VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.

6 Page: 1
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022

Project: Productos Ramo S.A.


Project-No: 1149_3_1
Building:
Object: Racks P-01
Contractor: Fire Tech Control Tecnologías Contra Incendios S.A.S.
Owner:
Project engineer: mrg
Date: 3/6/2022
Regulation rule for calculation of FK-5-1-12 quantities: NFPA 2001, Edition 2018
Altitude above sealevel: 2550 m
Atmospheric correction factor: 0.709

Project description:
2 x 1.0" 180° Sidewall Nozzles 10106 - 10108

Pipe catalogue: schedule40.rkl


Component catalogue: SEVOcomp_1_2.arm
Nozzle catalogue: SEVO.noz
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 2
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 3
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022

Pipesystem data:

Section- Starting- Endnode Length Height Pipetype Diameter Fitting Component Nb of containers
No: node [m] [m] [inch] ** * code coefficient FK-5-1-12 quantity

1 0 1 0.724 0.724 10 1 1/4 C 761 1.900 1.0


2 1 2 0.128 0.000 13 1 E - - 0.0
3 2 3 2.200 2.200 13 1 E - - 0.0
4 3 4 0.350 0.000 13 1 T-90° - - 0.0
5 4 5 0.950 0.000 13 1 E - - 0.0
6 5 10106 0.150 -0.150 13 1 E - - 0.0
7 3 7 1.700 0.000 13 1 T-90° - - 0.0
8 7 10108 0.150 -0.150 13 1 E - - 0.0

* C=Component, B=Bend, T=T-Piece, E=Elbow


** If a pipe diameter is equal zero see the extra table of the calculated diameters

Legend of pipetypes
Type Pipeclass Pipe roughness
10 schedule 40 smooth
13 schedule 40 black pipe

Legend of components
Code Type Resistance coefficient
761 SEVO 76 LB/1" (CV140079) W/ 1" Flex Hose 1.900

Nozzle data:

No. Calculation zone Diameter [mm]


10106 Operadores 9.3
10108 Racks 13.4

Legend of nozzles:
Type Number of C1 C2 C3 C4 C5 C6
orifices
1 Nozzle 1 1 0.10652 0.26900 0.23203 -0.20251 0.00000 0.00000
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 4
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022

Calculation zone data:

Calculation of design quantity:

Zone Total Volume of Calculated Total Max. Over- Design Extinguish- Design Design Design
volume building volume surface pressure temp. conc. factor conc. quantity
[m3] parts [m3] [m3] [mbar] [°C] [% Vol] [% Vol] [kg]

1 Operadores 23.8 0.0 23.8 51.1 1.000 20.0 3.3 1.35 4.5 11.06
2 Racks 45.4 0.0 45.4 76.9 1.000 20.0 3.3 1.35 4.5 21.06

Regulation rule for calculation of FK-5-1-12 quantities: NFPA 2001, Edition 2018
Calczone no. 1: Class C Fire, NFPA 2001 (Edition 2018)
Calczone no. 2: Class C Fire, NFPA 2001 (Edition 2018)
Altitude above sealevel: 2550.0 m
Atmospheric correction factor: 0.709

FK-5-1-12 storage input data:

Container volume: 29.0 l


Maximum filling ratio of a container: 1.200 kg/l
Filling pressure: 34.5 bar abs
Storage temperature: 20.0 °C
Supplement factor: 1.01
Minimum storage quantity: 32.33 kg
Number of containers: 1

Discharge time (input value): 10.0 s

Further information:
Design with included gas discharge time
Design with predeterminated orifice diameters
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 5
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022

Calculation results:

FK-5-1-12 storage data:


Design quantity: 32.1 kg
Supplement factor: 1.01
Minimum storage quantitiy: 32.4 kg

Container volume: 29.0 l


Filling ratio: 1.12 kg/l
Filling pressure: 34.5 bar abs
FK-5-1-12 -mass per container: 32.4 kg
Number of containers: 1
Actual storage quantity: 32.4 kg

Storage temperature: 20.0 °C


Starting container pressure: 34.5 bar abs

Discharge time:
Discharge time air: 0.1 s
Total gas discharge time: 0.3 s
Two-phase discharge time: 6.8 s
Total discharge time: 7.1 s

System information:
Container working pressure: 13.7 bar abs
Container working temperature: 20.0 °C
Total network volume: 3.7 l
Medium pipe content: 5.3 kg FK-5-1-12
Filling portion in pipe system: 0.16 kg FK-5-1-12 /kg FK-5-1-12 -storage
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 6
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022

Pipe system:
Section- Starting- Endnode Pressure Flowrate Pipedimension
No: node [bar abs] [kg/s] Di [mm] DN

1 0 1 13.44 4.46 35.1 1 1/4


2 1 2 12.91 4.48 26.6 1
3 2 3 11.72 4.48 26.6 1
4 3 4 11.28 1.55 26.6 1
5 4 5 11.20 1.55 26.6 1
6 5 10106 11.15 1.55 26.6 1
7 3 7 11.16 2.93 26.6 1
8 7 10108 10.94 2.93 26.6 1

Tee split table

T-Type Flow in 1th Flow out 2nd Flow out Regulation


Section Flow Section Flow Split Section Flow Split conform
No. kg/s No. kg/s % No. kg/s %

Bull Tee 3 4.48 4 1.55 34.598 7 2.93 65.402 Yes


VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 7
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022

Nozzle data:

Calculation- Nozzle Nozzle Number of Pipeconnection Orifice FK-5-1-12 out-


zone no: no. type orifices Di [mm] DN [mm] put [kg]

1 10106 1 1 26.6 1 9.3 11.2


2 10108 1 1 26.6 1 13.4 21.1

Two-phase discharge time: 6.8 s

MAXIMUM TRANSPORT TIME DIFF. BETWEEN NOZZLES: 10108./ 10106. IS 0.16 S

Calculation- Nozzle Outlet velocity Transport Jetdistance Evaporation


zone no: no. [m/s] time [s] [m] distance [m]

1 10106 17.2 1.28 3.7 3.0


2 10108 16.0 1.11 5.1 4.0
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 8
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022

Concentrations:

Calculation- Gascomposition after discharge [%]


zone no: O2 FK-5-1-12 N2

1 20.0 4.5 74.6


2 20.0 4.5 74.6

Pressure relief opening:

Calculation- Recommended area against overpressure


zone no: Area [m²] Overpressure [mbar] Max. flow [kg/s]

1 0.017 1.0 1.5


2 0.032 1.0 2.9
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 9
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022

Component list:

Component Number Code Coefficient

SEVO 76 LB/1" (CV14 1 761 1.900

Nozzle-type Number C1 C2 C3 C4 C5 C6

1 2 0.10650 0.26900 0.23200 -0.20250 0.00000 0.00000

Pipe-type Di [mm] DN Length [m]

10 35.10 1 1/4 0.700


13 26.60 1 5.400

Number of bends (+) and elbows (-)

Bend-type Di [mm] DN Number

-90 26.60 1 5

Number of T-distributors (in- and outdiameter)

Number Input 90-out 90-out 0-out

1 1 1 1 0