SHALL BE THE NECK SIZE OF THE
DIFFUSER/GRILLE.
COORDINATE ALL TEMPERATURE SENSOR LOCATIONS WITH ARCHITECT
AND FURNITURE.
3. TRANSITION TO ALL UNIT CONNECTIONS.

SHOWER SHOWER
E
CD2-6(40) EG1-6x6(50) EG1-6x6(50) CD2-6(40)
OFFICE

CD1-8(200)

RG1-10(200)
EG1-10x10(150) CD1-12(420) CD1-12(420)
EG1-10x10(225)
BREAK ROOM
10x10

SD

EWH
EWH 2
1 SD 24x16 UP
10x10 26x`14
24x16 UP
10x10 UP

CD1-6(80) CD1-6(80) CD1-8(200)

WOMEN'S MEN'S
RG1-18x18(840) OFFICE
RG1-10(200)
UC 1" UC 1"

1
H2.4 SCALE: 1/4" = 1'-0"

PROJECT:

MARCUS PARTNERS
WAREHOUSE BUILDING
5 MANLEY ST.
WEST BRIDGEWATER, MA
CONSTRUCTION MANAGER:

633 DIVISION ST. ELIZABETH, NJ 07201


ARCHITECT:

rkb architects, inc.


zero campanelli drive, braintree, ma 02184
p 781.848.6600 f 781.848.6660 w rkbarch.com

COPYRIGHT © BY RKB Architects Inc. ALL RIGHTS RESERVED


NO PART OF THIS DOCUMENT MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY
FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE, WITHOUT
THE EXPRESS WRITTEN CONSENT OF RKB Architects Inc. ANY MODIFICATIONS MADE TO THIS DOCUMENT WITHOUT
THE WRITTEN PERMISSION OF RKB Architects Inc. SHALL RENDER IT INVALID AND UNUSABLE.

MEP ENGINEER:

1 03.17.2023 TENANT CHANGES


- 9.9.2022 PERMIT SET
REVISIONS
PROJECT NO: 2216
STONERIDGE SCALE: AS NOTED

ENGINEERING DRAWN BY: RAA


1583 LIVINGSTON AVENUE, SUITE #4 ISSUE DATE: 9.9.2022
NORTH BRUNSWICK, NJ 08902 SHEET TITLE:
Tel. (732) 658-6302
SRE PROJECT NUMBER 22067

ENGINEER'S SEAL:
HVAC
ENLARGED FLOOR PLAN
ROBERT D. CIOFFI
PROFESSIONAL ENGINEER
REMOTE OFFICE DUCTWORK
MA LICENSE No. 53898
1

H2.4
1 2 3 4 5 6 7 8 9 10 11

E E
14x14 DN
CU RTU-1 Deleted
EF GV 2 Replaced with CU-2
2 3 HeatPump
EF-1 DELETED - REFRIGERANT
REPLACED W/ PIPING DN
Dispatch Area ERU
EF GV
Location Approximate 3 4

14x14 DN

42x24 DN 42x24 DN
MAU MAU
1 2

26x24 DN 26x24 DN
D D

LOCATE CONDENSING UNIT ON MITSUBISHI STAND MODEL QSSB48M +


QSSX48M (OR APPROVED EQUAL) ON ROOF. COORDINATE FINAL
LOCATION WITH ARCHITECT. PROVIDE ALL CLEARANCES, ELECTRICAL
SIZING/CONNECTIONS, REFRIGERANT PIPING SIZING/CONNECTIONS AND
ALL OTHER INSTALLATION REQUIREMENTS PER MANUFACTURER'S
REQUIREMENTS. PROVIDE REFRIGERANT LINES FROM CONDENSING
UNIT TO BRANCH BOX.

C C
CU
1

*NEW LOCATION*
FOR CU-1 Due to
REFRIGERANT
Structural Steel. PIPING DN
Above Demo Room

Actual Location May


be above Column
Line C - Field Verify

B B
14x14 DN

EF GV
14x14 DN 2 1

EF GV
22x22 DN 3 2

14x14 DN

A A

1 2 3 4 5 6 7 8 9 10 11

1
H2.5 SCALE: 1/16" = 1'-0"

PROJECT:

MARCUS PARTNERS
WAREHOUSE BUILDING
5 MANLEY ST.
WEST BRIDGEWATER, MA
CONSTRUCTION MANAGER:

633 DIVISION ST. ELIZABETH, NJ 07201


ARCHITECT:

rkb architects, inc.


zero campanelli drive, braintree, ma 02184
p 781.848.6600 f 781.848.6660 w rkbarch.com

COPYRIGHT © BY RKB Architects Inc. ALL RIGHTS RESERVED


NO PART OF THIS DOCUMENT MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY
FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE, WITHOUT
THE EXPRESS WRITTEN CONSENT OF RKB Architects Inc. ANY MODIFICATIONS MADE TO THIS DOCUMENT WITHOUT
THE WRITTEN PERMISSION OF RKB Architects Inc. SHALL RENDER IT INVALID AND UNUSABLE.

MEP ENGINEER:

2 05.02.2023 Updated Dispatch Area Changes - NGA SIGMA


1 03.17.2023 TENANT CHANGES
- 9.9.2022 PERMIT SET
REVISIONS
PROJECT NO: 2216
STONERIDGE SCALE: AS NOTED

ENGINEERING DRAWN BY: RAA


1583 LIVINGSTON AVENUE, SUITE #4 ISSUE DATE: 9.9.2022
NORTH BRUNSWICK, NJ 08902 SHEET TITLE:
Tel. (732) 658-6302
SRE PROJECT NUMBER 22067

ENGINEER'S SEAL: HVAC


ROBERT D. CIOFFI
ROOF PLAN
PROFESSIONAL ENGINEER
MA LICENSE No. 53898
1

H2.5
1 2 3 4 5 6 7 8 9 10 11

E E
RTU 20x12 DN
1
EF
1
28x14 DN

10x10 DN

42x24 DN 42x24 DN
MAU MAU
1 2

26x24 DN 26x24 DN
D D

LOCATE CONDENSING UNIT ON MITSUBISHI STAND MODEL QSSB48M +


QSSX48M (OR APPROVED EQUAL) ON ROOF. COORDINATE FINAL
LOCATION WITH ARCHITECT. PROVIDE ALL CLEARANCES, ELECTRICAL
SIZING/CONNECTIONS, REFRIGERANT PIPING SIZING/CONNECTIONS AND
ALL OTHER INSTALLATION REQUIREMENTS PER MANUFACTURER'S
REQUIREMENTS. PROVIDE REFRIGERANT LINES FROM CONDENSING
UNIT TO BRANCH BOX.

C C
CU
1

REFRIGERANT
PIPING DN

SU 14x14 DN

22x22 DN
14x14 DN

EF
2

EF
3
GV
1

GV
2
B

1
H2.5
1

SCALE: 1/16" = 1'-0"


2 3
PE 4 5 6 7 8 9
14x14 DN

10 11
A

R PROJECT:

MARCUS PARTNERS

C WAREHOUSE BUILDING
5 MANLEY ST.
WEST BRIDGEWATER, MA

ED CONSTRUCTION MANAGER:

ARCHITECT:
633 DIVISION ST.

rkb architects, inc.


ELIZABETH, NJ 07201

ED zero campanelli drive, braintree, ma 02184


p 781.848.6600 f 781.848.6660

COPYRIGHT © BY RKB Architects Inc. ALL RIGHTS RESERVED


w rkbarch.com

NO PART OF THIS DOCUMENT MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY
FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE, WITHOUT
THE EXPRESS WRITTEN CONSENT OF RKB Architects Inc. ANY MODIFICATIONS MADE TO THIS DOCUMENT WITHOUT
THE WRITTEN PERMISSION OF RKB Architects Inc. SHALL RENDER IT INVALID AND UNUSABLE.

MEP ENGINEER:

1 03.17.2023 TENANT CHANGES


- 9.9.2022 PERMIT SET
REVISIONS
PROJECT NO: 2216
STONERIDGE SCALE: AS NOTED

ENGINEERING DRAWN BY: RAA


1583 LIVINGSTON AVENUE, SUITE #4 ISSUE DATE: 9.9.2022
NORTH BRUNSWICK, NJ 08902 SHEET TITLE:
Tel. (732) 658-6302
SRE PROJECT NUMBER 22067

ENGINEER'S SEAL: HVAC


ROBERT D. CIOFFI
ROOF PLAN
PROFESSIONAL ENGINEER
MA LICENSE No. 53898
1

H2.5
9 10 11

HVAC SHEET NOTES:


1 NEW REFRIGERANT BRANCH BOX (208V / 1 PH). PROVIDE ALL CLEARANCES,
PRODUCTION SALES ELECTRICAL SIZING/CONNECTIONS, REFRIGERANT PIPING
SIZING/CONNECTIONS AND ALL OTHER INSTALLATION REQUIREMENTS PER

OPS FLEX OFFICE FLEX OFFICE PRE VIZ MANUFACTURER'S REQUIREMENTS.

MANAGER 2 NEW AIR CONDITIONING UNIT/HEAT PUMP. PROVIDE ALL CLEARANCES,


ELECTRICAL SIZING/CONNECTIONS, REFRIGERANT PIPING SIZING/CONNECTIONS
AND ALL OTHER INSTALLATION REQUIREMENTS PER MANUFACTURER'S
REQUIREMENTS. PROVIDE REFRIGERANT LINES FROM AIR CONDITIONING/HEAT
PUMP UNIT TO BRANCH BOX. PROVIDE 3/4" PUMPED CONDENSATE DRAIN TO MAIN
CONDENSATE DRAIN PIPING/MOP SINK.

PROVIDE
CLEANOUTS
(TYP)

HP
9 HP
2
8
2

OPEN
STORAGE OFFFICE

FLEX SYSTEMS ELECTRICAL


OFFICE ROOM C

FLEX FLEX
OFFICE
HP OFFICE 2
10

HP
REFRIGERANT 6
PIPING
(TYP)

HP FLEX
2 11
OPEN OFFICE
REFRIGERANT
OFFFICE PIPING TO
BRANCH BOX
REFRIGERANT CONTROLLER
PIPING UP (TYP)
FLEX
BRANCH BOX
OFFICE CONTROLLER

1
GM OFFICE

ACCOUNTING

1-1/2" PROJECT:
CONDENSATE
DRAIN PIPING

2
MARCUS PARTNERS
RENTAL
HP
7 WAREHOUSE BUILDING
WOMEN'S MEN'S
SERVER HP 5 MANLEY ST.
5
ROOM WEST BRIDGEWATER, MA
2 CONSTRUCTION MANAGER:

1-1/2"
CONDENSATE OPEN
B
DRAIN TO MOP
SINK
OFFFICE

2
JANITOR HP
4 633 DIVISION ST. ELIZABETH, NJ 07201
REFRIGERANT ARCHITECT:
PIPING SALES
(TYP)
COUNTER
rkb architects, inc.
ERU
1-1/2" SALES zero campanelli drive, braintree, ma 02184
CONDENSATE
1 DRAIN PIPING
p 781.848.6600 f 781.848.6660 w rkbarch.com
SALES
AREA PRODUCT
DISPLAY COPYRIGHT © BY RKB Architects Inc. ALL RIGHTS RESERVED
2 NO PART OF THIS DOCUMENT MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY
FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE, WITHOUT
THE EXPRESS WRITTEN CONSENT OF RKB Architects Inc. ANY MODIFICATIONS MADE TO THIS DOCUMENT WITHOUT
THE WRITTEN PERMISSION OF RKB Architects Inc. SHALL RENDER IT INVALID AND UNUSABLE.
HP
2

BREAK ROOM
VESTIBULE
MAIN
ELECTRIC
HP
ROOM 2
3 MEP ENGINEER:
HP
1

2
1 03.17.2023 TENANT CHANGES
CONFERENCE - 9.9.2022 PERMIT SET
REVISIONS
ROOM
PROJECT NO: 2216
RECEPTION STONERIDGE SCALE: AS NOTED

ENGINEERING DRAWN BY: RAA


1583 LIVINGSTON AVENUE, SUITE #4 ISSUE DATE: 9.9.2022
NORTH BRUNSWICK, NJ 08902 SHEET TITLE:
Tel. (732) 658-6302
SRE PROJECT NUMBER 22067

ENGINEER'S SEAL:
HVAC
ENLARGED FLOOR PLAN
ROBERT D. CIOFFI
OFFICE PIPING
A PROFESSIONAL ENGINEER
MA LICENSE No. 53898

H3.3
1
1
H3.3 SCALE: 1/4" = 1'-0"
MOTOR HOUSING

STAINLESS STEEL LOW PRESSURE


BAND CLAMP SUPPLY DUCT ELECTRICAL
CLEAN OUT PLUGS FLEXIBLE DUCT CONDUIT GUIDE
MAX. LENGTH 6'-0"

INSULATED

CONDENSATE DRAIN TO ROOF DRAIN PAN


DRAIN, FLOOR DRAIN, SPLASH SEE NOTE 1
BLOCK
PREFABRICATED
ROOF CURB SEE NOTE 2
"A"
SEE NOTE 2
12" MINIMUM ROOF
"C"
A = PLENUM NEGATIVE
"B" STATIC PRESSURE AT ROUND BRANCH
TAKEOFF FITTING W/
DESIGN OPERATING VOLUME DAMPER
CONDITIONS TRANSITION DUCT TO
RIGID CONDUIT TO FULL SIZE OF DAMPER
B = A/2 + 1 (MIN) CEILING
ACCOMODATE SUPPLIED w/ROOF FAN
SUPPLY AIR DIFFUSER OR RETURN ELECTRICAL WIRES
180° C=A+B GRILLE TO MATCH CEILING TYPE.
ROOF BEND
NOTE: FLEXIBLE DUCTWORK IS NOT ACCEPTABLE
GRAVITY BACKDRAFT DUCT, SEE DWGS.
FOR EXPOSED DUCTWORK.
OR MOTORIZED DAMPER
AS SPECIFIED

2 3
1
H5.1 NOT TO SCALE
H5.1 NOT TO SCALE
H5.1 NOT TO SCALE
NOTES:
1. SECURE FAN TO WIND RATED, PREFABRICATED ROOF CURB.
2. SECURE ROOF CURB TO ROOF STRUCTURE.

REFRIGERANT PIPING CONNECTIONS. COORDINATE ALL


INDOOR HORIZONTAL UNIT REFRIGERATION PIPING REQUIREMENTS WITH
MANUFACTURER.
1
STRUCTURE

HANGER RODS
(TYP)
VIBRATION ISOLATOR, SIZED FOR 1"
DEFLECTION
MAINTAIN FILTER REMOVAL CLEARANCES
(TYP)
FLEXIBLE CONNECTION FLEXIBLE CONNECTION

SECURE CAP TO
CURB WITH SHEET REFRIGERANT PIPE OR
METAL SCREWS 12" CONDUIT (TYPICAL)
O.C. AROUND
PERIMETER
RUBBER BOOT WITH
PIPE CLAMP
BASE
FLASHING PREFABRICATED, INSULATED
PIPE CURB. MOUNT AND
SECURE ON WOOD NAILER.
ROOFING
MATERIAL 12"
RETURN DUCTWORK SUPPLY DUCTWORK
MIN.
(TYP) A/C PUMPED CONDENSATE (TYP)
TO DRAIN

FIRE RESISTANT ROOF INSULATION


WOOD NAILER
NOTES
1. MAINTAIN ALL MANUFACTURER REQUIRED CLEARANCES.
2. COORDINATE INSTALLATION WITH ALL MANUFACTURER REQUIREMENTS.
3. PROVIDE AC UNIT WITH A WATER-LEVEL DETECTION DEVICE CONFORMING TO UL 508 THAT
WILL SHUT OFF THE EQUIPMENT IN THE EVENT THE PRIMARY CONDENSATE DRAIN LINE IS
BLOCKED.

PROJECT:
4 5
H5.1 NOT TO SCALE H5.1 NOT TO SCALE
MARCUS PARTNERS
WAREHOUSE BUILDING
5 MANLEY ST.
WEST BRIDGEWATER, MA
CONSTRUCTION MANAGER:

633 DIVISION ST. ELIZABETH, NJ 07201


ARCHITECT:

rkb architects, inc.


zero campanelli drive, braintree, ma 02184
p 781.848.6600 f 781.848.6660 w rkbarch.com

COPYRIGHT © BY RKB Architects Inc. ALL RIGHTS RESERVED


NO PART OF THIS DOCUMENT MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY
FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE, WITHOUT
THE EXPRESS WRITTEN CONSENT OF RKB Architects Inc. ANY MODIFICATIONS MADE TO THIS DOCUMENT WITHOUT
THE WRITTEN PERMISSION OF RKB Architects Inc. SHALL RENDER IT INVALID AND UNUSABLE.

MEP ENGINEER:

1 03.17.2023 TENANT CHANGES


- 9.9.2022 PERMIT SET
REVISIONS
PROJECT NO: 2216
STONERIDGE SCALE: AS NOTED

ENGINEERING DRAWN BY: RAA


1583 LIVINGSTON AVENUE, SUITE #4 ISSUE DATE: 9.9.2022
NORTH BRUNSWICK, NJ 08902 SHEET TITLE:
Tel. (732) 658-6302
SRE PROJECT NUMBER 22067

ENGINEER'S SEAL: HVAC


ROBERT D. CIOFFI
DETAILS
PROFESSIONAL ENGINEER
MA LICENSE No. 53898

H5.1
AC
ROOFTOP HEAT PUMP UNIT SCHEDULE #

SUPPLY FAN DATA RELIEF FAN DATA ELECTRIC HEATING COIL HEAT PUMP SECTION COOLING COIL FILTER EFFICIENCY (NOTE 2) ELECTRICAL
UNIT MIN MANUFACTURER
TOTAL CAPACITY EXTERNAL TOTAL MAX/MIN CAPACITY EXTERNAL AIR DATA AIR DATA AIR DATA
SERVICE LOCATION O.A. MODEL NUMBER
NO. AIRFLOW CONTROL STATIC STATIC MOTOR MOTOR AIRFLOW CONTROL STATIC STATIC MOTOR INPUT TOTAL TOTAL SENSIBLE MERV INTIAL FINAL COOLING HEATING VOLTS MCA MOP
CFM PRESSURE PRESSURE PRESSURE PRESSURE POWER EAT LAT EAT LAT EAT(°F) LAT(°F) PRESSURE PRESSURE SEER HPSF PHASE AMPS AMPS
CFM BHP HP CFM KW MBH MBH MBH
(IN WG) (IN WG) (IN WG) (IN WG) (°F) (°F) (°F) (°F) (IN.WG.) (IN.WG.) (@ 47 HERTZ
HP DB WB DB WB
DEG. F.)
1
CARRIER
RTU-1 OFFICE ROOF 1480 240 VFD 1.0 1.5 0.9 1.5 1240 CV 0.2 0.25 0.33 10.6 55.0 85.0 47.8 55.0 85.0 35.3 32.7 78.0 66.5 56.1 54.9 8 0.1 0.2 16.2 8.3 460/3/60 24 30
50GCQM05

1. PROVIDE RTU WITH VFD, EXHAUST FAN, OUTDOOR AIR INTAKE HOOD, HEAT PUMP, ELECTRIC HEATING COIL, DRAIN PAN, WIND RATED 24" HIGH DOWNFLOW ROOF CURB, ECONOMIZER WITH COMPARATIVE ENTHALPY CONTROL, DISCONNECT SWITCH, THROUGH THE BASE ELECTRICAL, POWERED CONVENIENCE OUTLET, RETURN AIR SMOKE DETECTOR AND HINGED
ACCESS DOORS.
2. UNITS SHALL EXCEED THE ENERGY CODE REQUIREMENTS BY 10%.

GF EUH
MAKE-UP AIR UNIT (SUPPLIED BY OWNER/INSTALLED BY CONTRACTOR) # ELECTRIC UNIT HEATER SCHEDULE #

SUPPLY FAN DATA NATURAL GAS FIRED HEATER FILTER ELECTRICAL UNIT HEAT VOLTS AIRFLOW TEMP. RISE MFR. MODEL NO.
TYPE CAPACITY PHASE REMARKS
MANUFACTURER REMARKS NO. (CFM) (DEG. F.)
UNIT MIN/MAX CAPACITY EXTERNAL TOTAL AIR DATA (KW) HERTZ
SERVICE LOCATION TOTAL MODEL NUMBER
NO. O.A. CONTROL STATIC STATIC MOTOR INPUT MERV INTIAL FINAL VOLTS MCA MOP
AIRFLOW CFM OUTPUT EFFICIENCY
PRESSURE PRESSURE HP MBH EAT LAT PRESSURE PRESSURE PHASE AMPS AMPS WALL
CFM EUH-1 5.0 480/3/60 350 45 QMARK / MUH 541 1, 2
(IN WG) (IN WG) MBH (°F) (°F) (IN.WG.) (IN.WG.) HERTZ MOUNTED
WALL
3,000 / ABSOLUT AIRE EUH-2 MOUNTED 5.0 480/3/60 350 45 QMARK / MUH 541 1, 2
MAU-1 MAIN WAREHOUSE ROOF 12,500 VFD 1.0 2.6 15 1397 1399 99% 0 103.5 8 0.1 0.2 480/3/60 25.5 40 SEE NOTE 1
12,500 AA4-HMX
3,000 / ABSOLUT AIRE SEE NOTE 1 NOTES:
MAU-2 MAIN WAREHOUSE ROOF 12,500 VFD 1.0 2.6 15 1397 1399 99% 0 103.5 8 0.1 0.2 480/3/60 25.5 40
12,500 AA4-HMX
1. PROVIDE THE FOLLOWING: INTEGRAL THERMOSTAT (SET AT 55 DEG. F. (ADJUSTABLE)), NEUTRAL GRAY COLOR,
NOTES: WALL/CEILING MOUNTING AND DISCONNECT SWITCH.
1. UNIT IS TO BE SUPPLIED BY OWNER AND INSTALLED BY CONTRACTOR. UNIT IS PROVIDED WITH FREEZESTAT, VFD FOR SOFT START, STATIC PRESSURE RECIRCULATING DAMPER CONTROL, ROOF CURB, 4-WAY DOWN DISCHARGE AIR DIFFUSER, OUTDOOR AIR AND RETURN DAMPERS, 2. APPROVED MANUFACTURERS: INDEECO, QMARK, MARKEL
DISCONNECT AND SMOKE DETECTOR/ALARM INTERLOCK. INSTALL UNIT PER ALL MANUFACTURER REQUIREMENTS AND RECOMMENDATIONS. PROVIDE ALL REQUIRED MANUFACTURER WIRING/CONNECTIONS.

L
FAN SCHEDULE
SF
#
LOUVER SCHEDULE # ELECTRIC WALL HEATER SCHEDULE EWH
#
MINIMUM MAX FREE SIZE MAX STATIC HEAT VOLTS AIRFLOW TEMP. RISE MFR. MODEL NO.
FAN FAN VOLTS UNIT FREE AREA FACE WIDTH x PRESSURE MFR. MODEL NO. UNIT TYPE
UNIT FAN E.S.P. DRIVE MANUFACTURER AIRFLOW CAPACITY PHASE (CFM) (DEG. F.) REMARKS
SERVICE LOCATION CFM MOTOR PHASE REMARKS NO. AREA VELOCITY HEIGHT DROP REMARKS NO. (KW) HERTZ
NO. TYPE (IN. W.G.) TYPE MODEL NUMBER SF FPM
RPM BHP HP HERTZ INCHES IN. W.G.
GREENHECK WALL
WAREHOUSE TOILET ROOMS ROOF 475 DOWNBLAST 1330 0.07 0.1 120/1/60 1 L-1 850 2.25 500 30x24 0.05 GREENHECK ESD-635 1,2 EWH-1 MOUNTED 1.8 277/1/60 100 25 QMARK / SSAR 4807 1, 2
EF-1 0.375 ECM G-090-VG
GREENHECK WALL
EF-2 ELECTRICAL ROOM ROOF 850 DOWNBLAST 0.375 ECM 1405 0.14 0.25 120/1/60 2 L-2 3500 7.6 500 24x78 0.05 GREENHECK ESD-635 1,2 EWH-2 MOUNTED 1.8 277/1/60 100 25 QMARK / SSAR 4807 1, 2
G-099-VG
GREENHECK
EF-3 SPRINKLER ROOM ROOF 3,200 DOWNBLAST 0.375 ECM 930 0.51 1.0 120/1/60 2
G-180-VG

NOTES: NOTES:
1. PROVIDE WITH DISCONNECT, WIND RATED ROOF CURB AND MOTORIZED DAMPER. TIE INTO ROOFTOP UNIT FOR TIME CLOCK OPERATION. 1. FURNISH DRAINABLE, ALUMINUM LOUVER WITH INTERNAL ALUMINUM BIRDSCREEN AND 1-1/2" PERIMETER FLANGE.
2. PROVIDE WITH DISCONNECT, WIND RATED ROOF CURB AND MOTORIZED DAMPER. PROVIDE WITH THERMOSTAT TO ENABLE FAN UPON A TEMPERATURE RISE ABOVE 85 DEG. F. (ADJ.) 2. COORDINATE FINAL SIZE, LOCATION, INSTALLATION AND LOUVER FINISH WITH ARCHITECT. NOTES:
3. PROVIDE EACH LOUVER WITH MOTOR OPERATED DAMPER - GREENHECK MODEL VCD-33 MOTOR OPERATED OPPOSED
BLADE DAMPER, WITH GALVANIZED INSULATED AIRFOIL BLADES, GASKETED FLANGES, BLADE AND JAMB SEALS, 1. PROVIDE THE FOLLOWING: 1" SEMI-RECESSED MOUNTING FRAME, INTEGRAL PROGRAMMABLE THERMOSTAT (SET
EXTERNAL 120 VOLT SPRING RETURN ELECTRIC TWO POSITION ACTUATOR. PROVIDE LOUVER CONNECTION TO AT 70 DEG. F. (ADJUSTABLE)), COLOR SELECTED BY ARCHITECT, SECURITY FRONT COVER KEY LOCK AND
DAMPER. PROVIDE CONTROLS TO OPEN DAMPER WHEN ASSOCIATED EXHAUST FAN/AND OR FIRE PUMP IS DISCONNECT SWITCH.
ENERGIZED. DAMPER SHALL CLOSE WHEN THE ASSOCIATED EQUIPMENT IS DE-ENERGIZED. 2. INSTALL PER MANUFACTURER RECOMMENDATIONS. APPROVED MANUFACTURERS: INDEECO, QMARK, MARKEL
DIFFUSER, REGISTER & GRILLE SCHEDULE
FACE SIZE SELECTION MANUFACTURER CU
SYMBOL OR LENGTH
NECK
RANGE MATERIAL FINISH MOUNTING ACCESSORIES MODEL NUMBER NOTES
VRF OUTDOOR HEAT RECOVERY UNIT SCHEDULE #
SIZE
(IN) (CFM) (AS STANDARD)
AMB COMPRESSOR ELECTRICAL DATA MANUFACTURER
SEE ARCH HEATING
SG1 SEE DWGS. SEE DWGS. SEE DWGS. STEEL WHITE - TITUS 300R 1,2 UNIT NOMINAL AIR MODEL NUMBER
DWGS. SERVICE LOCATION CAPACITY REFRIGERANT EER / IEER COP WEIGHT NOTES
DESIG. TONS TEMP.
(MBH) QUANTITY TYPE VOLT/PH MCA MOCP
SEE ARCH (DEG F)
CD1 24x24 SEE DWGS. SEE DWGS. STEEL WHITE - TITUS OMNI 1,2
DWGS.
SEE ARCH CU-1 HP-1,2,3,4,5,6,7,8,9,10,11 ROOF 24.0 320 95 R410A 11.2 / 23.6 3.36 2 SCROLL 1500 460/3 22 + 22 35 + 35 MITSUBISHI TURY-E288 1,2,3
CD2 12x12 SEE DWGS. SEE DWGS. STEEL WHITE - TITUS OMNI 1,2
DWGS.
SEE ARCH
RG1 24x24 SEE DWGS. SEE DWGS. STEEL WHITE - TITUS PAR 1,2
DWGS.
NOTES:
SEE ARCH
RG2 SEE DWGS. SEE DWGS. SEE DWGS. STEEL WHITE - TITUS 350RL 1,2
DWGS. 1. PROVIDE DISCONNECT, ALL MOUNTING/INSTALLATION ACCESSORIES AND LOW AMBIENT HEATING.
SEE ARCH 2. CONDENSING UNIT/HEAT PUMP SERVES MULTIPLE INDOOR UNITS. PROVIDE WITH BRANCH BOX, ADDITIONAL REFRIGERANT CHARGES, WITH ALL POWER AND CONTROL WIRING. PROVIDE ALL
EG1 SEE DWGS. SEE DWGS. SEE DWGS. STEEL WHITE OBD TITUS 350RL 1,2
DWGS. COMPONENTS FOR A COMPLETE SYSTEM AND OPERATION.
3. COORDINATE ALL REFRIGERANT PIPING LENGTHS AND INSTALLATION WITH MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS.
NOTES:

1. COORDINATE ALL DIFFUSER MOUNTING/BORDER TYPES WITH ARCHITECTURAL REFLECTED CEILING PLANS.
2. COORDINATE DIFFUSER COLOR FINISH WITH ARCHITECT. PAINT ALL DIFFUSERS AS REQUIRED.

PROJECT:
HP
VRF INDOOR UNIT SCHEDULE
SUPPLY FAN COOLING COIL HEAT PUMP CAPACITY ELECTRICAL DATA
MANUFACTURER
# DUCTWORK SCHEDULE MARCUS PARTNERS
UNIT SMACNA
OUTDOOR TOTAL EXT NOMINAL TOTAL SENSIBLE ENTERING DB ENTERING WB LEAVING DB TOTAL ENTERING DB LEAVING DB MODEL NUMBER DUCT PRESSURE DUCT
DESIG. VOLTS/ PRESSURE SEAL INSULATION NOTES

WAREHOUSE BUILDING
SERVICE LOCATION AIRFLOW AIRFLOW S.P. CAPACITY COOLING COOLING AIR TEMP AIR TEMP AIR TEMP HEATING AIR TEMP AIR TEMP MCA MOCP NOTES SYSTEM CLASS MATERIAL
PHASE CLASS
(CFM) (CFM) (IN.WC) TONS CAPACITY CAPACITY DEG. F. DEG. F. DEG. F. CAPACITY DEG. F. DEG. F.
(MBH) (MBH) (MBH) G90 GALVANIZED 1-1/2" MINERAL
SUPPLY 2" W.C. POSITIVE A
STEEL FIBER BLANKET
HP-1 RECEPTION ABOVE CEILING 75 650 0.2 2.0 23.3 19.7 78.0 64.5 57.0 19.3 64.0 83.0 208/1 3.0 15 MITSUBISHI TPEFY-024 1,2,3

CONFERENCE RM ABOVE CEILING 150 700 0.2 2.0 23.3 19.7 78.0 64.5 57.0 19.3 66.0 83.0 208/1 3.0 15 MITSUBISHI TPEFY-024 1,2,3
RETURN 2" W.C. NEGATIVE A
G90 GALVANIZED
STEEL
1-1/2" MINERAL
FIBER BLANKET 5 MANLEY ST.
HP-2

HP-3 BREAK RM ABOVE CEILING 100 600 0.2 2.0 23.3 19.7 78.0 64.5 57.0 19.3 66.0 83.0 208/1 3.0 15 MITSUBISHI TPEFY-024 1,2,3
OUTSIDE AIR 2" W.C.
POSITIVE/
NEGATIVE
A
G90 GALVANIZED
STEEL
1-1/2" MINERAL
FIBER BLANKET WEST BRIDGEWATER, MA
G90 GALVANIZED CONSTRUCTION MANAGER:
EXHAUST 2" W.C. NEGATIVE A
STEEL
HP-4 SALES ABOVE CEILING 80 775 0.2 2.0 23.3 19.7 78.0 64.5 57.0 19.3 66.0 83.0 208/1 3.0 15 MITSUBISHI TPEFY-024 1,2,3

HP-5 GM OFFICE ABOVE CEILING 30 300 0.2 1.0 11.6 8.6 78.0 64.5 56.5 9.6 66.0 88.0 208/1 2.2 15 MITSUBISHI TPEFY-024 1,2,3
NOTES:
HP-6 OPEN OFFICE ABOVE CEILING 130 1020 0.2 3.0 35.0 29.1 78.0 64.5 56.5 28.5 66.0 84.5 208/1 4.5 15 MITSUBISHI TPEFY-036 1,2,3

HP-7 OFFICES ABOVE CEILING 125 625 0.2 2.0 23.3 19.7 78.0 64.5 57.0 19.3 66.0 83.0 208/1 3.0 15 MITSUBISHI TPEFY-024 1,2,3

HP-8 OFFICES ABOVE CEILING 80 470 0.2 1.5 17.5 14.0 78.0 64.5 56.5 28.5 66.0 84.5 208/1 3.0 15 MITSUBISHI TPEFY-018 1,2,3
633 DIVISION ST. ELIZABETH, NJ 07201
HP-9 OFFICES ABOVE CEILING 140 775 0.2 2.0 23.3 19.7 78.0 64.5 57.0 19.3 66.0 83.0 208/1 3.0 15 MITSUBISHI TPEFY-024 1,2,3 ARCHITECT:

HP-10 OFFICES ABOVE CEILING 120 480 0.2 1.5 17.5 14.0 78.0 64.5 56.5 28.5 66.0 84.5 208/1 3.0 15 MITSUBISHI TPEFY-018 1,2,3

HP-11 OPEN OFFICE ABOVE CEILING 140 1175 0.2 3.0 35.0 29.1 78.0 64.0 56.5 28.5 70.0 84.5 208/1 4.5 15 MITSUBISHI TPEFY-036 1,2
rkb architects, inc.
zero campanelli drive, braintree, ma 02184
p 781.848.6600 f 781.848.6660 w rkbarch.com
NOTES:

1. PROVIDE WITH A MERV 8 FILTER, WALL MOUNTED CONTROLLER/THERMOSTAT, DISCONNECT AND CONDENSATE PUMP.
2. HEATING CAPACITIES LISTED ARE BASED ON 0 DEG. F. OUTDOOR AIR TEMPERATURES. COPYRIGHT © BY RKB Architects Inc. ALL RIGHTS RESERVED
NO PART OF THIS DOCUMENT MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY
FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE, WITHOUT
THE EXPRESS WRITTEN CONSENT OF RKB Architects Inc. ANY MODIFICATIONS MADE TO THIS DOCUMENT WITHOUT
THE WRITTEN PERMISSION OF RKB Architects Inc. SHALL RENDER IT INVALID AND UNUSABLE.

ERU
ENERGY RECOVERY UNIT SCHEDULE #
SUPPLY FAN EXHAUST FAN SUMMER CONDITIONS WINTER CONDITIONS ELECTRICAL DATA
UNIT MANUFACTURER
OUTDOOR TOTAL EXT TOTAL EXT TEMP. ENTHALPY ENTERING DB ENTERING WB RETURN DB RETURN WB LEAVING DB LEAVING WB TEMP. ENTERING DB RETURN DB LEAVING DB MODEL NUMBER
DESIG. SERVICE LOCATION VOLTS/ NOTES
AIRFLOW AIRFLOW S.P. AIRFLOW S.P. RECOVERY COOLING AIR TEMP AIR TEMP AIR TEMP AIR TEMP AIR TEMP AIR TEMP RECOVERY AIR TEMP AIR TEMP AIR TEMP MCA MOCP
PHASE
(CFM) (CFM) (IN.WC) (CFM) (IN.WC) (%) (%) DEG. F. DEG. F. DEG. F. DEG. F. DEG. F. DEG. F. (%) DEG. F. DEG. F. DEG. F.

ERU-1 OFFICE OFFICE 1150 1150 0.6 1100 0.6 67% 50% 91.0 73.0 75.0 64.0 80.3 68.1 64% 8.0 70.0 49.3 208/1 10.4 15 MITSUBISHI TLGHF-1200 1

MEP ENGINEER:
NOTES:

1. PROVIDE WITH A WALL MOUNTED CONTROLLER, DISCONNECT AND RETURN AIR/OUTDOOR AIR FILTERS. PROVIDE WITH AIRFLOW PROVING
SWITCH TO CONTROL ELECTRIC HEATING COIL.
1 03.17.2023 TENANT CHANGES
- 9.9.2022 PERMIT SET
ERC REVISIONS
GRAVITY VENTILATOR
GV
#
ELECTRIC HEATING COIL SCHEDULE #
PROJECT NO: 2216

TOTAL VOLTS
MANUFACTURER
UNIT
WIDTH x STATIC HEAT ENTERING LEAVING CAPACITY
MANUFACTURER STONERIDGE SCALE: AS NOTED
UNIT THROAT AREA PRESSURE DESIG. VOLTS/ MODEL NUMBER
NO.
SERVICE LOCATION CFM
(SQ. FT.) (IN. W.G.)
PHASE
MODEL NUMBER REMARKS TYPE HEIGHT AIRFLOW PRESSURE CAPACITY AIR TEMP AIR TEMP CONTROL PHASE
NOTES ENGINEERING DRAWN BY: RAA
HERTZ (INCHES) (CFM) DROP (KW) (DEG. F.) (DEG. F.)
1583 LIVINGSTON AVENUE, SUITE #4 ISSUE DATE: 9.9.2022
GREENHECK (IN.WG.)
GV-1 ERU-1 EXHAUST ROOF 1100 0.6 0.05 N/A 1,2 NORTH BRUNSWICK, NJ 08902 SHEET TITLE:
GRSR-20 Tel. (732) 658-6302
ERC-1 OPEN COIL 16x12 1150 0.1 5.0 8 21.7 1-STAGE 460/3 INDEECO / QUA 1 SRE PROJECT NUMBER 22067
ROOF 0.6 N/A GREENHECK 1,2
GV-2 ERU-1 OUTSIDE AIR 1150 0.05

NOTES:
GRSI-20
NOTES:
ENGINEER'S SEAL: HVAC
1.
2.
PROVIDE WITH ALL ALUMINUM CONSTRUCTION, BIRD SCREEN, MOTOR OPERATED DAMPER (120 V/ 1 PH) AND 18" HIGH WIND RATED ROOF CURB.
MOTOR OPERATED DAMPER (MOD) CONTROLS: UPON ERU BEING ENABLED, GV MOD SHALL OPEN. UPON ERU BEING DISABLED, MOD SHALL CLOSE.
1. PROVIDE WITH DISCONNECT SWITCH AND CONTROLS TRANSFORMER. PROVIDE WITH TEMPERATURE SENSOR TO MAINTAIN REQUIRED DISCHARGE
TEMPERATURE (20 DEG F). ROBERT D. CIOFFI
SCHEDULES
PROFESSIONAL ENGINEER
MA LICENSE No. 53898

H7.1
SECTION 1 - GENERAL
2.13 STEEL PIPE HANGERS AND SUPPORTS
1.11 WARRANTY H. FAN SHAFTS SHALL BE PRECISION GROUND AND POLISHED SOLID STEEL WITH AN ANTI-CORROSIVE COATING. G. NATURAL GAS HEATING
1.01 SCOPE FAN SHAFTS SHALL BE MOUNTED IN PERMANENTLY SEALED, LUBRICATED PILLOW BLOCK BALL BEARINGS. THE FIRST A. DEFINITIONS: MSS: MANUFACTURERS STANDARDIZATION SOCIETY FOR THE VALVE AND
A. EQUIPMENT, MATERIALS AND WORKMANSHIP OF THE MECHANICAL INSTALLATION SHALL BE CRITICAL SPEED ON A FAN SHAFT SHALL BE AT LEAST 25 PERCENT OVER MAXIMUM FITTINGS INDUSTRY INC. 1. THE NATURAL GAS HEATING WILL BE STAGED/MODULATED TO MAINTAIN THE SPACE AIR TEMPERATURE AT THE
A. THE GENERAL CONDITION REQUIREMENTS OF THE CONTRACT APPLY TO THE MECHANICAL WARRANTED BY THE CONTRACTOR FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF FINAL OPERATING SPEED. BEARINGS SHALL BE SELECTED FOR A MINIMUM L10 LIFE IN EXCESS OF 100,000 HOURS (L50 LIFE HEATING SET POINT. IF THE RTU IS IN THE HEATING MODE, THE UNIT WILL CONTROL TO THE SPACE TEMPERATURE
WORK. ACCEPTANCE OF THE WORK BY THE ARCHITECT OR ENGINEER. OF 500,000 HOURS) AT MAXIMUM CATALOGED OPERATING SPEED. ALL BEARINGS ARE 100 PERCENT FACTORY B. DESCRIPTION: MSS SP-58, TYPES 1 THROUGH 58, FACTORY-FABRICATED COMPONENTS. SET POINT. THE GAS HEATING WILL BE DISABLED IF THE OUTDOOR AIR DAMPER IS OPEN PAST ITS MINIMUM POSITION
TESTED. OR IF THE DX COOLING IS ENABLED.
B. PROVIDE ALL MATERIAL, TOOLS, SUPERVISION AND LABOR REQUIRED FOR THE MECHANICAL B. THE CONTRACTOR SHALL PROMPTLY CORRECT, REPAIR AND/OR REPLACE ANY AND ALL BREAKS, C. MANUFACTURERS: NATIONAL PIPE HANGER CORPORATION OR APPROVED EQUAL.
WORK DESCRIBED IN THESE SPECIFICATIONS AND INDICATED ON THE DRAWINGS. FAILURES OR WEAR DUE TO FAULTY MATERIALS, WORKMANSHIP OR EQUIPMENT. I. THE FAN HOUSING SHALL CONSIST OF THE MOTOR COVER, SHROUD, CURB CAP AND LOWER WINDBAND, AND H. DX COOLING
SHALL BE CONSTRUCTED OF HEAVY-GAUGE ALUMINUM. HOUSING SHALL HAVE A RIGID INTERNAL SUPPORT D. STEEL PIPE HANGER INSTALLATION: COMPLY WITH MSS SP-69 AND MSS SP-89. INSTALL
C. PROVIDE ALL NECESSARY INCIDENTAL MATERIALS AND ACCESSORIES REQUIRED TO MAKE THE SECTION 2 - PRODUCTS STRUCTURE AND LEAKPROOF DESIGN. THE FAN SHROUD SHALL BE ONE-PIECE WITH A ROLLED BEAD FOR EXTRA HANGERS, SUPPORTS, CLAMPS, AND ATTACHMENTS AS REQUIRED TO PROPERLY SUPPORT PIPING 1. THE DX COOLING WILL BE STAGED AND/OR MODULATED TO MAINTAIN THE SPACE AIR TEMPERATURE AT THE
WORK COMPLETE IN ALL RESPECTS, EVEN IF NOT PARTICULARLY INDICATED OR SPECIFIED.
STRENGTH WHICH DIRECTS EXHAUST AIR DOWNWARD. THE LOWER WINDBAND SHALL BE ONE PIECE WITH FORMED FROM BUILDING STRUCTURE. COOLING SET POINT AND WILL WORK CONCURRENTLY WITH THE VAV SUPPLY FAN. IF THE ECONOMIZER FUNCTION IS
2.01 DUCTWORK EDGES FOR ADDED STRENGTH AND THE CURB CAP SHALL INCLUDE PREPUNCHED MOUNTING HOLES TO ENSURE ENABLED, THE DX COOLING VALVE WILL BE DISABLED. THE DX COOLING WILL BE DISABLED IF THE RTU IS IN THE
D. OBTAIN ALL PERMITS AND SCHEDULE ALL REQUIRED INSPECTIONS. COPIES OF ALL PERMITS AND
CORRECT ATTACHMENT TO THE ROOF. E. INSTALL HANGERS AND SUPPORTS COMPLETE WITH NECESSARY INSERTS, BOLTS, RODS, HEATING MODE, THE SUPPLY FAN IS OFF, OR THE DISCHARGE AIR SENSOR HAS FAILED.
INSPECTION CERTIFICATES SHALL BE SUBMITTED TO THE OWNER AS AN INFORMATIONAL A. GENERAL NUTS, WASHERS, AND OTHER ACCESSORIES.
SUBMITTAL FOR RECORD.
J. DRIVE FRAME ASSEMBLIES SHALL BE CONSTRUCTED OF HEAVY-GAUGE STEEL AND MOUNTED ON TRUE J. FAN STATUS
1. INTERNAL AIR FLOW DIMENSIONS ARE SHOWN FOR DUCTS. CONTRACTOR SHALL INCREASE SIZE VIBRATION ISOLATORS. PULLEYS SHALL BE OF THE FULLY MACHINED CAST IRON-TYPE, KEYED AND SECURELY F. PROVIDE THERMAL-HANGER SHIELD INSERTS.
E. COORDINATE MECHANICAL WORK WITH THE WORK OF OTHER TRADES. FOR LINER IF APPLICABLE. ATTACHED TO THE WHEEL AND MOTOR SHAFTS. MOTOR PULLEYS SHALL BE ADJUSTABLE 1. PROVIDE A DIFFERENTIAL PRESSURE SWITCH OR A CURRENT SENSOR AT EACH SUPPLY AND
2. DIFFUSER SIZES SHOWN ARE NECK SIZES; REGISTER AND GRILLE SIZES ARE NOMINAL. FOR FINAL SYSTEM BALANCING. G. PIPING SHALL BE SUPPORTED FROM BUILDING STRUCTURAL ELEMENTS ONLY. PIPES SHALL RETURN/EXHAUST FAN. THE SWITCH/SENSOR SHALL PROVIDE FAN FLOW STATUS AND FAN FAILURE TO THE ATC
F. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALL EXISTING AND NEW 3. PROVIDE FLEXIBLE CONNECTIONS ON ALL DUCTS CONNECTING TO FANS AND HEAT PUMPS. ALL NOT BE HUNG FROM METAL DECK ROOFS, EQUIPMENT OR OTHER PIPING, DUCTWORK, CABLE SYSTEM.
CONDITIONS AND MATERIALS WITHIN THE CONSTRUCTION AREA. DUCTS SHALL BE GROUNDED ACROSS FLEXIBLE CONNECTION WITH FLEXIBLE COPPER GROUNDING K. A DISCONNECT SWITCH IS A POSITIVE ELECTRICAL SHUTOFF AND SHALL BE WIRED FROM THE FAN MOTOR TO TRAYS, OR CONDUITS.
STRAPS. A JUNCTION BOX INSTALLED WITHIN THE MOTOR COMPARTMENT. FACTORY STANDARD SHALL BE A NEMA-1 L. COOLING SETPOINTS
1.02 DEFINITIONS 4. MAXIMUM LENGTH OF FLEXIBLE RUN-OUT TO DIFFUSERS SHALL BE 6'-0". PROVIDE ADDITIONAL DISCONNECT SWITCH WITH OTHER NEMA RATED OPTIONS ALSO AVAILABLE. DISCONNECT SWITCHES SHALL BE H. PIPING SHALL BE SUPPORTED BY FACTORY MADE HANGERS FABRICATED SPECIFICALLY FOR 1. OCCUPIED: 75 DEG. F. (ADJUSTABLE)
LENGTH OF RIGID DUCT (ROUND OR RECTANGULAR) ON RUN-OUT AS REQUIRED. SAG SHALL NOT FACTORY MOUNTED AND/OR SHIPPED LOOSE FOR FIELD MOUNTING. THE SERVICE INTENDED. HANGERS AND SUPPORTS SHALL NOT BE OF STRAP OR BAND STEEL, 2. UNOCCUPIED: 85 DEG. F. (ADJUSTABLE)
A. ACTION SUBMITTALS: WRITTEN AND GRAPHIC INFORMATION THAT REQUIRES THE RESPONSIVE EXCEED 1/2" PER FOOT OF SPACING BETWEEN SUPPORTS. CHAIN OR WIRE.
ACTION. 5. ALL DUCTS PENETRATING RATED FIRE WALLS SHALL BE PROVIDED WITH FIRE DAMPERS AND L. ACCESSORIES SHALL INCLUDE: AUTO BELT TENSIONER (BELT DRIVE), BACKDRAFT DAMPERS AND WIND RATED M. HEATING SETPOINTS
ACCESS DOORS. DUCTWORK SHALL NOT RUN ALONG FULL HEIGHT PARTITIONS. ROOF CURB. I. ALL HANGERS, SUPPORTS, AND PIPE MOVEMENT CONTROL EQUIPMENT FOR PRESSURE 1. OCCUPIED: 72 DEG. F. (ADJUSTABLE)
B. FURNISH: TO PURCHASE, PROCURE, ACQUIRE AND DELIVER, COMPLETE WITH RELATED 6. PATCH AND SEAL ALL EXISTING OPENINGS IN DUCTWORK NOT UTILIZED FOR NEW LAYOUT. SERVICES SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE CODE FOR PRESSURE 2. UNOCCUPIED: 60 DEG. F. (ADJUSTABLE)
ACCESSORIES. 7. THE INSIDE OF ALL UNLINED DUCTWORK VISIBLE THROUGH A GRILLE OR DIFFUSER SHALL BE 2.03 ROOFTOP CONDENSATE DRAIN PIPING PIPING, ANSI B31.1, AS APPLICABLE.
PAINTED FLAT BLACK. N. ALARMS INDICATION
C. INFORMATIONAL SUBMITTALS: WRITTEN INFORMATION THAT DOES NOT REQUIRE RESPONSIVE 8. WHEN SECTION OF DUCTWORK IS NOT LABELED FOR SIZE, THE LARGER SIZE INDICATED ON THE A. CONDENSATE DRAIN LINES: SCHEDULE 40 PVC PIPE AND FITTINGS AND SOLVENT-WELDED J. INSTALL HANGERS FOR COPPER TUBING WITH THE FOLLOWING MAXIMUM SPACING AND 1. DIRTY FILTER ALARM, SUPPLY AIR ALARM, DX COOLING ALARM, FREEZESTAT ALARM, SMOKE DETECTION
ACTION. INFORMATIONAL SUBMITTALS MAY BE REJECTED FOR NOT COMPLYING WITH SUBMITTAL CONNECTED DUCT SHALL PREVAIL. SIZE OF DUCT RUN-OUTS TO DIFFUSER SHALL EQUAL DIFFUSER JOINTS. AIR CONDITIONING CONDENSATE PIPING SHALL COMPLY WITH THE NATIONAL STANDARD MINIMUM ROD SIZES: ALARM, CARBON MONOXIDE ALARM.
REQUIREMENTS. NECK SIZE. DUCT BRANCH CONNECTIONS AND TAKE OFFS SHALL BE MADE WITH 45° CONNECTION, PLUMBING CODE (CHAPTER 9) AND THE INTERNATIONAL MECHANICAL CODE (CHAPTER 3, SECTION
9. BELLMOUTH OR CONICAL ONLY. SPIN IN COLLARS AND STRAIGHT TAPS SHALL NOT BE USED. 307, CONDENSATE DISPOSAL), WHICHEVER IS STRICTER. SLOPE DRAIN LINES DOWN AWAY FROM 1. NPS 1/2" TO 5/8": MAXIMUM SPAN, 60 INCHES; MINIMUM ROD SIZE, 1/4 INCH. 4.02 FIRE ALARM (GENERAL)
D. INSTALL: TO ERECT, MOUNT AND CONNECT, COMPLETE WITH RELATED ACCESSORIES. ELBOWS AND BENDS FOR RECTANGULAR DUCTS SHALL HAVE CENTER LINE RADIUS UNITS AT 1/8 INCH PER FOOT. 2. NPS 1": MAXIMUM SPAN, 72 INCHES; MINIMUM ROD SIZE, 1/4 INCH.
OF 1.5 TIMES DUCT WIDTH WHEREVER POSSIBLE. WHERE CENTERLINE RADIUS IS LESS THAN 1.5 3. NPS 1.25" TO 2": MAXIMUM SPAN, 96 INCHES; MINIMUM ROD SIZE, 3/8 INCH. A. A DUCT SMOKE DETECTOR AND CARBON MONOXIDE DETECTOR SHALL BE FURNISHED AND INSTALLED IN THE
E. PROVIDE: TO FURNISH AND INSTALL. TIMES DUCT WITH, ELBOWS SHALL BE RADIUS THROAT WITH RADIUS HEEL AND FULL LENGTH 2.04 MECHANICAL IDENTIFICATION 4. NPS 2.5": MAXIMUM SPAN, 108 INCHES; MINIMUM ROD SIZE, 3/8 INCH. DUCTWORK BY THE MECHANICAL CONTRACTOR. PROVIDE WIRING FROM THE DUCT SMOKE DETECTOR AND CARBON
SPLITTER VANES. MATERIALS AND PRESSURE RATING 5. NPS 3": MAXIMUM SPAN, 10 FEET; MINIMUM ROD SIZE, 3/8 INCH. MONOXIDE (CO) DETECTOR TO THE ASSOCIATED UNIT'S MOTOR STARTER AND TO THE BUILDING FIRE ALARM SYSTEM.
G. CONTRACTOR OR MECHANICAL CONTRACTOR: THE CONTRACTOR FOR THE MECHANICAL WORK 10. SHEET METAL DUCTS SHALL BE CONSTRUCTED OF HOT DIPPED G90 GALVANIZED SHEET METAL A. EQUIPMENT IDENTIFICATION 6. NPS 4": MAXIMUM SPAN, 12 FEET; MINIMUM ROD SIZE, 1/2 INCH. WHENEVER PRODUCTS OF COMBUSTION OR HIGH LIMIT CO ARE SENSED, THE UNIT'S FANS WILL SHUTDOWN.
WHICH IS SPECIFIED HEREIN AND SHOWN ON THE DRAWINGS.
UNLESS OTHERWISE SPECIFIED.
11. ALL LOW PRESSURE SUPPLY DUCTWORK, RETURN DUCTWORK, OUTDOOR AIR DUCTWORK AND 1. INSTALL AND PERMANENTLY FASTEN EQUIPMENT NAMEPLATES ON EACH PIECE OF MECHANICAL EQUIPMENT IN 2.14 INDOOR CONDENSATE DRAIN PIPING INSULATION 4.03 MOTOR STARTERS OR VFD'S
1.03 QUALITY ASSURANCE
EXHAUST DUCTWORK SHALL BE MINIMUM 2"(wg) PRESSURE CLASS. SEAL CLASS A, LEAKAGE CLASS ACCESSIBLE AND VISIBLE LOCATIONS.
12. A. CONDENSATE DRAIN PIPING INSULATION SHALL BE JOHNS MANVILLE, FIBERGLASS OR A. ALL SAFETY DEVICES SHALL BE WIRED SO THEY STOP THE MOTOR WITH THE HAND-OFF-AUTO SWITCH IN THE
A. ALL WORK SHALL COMPLY WITH APPLICABLE CODES, REGULATIONS AND STANDARDS
2. EQUIPMENT NAMEPLATES SHALL BE METAL, WITH DATA ENGRAVED OR STAMPED WITH THE FOLLOWING MINERAL FIBER, 1 INCH THICKNESS, CONDUCTIVITY (K-VALUE) AT 0.23 (BTU-IN / HR-SQ FT-DEG F) AT HAND AS WELL AS THE AUTO POSITION. THIS WILL NORMALLY MEAN BREAKING THE COMMON WIRE FROM THE
GOVERNING THE PROJECT SITE INCLUDING:
B. FLEXIBLE DUCTWORK INFORMATION: MANUFACTURER, PRODUCT NAME, MODEL NUMBER, SERIAL NUMBER, CAPACITY, OPERATING AND 75 DEGREES F. MEAN TEMPERATURE. FACTORY-APPLIED JACKET SHALL BE ALL-SERVICE JACKET HAND-OFF-AUTO SWITCH TO THE STARTER'S HOLDING COIL THROUGH THE SAFETY DEVICES.
POWER CHARACTERISTICS, ALL OTHER ESSENTIAL EQUIPMENT DATA AND THE LABELS OF TESTED COMPLIANCES. ASJ (AP-T) VAPOR RETARDER JACKET WITH SELF-SEALING LAPS. HIGH DENSITY WHITE KRAFT
1. 2015 INTERNATIONAL BUILDING CODE W/ MASS. AMENDMENTS
1. FLEXIBLE DUCTWORK, CONNECTING TO UNINSULATED OR UNLINED DUCT, SHALL PAPER REINFORCED WITH GLASS FIBER YARN AND BONDED TO ALUMINUM FOIL. SECURE WITH 4.04 CONDENSATE OVERFLOW PROTECTION
2. 2015 INTERNATIONAL MECHANICAL CODE
BE VINYL COATED FIBERGLASS CLOTH 0.0057" MINIMUM THICKNESS, 25 STRANDS PER INCH 2.05 WIRING AND MOTOR CONTROLLERS SELF-SEALING LONGITUDINAL LAPS AND BUTT STRIPS.
3. 2017 NATIONAL ELECTRICAL CODE
4. 2018 IECC W/ MASS AMENDMENTS MINIMUM THREAD COUNT WITH CORROSION-RESISTANT HELICAL WIRE REINFORCEMENT, AND A. ALL UNITS WITH COOLING COILS SHALL REQUIRE A CONDENSATE LEAK DETECTOR (UNLESS THE DRAWINGS
RATED FOR 12" W.C. POSITIVE PRESSURE, RATING SHALL BE 2" W.C. NEGATIVE PRESSURE A. UNLESS OTHERWISE INDICATED PROVIDE ALL ELECTRICAL DISCONNECT SWITCHES, MOTOR 2.15 REFRIGERANT PIPING INSULATION SPECIFICALLY SHOW A SECONDARY DRAIN OR AUXILIARY DRAIN PAN WITH A SEPARATE DRAIN AS DESCRIBE IN THE
5. AMERICANS WITH DISABILITIES ACT (ADA)
WITH A MAXIMUM VELOCITY OF 4000 FPM. CONTROLLERS, STARTERS AND VARIABLE FREQUENCY DRIVES FOR ALL PROVIDED EQUIPMENT INTERNATIONAL MECHANICAL CODE 2018, CONDENSATE DISPOSAL). THE CONTROLS SHALL BE CAPABLE OF
2. FLEXDUCT MUST BE LISTED AS A CLASS 1 CONNECTOR ACCORDING TO UL 181 AND SHALL WHETHER UNIT MOUNTED OR REMOTE MOUNTED. COORDINATE ALL POWER REQUIREMENTS WITH A. REFRIGERANT PIPING INSULATION SHALL BE FLEXIBLE ELASTOMERIC (ARMACELL AP MONITORING A FIELD SUPPLIED AND INSTALLED CONDENSATE LEAK DETECTOR. WHENEVER THE SENSOR DETECTS
B. ALL WORK SHALL BE PERFORMED SAFELY AND IN COMPLIANCE WITH THE CURRENT
THE ELECTRICAL CONTRACTOR. ALL LOW VOLTAGE CONTROL WIRING SHALL BE PROVIDED BY ARMAFLEX OR EQUAL). INSULATE COPPER PIPE, ALL PIPE SIZES, WITH 1 INCH INSULATION CONDENSATE OVERFLOW, THE CONTROLS SHALL DISABLE ANY ACTIVE MECHANICAL COOLING AND GENERATE AN
REQUIREMENTS OF: MEET THE EQUIREMENTS OF NFPA 90A - MAXIMUM ASTM E-84 FIRE HAZARD RATING.
MECHANICAL CONTRACTOR. THICKNESS. THE CONDUCTIVITY (K-VALUE) SHALL BE 0.27 (BTU-IN / HR-SQ FT-DEG F) AT 75 DEGREES ALARM.
UNINSULATED FLEXIBLE DUCT SHALL BE EQUIVALENT TO FLEXMASTER TYPE 4. FLEXIBLE DUCT
F. MEAN TEMPERATURE. THE CONTRACTOR SHALL INSTALL THE INSULATION ACCORDING TO THE
1. FEDERAL OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA) CONNECTED TO INSULATED OR LINED DUCT SHALL BE INSULATED WITH 1-1/2", 1/2 LB. DENSITY
2.06 CONTROLS LATEST MANUFACTURER'S RECOMMENDATIONS AND INSTALLATION INSTRUCTIONS. FOR 4.05 WAREHOUSE CONTROLS
2. NFPA 70E - STANDARD FOR MECHANICAL SAFETY IN THE WORKPLACE FIBERGLASS INSULATION AND FLAME RETARDANT (UL LISTED) VAPOR BARRIER, MEETING
INSULATION LOCATED OUTDOORS, PROVIDE MANUFACTURER'S FINISH FOR WEATHER-PROOFING &
ASTM E-84 RATING. A. CONTROLS AND CONTROL COMPONENTS SHALL BE THE DIRECT DIGITAL TYPE AND SHALL BE UV PROTECTION (ARMAFLEX WB FINISH).
C. ALL WORK SHALL BE PERFORMED IN WORKMANLIKE MANNER. A. PROVIDE ALL CONTROLLERS/SENSORS TO EXECUTE THE FOLLOWING CONTROL SEQUENCES.
LOCAL CONTROLS PROVIDED BY EQUIPMENT MANUFACTURERS: MITSUBISHI, CARRIER, TRANE,
C. VOLUME DAMPERS DAIKIN OR APPROVED OWNER EQUAL.
D. ALL MATERIALS SHALL BE NEW AND LISTED BY A RECOGNIZED TESTING LABORATORY. SECTION 3 - EXECUTION B. MAKE-UP AIR/OCCUPIED MODE:
1
1. SUPPLY FAN AND BURNER SHALL RUN CONTINUOUSLY BASED ON OCCUPANCY SCHEDULE.
1. PROVIDE MANUAL ADJUSTABLE VOLUME DAMPERS, WITH EXTENDED MOUNT INDICATING AND LOCKING
B. CONTROLS SHALL BE INSTALLED BY COMPETENT CONTROL MECHANICS AND ELECTRICIANS 3.01 EXECUTION REQUIREMENTS 2. DISCHARGE TEMPERATURE MODULATES HEATER TO MAINTAIN SPACE SETPOINT (55 DEG F., ADJ).
1.04 DRAWINGS QUADRANTS ON EACH SUPPLY, RETURN, AND GENERAL EXHAUST DUCT TAKEOFF, AND AT EACH
REGULARLY EMPLOYED BY CONTROL EQUIPMENT MANUFACTURER. CONTROL EQUIPMENT SHALL 3. MODULATE RETURN AIR DAMPER BETWEEN MAXIMUM AND MINIMUM AIRFLOW TO MAINTAIN BUILDING
TAKEOFF TO A REGISTER, GRILLE, OR DIFFUSER (NOT ALL DAMPERS ARE SHOWN ON DRAWINGS).
BE COMMERCIAL GRADE. ATC CONTRACTOR SHALL HAVE RESPONSIBILITY FOR ALL CONTROL A. THE EXISTENCE AND LOCATION OF SITE IMPROVEMENTS, UTILITIES AND OTHER CONSTRUCTION PRESSURE. PROVIDE WITH DIFFERENTIAL PRESSURE CONTROLS/TUBING. MINIMUM OUTSIDE AIR DAMPER POSITION
A. THE DRAWINGS ARE DIAGRAMMATIC AND ILLUSTRATE THE APPROXIMATE LOCATIONS OF DAMPERS SHALL BE LOCATED AS FAR UPSTREAM AS POSSIBLE IN THE BRANCH DUCT OR TAKE OFF TO
ELEMENTS WHETHER HE MANUFACTURED THE COMPONENTS OR NOT. INDICATED AS EXISTING ARE NOT GUARANTEED. BEFORE BEGINNING WORK, INVESTIGATE AND SHALL BE SET FOR 6,000 CFM OA.
EQUIPMENT, DEVICES, DUCTWORK, AIR OUTLETS, AND ETCETERA. PRECISE LOCATIONS SHALL BE MINIMIZE DOWNSTREAM NOISE.
COORDINATED IN THE FIELD WITH THE PROJECT TEAM, ARCHITECTURAL DRAWINGS, AND THE VERIFY THE EXISTENCE AND LOCATION OF MECHANICAL AND ELECTRICAL SYSTEMS AND OTHER 4. HEATER WILL NOT OPERATE IF OUTDOOR TEMPERATURE IS ABOVE HEATING LOCKOUT SET POINT (55 DEG. F.,
D. DIFFUSERS, REGISTERS, AND GRILLES C. SCOPE OF WORK TO INCLUDE, BUT NOT BE LIMITED TO: CONSTRUCTION AFFECTING THE WORK. ADJ)
WORK OF ALL OTHER TRADES AS CONSTRUCTION PROCEEDS.

1. PROVIDE DIFFUSERS, REGISTERS, AND GRILLES FOR SUPPLY, RETURN, AND EXHAUST OUTLETS, OF 1) INTERFACE WITH ROOFTOP UNITS, AIR CONDITIONING UNITS AND ALL OTHER NEW EQUIPMENT. B. THE CONTRACTOR SHALL TAKE FIELD MEASUREMENTS AS REQUIRED TO FIT THE WORK 4.06 HEAT PUMP UNIT AND ASSOCIATED CONDENSING UNIT
B. THE CONTRACTOR SHALL VERIFY ALL INDICATED EXISTING CONDITIONS PRIOR TO STARTING
SIZE, TYPE, MATERIAL AND DESIGN SHOWN ON DRAWINGS. ACCEPTABLE MANUFACTURERS SHALL BE PROVIDE ALL NECESSARY PANELS, ACCESSORIES, WIRING, AND POWER REQUIREMENTS. PROPERLY. WHERE PORTIONS OF THE WORK ARE INDICATED TO FIT TO OTHER CONSTRUCTION,
WORK AND REPORT ANY DISCREPANCIES. THE DRAWINGS REFLECT CONDITIONS WHICH CAN BE
TUTTLE & BAILEY, ANEMOSTAT, KRUEGER, METALAIRE, PRICE OR TITUS. SOUND PRESSURE LEVELS INTERCONNECT CONTROL AND COMMUNICATION WIRING BETWEEN AIR CONDITIONING VERIFY DIMENSIONS OF OTHER CONSTRUCTION BY FIELD MEASUREMENTS BEFORE FABRICATION. A. THE VRF AC/HEAT PUMP UNIT SHALL MAINTAIN SPACE HEATING/COOLING SETPOINT THROUGH ITS INTEGRAL
REASONABLY INTERPRETED FROM THE EXISTING VISIBLE CONDITIONS OR FROM DRAWINGS AND
SHALL NOT EXCEED NC 30. COLOR AND FINISH SHALL BE SELECTED BY THE ARCHITECT. CONDENSING/HEAT PUMP UNITS, INDOOR AC UNITS, EXHAUST FANS, SUPPLY FANS, ELECTRIC CONTROLS AND THE ASSOCIATED ROOM THERMOSTAT. SUPPLY FANS SHALL OPERATE CONTINUOUSLY DURING OCCUPIED
INFORMATION FURNISHED BY THE OWNER.
HEATERS, THERMOSTATS, SPACE TEMPERATURE/HUMIDITY SENSORS, CONTROLLERS AND ALL C. THE CONTRACTOR SHALL VERIFY SPACE REQUIREMENTS OF ITEMS SHOWN DIAGRAMMATICALLY MODE AND MODULATE HEATING/COOLING AS REQUIRED TO MAINTAIN SPACE TEMPERATURE.
E. DUCT INSULATION (EXTERNAL) OTHER EQUIPMENT AS REQUIRED. ON DRAWINGS. IMMEDIATELY ON DISCOVERY OF THE NEED FOR CLARIFICATION OF THE CONTRACT B. COOLING OCCUPIED SETPOINT: 75 DEG. F. (ADJ.)
1.05 SUBMITTALS
DOCUMENTS, SUBMIT A REQUEST FOR INFORMATION TO THE ENGINEER. INCLUDE A DETAILED C. COOLING UNOCCUPIED SETPOINT: 80 DEG. F. (ADJ.)
1. INSULATION SHALL BE CERTAIN-TEED, KNAUF, MANVILLE, OR OWENS CORNING. MATERIALS 2) THE INSTALLATION OF CONTROL DEVICES INCLUDING PANELS, THERMOSTATS, AND SENSORS DESCRIPTION OF THE PROBLEM ENCOUNTERED, TOGETHER WITH RECOMMENDATIONS FOR D. HEATING OCCUPIED SETPOINT: 70 DEG. F. (ADJ.)
A. PREPARE AND SUBMIT FOUR (4) COPIES OF THE SUBMITTALS TO THE ARCHITECT AND/OR
SHALL MEET REQUIREMENTS OF ADHESIVE AND SEALANT COUNCIL STANDARDS AND SMACNA. PROVIDED BY EQUIPMENT MANUFACTURER. CHANGING THE CONTRACT DOCUMENTS. E. HEATING UNOCCUPIED SETPOINT: 65 DEG. F. (ADJ.)
ENGINEER FOR THE FOLLOWING: PERFORMANCE DATA AND MATERIAL SPECIFICATIONS FOR ALL
EQUIPMENT LISTED IN SCHEDULES/SPECIFICATIONS, DIMENSIONED SHEET METAL DRAWINGS, INSULATE SUPPLY AND FRESH AIR DUCTS AND PLENUMS AND RETURN DUCT NOT IN CEILING
PLENUM WITH AT LEAST 1 1/2" THICK, 3/4 LB/CU.FT. (MINIMUM R VALUE OF 5) DENSITY, FIBROUS 3) COORDINATION OF EQUIPMENT MANUFACTURER'S CONTROLS AND SYSTEM OPERATION. START D. THE CONTRACTOR SHALL INSTALL VERTICAL WORK PLUMB AND HORIZONTAL WORK LEVEL 4.07 ELECTRIC REHEAT COIL
DIMENSIONED PIPING DRAWINGS, MATERIAL SPECIFICATIONS FOR ITEMS LISTED IN PRODUCTS
GLASS DUCT WRAP, WITH FOIL-KRAFT FLAME RESISTANT VAPOR BARRIER. ASTM E-84 FIRE HAZARD UP AND ADJUSTMENT OF ALL CONTROLS. UNLESS OTHERWISE INDICATED. WHERE SPACE IS LIMITED, INSTALL COMPONENTS TO MAXIMIZE
SECTION, SEQUENCE OF OPERATIONS AND MATERIAL SPECIFICATIONS FOR AUTOMATIC
TEMPERATURE CONTROLS, AND TESTING, ADJUSTING, AND BALANCING REPORT. RATINGS SHALL BE 25 FLAME SPREAD. 50 SMOKE DEVELOPED AND 50 FUEL CONTRIBUTED. SPACE AVAILABLE FOR MAINTENANCE AND EASE OF REMOVAL FOR REPLACEMENT. CONCEAL PIPES, A. THE ELECTRIC REHEAT COIL SHALL BE CONTROLLED BY A DUCT MOUNTED TEMPERATURE SENSOR. INCREASE
D. PROVIDE FOR THE COORDINATION OF SERVICES BY THE EQUIPMENT MANUFACTURER'S DUCTS, WIRING, ETC, IN FINISHED AREAS UNLESS OTHERWISE INDICATED. HEATING STAGES TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT.
F. SEALANT MATERIALS REPRESENTATIVE ON SITE DURING THE ENTIRE TIME THAT THE STARTUP, TESTING, AND BALANCING B. OUTDOOR AIR INTAKE HEATER SETPOINT: 20 DEG. F. (ADJ.)
B. CONTRACTOR SHALL PREPARE AND SUBMIT FOUR (4) COPIES OF PROJECT SPECIFIC
PROCEDURES TAKES PLACE. E. THE CONTRACTOR SHALL COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND
COORDINATION DRAWINGS DRAWN ACCURATELY TO SCALE FOR AREAS INDICATED. DO NOT BASE
COORDINATION DRAWINGS ON REPRODUCTIONS OF THE CONTRACT DOCUMENTS OR STANDARD 1. JOINT AND SEAM TAPE SHALL BE 2-INCHES WIDE; GLASS-FIBER REINFORCED FABRIC. RECOMMENDATIONS FOR INSTALLING PRODUCTS IN APPLICATIONS INDICATED. 4.08 ENERGY RECOVERY UNIT
2. TAPE SEALING SYSTEM SHALL BE WOVEN-FIBER TAPE IMPREGNATED WITH GYPSUM MINERAL E. ELECTRICAL WIRING AND WIRING CONNECTIONS REQUIRED FOR INSTALLATION OF
PRINTED DATA. INDICATE FUNCTIONAL AND SPATIAL RELATIONSHIPS OF COMPONENTS OF
COMPOUND AND MODIFIED ACRYLIC/SILICONE ACTIVATOR TO REACT EXOTHERMICALLY WITH TAPE TEMPERATURE CONTROL SYSTEMS AS SPECIFIED HEREIN SHALL BE PROVIDED BY THE ATC F. THE CONTRACTOR SHALL PROVIDE ANCHORS AND FASTENERS AS REQUIRED TO ANCHOR EACH A. THE ENERGY RECOVERY UNITS SHALL BE ENABLED THROUGH ITS INTEGRAL TIME CLOCK.
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL AND ELECTRICAL SYSTEMS. INDICATE
TO FORM HARD, DURABLE AIRTIGHT SEAL CONTRACTOR, UNLESS OTHERWISE INDICATED ON THE DRAWINGS. WIRING SHALL COMPLY WITH COMPONENT SECURELY IN PLACE, LOCATED AND ALIGNED WITH OTHER PORTIONS OF THE WORK. UPON BEING ENABLED, THE MOTOR OPERATED DAMPERS SHALL OPEN AND THE FANS SHALL BE ENABLED.
DIMENSIONS AND MAKE SPECIFIC NOTE OF DIMENSIONS THAT APPEAR TO BE IN CONFLICT WITH
3. WATER-BASED JOINT AND SEAM SEALANT SHALL BE FLEXIBLE, ADHESIVE SEALANT, RESISTANT NEC CODES AND THE ELECTRICAL SPECIFICATION. ALLOW FOR BUILDING MOVEMENT, INCLUDING THERMAL EXPANSION AND CONTRACTION.
SUBMITTED EQUIPMENT AND MINIMUM CLEARANCE REQUIREMENTS.
TO UV LIGHT WHEN CURED, UL 723 LISTED, AND COMPLYING WITH NFPA REQUIREMENTS FOR CLASS COORDINATE INSTALLATION OF ANCHORAGES THAT ARE EMBEDDED IN CONCRETE OR MASONRY.
1 DUCTS. 2.07 FIRESTOP SYSTEMS
C. SUBMITTALS SHALL BE NEATLY PREPARED WITH THE INFORMATION SUBMITTED PERMANENTLY 1
BOUND. SUBMITTALS SHALL INCLUDE A COVER PAGE, A TABLE OF CONTENTS, AND NUMBERED 4. SOLVENT BASED JOINT AND SEAM SEALANT SHALL BE ONE PART, NONSAG, G. THE CONTRACTOR SHALL MAINTAIN WORK AREA FREE OF WASTE MATERIALS AND DEBRIS.
SOLVENT-RELEASE-CURING, POLYMERIZED BUTYL SEALANT FORMULATED WITH A MINIMUM 75 A. FURNISH AND INSTALL FIRESTOP SYSTEMS BY HILTI, JOHNS MANVILLE, SPECIFIED TECHNOLOGIES INCORPORATED REMOVE DEBRIS FROM CONCEALED SPACES BEFORE THE SPACE IS ENCLOSED.
PAGES. THE INFORMATION CONTAINED WITHIN THE SUBMITTAL SHALL BE CLEARLY MARKED AS TO
PERCENT SOLIDS. (STI), OR 3M; FIRE PROTECTION PRODUCTS DIVISION. THROUGH-PENETRATION FIRESTOP SYSTEMS SHALL HAVE
INDICATE THE PRODUCTS, FEATURES AND/OR ACCESSORIES BEING FURNISHED OR PROVIDED.
5. FLANGED JOINT MASTIC SHALL BE ONE-PART, ACID-CURING, SILICONE, ELASTORMERIC JOINT RATINGS DETERMINED PER ASTM E 814 AND UL 1479. H. THE CONTRACTOR SHALL START EQUIPMENT AND OPERATING COMPONENTS TO CONFIRM
CLEARLY INDICATE, MARK OR OTHERWISE IDENTIFY WHERE THE SUBMITTED INFORMATION
DEVIATES FROM THE CONTRACT DOCUMENTS. SUBMITTAL NOT CONFORMING TO THESE SEALANT COMPLYING WITH ASTM C 920, TYPE S, GRADE NS, CLASS 25, USE O. PROPER OPERATION. REMOVE MALFUNCTIONING UNITS, REPLACE WITH NEW UNITS, AND RETEST.
6. FLANGE GASKETS SHALL BE BUTYL RUBBER OR EPDM POLYMER WITH POLYISOBUTYLENE 2.08 ROOFTOP UNITS
REQUIREMENTS MAY BE REJECTED AND RETURNED.
PLASTICIZER. I. THE CONTRACTOR SHALL ADJUST OPERATING COMPONENTS FOR PROPER OPERATION WITHOUT
A. ROOFTOP UNITS SHALL BE SELF-CONTAINED COOLING WITH GAS HEAT, COMPLETE WITH AIR HANDLING AND PROJECT:
D. A SEPARATE SUBMITTAL SHALL BE SUBMITTED FOR EACH SUBMITTAL REQUIREMENT. COMBINED BINDING. ADJUST EQUIPMENT FOR PROPER OPERATION.
G. HANGERS AND SUPPORTS CONDENSING SECTIONS INCLUDING FANS, COMPRESSORS, COILS, PIPING, AND WIRING, WITH SINGLE POINT POWER
SUBMITTALS MAY BE REJECTED AND RETURNED.

E. SUBMITTAL REQUESTING APPROVAL FOR THE SUBSTITUTION OF EQUIPMENT AND MATERIALS 1. BUILDING ATTACHMENTS SHALL BE CONCRETE INSERTS, POWDER ACTUATED FASTENERS, OR
STRUCTURAL STEEL FASTENERS APPROPRIATE FOR CONSTRUCTION MATERIALS TO WHICH
AND GAS CONNECTIONS.

B. UNITS SHALL BE FULLY CHARGED WITH R-407C OR R-410A AND FACTORY TESTED. UNITS SHALL BE UL
J. TEST EACH PIECE OF EQUIPMENT TO VERIFY PROPER OPERATION. TEST AND ADJUST CONTROLS
AND SAFETIES. REPLACE DAMAGED AND MALFUNCTIONING CONTROLS AND EQUIPMENT. MARCUS PARTNERS
FROM THAT WHICH HAS BEEN SPECIFIED SHALL BE SUBMITTED SEPARATELY IN ADVANCE OF, AND
HANGERS ARE BEING ATTACHED. APPROVED, AND COOLING CAPACITIES SHALL BE IN ACCORDANCE WITH ARI STANDARD 360. 3.02 TESTING, ADJUSTING AND BALANCING (TAB)
IN ADDITION TO ANY REQUIRED SUBMITTAL IN ACCORDANCE WITH THE SUBSTITUTIONS SECTION OF
THIS SPECIFICATION. REQUIRED SUBMITTALS CONTAINING SUBSTITUTIONS MAY BE REJECTED AND
RETURNED.
2. HANGER MATERIALS SHALL BE GALVANIZED SHEET STEEL OR THREADED STEEL ROD COMPLYING
WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE.
3. DUCT ATTACHMENTS SHALL BE SHEET METAL SCREWS, BLIND RIVETS, OR SELF TAPPING METAL
C.

D.
CASING SHALL BE HEAVY GAUGE GALVANIZED STEEL AND FINISHED WITH A WEATHER RESISTANT PAINT.

ALL MOTORS SHALL BE HIGH EFFICIENCY TYPE. FAN/MOTOR ASSEMBLY SHALL BE STATICALLY AND
A. PROVIDE TAB SERVICES BY AN INDEPENDENT TAB CONTRACTOR NEBB OR AABC CERTIFIED.
TESTING AND BALANCING OF SYSTEMS SHALL NOT BEGIN UNTIL INSTALLER HAS CERTIFIED THAT
WAREHOUSE BUILDING
F. SUBMITTALS RECEIVED DIRECTLY FROM SUPPLIERS OR MANUFACTURERS WHICH DO NOT BEAR SCREWS; COMPATIBLE WITH DUCT MATERIALS. THE JOB IS COMPLETE.
4. TRAPEZE AND RISER SUPPORTS SHALL BE GALVANIZED STEEL SHAPES COMPLYING WITH ASTM A DYNAMICALLY BALANCED.
THE STAMP OF THE CONTRACTOR INDICATING THAT THE CONTRACTOR HAS REVIEWED THE
SUBMITTAL FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS MAY BE REJECTED AND 36.
E. UNIT SHALL INCLUDE MULTIPLE COMPRESSORS, HERMETIC, ROTARY SCROLL TYPE WITH EXTERNAL SPRING
B. THE INDEPENDENT TESTING CONTRACTOR SHALL PROVIDE QUALIFIED PERSONNEL, EQUIPMENT,
APPARATUS, AND SERVICES FOR STARTUP, TESTING, AND BALANCING OF MECHANICAL SYSTEMS,
5 MANLEY ST.
RETURNED.

G. THE ENGINEER'S REVIEW OF SUBMITTALS IS A COURTESY AND DOES NOT RELIEVE THE
H. FLEXIBLE CONNECTIONS VIBRATION ISOLATION, CRANK CASE HEATER, CENTRIFUGAL OIL PUMP AND OIL LEVEL SIGHT GLASS. TO PERFORMANCE DATA SHOWN ON PLANS AND SCHEDULES, AS SPECIFIED, AND AS REQUIRED BY
CODES, STANDARDS, REGULATIONS, AND AUTHORITIES HAVING JURISDICTION, INCLUDING CITY, WEST BRIDGEWATER, MA
1. PROVIDE NEOPRENE-COATED FLAMEPROOF FABRIC CRIMPED INTO DUCT FLANGES FOR ATTACHMENT TO DUCT F. SUPPLY FAN: SHALL BE CENTRIFUGAL DIRECT OR BELT DRIVEN TYPE. THE ENTIRE FAN/MOTOR ASSEMBLY TOWN, OR COUNTY INSPECTORS. ENSURE THAT ALL CONTRACTORS ARE AVAILABLE ONSITE
CONTRACTOR FROM CONFORMING TO THE REQUIREMENTS OF THE CONTRACT DOCUMENTS, CONSTRUCTION MANAGER:
AND EQUIPMENT. PROVIDE FLEXIBLE CONNECTIONS WHERE DUCTWORK CONNECTS TO EQUIPMENT OR WHERE SHALL BE COMPLETED ISOLATED FROM UNIT BY 2-INCH SPRING ISOLATORS AND FLEXIBLE DUCT CONNECTIONS. DURING THE ENTIRE TIME THESE PROCEDURES TAKE PLACE. ENSURE THAT ANY LISTED ORDERS OF
REGARDLESS OF THE ACTION INDICATED BY THE SUBMITTAL'S STAMP.
DUCTWORK CROSSES A BUILDING EXPANSION JOINT. PROVIDE ADEQUATE JOINT FLEXIBILITY TO ALLOW FOR PRECEDENCE OR PROCEDURES ARE FOLLOWED.
THERMAL, AXIAL, TRANSVERSE, TORSIONAL MOVEMENT, AND CAPABLE OF ABSORBING VIBRATION. MAKE JOINT G. CONDENSER FANS SHALL BE DIRECT DRIVEN, PROPELLER TYPE, MADE OF CORROSION RESISTANT BLADES
H. REVIEW OF SUBMITTALS BY THE ENGINEER SHALL BE LIMITED TO THE INITIAL REVIEW, AND A
AIRTIGHT. RIVETED TO CORROSION RESISTANT STEEL SUPPORTS, AND WITH SAFETY GUARDS. FAN MOTORS SHALL HAVE C. NOTIFY THE ENGINEER AND AUTHORITIES INVOLVED AT LEAST TWO WEEKS BEFORE STARTUP,
SECOND REVIEW OF ANY REQUIRED RESUBMITTED INFORMATION. IF THE ENGINEER IS REQUIRED
PERMANENTLY LUBRICATED BALL BEARINGS. TESTING AND BALANCING BEGINS.
TO REVIEW INFORMATION FOR A THIRD (OR MORE) SUBMISSION OF THE SAME SUBMITTAL, THE
CONTRACTOR SHALL BE LIABLE FOR COMPENSATING THE ENGINEER FOR THE ADDITIONAL TIME I. DUCT ACCESS DOORS
H. THE FILTER SECTION SHALL CONSIST OF 2-INCH DEEP PLEATED TYPE MERV 8/13 FILTERS (AS SCHEDULED) D. DESCRIPTION OF WORK
AND REIMBURSABLE EXPENSES OCCURRED BY THESE SUBSEQUENT REVIEWS IN ACCORDANCE
1. DUCT ACCESS DOORS SHALL BE CONSTRUCTED OF THE SAME MATERIAL AS THE DUCT IN WHICH THEY ARE WITH EFFICIENCY PER ASHRAE STANDARD 52-76.
WITH THE ENGINEER'S CURRENT SCHEDULE OF FEES.
INSTALLED AND SHALL BE THE SAME OR GREATER GAUGE AS THE DUCTWORK SERVED. INSULATED DOORS SHALL BE 1. BALANCE ALL ROOFTOP UNITS, VAV BOXES, AC UNITS, FANS, DAMPERS, DIFFUSERS, GRILLES,
INSTALLED IN INSULATED DUCTWORK. FLUSH FRAMES SHALL BE PROVIDED FOR UNINSULATED DUCTWORK. I. THE EVAPORATOR AND CONDENSER COILS SHALL HAVE ALUMINUM PLATE FINS MECHANICALLY BONDED TO AND REGISTERS NOTED WITH AIRFLOWS TO THE CAPACITY INDICATED (±10%).
1.06 SUBSTITUTIONS
EXTERNAL FRAMES SHALL BE PROVIDED FOR EXTERNALLY INSULATED DUCTS. ONE SIDE OF DOOR SHALL BE HINGED SEAMLESS COPPER TUBES WITH ALL JOINTS BRAZED. THE CONDENSER COILS SHALL BE PROVIDED WITH COIL GUARD 633 DIVISION ST. ELIZABETH, NJ 07201
AND THE AND THE OTHER SIDE SHALL BE PROVIDED WITH MINIMUM ONE LEVER LATCH. TO PREVENT DAMAGE. 2. ADJUST AND BALANCE FANS TO PROVIDE CAPACITY AS REQUIRED TO MEET THE AIRFLOW
A. ALL EQUIPMENT AND MATERIALS FURNISHED AND/OR PROVIDED SHALL BE AS SPECIFIED AND
PRODUCTS OF THE NAMED MANUFACTURER(S) IN THE CONTRACT DOCUMENT. THE CONTRACTOR 2. AT A MINIMUM ACCESS DOORS SHALL BE INSTALLED UPSTREAM OR DOWNSTREAM OF DUCT MOUNTED FIRE AND REQUIREMENTS OF THE PROJECT. ADJUST AND/OR REPLACE FAN DRIVES AND MAKE SHEAVE ARCHITECT:
SMOKE DAMPERS, AT CONTROL DAMPERS, SMOKE DETECTORS AND SENSOR INSTALLATION LOCATIONS. J. THE FOLLOWING FEATURES SHALL BE INCLUDED AND INTERNALLY WIRED; POWER EXHAUST FAN FOR CHANGES AS REQUIRED.
MAY REQUEST AN APPROVAL TO FURNISH AND/OR PROVIDE EQUIPMENT OR MATERIALS THAT ARE
3. ACCEPTABLE MANUFACTURERS: AIR BALANCE, INC., RUSKIN COMPANY, VENTFABRICS, INC., OR APPROVED EQUAL. ECONOMIZER OPERATION, RETURN SMOKE DETECTOR AND CARBON MONOXIDE DETECTOR FOR UNIT SHUT DOWN
DIFFERENT OR POSSESSES DIFFERENT FEATURES AND/OR ACCESSORIES THAN THOSE SPECIFIED,
UPON DETECTION OF SMOKE/CO, MOTOR OPERATORS FOR OUTSIDE AIR DAMPER. 3. COORDINATE WITH THE ALL OF THE TRADES TO ASSURE THAT ALL WORK IS COMPLETED AND
OR ARE A PRODUCT OF A MANUFACTURER OTHER THAN THOSE NAMED.
J. FIRE DAMPERS OPERATIONAL PRIOR TO STARTING TAB. rkb architects, inc.
K. THE GAS HEATING SECTION SHALL HAVE UNIT INTEGRATED CONTROLS. THE HEAT EXCHANGER SHALL BE OF
B. ALL SUBSTITUTION APPROVAL REQUESTS SHALL BE BY WRITTEN SUBMITTAL FOR EACH
TUBULAR DESIGN CONSTRUCTED OF STAINLESS STEEL AND BE COMPLETE WITH COMBUSTION BLOWER, IGNITION
zero campanelli drive, braintree, ma 02184
INDIVIDUAL SUBSTITUTION IN ACCORDANCE WITH THE SUBMITTAL REQUIREMENTS OF THIS 1.ACCEPTABLE MANUFACTURERS: AIR BALANCE INC., GREENHECK, NAILOR INDUSTRIES, INC., PENN VENTILATION 4. MAKE AIR QUANTITY MEASUREMENTS IN DUCTS BY PITOT TUBE TRAVERSES OF THE ENTIRE
COMPANY, INC., RUSKIN COMPANY, OR APPROVED EQUAL. SYSTEM AND CONTROLS. CROSS-SECTIONAL AREA OF THE DUCT. p 781.848.6600 f 781.848.6660 w rkbarch.com
SPECIFICATION.
2. FIRE DAMPERS SHALL BE LABELED ACCORDING TO UL FIRE RATING.
3. CURTAIN TYPE FRAME WITH BLADES OUTSIDE AIRSTREAM FABRICATED WITH ROLL-FORMED 0.034-INCH THICK L. THE UNIT SHALL BE PROVIDED WITH COMPLETELY FACTORY WIRED CONTROL SYSTEM MOUNTED IN THE MAIN 5. PROVIDE BALANCING REPORT TO THE ENGINEER FOR REVIEW.
C. SUBSTITUTION REQUEST SUBMITTALS SHALL CONTAIN THE PRODUCT DATA AND SHOP
GALVANIZED STEEL WITH MITERED AND INTERLOCKING CORNERS. CONTROL PANEL INCLUDING ALL CONTROL DEVICES, DISCONNECT SWITCH AND TRANSFORMERS. CONTROL
DRAWINGS SPECIFIED IN THE SUBMITTAL SECTION AND A LETTER OF EXPLANATION ON THE
4. FACTORY OR FIELD-INSTALLED GALVANIZED SHEET STEEL MOUNTING SLEEVE, WITH 0.052 MINIMUM THICKNESS FEATURES TO INCLUDE COOLING AND HEATING CONTROL INTERFACE, ANTI-SHORT CYCLING COMPRESSOR SECTION 4 - SEQUENCE OF OPERATION
CONTRACTOR'S LETTERHEAD STATING THE CONTRACTOR'S REASONS FOR THE REQUEST, THE
AND OF LENGTH TO SUIT APPLICATION. CONTROL, ECONOMIZER CONTROL, AND FAN CONTROLS. UNIT WIRING SHALL BE TERMINATED AT A DEDICATED
BENEFITS THAT THIS SUBSTITUTION WILL PROVIDE OVER THE SPECIFIED ITEM AND THE COST COPYRIGHT © BY RKB Architects Inc. ALL RIGHTS RESERVED
5. MOUNT VERTICALLY OR HORIZONTALLY AS INDICATED. TERMINAL STRIP FOR A SINGLE POINT OF POWER CONNECTION. 4.01 ROOFTOP UNITS (RTU-1) NO PART OF THIS DOCUMENT MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY
IMPLICATIONS TO THE CONTRACT.
6. FUSIBLE LINKS: REPLACEABLE, 165 DEG. FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE, WITHOUT
THE EXPRESS WRITTEN CONSENT OF RKB Architects Inc. ANY MODIFICATIONS MADE TO THIS DOCUMENT WITHOUT
M. MANUFACTURERS: CARRIER, TRANE, AAON OR DAIKIN. A. OCCUPIED COOLING MODE
D. THE ARCHITECT AND/OR ENGINEER SHALL DETERMINE THE ACCEPTABILITY OF ANY THE WRITTEN PERMISSION OF RKB Architects Inc. SHALL RENDER IT INVALID AND UNUSABLE.

SUBSTITUTIONS. K. INSTALLATION OF DUCT ACCESSORIES


N. INSTALL UNITS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS. 1. WHEN THE ROOFTOP UNIT (RTU) IS IN THE OCCUPIED COOLING MODE, THE SUPPLY FAN WILL OPERATE
E. IF APPROVED, THE CONTRACTOR ASSUMES ALL RESPONSIBILITY FOR COORDINATING THE WORK 1. DUCT ACCESSORIES SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS. CONTINUOUSLY AND MAINTAIN A CONSTANT AIRFLOW. AS REQUIRED, THE DX COOLING SHALL BE
APPLICABLE DETAILS OF CONSTRUCTION SHALL BE AS SHOWN IN SMACNA STANDARDS AND IN ACCORDANCE WITH 2.09 ROOFING & ROOFTOP ACCESSORIES STAGED/MODULATED OR THE NATURAL GAS HEATING SHALL BE MODULATED AND THE DAMPERS (OUTSIDE, RETURN,
OF OTHER TRADES WHICH MAY BE AFFECTED BY SUBSTITUTIONS, INCLUDING ALL RELATED COSTS.
RECOGNIZED INDUSTRY PRACTICES. AND RELIEF AIR) SHALL BE MODULATED IN SEQUENCE TO MAINTAIN THE SPACE AIR TEMPERATURE.
A. FURNISH AND INSTALL ROOFTOP ACCESSORIES AS MANUFACTURED BY CUSTOM CURB, THE PATE COMPANY,
1.07 AS-BUILT DRAWINGS
2.02 EXHAUST FANS ROOF PRODUCTS & SYSTEMS (RPS) CORPORATION, OR THYCURB FOR ALL DUCT ROOF CURBS, EQUIPMENT B. UNOCCUPIED MODE
SUPPORTS, PIPE CURB ASSEMBLIES, PIPE PORTALS, PIPE MOUNTING PEDESTALS, AND DUCT MOUNTING PEDESTALS.
A. THE CONTRACTOR SHALL PREPARE AND SUBMIT, AS AN INFORMATIONAL SUBMITTAL, RECORD
AS-BUILT DRAWINGS AFTER COMPLETION OF THE WORK INDICATING ALL ALTERATIONS, ADDITIONS A. ACCEPTABLE MANUFACTURERS ARE GREENHECK, PENN VENTILATION, AND COOK FANS. 1. WHEN THE RTU IS IN THE UNOCCUPIED MODE (AND SPACE TEMPERATURES DON'T DROP BELOW THE HEATING
B. COMPLY WITH NRCA (NATIONAL ROOFING CONTRACTORS ASSOCIATION) STANDARDS, MANUALS, AND DETAILS. NIGHT SETBACK TEMPERATURE SETPOINT OR EXCEED THE COOLING NIGHT-STEP-UP TEMPERATURE SETPOINT), THE
AND/OR DELETIONS TO THE SYSTEMS AS DESIGNED AND AS SHOWN ON THE CONTRACT
DOCUMENTS. B. CEILING MOUNTED FAN SHALL BE OF THE CENTRIFUGAL DIRECT DRIVE TYPE. THE FAN HOUSING SHALL BE SUPPLY FAN SHALL BE OFF. THE OUTSIDE AND RELIEF AIR DAMPER SHALL BE CLOSED. THE DX COOLING SHALL BE
CONSTRUCTED OF STEEL. THE STEEL DUCT COLLAR SHALL INCLUDE A BACKDRAFT DAMPER. THE GRILLE SHALL BE C. ALL WORK PERFORMED IN CONNECTION WITH NEW EQUIPMENT ON ROOF SHALL BE PERFORMED AND DISABLED. THE NATURAL GAS HEATING SHALL BE DISABLED.
CONSTRUCTED OF ALUMINUM WITH A WHITE ENAMEL FINISH AND ATTACHED TO THE HOUSING WITH HIDDEN INSTALLED IN ACCORDANCE WITH ROOF MANUFACTURER'S RECOMMENDATIONS. CONTRACTOR SHALL PAY FOR AND
1.08 OPERATION AND MAINTENANCE MANUALS MEP ENGINEER:
ATTACHMENT SCREWS. THE MOTOR DISCONNECT SHALL BE INTERNAL. PROVIDE CONTROL DEVICES AS INDICATED. ARRANGE FOR SERVICES OF AUTHORIZED REPRESENTATIVE OF ROOFING MANUFACTURER TO INSPECT ALL WORK C. NIGHT SETBACK / MORNING WARM-UP HEATING/COOLING MODE
PROVIDE FLEXIBLE DUCT CONNECTION BETWEEN FAN AND DUCTWORK. AFFECTING ROOF AND SHALL OBTAIN STATEMENT OF CONTINUATION OF ROOF WARRANTY FROM MANUFACTURER.
A. PREPARE AND SUBMIT, AS AN INFORMATIONAL SUBMITTAL, OPERATION AND MAINTENANCE
MANUALS FOR EACH INDIVIDUAL SPECIFICATION SECTION BELOW. 1. WHEN THE RTU IS IN THE NIGHT SETBACK / MORNING WARM-UP HEATING/COOLING MODE, THE SUPPLY FAN
C. FANS SHALL BE BELT DRIVE OR ECM MOTOR AS SCHEDULED. 1 2.10 VRF UNITS WILL OPERATE CONTINUOUSLY, THE VFD WILL MODULATE TO MAINTAIN THE DUCT STATIC PRESSURE, THE OUTDOOR
B. OPERATION AND MAINTENANCE MANUAL SUBMITTALS SHALL BE PREPARED ON A JOB SPECIFIC AIR AND RELIEF AIR DAMPER WILL BE CLOSED, THE DX COOLING SHALL BE DISABLED FOR MORNING WARMUP, THE
1 03.17.2023 TENANT CHANGES
D. EACH FAN SHALL BEAR A PERMANENTLY AFFIXED MANUFACTURER'S ENGRAVED METAL NAMEPLATE A. FURNISH & INSTALL SPLIT SYSTEM AIR CONDITIONERS WITH REMOTE OUTDOOR UNITS AS RETURN DAMPER WILL BE FULLY OPEN, AND THE NATURAL GAS HEATING WILL BE MODULATED TO MAINTAIN THE
BASIS WITH ALL SUBMITTED INFORMATION PLACED HEAVY-DUTY 3-RING BINDERS. BINDERS SHALL - 9.9.2022 PERMIT SET
CONTAINING THE MODEL NUMBER AND INDIVIDUAL SERIAL NUMBER. MANUFACTURED BY MITSUBISHI OR APPROVED EQUAL. SEE EQUIPMENT SCHEDULE FOR MAXIMUM HEATING DISCHARGE AIR TEMPERATURE SET POINT. DURING MORNING COOL DOWN, THE NATURAL GAS
BE LABELED WITH JOB-SPECIFIC INFORMATION AND IDENTIFY THE TYPE OF EQUIPMENT FURNISHED REVISIONS
REQUIREMENTS AND SPECIFICATION DETAILS. HEATER SHALL BE DISABLED, THE RETURN DAMPER WIL LBE FULLY OPEN AND THE DX COOLING WILL BE MODULATED
AND/OR PROVIDED.
E. ALL FANS SHALL BEAR THE AMCA SOUND AND AIR PERFORMANCE SEAL. TO MAINTIAIN THE MINIMUM COOLING DISCHARGE AIR TEMPERATURE SETPOINT. THE UNIT SHALL SIGNAL TO FULL PROJECT NO: 2216
1.09 TESTING AND COMMISSIONING
F. THE FAN WHEEL SHALL BE CENTRIFUGAL NON-OVERLOADING BACKWARD-INCLINED, CONSTRUCTED OF
2.11 ELECTRIC HEATING COIL FLOW UNTIL THE MORNING WARM-UP/COOLING SET POINT IS REACHED AND THE RTU RETURNS TO OCCUPIED MODE.
STONERIDGE SCALE: AS NOTED
ALUMINUM AND SHALL INCLUDE A WHEEL CONE CAREFULLY MATCHED TO THE INLET CONE FOR PRECISE RUNNING A.PROVIDE ELECTRIC HEATING COIL OF CAPACITIES INDICATED. COILS SHALL BE GRADE A COILED RESISTANCE WIRE E. ECONOMIZER POWER EXHAUST FAN
A. AT THE COMPLETION OF THE MECHANICAL WORK, COMPLETELY TEST THE ENTIRE MECHANICAL
TOLERANCES. WHEELS SHALL BE STATICALLY AND DYNAMICALLY BALANCED IN ACCORDANCE TO AMCA STANDARD OF 80% NICKEL, 20% CHROMIUM; SURROUNDED BY COMPACTED MAGNESIUM-OXIDE POWDER IN TUBULAR-STEEL ENGINEERING DRAWN BY: RAA
INSTALLATION FOR PROPER OPERATION. CORRECT ALL DEFICIENCIES FOUND.
204-05. SHEATH; WITH SPIRAL-WOUND, COPPER PLATED, STEEL FINS CONTINUOUSLY BRAZED TO SHEATH. 1. INSTALL A BUILDING DIFFERENTIAL PRESSURE SENSOR AND CONNECT TO RTU TO CONTROL EXHAUST FAN 1583 LIVINGSTON AVENUE, SUITE #4 ISSUE DATE: 9.9.2022
B. PERFORM ADDITIONAL TESTING AND COMMISSIONING AS REQUIRED BY THE INDIVIDUAL SPEED. THE POWER EXHAUST FAN SHALL MODULATE TO MAINTAIN BUILDING PRESSURIZATION. NORTH BRUNSWICK, NJ 08902 SHEET TITLE:
G. MOTORS SHALL BE HEAVY-DUTY BALL BEARING-TYPE, CAREFULLY MATCHED TO THE FAN LOAD AND B. ELECTRIC HEATER CONTROLS TO INCLUDE AUTOMATIC AND MANUAL THERMAL CUTOUTS, AIRFLOW SWITCH Tel. (732) 658-6302
SPECIFICATION SECTIONS BELOW.
FURNISHED AT THE SPECIFIED VOLTAGE, PHASE AND ENCLOSURE. DRIVES SHALL BE SIZED FOR A MINIMUM OF 150% WITH STAGES AS SCHEDULED, CONTACTORS, FUSES, CONTROL TRANSFORMER DOOR INTERLOCK DISCONNECT 2. THE EXHAUST FAN SHALL BE CAPABLE OF 100% POWER EXHAUST WITH OUTSIDE AIR TRACKING. SRE PROJECT NUMBER 22067
SWITCH.
C. PREPARE AND SUBMIT, AS AN INFORMATIONAL SUBMITTAL, CERTIFICATES OF COMPLETION AND
TEST REPORTS AS REQUIRED BY THE INDIVIDUAL SPECIFICATION SECTIONS BELOW.
OF DRIVEN HORSEPOWER. MOTORS AND DRIVES SHALL BE MOUNTED ON TRUE VIBRATION ISOLATORS, OUT OF THE
AIRSTREAM. FRESH AIR FOR MOTOR COOLING SHALL BE DRAWN INTO THE MOTOR COMPARTMENT FROM AN AREA
2.12 CONDENSATE DRAIN PIPING
F. ECONOMIZER DIFFERENTIAL ENTHALPY CONTROL ENGINEER'S SEAL: HVAC
FREE OF DISCHARGE CONTAMINANTS. MOTORS SHALL BE READILY ACCESSIBLE FOR MAINTENANCE. TRUE VIBRATION
1.10 TRAINING ISOLATORS SHALL BE DOUBLE-STUDDED OR PEDESTAL MOUNT WITH NO METAL TO METAL CONTACT. EACH
VIBRATION ISOLATOR SHALL BE SIZED TO MATCH THE WEIGHT OF EACH FAN. A. CONDENSATE DRAIN LINES: TYPE L DRAWN-TEMPER COPPER TUBING WITH SOLDERED
1. WHEN THE OUTDOOR AIR ENTHALPY IS LESS THAN THE CHANGEOVER SET POINT, THE OUTDOOR AIR DAMPER
WILL MODULATE BETWEEN THE ADJUSTABLE MINIMUM POSITION AND FULL OPEN TO MAINTAIN THE DISCHARGE AIR ROBERT D. CIOFFI
SPECIFICATIONS
JOINTS FOR INDOOR PIPING WITHIN THE BUILDING. AIR CONDITIONING CONDENSATE PIPING SHALL TEMPERATURE AT THE ECONOMIZER SET POINT.
A. PROVIDE TRAINING SERVICES ON THE OPERATIONS AND MAINTENANCE OF THE EQUIPMENT AND PROFESSIONAL ENGINEER
COMPLY WITH THE NATIONAL STANDARD PLUMBING CODE (CHAPTER 9) AND THE INTERNATIONAL
MATERIALS FURNISHED AND/OR PROVIDED AS REQUIRED BY THE INDIVIDUAL SPECIFICATION MA LICENSE No. 53898
MECHANICAL CODE (CHAPTER 3, SECTION 307, CONDENSATE DISPOSAL), WHICHEVER IS STRICTER. 2. THE OUTDOOR AIR DAMPER WILL BE SET TO ITS ADJUSTABLE MINIMUM POSITION IF THE ECONOMIZER
SECTIONS BELOW.
SLOPE DRAIN LINES DOWN AWAY FROM UNITS AT 1/8 INCH PER FOOT. FUNCTION IS DISABLED OR THE DISCHARGE AIR ENTHALPY SENSOR HAS FAILED. IF THE RTU IS IN THE MORNING
WARM-UP MODE, THE SUPPLY FAN IS OFF, OR THE MIXED AIR TEMPERATURE SENSOR HAS FAILED, THEN THE
OUTDOOR AIR DAMPER WILL BE CLOSED.
H9.1

You might also like