FENCE ANALYSIS
FENCE ANALYSIS
V. WIND LOAD
XI : REFERENCES
DESIGN LOADS :
BEAM = 0.20 x 0.30 x 23.54 =1.41 ->14.33 KN/m
SOIL = 15.70 x 0.25 x 3.292 =12.92 ->14.33 kN/m
MOMENT :
STEEL REQUIREMENTS
9.55 ( 1000 )² = 0.85 ( 20.70 ) a ( 200 ) 275 - 0.85 ( 20.70 ) a² ( 200 )
2
As = 133.53 mm², A16 = 201.10 mm²
DESIGN OF FOOTING ( F - 1 )
DESIGN LOADS : (Over Designed Loads)
PD = 337.26 KN , PL = 24.85 KN , PU = 514.41 KN
TRIAL AREA :
A = 391.08 = 0.78 m² ; 0.88 m
500
TRY : 1.00m x 1.00m ; A = 1.00m²
Nu = 514.41 = 514.41 KPa
1.00
Su = 500 ( 514.41 ) = 710.30 KPa > 357.23 KPa ( ok )
362.11
STEEL REQUIREMENTS :
As = 0.0051 ( 1200 ) 225 = 1377 mm²
N16mmØ = 1377.00 = SAY 6 - 16mmØ VERT. & 6 - 16mmØ HOR. 201.10
CHECK FOR SHEAR:
Ag = 46807.10 mm²
TRY: 250 mm x 250 mm ; Ag = 62,500 mm²
STEEL REQUIREMENTS :
As = 0.019 ( 250 ) 400 = 1900 mm² A16 = 201.10 mm² ;
USE : 4 - 16mmØ VERT. BARS
PROVIDE : 10mmØ TIES; 8 @ 0.05, 4 @ 0.10, 2 @ 0.15, REST @ 0.20m. O.C.
TO CHECK :
ACTUAL Pg = 4 ( 201.10 ) = 0.01287 > 0.01 < 0.06 ( ok )
62,500
C-1:
Pu = 0.7 ( 0.8 ) [ 0.85 ( 20.70 ) ( 62,500 - 1608.80 ) + 124.11 ( 1608.80 ) ]
Pu = 711.787 KN > 514.41 KN ( SAFE )
USE : 250 mm x 250 mm COLUMN w/ 4 - 16mmØ VERT. BARS w/ 10mmØ TIES
SPACED AT 2 @ 0.05, 2 @ 0.10, 2 @ 0.15 REST @ 0.20m. O.C.
PREPARED BY:
JOHN LORENZ S. MONTON
RCE 0180708, Valid Until 03/23/2025
PTR 9720328, Issued: January 5, 2024
TIN 513-927-358
STRUCTURAL
DESIGN &
ANALYSIS
Mr. Denmark Solar’s Proposed Reinforced Firewall/Fencing
Block 28, Lot 44, One Communities South Hills, Bacolod City