Model PRV-1 Pressure Reducing Valve

Pilot Operated, Globe and Angle Body Styles

General • One piece,


diaphragm
one moving part

Description • In-line service


• One pilot valve sub-assembly
The TYCO Model PRV-1 Pressure provides for any outlet “set
Reducing Valves, 2 through 8 in. (DN50 pressure”, that is, 80 to 225 psi (5,5
through DN200), are factory-assem- to 15,5 bar)
bled and fully trimmed valve arrange-
ments for pressure control. They are
used on water filled pipe where it is NOTICE
necessary to reduce a higher inlet The TYCO Model PRV-1 Pressure
pressure to a lower delivery pressure Reducing Valves described herein must
under static and/or residual flowing be installed and maintained in compli-
conditions. The Model PRV-1 Valve is ance with this document and with the
intended to automatically maintain the applicable standards of the National
outlet "set pressure" (static and resid- Fire Protection Association (NFPA), in
ual) within a close range, regardless of addition to the standards of any author-
fluctuations in the higher pressure inlet ities having jurisdiction. Failure to do so
line or varying flow rates. may impair the performance of these
The Model PRV-1 Valve is provided devices.
with a factory outlet “set pressure” of Owners are responsible for maintaining
125 psi (8,6 bar); however, it may their fire protection system and devices
be field set to a nominal outlet “set in proper operating condition. Contact
pressure” of 80 to 225 psi (5,5 to the installing contractor or sprinkler
15,5 bar) per its FM Approval or manufacturer with any questions.
80 to 150 psi (5,5 to 10,3 bar) per its
Due to the flow regulating characteris-
UL Listing.
tic of this device, its impact on system
Typical applications hydraulics should be carefully consid-
• Within the main header (Ref. ered, especially when retrofitted into
Figure 1) supplying wet pipe, dry existing systems.
pipe, deluge, or preaction system
risers, and/or a standpipe system WARNING
supplying hose connections
Adjustment of the Needle Valve is
• As part of a sectional floor control factory set and must not be altered. • Filed-setting of the Model PRV-1 Valve
assembly (Ref. Figure 2) supplying to provide required outlet pressures and
sprinkler systems, and/or hose
stations Technical flows for the given application.
• Testing of the Model PRV-1 Valve after
Features Data installation in accordance with NFPA 13
and/or NFPA 14 as applicable.
• Can be installed in vertical or hori-
zontal orientation Approvals • Testing the Model PRV-1 Valve tested
UL and C-UL Listed periodically thereafter in accordance
• Eliminates any required bleeding FM Approved with NFPA 25.
of trapped air from the diaphragm
The UL Listing is based on: Maximum Inlet Pressure
chamber during installation
• Installation requirements referenced in 250 psi (17,2 bar)
• Globe or angle pattern the Standard for Installation of Sprinkler Factory Outlet “Set Pressure”
• Accurate pressure control Systems, NFPA 13, or the Standard 125 psi (8,6 bar)
for Installation of Standpipe and Hose
• RILSAN Red coated internal and Valves, NFPA 14, as applicable. Field Outlet “Set Pressure” Range
external 80 to 225 psi (5,5 to 15,5 bar) per FM
• Inspection, testing, and maintenance
Approval, or 80 to 150 psi (5,5 to 10,3 bar)
requirements referenced in the
per UL Listing
Standard for Inspection, Testing, and
IMPORTANT Maintenance of Water-Based Fire Pressure Loss With Inlet Pressure
Refer to Technical Data Sheet Protection Systems, NFPA 25. Above “Set Pressure”
TFP2300 for warnings pertaining to The inlet pressure minus the outlet “set
regulatory and health information. pressure” equals pressure loss. For

Page 1 of 16 AUGUST 2018 TFP1580


TFP1580
Page 2 of 16

example, assuming that the inlet flowing


WET PIPE DRY PIPE
pressure is 225 psi (15,5 bar) and the field
SPRINKLER SPRINKLER
outlet “set pressure” is 130 psi (9,0 bar),
RISER RISER
the pressure loss is 95 psi (6,5 bar).
Pressure Loss with Inlet Pressure MAIN MAIN
Below “Set Pressure” DRAIN DRAIN
Refer to Graphs A through E. These
graphs are a requirement of UL and MAIN
should be used as reference only. PRV-1 CONTROL MAIN
VALVE RELIEF HOSE
CONTROL
Rated Flowing Range MAIN VALVE STATIONS
VALVE
2 in. . . . . . . . . . . . . . . . . . . . 0 to 250 GPM HEADER
(DN50) . . . . . . . . . . . . . . . . (0 to 946 LPM)
3 in. . . . . . . . . . . . . . . . . . . . 0 to 550 GPM
(DN80) . . . . . . . . . . . . . . . (0 to 2080 LPM) PRV-1
4 in. . . . . . . . . . . . . . . . . . . 0 to 1000 GPM
(DN100) . . . . . . . . . . . . . . (0 to 3785 LPM)
6 in. . . . . . . . . . . . . . . . . . . 0 to 2200 GPM FIGURE 1
(DN150) . . . . . . . . . . . . . . (0 to 8325 LPM) TYPICAL MAIN HEADER APPLICATION
8 in. . . . . . . . . . . . . . . . . . . 0 to 4000 GPM
(DN200) . . . . . . . . . . . . . (0 to 15140 LPM)
End Connections
• Threaded end connections are available RELIEF VALVE
as NPT threaded or threaded per ISO
7-1.
• Flanged end connections are available
as drilled per Table C. PRV-1
SPRINKLERS
• Grooved end connections follow
industry standard groove specifications. SECTIONAL CHECK
FLOOR VALVE
Materials of
RISER
CONTROL
SECTIONAL MANIFOLD

Construction
HOSE CONTROL OR
VALVE VALVE ZONE
CHECK
(Refer to Figure 3)
• The Body is RILSAN polyamide 11
coated, ductile iron per ASTM A RELIEF VALVE
536-77, Grade 65-45-12.
• The Diaphragm Cover is RILSAN Z
polyamide 11 coated, ductile
iron per ASTM A 536-77, Grade PRV-1
SPRINKLERS
65-45-12.
• The Diaphragm is nylon fabric-rein- SECTIONAL CHECK
forced, natural rubber per ASTM FLOOR VALVE
CONTROL
D2000. Diaphragm Cover Fasteners SECTIONAL
are galvanized carbon steel. HOSE CONTROL
• The Pilot Valve is brass and VALVE VALVE
stainless steel with nylon fabric-
reinforced, natural rubber per ASTM
D 2000 diaphragm.
• The Strainer is brass and stainless
steel. FIGURE 2
TYPICAL SECTIONAL FLOOR CONTROL APPLICATION
• Pressure Gauges have a 2 1/2 in.
(65 mm) diameter, stainless steel
case, and 0 to 350 psi (0 to 25 bar)
pressure rating.
• Tube, Fittings, and Needle Valve are
copper, brass, and stainless steel.
TFP1580
Page 3 of 16

Nominal Valve Size


Body End
Style Connection 2 in. 3 in. 4 in. 6 in. 8 in.
(DN50) (DN80) (DN100) (DN150) (DN200)

Thread x Thread ✓ N/A N/A N/A N/A

Globe Groove x Groove ✓ ✓ ✓ ✓ ✓

Flange x Flange N/A N/A ✓ ✓ ✓

NOTES:
• ✓ = Available
• N/A = Not Available

TABLE A
AVAILABLE SIZES AND CONFIGURATIONS
NORTH AMERICA

Nominal Valve Size


Body End
Style Connection 2 in. 3 in. 4 in. 6 in. 8 in.
(DN50) (DN80) (DN100) (DN150) (DN200)

Thread x Thread ✓ ✓ N/A N/A N/A

Globe Groove x Groove ✓ ✓ ✓ ✓ N/A

Flange x Flange N/A ✓ ✓ ✓ ✓

Thread x Thread ✓ ✓ N/A N/A N/A

Angle Groove x Groove ✓ ✓ ✓ ✓ N/A

Flange x Flange N/A ✓ ✓ ✓ N/A

NOTES:
• ✓ = Available
• N/A = Not Available

TABLE B
AVAILABLE SIZES AND CONFIGURATIONS
SOUTH AND CENTRAL AMERICA AND EASTERN HEMISPHERE

Flange Drilling Specification

Nominal Nominal Installation Dimensions


Valve in.
Size (mm)
Inches Dim. A
(DN) ANSI B16.11a ISO 7005-2 ISO 7005-2 JIS B 2210 AS 2129
(Class 125) (PN10)2 b (PN16)3c (10K) (Table E) Bolt Circle
Diameter
A B N A B N A B N A B N A B N
5.75 0.71 Dim. B
3 6.00 0.75 6.30 0.75 5.90 0.59
4 8 (150,0) 8 (146,0) (18,0) 4
(DN80) (152,4) (19,0) (160,0) (19,0) (15,0) Bolt Hole
USE Diameter
4 7.50 0.75 7.09 0.75 6.89 0.60 7.00 0.71
8 ISO 7005-2 8 (175,0) 8 178,0) 8
(DN100) (190,5) (19,0) (180,0) (19,0) (15,0) (18,0)
(PN16) Qty. N
6 9.50 0.88 9.45 0.91 9.45 0.75 9.25 0.87 Number of
8 8 (240,0) 8 8 Bolt Holes
(DN150) (241,3) (22,2) (240,0) (23,0) (19,0) (235) (22,0)

8 11.75 0.88 11.61 0.91 11.61 0.91 12 11.42 0.75 12 11.50 0.87
8 (295,0) 8 (295,0) 8
(DN200) (298,5) (22,2) (23,0) (23,0) (290,0) (19,0) (292,0) (22,0)
NOTES:
a. Same drilling as for ANSI B16.5 (Class 150) and ANSI B16.42 (Class 150)
b. Same drilling as for BS 4504 Section 3.2 (PN10) and DIN 2532 (PN10)
c. Same drilling as for BS 4504 Section 3.2 (PN16) and DIN 2532 (PN16)

TABLE C
DIMENSIONAL SPECIFICATION FOR SELECTION OF FLANGE DRILLING
TFP1580
Page 4 of 16

VALVE PARTS
DIAPHRAGM
NO. DESCRIPTION QTY. KIT 7 11 12 3 2
CHAMBER
1 Valve Body . . . . . . . . . . . 1 NR
2 Diaphragm . . . . . . . . . . . 1 (a) OUTLET
3 Diaphragm Cover. . . . . . . 1 NR PRESSURE
4, 5, 6
4 Flat Washer, GAUGE
2 Inch Valve, M12 . . . . . . 4 CH
3 & 4 Inch Valves, M16 . . 4 CH
6 & 8 Inch Valves, M16 . . 8 CH
5 Hex Bolt,
2 Inch Valve, M12 x 35 . . 4 CH 8
3 & 4 Inch Valves,
M16 x 55 . . . . . . . . . . . . . 4 CH
6 Inch Valve, M16 x 45 . . 8 CH
8 Inch Valve, M16 x 55 . . 8 CH DOWNSTREAM UPSTREAM
6 Hex Nut, M16, OUTLET INLET
4 Inch Valve Only . . . . . . . 4 CH CAVITY CAVITY
7 Pilot Valve . . . . . . . . . . . . 1 (b)
8 Water Pressure Gauge . . 2 (c)
9 Strainer . . . . . . . . . . . . . . 1 (d) 8
10 Pressure Sensor Insert . . 1 (e)
11 Tubing and Fittings . . . . . 1 (f) INLET
12 Needle Valve . . . . . . . . . . 1 (g) PRESSURE
REPLACEMENT PART KITS
GAUGE
PRESSURE STRAINER
KIT DESCRIPTION P/N SENSOR INSERT (SEE DETAIL)
1
(a) Diaphragm, (SEE DETAIL)
Fits Either Body Style, GLOBE BODY STYLE
Includes Item 2 only:
2 Inch Valves . . . . . . . . . . . . . 92-570-2-011 OUTLET CAVITY INLET CAVITY
3 Inch Valves . . . . . . . . . . . . . 92-570-2-012 INTERIOR 1 11 INTERIOR 1 11
4 Inch Valves . . . . . . . . . . . . . 92-570-2-013
6 Inch Valves . . . . . . . . . . . . . 92-570-2-014 SENSOR
8 Inch Valves . . . . . . . . . . . . . 92-570-2-015 INLET FACES
(b) Pilot Valve . . . . . . . . . . . . . . . 92-570-2-200 DOWNSTREAM
(c) Water Pressure Gauge . . . . . 92-570-2-211 9
10 PRESSURE SENSOR STRAINER
(d) Strainer:
2, 3, & 4 Inch Valves . . . . . . . 92-570-2-202 INSERT DETAIL DETAIL
6 & 8 Inch Valves . . . . . . . . . . 92-570-2-209
(e) Pressure Sensor Insert:
2 Inch Valve . . . . . . . . . . . . . . 92-570-2-203 DIAPHRAGM
7 11 12 3 2
3 Inch Valve . . . . . . . . . . . . . . 92-570-2-204 CHAMBER
4 Inch Valve . . . . . . . . . . . . . . 92-570-2-205 OUTLET
6 Inch Valve . . . . . . . . . . . . . . 92-570-2-206 PRESSURE
8 Inch Valve . . . . . . . . . . . . . . 92-570-2-207 GAUGE 4, 5, 6
(f) Tubing and Fitting Kit,
Excludes Items 7, 8, 9, 10 and 12
Globe Style Valve:
2 Inch Valve . . . . . . . . . . . . . . 92-570-3-001
3 Inch Valve . . . . . . . . . . . . . . 92-570-3-002
4 Inch Valve . . . . . . . . . . . . . . 92-570-3-003 8
6 Inch Valve . . . . . . . . . . . . . . 92-570-3-004
8 Inch Valve . . . . . . . . . . . . . . 92-570-3-005
Angle Style Valve:
2 Inch Valve . . . . . . . . . . . . . . 92-571-3-001
3 Inch Valve . . . . . . . . . . . . . . 92-571-3-002 DOWNSTREAM
INLET
4 Inch Valve . . . . . . . . . . . . . . 92-571-3-003 OUTLET
6 Inch Valve . . . . . . . . . . . . . . 92-571-3-004 PRESSURE
CAVITY
(g) Needle Valve . . . . . . . . . . . . . 92-570-2-212 GAUGE

NOTES: 8
1. NR - Not Replaceable ORIENT
2. CH - Common Hardware DIAPHRAGM TAB
3. Install Item 8 in field UPSTREAM
PERPENDICULAR
INLET
TO OUTLET
CAVITY

1
OUTLET OUTLET PRESSURE
SENSOR INSERT STRAINER
(SEE DETAIL) (SEE DETAIL)
GLOBE ANGLE ANGLE BODY STYLE
FIGURE 3
MODEL PRV-1 PRESSURE REDUCING VALVE
ASSEMBLY
TFP1580
Page 5 of 16

TAMPER NOTES:
CAP 1. SOME PARTS SHOWN IN
PILOT ALTERED POSITIONS AND
VALVE ADJUSTING ORIENTATIONS TO
SCREW NEEDLE VALVE CLARIFY FUNCTION
OUTLET (FACTORY SET,
DO NOT READJUST) 2. ELBOW AND TEE FITTINGS
PRESSURE LOCKNUT
VARY BY VALVE SIZE AND
GAUGE BODY TYPE
REGULATING COMPRESSION
SPRING EXIT FITTING
FLOW
SUPPLY
DIAPHRAGM LINE
CHAMBER
COMPRESSION
PILOT FITTING
VALVE SYSTEM
DIAPHRAGM WATER INLET
WATERFLOW SUPPLY PRESSURE
PILOT TO SYSTEM PRESSURE GAUGE
VALVE
SEAT

SENSING
LINE
PRESSURE STRAINER
SENSOR
INSERT SUPPLY COMPRESSION
PRESSURE
LINE FITTING
SENSOR INSERT PRV-1
(INLET FACES VALVE SEAT VALVE
DOWNSTREAM) BODY PRV-1 BODY
DIAPHRAGM

DOWNSTREAM UPSTREAM
OUTLET CAVITY INLET CAVITY
OUTLET CAVITY SENSING INLET CAVITY
INTERIOR LINE INTERIOR STRAINER GAUGE
FIGURE 4
MODEL PRV-1 PRESSURE REDUCING VALVE
OPERATION

Operation pressure falls below the “set pressure”


of the spring, exit flow from the Dia-
• As the flow demand continues
downstream of the Model PRV-1
phragm Chamber through the Pilot Valve and the “set pressure” is met,
With reference to Figure 4, the system
Valve to the Model PRV-1 Valve outlet the Pilot Valve Seat closes. As the
water supply pressure from the inlet
cavity resumes and pressure in the Dia- Pilot Valve Seat closes to reduce
cavity of the Model PRV-1 Valve enters
phragm Chamber decreases. the opening, pressure is trapped in
the Diaphragm Chamber through
the Diaphragm Chamber at a point
a Strainer and Needle Valve. The The regulated flow through the Pilot
that allows the Diaphragm to remain
factory set Needle Valve provides the Valve decreases and increases the
lifted from the Model PRV-1 Valve
required orifice size for the supply line pressure in the diaphragm chamber to
Seat to retain the downstream “set
to the Diaphragm Chamber to optimize sufficiently open and close the Model
pressure”.
performance. PRV-1 Valve, as required, to regulate
the downstream “set pressure”. • Should the downstream pressure
Exit flow from the Diaphragm Chamber
start to fall below the “set pressure”,
through the Pilot Valve is controlled by The operation sequence is as follows:
the Pilot Valve Seat re-opens to
a regulating spring that is factory set, • When there is no flow demand allow for a decrease in pressure
and subsequently field adjustable, to downstream of the Model PRV-1 in the Diaphragm Chamber to
the desired downstream “set pressure” Valve, the Seat is closed and the allow the Model PRV-1 Valve to
that is to be maintained. A sensing line Pilot Valve Seat is closed. With the open further and then once again
connects the outlet of the Pilot Valve to Pilot Valve Seat closed, pressure is establish the downstream “set
the system piping downstream of the trapped in the Diaphragm Chamber pressure”.
Model PRV-1 Valve via the Pressure to seat the Diaphragm and the
Sensor Insert in the outlet cavity. • When the downstream pressure is
Model PRV-1 Valve remains closed.
at or above the “set pressure” and
When the downstream pressure rises • When there is a flow demand down- assuming there is a flow demand
above the “set pressure” of the spring, stream of the Model PRV-1 Valve downstream of the Model PRV-1
exit flow from the Diaphragm Chamber and the outlet pressure drops below Valve, the Pilot Valve Seat is closed
through the Pilot Valve to the Model the “set pressure”, the Pilot Valve to trap a sufficient pressure in the
PRV-1 Valve outlet cavity is stopped Seat opens to relieve pressure from Diaphragm Chamber to allow the
and pressure increases in the Dia- the Diaphragm Chamber allowing Model PRV-1 Valve to remain open
phragm Chamber. When downstream the Model PRV-1 Valve to open. to provide the “set pressure”.
TFP1580
Page 6 of 16

Design • When reducing pressure for a


sprinkler system, means shall be
as applicable. The sprinkler demand
or hose stream demand must be
Considerations provided downstream of the Model
PRV-1 Valve to facilitate a flow test
at least 50 GPM (190 LPM) for 2 to
6 in. (DN50 to DN150) valves and at
at the sprinkler system demand. least 100 GPM (380 LPM) for 8 in.
The following items must be consid-
(DN200) valves.
ered and applied accordingly for an
installation that will be using the Model Installation There is no need to vent any trapped air
PRV-1 Pressure Reducing Valve: from the Diaphragm Chamber.
The TYCO Model PRV-1 Pressure
• The Model PRV-1 Valve may be Reducing Valve must be installed with Filling the System
installed vertically or horizon- the flow arrow located on the Dia- Step 1. Install gauges at the Pilot Valve
tally and in any orientation without phragm Cover pointing in the intended and inlet Sensing Line. Apply thread-
affecting its operating efficiency. direction of flow. Installation dimen- sealant to the male end of the threads.
When planning the positioning of sions are provided in Figures 5 and 6. Ensure the pips on the pressure gauges
the Model PRV-1 Valve, it is recom- are in the upright position.
mended that consideration be Before the Model PRV-1 Valve is
given to the viewing of the pressure installed, pipe lines should be flushed Step 2. Verify that downstream drain
gauges. Consideration should also of all chips, scale and foreign matter. valves are closed and that there are no
be given to positioning the Model Care must be exercised to assure leaks.
PRV-1 Valve so that the diaphragm that the trim is not damaged during
Step 3. Partially open a valve or valves
cover is facing up. With the cover installation.
at the end of the system (such as, an
facing up, internal access is more inspector’s test connection on a wet
easily achieved. NOTICE pipe system) to allow trapped air to
• The Model PRV-1 Valve must be in Do not lift the valve by its trim. Other- escape when filling the system.
an area that is easily accessible for wise, the trim may be damaged and Step 4. Slowly and partially open the
maintenance purposes, not subject impair system operation. The inlet water supply control valve feeding the
to freezing temperatures, and not and outlet connections must be made Model PRV-1 Valve.
subject to physical damage. based on the direction of flow arrow
provided on the Diaphragm Cover. Step 5. After the system fills with water,
• The valve is designed for fresh The valve cannot operate if connected close the valve or valves that had been
water service. When corrosive backwards. partially opened in Step 2.
atmospheres and/or contaminated
Do not alter the trim. Altering the trim Step 6. Completely open the main
water supplies are present, it is
may render the valve ineffective and water supply control valve feeding the
the owner’s responsibility to verify
impair the system operation. Model PRV-1 Valve.
compatibility with the pressure
reducing valve, pilot valve, and trim. Adjusting Downstream Pressure
• The difference between the water Placing the NOTICE
supply pressure and the desired
outlet (downstream) pressure must Valve in Service After any downstream pressure adjust-
be 25 psi (1,7 bar) or greater per its ment, the following items are to be
Perform the following 13 Steps when recorded on a tag attached to the valve:
FM Approval or 50 psi (3,4 bar) or placing the TYCO Model PRV-1 Pres-
greater per its UL Listing. The differ- sure Reducing Valve in service. • Valve installation location
ential maintains accuracy control of
the discharging pressure over the • Inlet static pressure
full rated flowing range. WARNING
• Outlet static pressure
Downstream pressure adjustment is
• Cavitation may occur when the inlet only to be performed by experienced • Inlet residual pressure
pressure is greater than twice the personnel who understand the impact
“set pressure”. For this case, the • Outlet residual pressure
of adjusting the downstream pressure
pressure should be reduced in two and who take full responsibility of the • Intended outlet flow
steps by using two Model PRV-1 readjustment from the factory setting. The tag is not to be removed until after
Valves in series. The Pilot Valve is provided with a the system has been accepted by the
• When reducing pressure for a sprin- Tamper Cap, which upon removal will authority having jurisdiction. It is rec-
kler system, a ½ in. (DN15) or larger allow for field adjustment by using the ommended that the tag not be removed
relief valve shall be located down- Adjusting Screw. even after acceptance by the author-
stream of the Model PRV-1 Valve. Adjustment of the Needle Valve is ity having jurisdiction unless another
The relief valve shall be set at a factory set and must not be altered. means of record keeping is maintained.
pressure equal to the lowest pres-
Per the requirements of NFPA 13, a Step 1. Remove the Tamper Cap from
sure rated component downstream
means shall be provided downstream the Pilot Valve by first loosening its set
of the Model PRV-1 Valve.
of the Model PRV-1 Valve to simulate screw and then unscrewing the Tamper
Note: FM Approval is based on the use the sprinkler system demand. In the Cap.
of the 1/2 in. Watts Regulator, Series case of hose stations, the opening of a Step 2. Open the “flow test valve” to
530C Pressure Relief Valve. hose valve or multiple hose valves, as simulate either the desired sprinkler
• When reducing pressure for a required, will be necessary to simulate demand or hose stream demand.
sprinkler system, a listed indicating hose stream demand.
Step 3. If surging flow occurs, attempt
valve shall be provided on the inlet For the purposes of the following to bleed trapped air from the system via
side of the Model PRV-1 Valve. instruction, the opening of a “flow the inspector’s test valve and any other
test valve” simulates either the sprin- valve that can vent trapped air.
kler demand or hose stream demand,
TFP1580
Page 7 of 16

Step 4. Loosen the locknut on the NOTICE


adjusting screw of the Pilot Valve. Nominal Torque
Valve Sizes The Pilot Valve is not field repairable.
Step 5. Turn the adjusting screw clock- lb-ft Attempting to repair the Pilot Valve may
Inches (N·m)
wise to increase outlet pressure or (DN) render the valve ineffective and impair
counterclockwise to decrease outlet the system operation.
pressure. 2 29
(DN50) (39,32) Completely unscrewing the Adjusting
Step 6. After achieving the desired per- Screw of the replacement Pilot Valve
3 54
formance, tighten the locknut on the (DN80) (73,21) will help to avoid an accidental over
adjusting screw. pressurization of the system piping
4 65 prior to achieving the desired “set
Step 7. Close the “flow test valve”. (DN100) (88,13)
Observe the outlet pressure gauge and pressure”.
compare to the required “set pressure”. 6 72 Strainer Maintenance
If the required “set pressure” is not (DN150) (97,62)
Prior to performing strainer mainte-
achieved, repeat Step 2 and proceed 8 87 nance, the Model PRV-1 Valve must
accordingly. (DN200) (117,96) be taken out of service and completely
Replace the Tamper Cap and tighten drained. Be prepared for small amounts
TABLE D of residual liquid when disconnecting
its set screw.
DIAPHRAGM COVER BOLTS any trim part. Refer to Figure 4 to iden-
The pressure reducing valve is now set MAXIMUM TORQUE tify parts and key features.
for service.
Step 1. Loosen compression fitting on
Due to the spring tolerance within the The Model PRV-1 Pressure Reducing supply line at needle valve inlet trim.
Pilot Valve, it may be necessary to Valve requires no lubrication, packing
alternate back and forth between resid- or preventative maintenance; however, Step 2. Disconnect compression fitting
ual and static conditions to achieve the replacement of the diaphragm every on supply line at strainer outlet and
desired “set pressure” for both residual five years is recommended. swing supply line away for access.
and static conditions. Flow Tests Step 3. Remove inlet pressure gauge
Flow tests per NFPA are required every and trim as sub-assembly from strainer
Care and five years, at which point the outlet
pressure is compared to previous tests.
outlet.

Maintenance
Note: When removing, do not grip
If necessary the Model PRV-1 Valve can gauge itself, loosen sub-assembly by
be readjusted following the Placing the wrench on fitting closest to strainer
The TYCO Model PRV-1 Pressure Valve in Service section. If the desired only.
Reducing Valve must be maintained pressure cannot be achieved, the Dia-
and serviced in accordance with this phragm and/or Pilot Valve should be Step. 4 Remove strainer from valve
section. replaced. body.
Before closing a fire protection system Diaphragm Replacement Step 5. Disassemble strainer for clean-
main control valve for maintenance Prior to replacing the Diaphragm, the ing. Remove end lock washer and slide
work on the fire protection system Model PRV-1 Valve must be taken out screen off strainer body. Clean screen
that it controls, obtain permission to of service and completely drained. With and body.
shut down the affected fire protection reference to Figure 3, the Diaphragm Step 6. Reassemble screen onto body
system from the proper authorities Tab is oriented perpendicular to the and secure with lock washer.
and notify all personnel who may be outlet flow. When reinstalling the Dia-
affected by this action. Note: Prior to installing strainer and gauge
phragm Cover, the Diaphragm Cover
and trim sub-assembly, clean all exposed
Fasteners (Hex Bolts) must be uni-
NOTICE male NPT pipe threads and apply TEFLON
formly and securely tightened using a
pipe thread sealant as required. Do not
Inspection, testing, and maintenance cross-draw sequence - for information
apply sealant to male threads of separated
must be performed in accordance about the maximum torque values, see
compression fitting. Do not contaminate
with the requirements of the NFPA, and Table D. After tightening, double check
strainer screen.
any impairment must be immediately to make certain that all of the Dia-
corrected. phragm Cover fasteners are securely Step 7. Install strainer into valve body.
tightened. Install gauge and trim sub-assembly
Responsibility lies with sprinkler into strainer outlet.
owners for the inspection, testing, Pilot Valve Replacement
and maintenance of their fire protec- Prior to removing the Pilot Valve, the Step 8. Reconnect supply line com-
tion system and devices in compliance Model PRV-1 Valve must be taken out pression fitting to strainer outlet trim
with this document, as well as with of service and completely drained. and tighten compression fitting on
the applicable standards of the NFPA When installing the replacement Pilot supply line at needle valve inlet trim.
(for example, NFPA 25), in addition to Valve, the trim components must be Refer to Placing the Valve in Service
the standards of any other authorities replaced exactly as they were. After section to place the Model PRV-1 Valve
having jurisdiction. Contact the install- reinstalling the Pilot Valve and before in service.
ing contractor or product manufacturer returning the Model PRV-1 Valve into
with any questions. service, completely unscrew the
Adjusting Screw of the replacement
Automatic sprinkler systems are rec- Pilot Valve so as to obtain a minimum
ommended to be inspected, tested, outlet “set pressure”. Then proceed to
and maintained by a qualified Inspec- use the instructions under Placing The
tion Service in accordance with local Valve In Service section to place the
requirements and/or national code. Model PRV-1 Valve in service.
TFP1580
Page 8 of 16

Thread x Thread End Connections

Nominal Nominal Installation Dimensions


in. Approx.
Valve
(mm) Weight
Sizes lb
Inches (kg)
(DN) A B C D E F

2 7.51 1.34 7.32 6.41 8.18 1.34 16.5


(50) (191) (34) (186) (163) (208) (34) (7,5)
3 11.42 1.97 8.19 7.48 9.25 1.97 30.6
(80) (290) (50) (208) (190) (235) (50) (13,9)

Groove x Groove End Connections

Nominal Nominal Installation Dimensions


in. Approx.
Valve
(mm) Weight
Sizes lb F
Inches
(DN) (kg)
A B C D E F

2 7.71 1.18 7.32 6.41 8.18 1.18 15.2


(50) (196) (30) (186) (163) (208) (30) (6,9) E

3 11.42 1.77 8.19 7.48 9.25 1.77 30.6


(80) (290) (45) (208) (190) (235) (45) (13,9)
D
4 13.62 2.24 8.70 7.91 9.68 2.24 40.6
(100) (346) (57) (221) (201) (246) (57) (18,4)
C
6 17.80 3.30 9.88 6.73 11.49 3.30 75.6
(150) (452) (84) (251) (171) (292) (84) (34,3)
8 18.50 6.30 11.14 9.25 12.55 6.69 110.0
(200) (470) (160) (283) (235) (319) (170) (49,9)

Flange x Flange End Connections B

Nominal Installation Dimensions A


Nominal
in. Approx.
Valve
(mm) Weight
Sizes lb
Inches (kg)
(DN) A B C D E F

3 11.14 3.93 8.19 7.48 9.25 3.93 46.3


(80) (283) (100) (208) (190) (235) (100) (21,0)
4 12.00 4.37 8.70 7.91 9.68 4.37 57.3
(100) (305) (111) (221) (201) (246) (111) (26,0)
6 15.98 5.59 9.88 6.73 11.49 5.60 112.4
(150) (406) (142) (251) (171) (292) (142) (51,0)
8 18.50 6.30 11.14 7.16 12.55 6.69 149.9
(200) (470) (160) (283) (182) (319) (170) (68,0)

FIGURE 5
MODEL PRV-1 PRESSURE REDUCING VALVE
GLOVE STYLE INSTALLATION DIMENSIONS
TFP1580
Page 9 of 16

Thread x Thread End Connections

Nominal Nominal Installation Dimensions


in. Approx.
Valve
(mm) Weight
Sizes lb
Inches (kg)
(DN) A B C D E F

2 3.62 3.23 7.32 6.41 8.18 2.40 16.5


(50) (92) (83) (186) (163) (208) (61) (7,5)
3 5.91 4.21 8.19 7.48 9.25 3.93 30.6
(80) (150) (107) (208) (190) (235) (100) (13,9)

F
Groove x Groove End Connections

Nominal Nominal Installation Dimensions E


in. Approx.
Valve
(mm) Weight
Sizes lb
Inches
(DN) (kg)
A B C D E F
D G
2 3.62 3.23 7.32 6.41 8.18 2.40 15.2
(50) (92) (83) (186) (163) (208) (61) (6,9) C

3 5.91 4.21 8.19 7.48 9.25 3.93 33.5


(80) (150) (107) (208) (190) (235) (100) (15,2)
4 6.42 4.57 8.70 7.91 9.68 4.52 42.8
(100) (163) (116) (221) (201) (246) (115) (19,4)
6 8.9 6.69 9.88 6.73 11.49 5.90 83.8 B
(150) (226) (170) (251) (171) (292) (150) (38,0)
A
Flange x Flange End Connections

Nominal Nominal Installation Dimensions


in. Approx.
Valve
(mm) Weight
Sizes lb
Inches (kg)
(DN) A B C D E F

3 6.26 4.53 8.19 7.48 9.25 3.93 48.5


(80) (159) (115) (208) (190) (235) (100) (22)
4 6.85 4.65 8.70 7.91 9.68 4.52 61.1
(100) (174) (118) (221) (201) (246) (115) (27,7)
6 7.99 5.83 9.88 6.73 11.49 5.90 110.2
(150) (203) (148) (251) (171) (292) (150) (50)

FIGURE 6
MODEL PRV-1 PRESSURE REDUCING VALVE
ANGLE STYLE INSTALLATION DIMENSIONS
TFP1580
Page 10 of 16

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 70 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 50 PSI INLET PRESSURE


120

110

100

90

80

70
A
60

50

40 B

30

20

10

0
0 25 50 75 100 125 150 175 200 225 250
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A-1
2 INCH (DN50) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 140 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 100 PSI INLET PRESSURE


A
120 C = 50 PSI INLET PRESSURE
110

100
B
90

80

70

60

50

40
C
30

20

10

0
0 25 50 75 100 125 150 175 200 225 250
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A-2
2 INCH (DN50) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 11 of 16

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 70 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 50 PSI INLET PRESSURE


120

110

100

90

80

70

60
A
50

40
B
30

20

10

0
0 50 100 150 200 250 300 350 400 450 500 550
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH B-1
3 INCH (DN80) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 140 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

A B = 100 PSI INLET PRESSURE


120 C = 50 PSI INLET PRESSURE
110

100

90 B

80

70

60

50

40
C
30

20

10

0
0 50 100 150 200 250 300 350 400 450 500 550
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH B-2
3 INCH (DN80) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 12 of 16

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 70 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 50 PSI INLET PRESSURE


120

110

100

90

80

70
A
60

50

40 B

30

20

10

0
0 100 200 300 400 500 600 700 800 900 1000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH C-1
4 INCH (DN100) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140
A
130
OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

120

110 A = 140 PSI INLET PRESSURE


B = 100 PSI INLET PRESSURE
100 C = 50 PSI INLET PRESSURE
B
90

80

70

60

50
C
40

30

20

10

0
0 100 200 300 400 500 600 700 800 900 1000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH C-2
4 INCH (DN100) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 13 of 16

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 70 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 50 PSI INLET PRESSURE


120

110

100

90

80

70

60
A
50

40
B
30

20

10

0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH D-1
6 INCH (DN150) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 140 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

A B = 100 PSI INLET PRESSURE


120 C = 50 PSI INLET PRESSURE
110

100
B
90

80

70

60

50

40
C
30

20

10

0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH D-2
6 INCH (DN150) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 14 of 16

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 70 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 50 PSI INLET PRESSURE


120

110

100

90

80

70
A
60

50

40 B

30

20

10

0
0 500 1000 1500 2000 2500 3000 3500 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH E-1
8 INCH (DN200) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140
A A = 140 PSI INLET PRESSURE
130
OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 100 PSI INLET PRESSURE


120 C = 50 PSI INLET PRESSURE
110

100
B
90

80

70

60

50

40 C

30

20

10

0
0 500 1000 1500 2000 2500 3000 3500 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH E-2
8 INCH (DN200) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 15 of 16

South America, Central Globe Body Style


America and Eastern 2 in. T x T
NPT . . . . . . . . . . . . . . . . . . . . . . . . 52-570-8-060
Hemisphere
Pressure Reducing Valve 2 in. T x T
ISO . . . . . . . . . . . . . . . . . . . . . . . . 52-570-8-160
Specify: (Globe or Angle) Type, (specify
size), 125 psi (8,6 bar) Outlet “Set Pres- 2 in. G x G
sure” with (specify) Connection (and for 2.37 in. (60,3 mm)

Ordering
Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-920
flanged valves specify flange drilling),
P/N (specify from complete listing on 3 in. T x T

Procedure Page 16).


• Valve Type and Size
NPT . . . . . . . . . . . . . . . . . . . . . . . . 52-570-8-062
3 in. T x T
ISO . . . . . . . . . . . . . . . . . . . . . . . . 52-570-8-162
North America Globe, 2, 3, 4, 6, or 8 in. 3 in. G x G
Pressure Reducing Valve 3.50 in. (88,9 mm)
Angle, 2, 3, 4, or 6 in.
Specify: Globe Type, (specify size), Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-922
125 psi (8,6 bar) Outlet “Set Pressure” • 125 psi (8,6 bar) Outlet “Set 3 in. F x F
with (T x T, G x G, or F x F) Connection, Pressure” Pressure ANSI Flange . . . . . . . . . . . . . . . . . 52-570-8-022
P/N (specify from below). • Conne ction Type ( Threade d, 3 in. F x F
2 in. T x T Grooved, Flanged) ISO (PN16) Flange ���������������������������52-570-8-112
NPT . . . . . . . . . . . . . . . . . . . . . . . . 52-570-8-060
For threaded, specify NPT or ISO 3 in. F x F
2 in. G x G JIS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-722
2.37 in. (60,3 mm) For grooved, specify O.D. Pipe Size
Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-920 3 in. F x F
2 in. (DN50) . . . . . . . . . . 2.88 in. (60,3 mm) O.D. AS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-522
3 in. G x G
3 in. (DN80) . . . . . . . . . . . 3.50 in. (88,9 mm) O.D. 4 in. G x G
3.50 in. (88,9 mm)
Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-922 4.50 in. (114,3 mm)
4 in. (DN100) . . . . . . . . . 4.50 in. (114,3 mm) O.D.
Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-923
4 in. G x G 6 in. (DN150) . . . . . . . . . 6.62 in. (168,3 mm) O.D.
4.50 in. (114,3 mm) 4 in. F x F
or 6.50 in. (165,1 mm) O.D.
Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-923 ANSI Flange . . . . . . . . . . . . . . . . . 52-570-8-023
8 in. (DN200) . . . . . . . . . 8.62 in. (219,1 mm) O.D.
4 in. F x F 4 in. F x F
ANSI Flange . . . . . . . . . . . . . . . . . 52-570-8-023 • For flanged, specify flange drilling ISO (PN16) Flange ���������������������������52-570-8-113

6 in. G x G
per 4 in. F x F
6.62 in. (168,3 mm) ANSI B16-1 (Class 125) JIS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-723
Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-925 4 in. F x F
ISO 7005-2 (PN16)
6 in. F x F AS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-523
ISO 7005-2 (PN10), 8 in. valve only
ANSI Flange. . . . . . . . . . . . . . . . . . 52-570-8-025 6 in. G x G
JIS B2210 (10K) 6.62 in. (168,3 mm)
8 in. G x G
8.62 in. (219,1mm) AS 2129 (Table E) Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-925
Groove O.D . . . . . . . . . . . . . . . . . . 52-570-8-926 6 in. G x G
Note: Refer to Table C for flange drilling 6.50 in. (165,1 mm)
8 in. F x F dimensional specifications.
ANSI Flange . . . . . . . . . . . . . . . . . 52-570-8-026 Groove O.D. . . . . . . . . . . . . . . . . . 52-570-8-945
6 in. F x F
Pressure Relief Valve ANSI Flange . . . . . . . . . . . . . . . . . 52-570-8-025
Specify: 1/2 in. (DN15) Watts Regula-
6 in. F x F
tor, Series 530C Pressure Relief Valve ISO (PN16) Flange ���������������������������52-570-8-115
for use downstream of a Model PRV-1
Valve being used for reducing pressure 6 in. F x F
JIS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-725
in sprinkler system, P/N 20608
6 in. F x F
Replacement Valve Parts AS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-525
Specify: (description) for use with
8 in. G x G
(specify) size Model PRV-1 Pressure 8.62 in. (219,1mm)
Reducing Valve, P/N (see Figure 3) Groove O.D . . . . . . . . . . . . . . . . . . 52-570-8-926
8 in. F x F
ANSI Flange . . . . . . . . . . . . . . . . . 52-570-8-026
8 in. F x F
ISO (PN10) Flange ������������������������� 52-570-8-116
8 in. F x F
ISO (PN16) Flange �������������������������� 52-570-8-126
8 in. F x F
JIS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-726
8 in. F x F
AS Flange . . . . . . . . . . . . . . . . . . . 52-570-8-526
TFP1580
Page 16 of 16

Angle Body Style


2 in. T x T
NPT . . . . . . . . . . . . . . . . . . . . . . . . 52-571-8-060
2 in. T x T
ISO . . . . . . . . . . . . . . . . . . . . . . . . 52-571-8-160
2 in. G x G
2.37 in. (60,3 mm)
Groove O.D. . . . . . . . . . . . . . . . . . 52-571-8-920
3 in. T x T
NPT . . . . . . . . . . . . . . . . . . . . . . . . 52-571-8-062
3 in. T x T
ISO . . . . . . . . . . . . . . . . . . . . . . . . 52-571-8-162
3 in. G x G
3.50 in. (88,9 mm)
Groove O.D. . . . . . . . . . . . . . . . . . 52-571-8-922
3 in. F x F
ANSI Flange . . . . . . . . . . . . . . . . . 52-571-8-022
3 in. F x F
ISO (PN16) Flange ���������������������������52-571-8-112
3 in. F x F
JIS Flange . . . . . . . . . . . . . . . . . . . 52-571-8-722
3 in. F x F
AS Flange . . . . . . . . . . . . . . . . . . . 52-571-8-522
4 in. G x G
4.50 in. (114,3 mm)
Groove O.D. . . . . . . . . . . . . . . . . . 52-571-8-923
4 in. F x F
ANSI Flange . . . . . . . . . . . . . . . . . 52-571-8-023
4 in. F x F
ISO (PN16) Flange ���������������������������52-571-8-113
4 in. F x F
JIS Flange . . . . . . . . . . . . . . . . . . . 52-571-8-723
4 in. F x F
AS Flange . . . . . . . . . . . . . . . . . . . 52-571-8-523
6 in. G x G
6.62 in. (168,3 mm)
Groove O.D. . . . . . . . . . . . . . . . . . 52-571-8-925
6 in. G x G
6.50 in. (165,1 mm)
Groove O.D. . . . . . . . . . . . . . . . . . 52-571-8-945
6 in. F x F
ANSI Flange . . . . . . . . . . . . . . . . . 52-571-8-025
6 in. F x F
ISO (PN16) Flange ���������������������������52-571-8-115
6 in. F x F
JIS Flange . . . . . . . . . . . . . . . . . . . 52-571-8-725
6 in. F x F
AS Flange . . . . . . . . . . . . . . . . . . . 52-571-8-525

Pressure Relief Valve


Specify: Size (specify) Watts Regula-
tor, Series 530C Pressure Relief Valve
for use downstream of a Model PRV-1
Valve being used for reducing pressure
in sprinkler system, P/N (Specify):
South America and Central America
1/2 in. (DN15) . . . . . . . . . . . . . . . . . . . . . . . 20608
Eastern Hemisphere
1/2 in. (DN15). . . . . . . . . . . . . . . . . . 92-570-2-208

Replacement Valve Parts


Specify: (description) for use with
(specify) size Model PRV-1 Pressure
Reducing Valve, P/N (see Figure 3)