NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS


UNLESS OTHERWISE SPECIFIED.
2. CONCRETE BLOCK SHALL BE
INSTALLED ON ASPHALT PAVEMENT
AND MACADAM.
3. IF CONCRETE PAVED, CONCRETE
BLOCK SHALL BE PART OF CONCRETE
RESTORATION.
4. ITEM NOS. ® ® AND © ARE ONLY
APPLICABLE FOR THE INSTALLATION
OF NEW METER SET ASSEMBLY.

17MPa
CONCRETE BLOCK

FINISHED GRADE LINE


(CONCRETE PAVED)

ISOMETRIC VIEW
NTS

LABEL QTY.
ITEM DESCRIPTION END TYPE MAT CODE
NO. (PC)
GSP SHORT PIPE (VERT. RISER; 20mmfl> x
1 1 MTE
700mm) OR TO FIT ACTUAL FIELD CONDITION -

BRASS STRAIGHT VALVE 15mm W/ LOCKWING (3


2 MTE ISO 7 x J FTE ISO 228 FIXED NUT, W/ 2 MTE x FTE 4529
2.4mm0 SEALING RING)
3 WATER METER. 15mm (VOLUMETRIC) 2 MTE x MTE 5725

4
BRASS STRAIGHT COUPLING (J FTE ISO 228 x } 2 FTE x FTE 5111
FTE ISO 7)

5
G.S. NIPPLE (2Omm0 x 400mm) OR TO FIT 2 MTE 945
ACTUAL FIELD CONDITION

6 G.S. NIPPLE (2Omm0 x 100mm) 2 MTE 940

7 GALV. M.I. TEE (2Omm0 x 2Omm0 x 2Omm0) 1 FTE x FTE x FTE 1525

8 GALV. M.I. BEND (20mm<2> x 90*) 2 FTE 345

9 GALV. M.I. BEND (20mm<» x 90') 2 F II 345

10 GS NIPPLE (2Omm0 x 100mm) 2 MTE 940

11 GALV. M.I. END CAP 2 FTE -

CAD CHECKED:
STANDARD DRAWINGS

TYPE III METER SET ASSEMBLY


Maynilad REC

(TYPE III-A2)
Kalipunan Road, Balara, rerDELA cruz
Quezon City, Philippines HEAD. Engineering DATE: SET CODE:
OCTOBER 2019 2019 EDITION M-1
PMD
Engineering SCALE: REVISION NO: PAGE NO. SHEET NO.
ssp & pqc HEAD, Pnogram Management NTS 00 010F02 1.37
100 (330) 100

CUSTOMER'S
PROPERTY LINE
ROAD RIGHT OF WAY

IHI
/
17MPa CONCRETE
BLOCK

NOTES: TOP VIEW/B


1. ALL DIMENSIONS ARE IN MILLIMETERS NTS
UNLESS OTHERWISE SPECIFIED.
CONCRETE BLOCK SHALL BE
INSTALLED ON ASPHALT PAVEMENT
AND MACADAM.
IF CONCRETE PAVED, CONCRETE
BLOCK SHALL BE PART OF CONCRETE
RESTORATION.

FINISH GRADE LINE


T(CONCRETE PAVED)

VNGL (UNPAVED SURFACE)

17MPa CONCRETE
BLOCK
(SEE NOTES)

LIMIT OF TYPE 17MPa CONCRETE BLOCK


(150mm x 150mm)
LIMIT OF HSC (PL-5/5.3-5.5A)
BITUMINOUS COATING 25
MICRONS (TO BE APPLIED
DURING INSTALLATION)
FRONT VIEW/C

STANDARD DRAWINGS

TYPE METER SET ASSEMBLY


Maymlad (TYPE III-A2)
Katipunan Road, Balara.
Quezon City, Philippines DATE: SET CODE:
OCTOBER 2019 2019 EDITION M-1
PMD
Engineering REVISION NO: PAGE NO. SHEET NO.
ssp & PQC 00 020F02 1.38
NOTES:
ALL DIMENSIONS ARE IN MILLIMETERS
UNLESS OTHERWISE SPECIFIED.
CONCRETE BLOCK SHALL BE
INSTALLED ON ASPHALT PAVEMENT
AND MACADAM.
IF CONCRETE PAVED, CONCRETE
BLOCK SHALL BE PART OF CONCRETE
RESTORATION.
ITEM NOS. (?) © AND © ARE ONLY
APPLICABLE FOR THE INSTALLATION
OF NEW METER SET ASSEMBLY.

17MPa CONCRETE
BLOCK
FINISHED GRADE LINE
(CONCRETE PAVED)

ISOMETRIC VIEW/A
NTS

LABEL QTY.
ITEM DESCRIPTION END TYPE MAT CODE
NO. (PC)
GSP SHORT PIPE (VERT. RISER; 2Omm0 x
1 1 MTE
700mm) OR TO FIT ACTUAL FIELD CONDITION -

BRASS STRAIGHT VALVE 15mm W/ LOCKWING (j


2 MTE ISO 7 x $ FTE ISO 228 FIXED NUT, W/ 3 MTE x FTE 4529
2.4mm0 SEALING RING)
3 WATER METER, 15mm (VOLUMETRIC) S MTE x MTE 5725

4
BRASS STRAIGHT COUPLING ($ FTE ISO 228 x J
3 FTE x FTE 5111
FTE ISO 7)

5
G.S. NIPPLE (2Omm0 x 400mm) OR TO FIT
3 MTE 945
ACTUAL FIELD CONDITION

6 G.S. NIPPLE (2Omm0 x 100mm) 3 MTE 940

7 GALV. M.I. TEE (2Omm0 x 2Omm0 x 2Omm0) 2 FTE x FTE x FTE 1525

8 GALV. M.I. BEND (2Omm0 x 90*) 2 FTE 345

9 GALV. M.I. BEND (2Omm0 x 90*) 3 FTE 345

10 GS NIPPLE (2Omm0 x 100mm) 3 MTE 940

11 GALV. M.I. END CAP 3 FTE -

STANDARD DRAWINGS

TYPE III METER SET ASSEMBLY


Maymlad (TYPE III-A3)
Katipunan Road, Balara,
Quezon City, Philippines DATE: SET CODE:
OCTOBER 2019 2019 EDITION M-1
PMO
Engineering REVISION NO: PAGE NO. SHEET NO.
SSP & PQC 00 01OF02 1.39
100 (330) (170) 100

CUSTOMER'S
PROPERTY LINE

ROAD RIGHT OF WAY

17MPa CONCRETE
BLOCK

NOTES:
ALL DIMENSIONS ARE IN MILLIMETERS
TOP VIEW/ B
UNLESS OTHERWISE SPECIFIED.
CONCRETE BLOCK SHALL BE
INSTALLED ON ASPHALT PAVEMENT
AND MACADAM.
IF CONCRETE PAVED, CONCRETE
BLOCK SHALL BE PART OF CONCRETE
RESTORATION.

FINISH GRADE LINE


^(CONCRETE PAVED)

NGL
y(UNPAVED SURFACE)

17MPa CONCRETE
BLOCK (SEE NOTES)

- 17MPa CONCRETE BLOCK


LIMIT OF HSC (PL-5/5.3-5.5A) (150mm x 150mm)
BITUMINOUS COATING 25
MICRONS (TO BE APPLIED
DURING INSTALLATION)

FRONT VIEW

STANDARD DRAWINGS

TYPE III METER SET ASSEMBLY


Maynilad (TYPE III-A3)
Katipunan Road, Balara,
Quezon City, Philippines DATE: SET CODE:
OCTOBER 2019 2019 EDITION M-1
PMD
Engineering SCALE: REVISION NO: PAGE NO. SHEET NO.
SSP & PQC HEAD,/Program Management NTS 00 02OF02 1.40
NOTES:
ALL DIMENSIONS ARE IN MILLIMETERS
UNLESS OTHERWISE SPECIFIED.
CONCRETE BLOCK SHALL BE
INSTALLED ON ASPHALT PAVEMENT
AND MACADAM.
IF CONCRETE PAVED, CONCRETE
BLOCK SHALL BE PART OF
CONCRETE RESTORATION.
ITEM NOS. ® © AND @
ARE ONLY APPLICABLE
FOR THE INSTALLATION
OF NEW METER SET
ASSEMBLY.

17MPa CONCRETE
BLOCK
FINISHED GRADE LINE
(CONCRETE PAVED)

ISOMETRIC VIEW^A
NTS

LABEL QTY.
ITEM DESCRIPTION END TYPE MAT CODE
NO. (PC)
GSP SHORT PIPE (VERT. RISER; 2Omm0 x
1 1 MTE
700mm) OR TO FIT ACTUAL FIELD CONDITION -

BRASS STRAIGHT VALVE 15mm W/ LOCKWING (|


2 MTE ISO 7 x i FTE ISO 228 FIXED NUT. W/ 4 MTE x FTE 4529
2.4mm0 SEALING RING)
3 WATER METER, 15mm (VOLUMETRIC) 4 MTE x MTE 5725

BRASS STRAIGHT COUPLING (% FTE ISO 228 x $


4 4 FTE x FTE 5111
FTE ISO 7)

5
G.S. NIPPLE (2Omm0 x 400mm) OR TO FIT 4 MTE 945
ACTUAL FIELD CONDITION

6 G.S. NIPPLE (20mm* x 100mm) 4 MTE 940

7 GALV. M.I. TEE (2Omm0 x 2Omm0 x 2Omm0) 3 FTE x FTE x FTE 1525

8 GALV. M.I. BEND (2Omm0 x 90') 2 FTE J545

9 GALV. M.I. BEND (2Omm0 x 90*) 4 FTE 345

10 GS NIPPLE (2Omm0 x 100mm) 4 MTE 940

11 GALV. M.I. END CAP 4 FTE -

STANDARD DRAWINGS
Q TYPE III METER SET ASSEMBLY
Maynilad (TYPE III-A4)
Katipunan Road, Balara,
Quezon City, Philippines DATE: SET CODE:
OCTOBER 2019 2019 EDITION M-1
PMD
Engineering REVISION NO: PAGE NO. SHEET NO.
SSP & PQC 00 010F02 1.41
00 (170) (330) (170) 100

CUSTOMER'S
PROPERTY LINE

ROAD RIGHT OF WAY

17MPa CONCRETE /
BLOCK J

NOTES: TOP VIEW/B


1. ALL DIMENSIONS ARE IN MILLIMETERS
UNLESS OTHERWISE SPECIFIED.
2. CONCRETE BLOCK SHALL BE
INSTALLED ON ASPHALT PAVEMENT
AND MACADAM.
3. IF CONCRETE PAVED, CONCRETE
BLOCK SHALL BE PART OF CONCRETE
RESTORATION.

FINISH GRADE LINE


^(CONCRETE PAVED)

NGL (UNPAVED
TSURFACE)

CONCRETE
BLOCK
(SEE NOTES)

17MPa CONCRETE BLOCK


LIMIT OF HSC (PL-5/5.3-5.5A) (150mm x 150mm)
BITUMINOUS COATING 25
MICRONS (TO BE APPLIED
DURING INSTALLATION)
FRONT VIEW
NTS

STANDARD DRAWINGS

METER SET ASSEMBLY


Maynilad (TYPE III-A4)
Katipunan Road, Balara,
Quezon City, Philippines DATE: SET CODE:
OCTOBER 2019 2019 EDITION M-1
PMD
Engineering SCALE: REVISION NO: PAGE NO. SHEET NO.

SSP & PQC NTS 00 02OF02 1.42


NOTE:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE SPECIFIED.

Ld
LU

PROPERTY LINE a

80 80

FINISH GRADE LINE FINISH GRADE LINE


y (CONCRETE PAVED) T(CONCRETE PAVED)

T NGL (UNPAVED SURFACE) v NGL (UNPAVED SURFACE)

LIMIT OF TYPE III MSA


LIMIT OF HSC
(PL-5/5.3-5.5A) 180
180

SECTION SECTION
NTS NTS

CHECKED: CHECKED:
STANDARD DRAWINGS
rffic/CGR GJG
TYPE III METER SET ASSEMBLY
Maynilad (SECTION)
Katipunan Road, Balara, JOEL C. DELA CRUZ
Quezon City, Philippines HEAD, Engineering DATE: SET CODE:
OCTOBER 2019 2019 EDITION M-1
PMD
Engineering SCALE: REVISION NO: PACE NO. SHEET NO.

SSP A PQC NTS 00 01OF01 1.43