FRENIC-HVAC Function
FRENIC-HVAC Function
% Percentage
r/min Revolutions per minute
kW KiloWatts
Flowrate
m3/s Cubic metre per second
m3/min Cubic metre per minute
m3/h Cubic metre per hour
L/s Liter per second
L/min Liter per minute
L/h Liter per hour
Pressure
Pa Pascal
kPa Kilopascal
MPa Megapascal
mbar Millibar
bar Bar
mmHg Millimeters of mercury
psi Pound per square inch
mWG Metres of water gauge
inWG Inches of Water Gauge
Temperature
K Kelvin
°C Celsius
°F Fahrenheit
Density
ppm Parts Per Million
Variable Speed Drives
USB connector ready Drives with DC Reactor, EMC filter
(FRENIC-HVAC Loader Software) FEATURES
Connecting the inverter to a PC with a USB cable enables remote control from FRENIC-HVAC Loader.
On the PC running FRENICHVAC Loader, it is possible to edit, check and manage the inverter's
function code data and monitor the running/alarm status of the inverter.
With the FRENIC Loader software. The inverter can support the following function
1) Editing. Comparing and copying the function code data
2) Real-time operation monitor
3) Trouble history (latest ten troubles)
4) Maintenance information
5) Historical trace
During Fire
Alarm is ignored and operation continues until the inverter is damaged, and evacuation route is secured
without smoke permeation.
1) Ignores the inverter alarm and forcibly performs retry operation.
2) Displays an alarm during running in fire mode (without stopping due to alarm).
Confirmation time
Data setting range: 0.5 to 10.0 (s)
Set ON/OFF setting time for FMS signals. If FMS is turned ON/OFF in time shorter than
the specified value, forced operation (Fire Mode) is not enabled. FMS signals are to be
kept ON longer than the (H117) confirmation time. (in the event of false alarm)
Reference frequency
Data setting range: Inherit, 0.1 to 120.0 (Hz)
Specify speed (reference frequency) at which operation is to be performed when forced
operation (Fire Mode) is enabled.
Rotation direction
Data setting range: 0, 2, 3 (No change, Forward, Reverse)
Set an operation instruction (rotation direction) to be followed when forced operation
(Fire Mode) is enabled.
Start method
Data setting range: 0, 1 (follow setting mode, STM mode (catch on the fly) )
Set the start method to be followed when Fire Mode is enabled.
Reset interval
Data setting range: 0.5 to 20.0 (s)
Set time delay to auto cancel of trip status for a case where the inverter enters trip
status and stops during forced operation (Fire Mode).
Variable Speed Drives
Pick-up operation function Drives with DC Reactor, EMC filter
(speed sensor / Catch on the fly) FEATURES
The customizable logic interface function is provided to the inverter body. This enables forming
of logic circuit and arithmetic circuit to the digital and analog input and output signals, allowing
simple relay sequence to be built while processing the signals freely.
Logic function
Digital
AND, OR, XOR, flip-flop, rise/fall detection, counter, etc.
Analog
Addition, subtraction, multiplication, limiter, absolute value, inverted addition, comparison,
max. value selection, min. value selection, avg., scale conversion
General-purpose timer
On-delay, off-delay, pulse train, etc.
Time setting: 0.0–600s
Input/output signal
Terminal input/output, inverter control function
Others
Can comprise up to 14 steps, with each step input/output occurring in combination
You can check the input/output status of the various steps by the keypad having
the LCD monitor.
Variable Speed Drives
Trip-less by regenerative avoidance control Drives with DC Reactor, EMC filter
(effective for acceleration, deceleration and fixed speed) FEATURES
Setting include
Alarm information date/time display
Timer operation function
You can set up to 4 timers by units of 1 week.
Holiday setting (20 days a year) is also possible.
Daylight saving time auxiliary function
Battery (optional) * Battery connection status displayed on the LCD monitor.
Variable Speed Drives
Overload avoidance control Drives with DC Reactor, EMC filter
FEATURES
Because the inverter is equipped with a commercial frequency start processing function for switching
commercial / inverter operation by external sequence, peripheral equipment configuration can be simplified.
The inverter is equipped with 2 types of commercial operation switching sequences:
Fuji standard and inverter alarm automatic commercial switching sequence.
Variable Speed Drives
Operation signal loss detection Drives with DC Reactor, EMC filter
FEATURES
Setting
This output signal comes ON when the torque value calculated by the inverter or torque command
drops below the level specified set point (by E80) (Low torque detection (Level)) for the period
specified set time (by E81) (Low torque detection (Timer)). The minimum ON-duration is 100 ms.
In the inverter’s low frequency operation, as a substantial error in torque calculation occurs,
no low torque can be detected within the operation range at less than 20% of the base
frequency (F04). (In this case, the result of recognition before entering this operation range is
retained.)
The U-TL signal goes off when the inverter is stopped.
Variable Speed Drives
Slow flowrate function Drives with DC Reactor, EMC filter
(Energy Saving) FEATURES
Mode selection
Operation level
Elapsed time
Auto-operation frequency lower-limit
Pressurization starting frequency
Pressurizing time
Initiation inhibition time
Cancel frequency
Cancel deviation level 1
Cancel delay timer
Cancel deviation level 2
Flowrate Sensor Input selection (ON level) (OFF level) (Input filter)
PV1
m3/s
m3/min
m3/h
L/s
L/min
L/h
Function codes can be read/write, displayed or hidden by setting the two passwords. This prevents
erroneous operation or overwriting of function codes. In addition, if a wrong password was input exceeding
the specified number of times, the inverter is restricted from operating as the user is regarded as improper.
Password function
Protects function code data from unintentional change and hides data (at 2 levels).
Entering a wrong password five times causes an alarm.
Password control
Setting the password allows the setting of access to inverter function codes and to prevent data
revision.
Password functions are different, as shown below, depending on whether Password 1 or
Password 2 are selected.
Variable Speed Drives
Filter clogging prevention Drives with DC Reactor, EMC filter
FEATURES
AHU
Variable Speed Drives
Anti Jam Function Drives with DC Reactor, EMC filter
FEATURES
impeller jam
Variable Speed Drives
Wet-bulb temperature presumption control Drives with DC Reactor, EMC filter
(Energy Saving) FEATURES
Linearization function
The best location for a pressure sensor in a closed pump system is at the most distant, key
load point. This allows the system to maintain constant system pressure at all loads and takes
all system resistance into consideration.
It is not always possible to place the pressure sensor at this point in the system. Often the
pressure sensor is located near the pump discharge. In these cases, the drive regulates the
pump speed to produce a constant pressure at the outlet of the pump regardless of the actual
load requirements of the system. At reduced demand, the energy that is required to produce
pressure in excess of actual load requirements is wasted.
The Linearization Function of the FRENIC HVAC allows the user to adapt the control system to
imperfect placement of the sensor. By calculating the pump control curve of the system the
drive reduces the pump speed to meet actual load requirements. Significant Energy savings
are possible with adaptive control macros.
Variable Speed Drives
Motor PTC thermistor Drives with DC Reactor, EMC filter
FEATURES
Main Capacitor
Temperature
Motor
Variable Speed Drives
Enhanced maintenance Drives with DC Reactor, EMC filter
FEATURES
Keypad
Keypad may be mounted up to 20 Meters from drive using standard RJ-45 Port and
10BASE-T/100BASE-TX Lan Cable – Cat. 5 Compliant