1149_3_1 Productos Ramo S.A. - Fire Tech Control
1149_3_1 Productos Ramo S.A. - Fire Tech Control
6 Page: 1
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022
Project description:
2 x 1.0" 180° Sidewall Nozzles 10106 - 10108
Pipesystem data:
Section- Starting- Endnode Length Height Pipetype Diameter Fitting Component Nb of containers
No: node [m] [m] [inch] ** * code coefficient FK-5-1-12 quantity
Legend of pipetypes
Type Pipeclass Pipe roughness
10 schedule 40 smooth
13 schedule 40 black pipe
Legend of components
Code Type Resistance coefficient
761 SEVO 76 LB/1" (CV140079) W/ 1" Flex Hose 1.900
Nozzle data:
Legend of nozzles:
Type Number of C1 C2 C3 C4 C5 C6
orifices
1 Nozzle 1 1 0.10652 0.26900 0.23203 -0.20251 0.00000 0.00000
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 4
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022
Zone Total Volume of Calculated Total Max. Over- Design Extinguish- Design Design Design
volume building volume surface pressure temp. conc. factor conc. quantity
[m3] parts [m3] [m3] [mbar] [°C] [% Vol] [% Vol] [kg]
1 Operadores 23.8 0.0 23.8 51.1 1.000 20.0 3.3 1.35 4.5 11.06
2 Racks 45.4 0.0 45.4 76.9 1.000 20.0 3.3 1.35 4.5 21.06
Regulation rule for calculation of FK-5-1-12 quantities: NFPA 2001, Edition 2018
Calczone no. 1: Class C Fire, NFPA 2001 (Edition 2018)
Calczone no. 2: Class C Fire, NFPA 2001 (Edition 2018)
Altitude above sealevel: 2550.0 m
Atmospheric correction factor: 0.709
Further information:
Design with included gas discharge time
Design with predeterminated orifice diameters
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 5
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022
Calculation results:
Discharge time:
Discharge time air: 0.1 s
Total gas discharge time: 0.3 s
Two-phase discharge time: 6.8 s
Total discharge time: 7.1 s
System information:
Container working pressure: 13.7 bar abs
Container working temperature: 20.0 °C
Total network volume: 3.7 l
Medium pipe content: 5.3 kg FK-5-1-12
Filling portion in pipe system: 0.16 kg FK-5-1-12 /kg FK-5-1-12 -storage
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 6
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\2022\1149_3_1 Productos Ramo S.A. - Fire Tech Control.prj - Results 3/6/2022
Pipe system:
Section- Starting- Endnode Pressure Flowrate Pipedimension
No: node [bar abs] [kg/s] Di [mm] DN
Nozzle data:
Concentrations:
Component list:
Nozzle-type Number C1 C2 C3 C4 C5 C6
-90 26.60 1 5
1 1 1 1 0