Professional Documents
Culture Documents
Continous RC Beam Rebar Curtailment Example 4 BS 8110-1985
Continous RC Beam Rebar Curtailment Example 4 BS 8110-1985
The column and beam moments are found by multiplying the appropriate shear force
by one-half the member length. For example,
Column FE MF=ME=18.83×2.75=51.78×1.2=62.1 kN m
Beam BF MB=MF=10.17×3=30.51×1.2=36.6 kN m
Beam FK MF=MK=11.22×4=44.88×1.2=53.8 kN m
The final moments are multiplied by 1.2 to give the design moments. Compare
moments with those obtained by the portal method. ■
Specification
The framing plans for a multistorey building are shown in Fig. 13.11. The main
dimensions, structural features, loads, materials etc. are set out below.
(c) Stability
Stability is provided by shear walls at the lift shafts and staircases in the end bays.
The load due to self-weight is estimated from preliminary sizing of members. The
imposed load contributing to axial load in the columns is reduced by 50% for a
building with ten floors including the roof.
Page 409
(g) Materials
Concrete grade 30
Reinforcement grade 460
h) Foundations
Pile foundations are provided under each column and under the shear walls.
The design is to meet requirements for robustness. In this design, the frame is taken as
completely braced by the shear walls in both directions. A link-frame analysis can be
carried out to determine the share of wind load carried by the rigid frames (Chapter
14). The design for dead and imposed load will be the critical design load case.
2×24[(0.5×0.275)−(0.375×0.215)]=2.73 kN/m2
Preliminary beam sizes for roof and floors are shown in Fig. 13.12. The weights of the
beams including the solid part of the slab are: roof beams, 24[(0.3×0.45)+
(0.6×0.275)]=7.2 kN/m and floor beams, 8.8 kN/m.
Fig. 13.12 (a) Roof and floor slab; (b) roof and floor beams; (c) columns.
Page 411
Vertical loads
(2.73×5.1)+7.2+(1.5×6)=35 kN/m
6×1.5=9 kN/m
(2.73×5)+8.8+(3×6)=40.5 kN/m
6×3=18 kN/m
7[35+(40.5×9)]+3.5[7.3+4(4.9+3.8)]=2939.7 kN
7×0.5[9+(18×9)]=598.5 kN
Subframe analysis
(a) Subframe
The subframe consisting of the beams and columns above and below the floor level
1 is shown in Fig. 13.13.
Fig. 13.13 (a) Subframe; (b) case 1, all spans 1.4Gk+1.6Qk; (c) case 2A, maximum load on
outer spans; (d) case 2B, maximum load on centre span.
Page 413
Fig. 13.14
design load=(1.4×40.5)+(1.6×18)
=85.5 kN/m
(ii) Case 2 Alternate spans are loaded with the maximum design load 1.4Gk+1.6Qk
and the other spans are loaded with 1.0Gk:
The design load cases are shown in Fig. 13.13. Case 2 involves two separate analyses
(A and B).
(d) Analysis
The moment distribution for case 1 is shown in Fig. 13.14. The shear force and
bending moment diagrams for the load cases are shown in Fig. 13.15.
Provide 4T25 to give an area of 1963 mm2 (Fig. 13.16). This will provide for tie
reinforcement.
(ii) Section at outer support, M=367 kN m The beam section is rectangular of
breadth b=400 mm. Provide for 25 mm bars in vertical pairs; d=435 mm.
Fig. 13.15 (a) Case 1, all spans 1.4Gk+1.6Qk; (b) case 2A, maximum load on outer spans; (c)
case 2B, maximum load on centre span.
Page 416
Fig. 13.16 (a) Mid-span; (b) outer column; (c) inner column.
For the compression steel, carry 2T25 through from the centre span. For the tension
steel, provide 6T25 to give an area of 2944 mm2. Refer to Fig. 13.16.
(iii) Section at inner support, M=428.4 kN m
For the compression steel, carry 2T25 through from the centre span. For the tension
steel, provide 4T32+2T20 to give an area of 3844 mm2. The steel area is 1.92% of the
gross concrete area. Refer to Fig. 13.16.
0.87×460×1963=0.45×30×400(0.9x)+700(x−52.5)981/x
Page 418
z=447.5−0.9×96.9/2=403.9 mm
MR=[(0.45×30×400×0.9×96.9×403.9) +700(96.9−52.5)981×395/96.9]/106
=314.5 kN m
Refer to the load diagram for case 2 loads for the end span shown in Fig. 13.17(b).
The theoretical cut-off point for two bars is given by the solution of the equation
314.5=367+85.5a2/2−329.3a
This is a=0.16 m.
In accordance with the general rules for curtailment of bars in the tension zone
given in clause 3.12.9.1, the code states that one of the following requirements should
be satisfied:
(c)The bar must continue for an anchorage length (37 diameters) beyond
the point where it is no longer required to resist bending moment;
(e)The bar must reach a point where other bars continuing past provide
double the area required to resist moment at the section.
Note that (c) and (e) are the code designation. Requirement (e) will be satisfied.
In a similar manner to the above, the point where a second pair of 25 mm bars can
be cut off can be determined. The theoretical cut off is at 0.68 m, say 0.7 m, from the
centreline of the support. Hence, this is the point where the first 2T25 bars can be cut
off.
Again, the point where 1T25 bar can be cut off is calculated. This is at 0.98 m, say
1.0 m, from the support. The second 2T25 bars can be cut off at this point.
Continue the remaining bars to say 1.6 m from support and lap 2T25 bars on to
carry links. This satisfies the requirement that 20% of the inner support steel should
run through as set out in the simplified rules. The point of contraflexure, at its furthest
extent, is 1.35 m from the support.
1T32 bar can be cut off at 1.11 m from the support. The 2T32 bars can be cut off at
1150 mm from the support.
The remaining 2T32 bars are lapped onto 2T25 bars to support the links. The point
of contraflexure is at 1.69 m from the support. See section (e), p. 424.
0.87×460×981=0.43×30×1000×0.9x
x=32.3 mm
z=447.5−0.5×0.9×32.3=432.9 mm
≮0.95d=425.1 mm
The steel at the top actually has a small tensile stress, which is neglected.
MR =0.87×460×981×425.1/103
=166.9 kN m
Consider case 2A loads shown in Fig. 13.17(b) and solve the following equation to
give the theoretical cut off points:
166.9=329.9a−367−85.5a2/2
(iv) Outer support—anchorage of top bars 6T25 bars which include two pairs are to
be anchored. The arrangement for anchorage is shown in Fig. 13.18. The anchorage
length is calculated for pairs of bars.
A larger steel area has been provided than is required (section 13.5.6(a)(ii)). The
stress in the bars at the start of the bend is
From Table 3.28 of the code β=0.5 for type 2 deformed bars in tension:
Fig. 13.18
The bearing stress is checked at the centre of the bend with an average radius of 275
mm for the pairs of bars.
The centre of the bend is at 107.9 mm from the start. The stress at the centre of the
bend is
where the centre-to-centre distance of the bars is 98.3 mm. The bend radius is
satisfactory. The top bars will extend to 1.6 m to lap on the beam reinforcement.
The effective tension steel is 4T32 bars, As=3216 mm2, d=444 m (Fig. 13.19). The
bars continue for 481 mm past the section.
vc=0.65 N/mm2
Then taking account of the shear resistance of the T10 links at 300 mm centres, the
average shear stress v in the concrete can be found:
Page 422
Fig 13.19
Page 423
Fig. 13.20
and
v=1.17 N/mm2
V=1.17×444×400/103=207.8 kN
The distance a from the centre support where the shear is 207.8 kN is given by
(ii) Outer support, d=447.5 mm The shear at d from the face of the support is 271.8
kN. The shear stress v=1.55 N/mm2. The design stress for 4T25 bars, As=1963 mm2, at
the top gives vc=0.69 N/mm2.
The spacing sv for the T10 links is 182.6 mm. For a minimum spacing of 300 mm
with vc=0.55 N/mm2 for 2T25 bars, the shear V=191.5 kN. This shear occurs at 1.61
m from the centre of the support.
(d) Deflection
Refer to Fig. 13.16.
Interpolating from Table 3.10 of the code the basic span/d ratio is
The modification factor for compression reinforcement with 2T25 bars supporting the
links is
(e) Cracking
Referring to Table 3.20 in the code the clear spacing between bars in the tension
zone for grade 460 steel and no redistribution should not exceed 160 mm. The cut-off
points calculated above are re-examined. Refer to Figs 13.17 and 13.19.
(i) Outer support—top steel The maximum distance of the point of contraflexure
from the support is 1350 mm; 2T25–4 bars are cut off at 1000 mm giving a clear
spacing between bars of 270 mm. A small bar must be added in the centre of the beam
to control cracking.
(ii) Inner support—top steel The point of contraflexure is 1690 mm from the
support. The centre 2T32–8 bars are cut off at 1200 mm from the
Page 425
support. A small bar is necessary in the centre of the beam to control cracking.
(iii) Outer support—bottom steel For case 3 loads the point of contraflexure is 630
mm from the support. It is necessary to add a small bar in the centre of the beam to
control cracking between the cut-off of the inner two bars and the column (Fig. 13.19,
section AA).
(iv) Inner support—bottom steel For case 3 loads the point of contraflexure is 990
mm from the support. A centre bar to control cracking is added (Fig. 13.19, section
CC).
axial load=(1.4×2939.7)+(1.6×598.5)
=5073.2 kN
moment=89.6 kN m
In case 2, at the first floor the centre beam carries dead load only:
axial load=5073.2−[(0.4×40.5)+18]3
=4970.6
moment=137.8 kN m
Check the slenderness in the longitudinal direction. The end conditions for a braced
column are (Table 3.21 of the code)
β=0.9
effective length lc=0.9(5500−250)=4725 mm
slenderness=4725/550=8.59
<15
100Asc/bh=1.4
Asc=1.4×5502/100=4235 mm2
Fig. 13.21
Page 427
Robustness—design of ties
The design must comply with the requirements of sections 2.2.2.2 and 3.12.3 of the
code regarding robustness and the design of ties. These requirements are examined.
where
gk=2.73+8.8/6+3.0=7 kN/m2
qk=3.0 kN/m2
lr=8.0 m (transverse direction)
or
1.0Ft
where
Ft=20+4n0=60 kN
Provide 3T12 bars, As=339 mm2, in the topping of the ribbed slab per metre width.
(ii) Longitudinal direction The area of ties must be added to the area of steel in the
ribs.
2.0Ft=120 kN
Page 428
or
(ls/2.5)Ft=3×60/2.5=72 kN
where ls is the floor to ceiling height (3.0 m), or 3% of the design ultimate vertical
load at that level (p. 425) which is
The moment reinforcement provided at the bottom of the beam is just adequate to
resist this force. At the centre of the beam 1963 mm2 are provided whereas 1569.4
mm2 are required. The top reinforcement will also provide resistance. The bars are
anchored at the external column.
The corner columns must be anchored in two directions at right angles.