Professional Documents
Culture Documents
15-10
15-10
Construction
HOSE CONTROL OR
VALVE VALVE ZONE
CHECK
(Refer to Figure 3)
• The Body is RILSAN polyamide 11
coated, ductile iron per ASTM A RELIEF VALVE
536-77, Grade 65-45-12.
• The Diaphragm Cover is RILSAN Z
polyamide 11 coated, ductile
iron per ASTM A 536-77, Grade PRV-1
SPRINKLERS
65-45-12.
• The Diaphragm is nylon fabric-rein- SECTIONAL CHECK
forced, natural rubber per ASTM FLOOR VALVE
CONTROL
D2000. Diaphragm Cover Fasteners SECTIONAL
are galvanized carbon steel. HOSE CONTROL
• The Pilot Valve is brass and VALVE VALVE
stainless steel with nylon fabric-
reinforced, natural rubber per ASTM
D 2000 diaphragm.
• The Strainer is brass and stainless
steel. FIGURE 2
TYPICAL SECTIONAL FLOOR CONTROL APPLICATION
• Pressure Gauges have a 2 1/2 in.
(65 mm) diameter, stainless steel
case, and 0 to 350 psi (0 to 25 bar)
pressure rating.
• Tube, Fittings, and Needle Valve are
copper, brass, and stainless steel.
TFP1580
Page 3 of 16
NOTES:
• ✓ = Available
• N/A = Not Available
TABLE A
AVAILABLE SIZES AND CONFIGURATIONS
NORTH AMERICA
NOTES:
• ✓ = Available
• N/A = Not Available
TABLE B
AVAILABLE SIZES AND CONFIGURATIONS
SOUTH AND CENTRAL AMERICA AND EASTERN HEMISPHERE
8 11.75 0.88 11.61 0.91 11.61 0.91 12 11.42 0.75 12 11.50 0.87
8 (295,0) 8 (295,0) 8
(DN200) (298,5) (22,2) (23,0) (23,0) (290,0) (19,0) (292,0) (22,0)
NOTES:
a. Same drilling as for ANSI B16.5 (Class 150) and ANSI B16.42 (Class 150)
b. Same drilling as for BS 4504 Section 3.2 (PN10) and DIN 2532 (PN10)
c. Same drilling as for BS 4504 Section 3.2 (PN16) and DIN 2532 (PN16)
TABLE C
DIMENSIONAL SPECIFICATION FOR SELECTION OF FLANGE DRILLING
TFP1580
Page 4 of 16
VALVE PARTS
DIAPHRAGM
NO. DESCRIPTION QTY. KIT 7 11 12 3 2
CHAMBER
1 Valve Body . . . . . . . . . . . 1 NR
2 Diaphragm . . . . . . . . . . . 1 (a) OUTLET
3 Diaphragm Cover. . . . . . . 1 NR PRESSURE
4, 5, 6
4 Flat Washer, GAUGE
2 Inch Valve, M12 . . . . . . 4 CH
3 & 4 Inch Valves, M16 . . 4 CH
6 & 8 Inch Valves, M16 . . 8 CH
5 Hex Bolt,
2 Inch Valve, M12 x 35 . . 4 CH 8
3 & 4 Inch Valves,
M16 x 55 . . . . . . . . . . . . . 4 CH
6 Inch Valve, M16 x 45 . . 8 CH
8 Inch Valve, M16 x 55 . . 8 CH DOWNSTREAM UPSTREAM
6 Hex Nut, M16, OUTLET INLET
4 Inch Valve Only . . . . . . . 4 CH CAVITY CAVITY
7 Pilot Valve . . . . . . . . . . . . 1 (b)
8 Water Pressure Gauge . . 2 (c)
9 Strainer . . . . . . . . . . . . . . 1 (d) 8
10 Pressure Sensor Insert . . 1 (e)
11 Tubing and Fittings . . . . . 1 (f) INLET
12 Needle Valve . . . . . . . . . . 1 (g) PRESSURE
REPLACEMENT PART KITS
GAUGE
PRESSURE STRAINER
KIT DESCRIPTION P/N SENSOR INSERT (SEE DETAIL)
1
(a) Diaphragm, (SEE DETAIL)
Fits Either Body Style, GLOBE BODY STYLE
Includes Item 2 only:
2 Inch Valves . . . . . . . . . . . . . 92-570-2-011 OUTLET CAVITY INLET CAVITY
3 Inch Valves . . . . . . . . . . . . . 92-570-2-012 INTERIOR 1 11 INTERIOR 1 11
4 Inch Valves . . . . . . . . . . . . . 92-570-2-013
6 Inch Valves . . . . . . . . . . . . . 92-570-2-014 SENSOR
8 Inch Valves . . . . . . . . . . . . . 92-570-2-015 INLET FACES
(b) Pilot Valve . . . . . . . . . . . . . . . 92-570-2-200 DOWNSTREAM
(c) Water Pressure Gauge . . . . . 92-570-2-211 9
10 PRESSURE SENSOR STRAINER
(d) Strainer:
2, 3, & 4 Inch Valves . . . . . . . 92-570-2-202 INSERT DETAIL DETAIL
6 & 8 Inch Valves . . . . . . . . . . 92-570-2-209
(e) Pressure Sensor Insert:
2 Inch Valve . . . . . . . . . . . . . . 92-570-2-203 DIAPHRAGM
7 11 12 3 2
3 Inch Valve . . . . . . . . . . . . . . 92-570-2-204 CHAMBER
4 Inch Valve . . . . . . . . . . . . . . 92-570-2-205 OUTLET
6 Inch Valve . . . . . . . . . . . . . . 92-570-2-206 PRESSURE
8 Inch Valve . . . . . . . . . . . . . . 92-570-2-207 GAUGE 4, 5, 6
(f) Tubing and Fitting Kit,
Excludes Items 7, 8, 9, 10 and 12
Globe Style Valve:
2 Inch Valve . . . . . . . . . . . . . . 92-570-3-001
3 Inch Valve . . . . . . . . . . . . . . 92-570-3-002
4 Inch Valve . . . . . . . . . . . . . . 92-570-3-003 8
6 Inch Valve . . . . . . . . . . . . . . 92-570-3-004
8 Inch Valve . . . . . . . . . . . . . . 92-570-3-005
Angle Style Valve:
2 Inch Valve . . . . . . . . . . . . . . 92-571-3-001
3 Inch Valve . . . . . . . . . . . . . . 92-571-3-002 DOWNSTREAM
INLET
4 Inch Valve . . . . . . . . . . . . . . 92-571-3-003 OUTLET
6 Inch Valve . . . . . . . . . . . . . . 92-571-3-004 PRESSURE
CAVITY
(g) Needle Valve . . . . . . . . . . . . . 92-570-2-212 GAUGE
NOTES: 8
1. NR - Not Replaceable ORIENT
2. CH - Common Hardware DIAPHRAGM TAB
3. Install Item 8 in field UPSTREAM
PERPENDICULAR
INLET
TO OUTLET
CAVITY
1
OUTLET OUTLET PRESSURE
SENSOR INSERT STRAINER
(SEE DETAIL) (SEE DETAIL)
GLOBE ANGLE ANGLE BODY STYLE
FIGURE 3
MODEL PRV-1 PRESSURE REDUCING VALVE
ASSEMBLY
TFP1580
Page 5 of 16
TAMPER NOTES:
CAP 1. SOME PARTS SHOWN IN
PILOT ALTERED POSITIONS AND
VALVE ADJUSTING ORIENTATIONS TO
SCREW NEEDLE VALVE CLARIFY FUNCTION
OUTLET (FACTORY SET,
DO NOT READJUST) 2. ELBOW AND TEE FITTINGS
PRESSURE LOCKNUT
VARY BY VALVE SIZE AND
GAUGE BODY TYPE
REGULATING COMPRESSION
SPRING EXIT FITTING
FLOW
SUPPLY
DIAPHRAGM LINE
CHAMBER
COMPRESSION
PILOT FITTING
VALVE SYSTEM
DIAPHRAGM WATER INLET
WATERFLOW SUPPLY PRESSURE
PILOT TO SYSTEM PRESSURE GAUGE
VALVE
SEAT
SENSING
LINE
PRESSURE STRAINER
SENSOR
INSERT SUPPLY COMPRESSION
PRESSURE
LINE FITTING
SENSOR INSERT PRV-1
(INLET FACES VALVE SEAT VALVE
DOWNSTREAM) BODY PRV-1 BODY
DIAPHRAGM
DOWNSTREAM UPSTREAM
OUTLET CAVITY INLET CAVITY
OUTLET CAVITY SENSING INLET CAVITY
INTERIOR LINE INTERIOR STRAINER GAUGE
FIGURE 4
MODEL PRV-1 PRESSURE REDUCING VALVE
OPERATION
Maintenance
Note: When removing, do not grip
If necessary the Model PRV-1 Valve can gauge itself, loosen sub-assembly by
be readjusted following the Placing the wrench on fitting closest to strainer
The TYCO Model PRV-1 Pressure Valve in Service section. If the desired only.
Reducing Valve must be maintained pressure cannot be achieved, the Dia-
and serviced in accordance with this phragm and/or Pilot Valve should be Step. 4 Remove strainer from valve
section. replaced. body.
Before closing a fire protection system Diaphragm Replacement Step 5. Disassemble strainer for clean-
main control valve for maintenance Prior to replacing the Diaphragm, the ing. Remove end lock washer and slide
work on the fire protection system Model PRV-1 Valve must be taken out screen off strainer body. Clean screen
that it controls, obtain permission to of service and completely drained. With and body.
shut down the affected fire protection reference to Figure 3, the Diaphragm Step 6. Reassemble screen onto body
system from the proper authorities Tab is oriented perpendicular to the and secure with lock washer.
and notify all personnel who may be outlet flow. When reinstalling the Dia-
affected by this action. Note: Prior to installing strainer and gauge
phragm Cover, the Diaphragm Cover
and trim sub-assembly, clean all exposed
Fasteners (Hex Bolts) must be uni-
NOTICE male NPT pipe threads and apply TEFLON
formly and securely tightened using a
pipe thread sealant as required. Do not
Inspection, testing, and maintenance cross-draw sequence - for information
apply sealant to male threads of separated
must be performed in accordance about the maximum torque values, see
compression fitting. Do not contaminate
with the requirements of the NFPA, and Table D. After tightening, double check
strainer screen.
any impairment must be immediately to make certain that all of the Dia-
corrected. phragm Cover fasteners are securely Step 7. Install strainer into valve body.
tightened. Install gauge and trim sub-assembly
Responsibility lies with sprinkler into strainer outlet.
owners for the inspection, testing, Pilot Valve Replacement
and maintenance of their fire protec- Prior to removing the Pilot Valve, the Step 8. Reconnect supply line com-
tion system and devices in compliance Model PRV-1 Valve must be taken out pression fitting to strainer outlet trim
with this document, as well as with of service and completely drained. and tighten compression fitting on
the applicable standards of the NFPA When installing the replacement Pilot supply line at needle valve inlet trim.
(for example, NFPA 25), in addition to Valve, the trim components must be Refer to Placing the Valve in Service
the standards of any other authorities replaced exactly as they were. After section to place the Model PRV-1 Valve
having jurisdiction. Contact the install- reinstalling the Pilot Valve and before in service.
ing contractor or product manufacturer returning the Model PRV-1 Valve into
with any questions. service, completely unscrew the
Adjusting Screw of the replacement
Automatic sprinkler systems are rec- Pilot Valve so as to obtain a minimum
ommended to be inspected, tested, outlet “set pressure”. Then proceed to
and maintained by a qualified Inspec- use the instructions under Placing The
tion Service in accordance with local Valve In Service section to place the
requirements and/or national code. Model PRV-1 Valve in service.
TFP1580
Page 8 of 16
FIGURE 5
MODEL PRV-1 PRESSURE REDUCING VALVE
GLOVE STYLE INSTALLATION DIMENSIONS
TFP1580
Page 9 of 16
F
Groove x Groove End Connections
FIGURE 6
MODEL PRV-1 PRESSURE REDUCING VALVE
ANGLE STYLE INSTALLATION DIMENSIONS
TFP1580
Page 10 of 16
110
100
90
80
70
A
60
50
40 B
30
20
10
0
0 25 50 75 100 125 150 175 200 225 250
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A-1
2 INCH (DN50) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
100
B
90
80
70
60
50
40
C
30
20
10
0
0 25 50 75 100 125 150 175 200 225 250
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A-2
2 INCH (DN50) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 11 of 16
110
100
90
80
70
60
A
50
40
B
30
20
10
0
0 50 100 150 200 250 300 350 400 450 500 550
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH B-1
3 INCH (DN80) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
100
90 B
80
70
60
50
40
C
30
20
10
0
0 50 100 150 200 250 300 350 400 450 500 550
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH B-2
3 INCH (DN80) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 12 of 16
110
100
90
80
70
A
60
50
40 B
30
20
10
0
0 100 200 300 400 500 600 700 800 900 1000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH C-1
4 INCH (DN100) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
120
80
70
60
50
C
40
30
20
10
0
0 100 200 300 400 500 600 700 800 900 1000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH C-2
4 INCH (DN100) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 13 of 16
110
100
90
80
70
60
A
50
40
B
30
20
10
0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH D-1
6 INCH (DN150) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
100
B
90
80
70
60
50
40
C
30
20
10
0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH D-2
6 INCH (DN150) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 14 of 16
110
100
90
80
70
A
60
50
40 B
30
20
10
0
0 500 1000 1500 2000 2500 3000 3500 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH E-1
8 INCH (DN200) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
100
B
90
80
70
60
50
40 C
30
20
10
0
0 500 1000 1500 2000 2500 3000 3500 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH E-2
8 INCH (DN200) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 15 of 16
Ordering
Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-920
flanged valves specify flange drilling),
P/N (specify from complete listing on 3 in. T x T
6 in. G x G
per 4 in. F x F
6.62 in. (168,3 mm) ANSI B16-1 (Class 125) JIS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-723
Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-925 4 in. F x F
ISO 7005-2 (PN16)
6 in. F x F AS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-523
ISO 7005-2 (PN10), 8 in. valve only
ANSI Flange. . . . . . . . . . . . . . . . . . 52-570-8-025 6 in. G x G
JIS B2210 (10K) 6.62 in. (168,3 mm)
8 in. G x G
8.62 in. (219,1mm) AS 2129 (Table E) Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-925
Groove O.D . . . . . . . . . . . . . . . . . . 52-570-8-926 6 in. G x G
Note: Refer to Table C for flange drilling 6.50 in. (165,1 mm)
8 in. F x F dimensional specifications.
ANSI Flange . . . . . . . . . . . . . . . . . 52-570-8-026 Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-945
6 in. F x F
Pressure Relief Valve ANSI Flange . . . . . . . . . . . . . . . . . 52-570-8-025
Specify: 1/2 in. (DN15) Watts Regula-
6 in. F x F
tor, Series 530C Pressure Relief Valve ISO (PN16) Flange ���������������������������52-570-8-115
for use downstream of a Model PRV-1
Valve being used for reducing pressure 6 in. F x F
JIS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-725
in sprinkler system, P/N 20608
6 in. F x F
Replacement Valve Parts AS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-525
Specify: (description) for use with
8 in. G x G
(specify) size Model PRV-1 Pressure 8.62 in. (219,1mm)
Reducing Valve, P/N (see Figure 3) Groove O.D . . . . . . . . . . . . . . . . . . 52-570-8-926
8 in. F x F
ANSI Flange . . . . . . . . . . . . . . . . . 52-570-8-026
8 in. F x F
ISO (PN10) Flange ������������������������� 52-570-8-116
8 in. F x F
ISO (PN16) Flange �������������������������� 52-570-8-126
8 in. F x F
JIS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-726
8 in. F x F
AS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-526
TFP1580
Page 16 of 16
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
RILSAN is a registered trademark of Arkema, Inc