Px4x-92LE-TM-EN-4

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 160

GE

Grid Solutions

MiCOM P40 Agile


Px4x-92LE

Technical Manual
IEC 61850-9-2LE Interface

Hardware Version: A
Software Version: P441SV v80, (P442/P444 v71 & 82), (P446/P546 v74 & v80), (P645SV v12
& v20), P743 v60, P746 v12, P841B v74
Publication Reference: Px4x-92LE-TM-EN-4
Contents

Chapter 1 Introduction 1
1 Chapter Overview 3
2 Foreword 4
3 Product Scope 5
4 Ordering Options 6

Chapter 2 Hardware Design 7


1 Chapter Overview 9
2 List of Boards 10
3 Redundant IEC61850-9-2LE Board 11
4 Rear Panel 12

Chapter 3 Operation 13
1 Chapter Overview 15
2 IEC 61850 16
2.1 Benefits of IEC 61850 16
2.2 IEC 61850 Interoperability 16
2.3 Introduction to IEC 61850-9-2LE 16
2.4 IEDs with an IEC61850-9-2LE Interface 17
3 Data Resampling 18
4 Sampled Value Alignment 19
4.1 Channel mappings for SAV Test, SAV Questionable, SAV Invalid 19
4.2 Channel Mappings 19
5 Data Quality 21
5.1 Impact of Data Quality on Protection Functions 21
5.1.1 P441SV, P442, P444 21
5.1.2 P446, P546, P841B 22
5.1.3 P645 22
5.1.4 P743 23
5.1.5 P746 23
6 Process Bus Performance 25
6.1 Sample Loss Data 25
7 VT Switching 26
8 Virtual Inputs and Outputs 27
8.1 P441SV, P442, P444 Virtual Inputs and Outputs DDBs 27
8.2 P446, P546, P841B Virtual Inputs and Outputs DDBs 27
8.3 P645 Virtual Inputs and Outputs DDBs 27
8.4 P743 Virtual Inputs and Outputs DDBs 27
8.5 P746 Virtual Inputs and Outputs DDBs 28
8.6 Virtual CT and VT Ratio Settings 28
9 IED Alarms 29
9.1 P441SV, P442, P444 Alarms 29
9.1.1 Alarm Signals Settings Table 29
9.1.2 Alarm Signals DDB Table 30
9.2 P446, P546, P841B Alarms 31
9.2.1 Alarm Signal Settings 31
9.2.2 Alarm Signals DDB Table 31
9.3 P645 Alarms 32
9.3.1 Alarm Signal Settings 32
9.3.2 Alarm Signals DDB Table 32
9.4 P743 Alarms 32
9.4.1 Alarm Signal Settings 33
Contents

9.4.2 Alarm Signals DDB Table 34


9.5 P746 Alarms 34
9.5.1 Alarm Signal Settings 35
9.5.2 Alarm Signals DDB Table 35
10 P546 37
10.1 Current Differential Function 37

Chapter 4 Application Examples 41


1 Application Examples 43
2 Overview 44
3 Bay Architecture 45
4 Station and Process Bus Arrangement 47
5 Voltage Input Switching 48
6 P441SV, P442, P444 50
6.1 Sampled Value Distribution 50
7 P446 52
7.1 Sampled Value Distribution 52
8 P546 54
8.1 Sampled Value Distribution 54
8.2 Current Differential Schemes 55
9 P645 58
9.1 Sampled Value Distribution 58
10 P743 60
10.1 Sampled Value Distribution 60
11 P746 62
11.1 Sampled Value Distribution 62
12 P841B 63
12.1 Sampled Value Distribution 63

Chapter 5 Commissioning Instructions 65


1 Chapter Overview 67
2 General Guidelines 68
3 Commissioning Test Equipment 69
4 Check Connections 70
5 IED Configured with One Logical Node 71
6 IED Configured with Two or More Logical Nodes 72
7 Logical Node Names 73
8 P546 74
8.1 Comissioning the GPS functionality 74
8.1.1 Strength of P594 Optical Signal at IED 74
8.1.2 Checking the GPS Synchronisation Signal at the IED 74
8.1.3 Commissioning Mode 74
9 P645, P746 75
9.1 Differential Protection Function Testing 75
10 P743 76
10.1 Current Differential Commissioning Mode 76

Chapter 6 Technical Specifications 77


1 Chapter Overview 79
2 Interfaces 80
2.1 100 Base FX Transmitter Characteristics 80
2.2 100 Base FX Receiver Characteristics 80

Chapter 7 Settings and Records 81

ii Px4x-92LE-TM-EN-4
Contents

1 Chapter Overview 83
2 P441SV, P442, P444 84
2.1 Settings Table 84
2.2 DDB Table 87
3 P446, P546, P841B 89
3.1 Settings Table 89
3.2 DDB Signals Table 92
4 P645 94
4.1 Settings Table 94
4.2 DDB Signals Table 96
5 P743 97
5.1 Settings Table 97
5.2 DDB Signals Table 98
6 P746 100
6.1 Settings Table 100
6.2 DDB Signals Table 102

Appendix A Ordering Options 105

Appendix B Wiring Diagrams 119

Px4x-92LE-TM-EN-4 iii
Contents

iv Px4x-92LE-TM-EN-4
CHAPTER 1

INTRODUCTION
Chapter 1 - Introduction

2 Px4x-92LE-TM-EN-4
Chapter 1 - Introduction

1 CHAPTER OVERVIEW
This chapter provides some general information about the technical manual and an introduction to the device(s)
described in this technical manual.
This chapter contains the following sections:
Chapter Overview 3
Foreword 4
Product Scope 5
Ordering Options 6

Px4x-92LE-TM-EN-4 3
Chapter 1 - Introduction

2 FOREWORD
This technical manual provides a functional and technical description of GE's Px4x-92LE, as well as a
comprehensive set of instructions for using the device. The level at which this manual is written assumes that you
are already familiar with protection engineering and have experience in this discipline. The description of principles
and theory is limited to that which is necessary to understand the product. For further details on general
protection engineering theory, we refer you to GE's publication, Protection and Automation Application Guide,
which is available online or from our Contact Centre.
We have attempted to make this manual as accurate, comprehensive and user-friendly as possible. However we
cannot guarantee that it is free from errors. Nor can we state that it cannot be improved. We would therefore be
very pleased to hear from you if you discover any errors, or have any suggestions for improvement. Our policy is to
provide the information necessary to help you safely specify, engineer, install, commission, maintain, and
eventually dispose of this product. We consider that this manual provides the necessary information, but if you
consider that more details are needed, please contact us.
All feedback should be sent to our contact centre via:
contact.centre@ge.com

4 Px4x-92LE-TM-EN-4
Chapter 1 - Introduction

3 PRODUCT SCOPE
The IEC 61850-9-2LE interface board assures communication with compliant Merging Units (MU). To order an IEC
61850-9-2LE version of the IED, see the relevant option in the IED's Cortec.

Px4x-92LE-TM-EN-4 5
Chapter 1 - Introduction

4 ORDERING OPTIONS
All current models and variants for this product are defined in an interactive spreadsheet called the CORTEC. This is
available on the company website.
Alternatively, you can obtain it via the Contact Centre at:
contact.centre@ge.com
A copy of the CORTEC is also supplied as a static table in the Appendices of this document. However, it should only
be used for guidance as it provides a snapshot of the interactive data taken at the time of publication.

6 Px4x-92LE-TM-EN-4
CHAPTER 2

HARDWARE DESIGN
Chapter 2 - Hardware Design

8 Px4x-92LE-TM-EN-4
Chapter 2 - Hardware Design

1 CHAPTER OVERVIEW
This chapter provides information about the product's hardware design.
This chapter contains the following sections:
Chapter Overview 9
List of Boards 10
Redundant IEC61850-9-2LE Board 11
Rear Panel 12

Px4x-92LE-TM-EN-4 9
Chapter 2 - Hardware Design

2 LIST OF BOARDS
The product's hardware consists of several modules drawn from a standard range. The exact specification and
number of hardware modules depends on the model number and variant. Depending on the exact model, the
product in question will use a selection of the following boards.
Board Use
Main Processor board - 40TE or smaller Main Processor board – without support for function keys
Main Processor board - 60TE or larger Main Processor board – with support for function keys
Power supply board - 24/54V DC Power supply input. Accepts DC voltage between 24V and 54V
Power supply board - 48/125V DC Power supply input. Accepts DC voltage between 48V and 125V
Power supply board - 110/250V DC Power supply input. Accepts DC voltage between 110V and 125V
Transformer board Contains the voltage and current transformers
Input board Contains the A/D conversion circuitry
Input board with opto-inputs Contains the A/D conversion circuitry + 8 digital opto-inputs
IRIG-B board - modulated input Interface board for modulated IRIG-B timing signal
IRIG-B board - demodulated input Interface board for demodulated IRIG-B timing signal
Fibre board Interface board for fibre-based RS485 connection
Fibre board + IRIG-B Interface board for fibre-based RS485 connection + demodulated IRIG-B
2nd rear communications board Interface board for RS232 / RS485 connections
2nd rear communications board with IRIG-B
Interface board for RS232 / RS485 + IRIG-B connections
input
High-break output relay board Output relay board with high breaking capacity relays
Redundant Ethernet RSTP + PRP + HSR + Failover Redundant Ethernet running RSTP + PRP + HSR + Failover (two fibre pairs), with on-board
universal IRIG-B universal IRIG-B
Redundant Ethernet RSTP + PRP + HSR + Failover Redundant Ethernet running RSTP + PRP + HSR + Failover (two copper pairs), with on-board
universal IRIG-B universal IRIG-B
Redundant Ethernet RSTP + PRP + HSR + Failover Redundant Ethernet running RSTP + PRP + HSR + Failover (one copper, one multi-mode
universal IRIG-B fibre), with on-board universal IRIG-B
Output relay output board Standard output relay board
Redundant Ethernet PRP + Failover IEC Redundant Ethernet for IEC 61850-9-2LE process bus running PRP + Failover (two multi-
61850-9-2LE mode fibre)

10 Px4x-92LE-TM-EN-4
Chapter 2 - Hardware Design

3 REDUNDANT IEC61850-9-2LE BOARD

L1

A1
IEC 61850-9-2LE

RXA
!

TXA
SK7

L2

A2
IEC 61850-9-2LE

RXB
!

TXB
E00107

Figure 1: Redundant IEC 61850-9-2LE board

This board provides dual redundant Ethernet for IEC 61850-9-2LE process bus. The PRP and Failover redundancy
protocols are supported.

Optical Fibre Connectors


The board uses 1300 nm multi mode 100BaseFx with ST connectors.

SK7 Connector
This is a service port for commissioning and testing only. Do not use this for permanent connections.

LEDs
LED Function On Off Flashing
Green Link Link ok Link broken
Yellow Activity Traffic

Note:
The 9-2LE interface fibre port does not support auto negotiation. Ensure the Ethernet port of the device connected to the 9-2
LE interface fibre port is set to 100Mbps full duplex.

Px4x-92LE-TM-EN-4 11
Chapter 2 - Hardware Design

4 REAR PANEL
The MiCOM Px40 series uses a modular construction. Most of the internal workings are on boards and modules
which fit into slots. Some of the boards plug into terminal blocks, which are bolted onto the rear of the unit.
However, some boards such as the communications boards have their own connectors. The rear panel consists of
these terminal blocks plus the rears of the communications boards.
The back panel cut-outs and slot allocations vary. This depends on the product, the type of boards and the
terminal blocks needed to populate the case. The following diagram shows a typical rear view of a case populated
with various boards. The IEC 61850-9-2LE interface is highlighted in grey.

D E F G H J K L M N
A B C

E00108

Figure 2: Rear view of populated case

Note:
This diagram is a typical example and may not show the exact same arrangement of boards as your particular model. Refer
to the Cortec for product details.

12 Px4x-92LE-TM-EN-4
CHAPTER 3

OPERATION
Chapter 3 - Operation

14 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

1 CHAPTER OVERVIEW
This chapter provides details of how the product functions.
This chapter contains the following sections:
Chapter Overview 15
IEC 61850 16
Data Resampling 18
Sampled Value Alignment 19
Data Quality 21
Process Bus Performance 25
VT Switching 26
Virtual Inputs and Outputs 27
IED Alarms 29
P546 37

Px4x-92LE-TM-EN-4 15
Chapter 3 - Operation

2 IEC 61850
This section describes how the IEC 61850 standard is applied to GE products. It is not a description of the standard
itself. The level at which this section is written assumes that the reader is already familiar with the IEC 61850
standard.
IEC 61850 is the international standard for Ethernet-based communication in substations. It enables integration of
all protection, control, measurement and monitoring functions within a substation, and additionally provides the
means for interlocking and inter-tripping. It combines the convenience of Ethernet with the security that is so
essential in substations today.
There are two editions of most parts of the IEC 61850 standard; edition 1 and edition 2. The edition which this
product supports depends on the Software Version.
From Software Version 90 onwards, it is possible to select between edition 1 and edition 2. Switching between
edition 1 and edition 2 is described in the Selection of the IEC 61850 Edition section.
An additional section detailing the enhancements in edition 2 models is documented later in this chapter, if
applicable.

2.1 BENEFITS OF IEC 61850


The standard provides:
● Standardised models for IEDs and other equipment within the substation
● Standardised communication services (the methods used to access and exchange data)
● Standardised formats for configuration files
● Peer-to-peer communication

The standard adheres to the requirements laid out by the ISO OSI model and therefore provides complete vendor
interoperability and flexibility on the transmission types and protocols used. This includes mapping of data onto
Ethernet, which is becoming more and more widely used in substations, in favour of RS485. Using Ethernet in the
substation offers many advantages, most significantly including:
● Ethernet allows high-speed data rates (currently 100 Mbps, rather than tens of kbps or less used by most
serial protocols)
● Ethernet provides the possibility to have multiple clients
● Ethernet is an open standard in every-day use
● There is a wide range of Ethernet-compatible products that may be used to supplement the LAN installation
(hubs, bridges, switches)

2.2 IEC 61850 INTEROPERABILITY


A major benefit of IEC 61850 is interoperability. IEC 61850 standardizes the data model of substation IEDs, which
allows interoperability between products from multiple vendors.
An IEC 61850-compliant device may be interoperable, but this does not mean it is interchangeable. You cannot
simply replace a product from one vendor with that of another without reconfiguration. However, the terminology
is pre-defined and anyone with prior knowledge of IEC 61850 should be able to integrate a new device very quickly
without having to map all of the new data. IEC 61850 brings improved substation communications and
interoperability to the end user, at a lower cost.

2.3 INTRODUCTION TO IEC 61850-9-2LE


IEC 61850-9-2LE defines Process Bus communications between the different components of the substation
automation system. MiCOM IEDs with an IEC 61850-9-2LE interface can communicate with the Process Bus and
receive IEC 61850-9-2LE data from Merging Units. Analogue Merging Units digitise analogue values from

16 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

conventional CTs and VTs, replacing analogue inputs. This simplifies the installation by replacing low voltage
analogue measurement wiring with the Process Bus Local Area Network. Using a fibre optic network instead of
heavy copper cables between the measuring device and the IED provides safer and more economical cross-site
cabling. It also allows IEDs to receive current and voltage sampled data through Digital Merging Units from non-
conventional instrument transformers such as optical and Rogowski devices.

2.4 IEDS WITH AN IEC61850-9-2LE INTERFACE


The implementation has been designed to be especially resilient and reliable in the presence of interference, such
as latency, jitter and missing or suspect data.

Va
Vb
Vc CT/VT Sampling
input CPU
Ia module
Ib
IED
Ic
E01034

Figure 3: MiCOM IED with conventional CT and VT inputs

Va
Vb
Vc Analogue
Merging
Ia Unit
IED with
Ib Digital Ethernet
IEC 61850 9-2LE
Merging Switch
Ic Interface
Unit

NCIT Va
NCIT Vb
NCIT Vc
NCIT Ia
NCIT Ib
NCIT Ic
E01032

Figure 4: IED with IEC 61850 9-2LE inputs

Px4x-92LE-TM-EN-4 17
Chapter 3 - Operation

3 DATA RESAMPLING
An IEC 61850-9-2LE SV interface receives 80 Sampled Values per cycle from the Process Bus. This is the same for
both 50 and 60 Hz. The SV interface then resamples these Sampled Values to make the data appear the same to
the IED as analogue signals would do on its normal inputs from CTs and VTs. The resampling frequency depends
on the device.
The IEC 61850-9-2LE interface also tracks the supply frequency. This is because the Sampled Values from the
Process Bus are fixed at 4000 samples/sec for 50 Hz and 4800 samples/sec at 60 Hz.

SV IED
IA
IB
IC
Analog Sampled Values IEC 61850
IN Resampling
Merging Unit (80 samples per cycle) SV CPU
VA
Interface
VB
VC
VN

Process Bus
V03701

Figure 5: Data sampling using an IEC 61850-9-2LE interface

Note:
The resampling rate for the P743 is 48 samples/cycle.

18 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

4 SAMPLED VALUE ALIGNMENT


Sampled Value frames from different Merging Units on the Process Bus may not arrive at the same time at the IED.
The transmission delay depends on the background Ethernet traffic and how many switches are used in the
Process Bus network.
Transmission delays do not usually matter for functions such as three-phase overcurrent protection where current
signals are all received in a single frame. However, a function such as distance protection uses voltage and current
signals which may be from different merging units with different transmission delays. The SV interface
synchronises the voltage and current samples that are sent to the IED’s distance protection function. The IED then
uses the Merge Unit Delay setting, which is set to the maximum expected delay between the first and last
Sampled Value.
The following examples show how you would need to set the delay.
● If the IED receives one Logical Node only, no delay is needed so set the merging unit delay to 0 ms.
● If the IED receives several Logical Nodes at the same time, no delay is needed so set the merging unit delay
to 0 ms.
● If the IED receives several Logical Nodes but not at the same time, set the merging unit delay to an
appropriate non-zero value.
If all the Logical Nodes configured in the IED are not received during the merging unit delay time, an alarm is
raised.
To set the merging unit delay during commissioning, set MUs Delay Search to Yes. The IED then monitors the
Sampled Value frames received for the next two seconds and displays the maximum delay between identical
samples.

4.1 CHANNEL MAPPINGS FOR SAV TEST, SAV QUESTIONABLE, SAV INVALID
These signals correspond to the analogue channels in a conventional MiCOM IED. The channel name appears on
the IED display against each bit.

P441SV, P442, P444


0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
VA VB VC VSC1 IA1 IB1 IC1 IM INSEN IA2 IB2 IC2 VSC2

P446, P546, P841B


0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
VA VB VC VSC1 IA1 IB1 IC1 IM INSEN IA2 IB2 IC2 VSC2

4.2 CHANNEL MAPPINGS


Each sampled value that enters the device is assigned a channel number from 0 to 23 according to the table
below:
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
VA VB IY1 IY2 IY3 IA2 IB2 IC2 IA1 IB1 IC1 VC VFLUX IA5 IB5 IC5 IA4 IB4 IC4 IA3 IB3 IC3

The cells SAV Test, SAV Questionable and SAV Invalid, are 24 bit registers which represent the corresponding
Sampled Value according to the above table. For example, if the VB sampled value was questionable, bit 1 in the
SAV Questionable register would be set to 1 and this would be displayed accordingly on the HMI panel.

Px4x-92LE-TM-EN-4 19
Chapter 3 - Operation

P743
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
IA IB IC IN

P746
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
VA VB IA3 IB3 IC3 IA2 IB2 IC2 IA1 IB1 IC1 VC IA6 IB6 IC6 IA5 IB5 IC5 IA4 IB4 IC4

20 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

5 DATA QUALITY
Any degradation in the measurement or transmission of Sampled Values means that the protection function of the
IED may not operate correctly. Data frames from a typical Logical Node have quality flags assigned to each of the
channels. The device adapts the behaviour of protection functions according to these quality flags. The available
quality flags are Good, Invalid and Questionable. A Test flag is also available for test purposes.
A protection function operates normally when all the necessary Sampled Value inputs are available and have a
Good Quality flag. When the flag for one or more of the Sampled Value inputs changes to Invalid, the protection
function is inhibited. When the flag for one or more of the Sampled Value inputs changes to Questionable, the
protection function can either be inhibited or not, depending on the chosen options in the Trus Ques Data setting.
The options are:
● Bit 0:Out of Range
● Bit 1:Bad Reference
● Bit 2:Oscillatory
● Bit 3:Old Data
● Bit 4:Inconsistent
● Bit 5:Inaccurate

The protection function will be trusted and NOT inhibited for questionable data for the items above which have
been set.
The protection function returns to the Normal state when the quality flags for all the necessary Sampled Value
inputs are Good. The quality flags can change with each sample, therefore there is a one-cycle transition delay
between the Normal and Inhibit states for each protection function.

5.1 IMPACT OF DATA QUALITY ON PROTECTION FUNCTIONS


The following table shows how Sampled Value errors affect protection functions in the IED.
For example, overcurrent protection can be configured as directional, in which case the voltage inputs have an
impact on the function. The quality of the voltage input is not important if the overcurrent is non-directional.
X means the SV input affects the Normal and Inhibit states of the protection function.
# means the protection function is affected where configured to work with this input.
$ means that frequency protection operates if any one current or voltage phase is good quality.

5.1.1 P441SV, P442, P444


[IA1 IB1 IC1] [IA2 IB2 IC2] [VA VB VC] VSC1 VSC2 IN SEN IM
Distance Protection X # X #
Overcurrent Protection X # #
Negative Sequence Overcurrent
X # #
Protection
Broken Conductor Protection X # #
Earth Fault Overcurrent
# # # #
Protection
Directional Earth Fault Protection X # X #
Residual Overvoltage Protection X
Zero Sequence Power Protection # # X #
Undercurrent Protection X #
Voltage Protection X

Px4x-92LE-TM-EN-4 21
Chapter 3 - Operation

[IA1 IB1 IC1] [IA2 IB2 IC2] [VA VB VC] VSC1 VSC2 IN SEN IM
Frequency Protection X

5.1.2 P446, P546, P841B


[IA1 IB1 IC1] [IA2 IB2 IC2] [VA VB VC] VSC1 VSC2 IN SEN IM
Differential
X # #
Protection
Distance
X # X
Protection
Directional
X # X
Earth Fault
Overcurrent
X # #
Protection
Negative
X # #
Sequence
Broken
X #
Conductor
Earth Fault
X # #
Protection
REF
X
Protection
SEF
X
Protection
Residual
X
Overvoltage
Voltage
X
Protection
Frequency
$ $ $
Protection

5.1.3 P645
[IA1 IB1 IC1]

[IA2 IB2 IC2]

[IA3 IB3 IC3]

[IA4 IB4 IC4]

[IA5 IB5 IC5]

[VA VB VC]

IY1 IY2 IY3


VFLUX

Differential
X # # # X
Protection
REF HV Protection X # X
REF LV Protection # X X
REF TV Protection # X # X
Overcurrent HV
X # #
Protection
Overcurrent LV
# X #
Protection
Overcurrent TV
# X # #
Protection
NPS HV Protection X # #
NPS LV Protection # X #

22 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

[IA1 IB1 IC1]

[IA2 IB2 IC2]

[IA3 IB3 IC3]

[IA4 IB4 IC4]

[IA5 IB5 IC5]

[VA VB VC]
IY1 IY2 IY3

VFLUX
NPS TV Protection # X # #
Earth Fault HV
# # # #
Protection
Earth Fault LV
# # # #
Protection
Earth Fault TV
# # # # #
Protection
Voltage Protection X
Residual
X
Overvoltage NVD
Overfluxing
X
Volts/Hz W1
Overfluxing
X
Volts/Hz W2
Frequency
$ $ $ $ $ $ $
Protection

5.1.4 P743
In most IEDs, Sampled Value frames that have an Invalid flag are ignored by the IED and are treated as missing.
However, if the P743 receives an Invalid flag, it blocks its protection functions and generates alarms. The P743
works with direct samples, therefore the quality status needs to be monitored to prevent an unexpected trip.
[IA IB IC IN]
Differential Protection X
Dead Zone Protection X
Circuit Breaker Failure X
Three Phase Overcurrent X
Earth Fault Current X
CT Supervision X

5.1.5 P746
[IA1 IB1 IC1]

[IA2 IB2 IC2]

[IA3 IB3 IC3]

[IA4 IB4 IC4]

[IA5 IB5 IC5]

[IA6 IB6 IC6]

[VA VB VC]

Differential Protection # # # # # # #
Overcurrent Terminal 1 X
Overcurrent Terminal 2 X
Overcurrent Terminal 3 X
Overcurrent Terminal 4 X
Overcurrent Terminal 5 X
Overcurrent Terminal 6 X
Earth Fault Terminal 1 X

Px4x-92LE-TM-EN-4 23
Chapter 3 - Operation

[IA1 IB1 IC1]

[IA2 IB2 IC2]

[IA3 IB3 IC3]

[IA4 IB4 IC4]

[IA5 IB5 IC5]

[IA6 IB6 IC6]

[VA VB VC]
Earth Fault Terminal 2 X
Earth Fault Terminal 3 X
Earth Fault Terminal 4 X
Earth Fault Terminal 5 X
Earth Fault Terminal 6 X
Dead Zone OC 1 X
Dead Zone OC 2 X
Dead Zone OC 3 X
Dead Zone OC 4 X
Dead Zone OC 5 X
Dead Zone OC 6 X

24 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

6 PROCESS BUS PERFORMANCE


Ethernet networks sometimes lose frames, so the IED tolerates some loss of samples to ensure availability of its
protection functions. The IED calculates a Frame Loss Rate every cycle for each Merging Unit (Logical Node) with
which it communicates. If the Frame Loss Rate is less than the Loss Rate Level setting (set in %), the IED tolerates
network losses of up to three consecutive samples. If the Frame Loss Rate is greater than the Loss Rate Level
setting (set in %), the protection functions are temporarily inhibited.
The IED display shows information about Sampled Analogue Value losses on the Process Bus for each Logical
Node associated with the IED in the following cells in the IEC 61850-9.2LE column. This is useful during testing or
commissioning to identify and resolve any network problems which could degrade the protection scheme.
The following data is provided:
LNx LossRate Sec: This is the percentage of SAV frames missing during the past second for LNx.
LNx FrmLoss Cuml: This is the number of frames lost since the last reset. The most recent reset time is listed in the
IED menu.
LNx Error Second: The Frame Error Seconds is a cumulative value since the last reset. If the Frame Loss Rate
exceeds 1.25% (one sample per cycle on average for one second), the IED records this as an Error Second.
where x is the number of the node (e.g. LN1)
The Sampled Analogue Values loss data can be reset manually with the LossRate Reset command in the
IEC61850-9.2LE setting column.

6.1 SAMPLE LOSS DATA


The Sampled Value loss data can be reset manually. The following data is provided:
LNx LossRate Sec: This is the percentage of SV frames missing during the past second for LNx.
LNx FrmLoss Cuml: This is the number of frames lost since the last reset. The most recent reset time is listed in the
IED menu.
LNx Error Second: The Frame Error Seconds is a cumulative value since the last reset. If the Frame Loss Rate
exceeds 1.25% (one sample per cycle on average for one second), the IED records this as an Error Second.
where x is the number of the node (e.g. LN1)

Px4x-92LE-TM-EN-4 25
Chapter 3 - Operation

7 VT SWITCHING
This function is used in the P442, P444, P446, P546 and P841B IEDs which have an IEC 61850-9-2LE interface. It
allows the user to switch the three-phase voltage input between two independent Sampled Value frames while the
IED is in service. This may correspond to two separate voltage transformers in the primary system. The VT Switch
function also allows the single-phase check synchronising voltages to be selected from three independent
Sampled Value frames.
The VT switching function is disabled by default. To enabled it, in the IED menu IEC 61850-9-2LE, select VT Switch
Mode then Enabled.

Three-Phase Voltage Input Switching


The three-phase voltage can be switched between two Sampled Value frames. These are [VA1 VB1 VC1] and [VA2
VB2 VC2]. The switching is controlled by the status of the DDB VABC Select x. The logic is shown in the following
table.
DDB
VABC Select x VA VB VC Selection
0 VA1 VB1 VC1
1 VA2 VB2 VC2
The change of VT input is accepted only if the DDB status change is effective for a minimum of 20 ms. The selected
three-phase voltage is only displayed when VT Switch Mode is enabled.

Single-Phase Voltage Input Switching


There are two single-phase voltages associated with the System Check function. These are Vsc1 and Vsc2. The
selection of voltage Vsc1 is controlled by the combined status of two DDBs, Vsc1 Select x1 and Vsc1 Select 1x as
shown in the following table.
DDB DDB
Vsc1 Select x1 Vsc1 Select 1x Vsc1 Selection
0 0 Vcs1
0 1 Vcs2
1 0 Vcs3
1 1 Unused
The selection of voltage Vsc2 is controlled by the combined status of two DDBs, Vsc2 Select x1 and Vsc2 Select 1x
as shown in the following table.
DDB DDB
Vsc2 Select x1 Vsc2 Select 1x Vsc2 Selection
0 0 Vcs2
0 1 Vcs3
1 0 Vcs1
1 1 Unused
The selected single-phase voltages are only displayed when VT Switch Mode is enabled.

26 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

8 VIRTUAL INPUTS AND OUTPUTS


Sampled Value IEDs have additional virtual inputs and virtual outputs. These are mapped as new DDBs in the IED’s
PSL and are used as triggers for GOOSE messages to and from the IED. The GOOSE Control Blocks can be
configured using the IEC 61850 Configurator software tool, which is part of the Settings Application Software.
The additional inputs and outputs make it easier to apply the IEDs in full Digital Substations where switchgear
status, controls and commands are exchanged as GOOSE messages between the IEDs and Merging Units.

8.1 P441SV, P442, P444 VIRTUAL INPUTS AND OUTPUTS DDBS

Ordinal Signal Name Source Type Response


Description
512 to 543 GOOSEOUT_1-32 PSL PFSI Protection Event Log
Virtual outputs. These allow you to control binary signals which can be mapped using the SCADA protocol output to other devices.
1224 to 1287 GOOSEIN_1-64 Software PFSI Protection Event Log
Virtual Input received from GOOSE message.

8.2 P446, P546, P841B VIRTUAL INPUTS AND OUTPUTS DDBS

Ordinal Signal Name Source Type Response


Description
1792 to 1823 GOOSEIN_33-64 Software GOOSEIN Protection Event
Virtual Input received from GOOSE message.
1888 to 1919 GOOSEOUT_33-64 PSL GOOSEOUT Protection Event
Virtual outputs. These allow you to control binary signals which can be mapped using the SCADA protocol output to other devices.

8.3 P645 VIRTUAL INPUTS AND OUTPUTS DDBS

Ordinal Signal Name Source Type Response


Description
672-703 GOOSEOUT_1-32 PSL GOOSEOUT Protection event
Virtual outputs. These allow you to control binary signals which can be mapped using the SCADA protocol output to other devices.
1754-1769 GOOSEOUT_33-48 PSL GOOSEOUT Protection event
Virtual outputs. These allow you to control binary signals which can be mapped using the SCADA protocol output to other devices.
1856-1919 GOOSEIN_1-64 SW GOOSEIN Protection event
Virtual inputs received from GOOSE message.

8.4 P743 VIRTUAL INPUTS AND OUTPUTS DDBS

Ordinal Signal Name Source Type Response


Description
112 to 127 VIRTUAL_TC 1-16 PSL PFSI Protection Event Log
Virtual outputs. These allow you to control binary signals which can be mapped using the SCADA protocol output to other devices.
368 to 383 VIRTUAL TS 1-16 Software PFSI Protection Event Log
Virtual Input received from GOOSE message.

Px4x-92LE-TM-EN-4 27
Chapter 3 - Operation

8.5 P746 VIRTUAL INPUTS AND OUTPUTS DDBS

Ordinal Signal Name Source Type Response


Description
663-715 GOOSEIN_65-117 Software GOOSEIN Protection event
Virtual inputs received from GOOSE message.
1044-1103 GOOSEOUT_33-92 PSL GOOSEOUT Protection event
Virtual outputs. These allow you to control binary signals which can be mapped using the SCADA protocol output to other devices.
1484-1494 GOOSEIN_118-128 Software GOOSEIN Protection event
Virtual inputs received from GOOSE message.
1592-1623 GOOSEOUT_1-32 PSL GOOSEOUT Protection event
Virtual outputs. These allow you to control binary signals which can be mapped using the SCADA protocol output to other devices.
1678-1695 GOOSEOUT_93-110 PSL GOOSEOUT Protection event
Virtual outputs. These allow you to control binary signals which can be mapped using the SCADA protocol output to other devices.
1722-1739 GOOSEOUT_111-128 PSL GOOSEOUT Protection event
Virtual outputs. These allow you to control binary signals which can be mapped using the SCADA protocol output to other devices.
1856-1887 GOOSEIN_1-32 Software GOOSEIN Protection event
Virtual inputs received from GOOSE message.
1888-1919 GOOSEIN_33-64 Software GOOSEIN Protection event
Virtual inputs received from GOOSE message.

8.6 VIRTUAL CT AND VT RATIO SETTINGS


The Sampled Value frames are primary measurements. These come from Merging Units (MU) connected to
conventional CTs and VTs or Non-Conventional Instrument Transformers (NCITs). Alternatively they may come
directly from NCITs. The IED algorithms are typically based on secondary values. If primary values are needed, they
are calculated by the IED based on set CT or VT ratios.
The amplitudes for 1A CT inputs are limited to 64 A secondary. The amplitudes for 5A CT inputs are limited to 320 A
secondary. The VT secondary is limited to 200 V phase-to-earth. Therefore it is necessary to set appropriate CT and
VT ratios for the protection functions to operate correctly. The instrument transformer ratios are set in the IED
menu CT AND VT RATIOS, which is common to both conventional and Sampled Value IEDs.

Measurement from a Merging Unit connected to a CT


As this has a real CT ratio, set the real primary CT ratio.

Direct measurement from an NCIT


There is no physical CT ratio. Set the CT ratio high enough so the maximum primary current (maximum fault level)
when converted to secondary is not clamped.
For example if the maximum primary current is 50 kA:
● If the CT ratio is set to 1000:1 the converted secondary current is up to 50 A. This is less than 64 A so is
acceptable.
● If the CT ratio is set to 500:1 the converted secondary current is up to 100 A. This is above 64 A so is not
acceptable.

28 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

9 IED ALARMS
Sampled Analogue Value IEDs have additional alarms.

9-2 Configuration Alarm (9-2LE Cfg Alarm)


This alarm is raised if analogue channels in the IED are assigned incorrectly (Illegal Channel Map). For example, if
you assign two current inputs to the same Logical Node.

Sampled Analogue Values quality alarm (9-2LE SAV Alarm)


This alarm is raised if any of the following conditions exist:
● One or more of the Sampled Analogue Value frames received are not synchronised as required by the IED
configuration.
● One or more of the Sampled Analogue Value frames expected are not received.
● One or more of the Sampled Analogue Value frames received are of Invalid quality.
● One or more of the Sampled Analogue Value frames received are of Questionable quality and the IED is
configured not to accept such Sampled Analogue Value frames.
● One or more of the Sampled Analogue Value frames received has a test flag, and the IED is configured to
inhibit protection functions when receiving frames with a test flag.
● One or more of the Sampled Analogue Value frames received does not have a test flag, and the IED is
configured to receive only frames with a test flag.
● Sampled Analogue Values received have a nominal frequency different to that set in the IED.
● The secondary current or voltage exceeds the acceptable limit.

9.1 P441SV, P442, P444 ALARMS

9.1.1 ALARM SIGNALS SETTINGS TABLE


MENU TEXT Col Row Default Setting Available Setting
Description
Process Bus Alarm* 18 45 Self Reset Self-Reset, Alarm Latched
This alarm shows there is an error on the Process Bus.
SAV Absence 18 51 00000000
This is a data cell with 8 binary flags. It shows the presence or absence of Sampled Values from each of the Merging Units the
IED is communicating with. There is a maximum of 8 Logical Nodes. The cell data for each Logical Node is continuously
refreshed.
0: No Sampled Values being received from the Merging Unit.
1: Sampled Values being received from the Merging Unit.
SAV No SmpSynch 18 52 00000000
This is a data cell with 8 binary flags. It indicates the healthiness of the Sampled Values being received from each of the
configured Merging Units.
0: Sampled Values received are synchronised and any loss of samples is within acceptable limits.
1: Sampled Values received are not synchronised (Setting :Synchro Alarm) or the Sampled Value delay exceeds the acceptable
value (Merging Unit Delay setting). The IED raises a 9-2 Sample Alarm when any one of the binary flags is 1.
00000000 00000000
SAV Questionable 18 54
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Questionable’ in the Sampled
Value frames for each of the analogue channels. The channel assignment depends on the IED.
00000000 00000000
SAV Invalid 18 55
00000000

Px4x-92LE-TM-EN-4 29
Chapter 3 - Operation

MENU TEXT Col Row Default Setting Available Setting


Description
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Invalid’ in the Sampled Value
frames for each of the analogue channels. The channel assignment depends on the IED.
*Setting not available on P441SV

9.1.2 ALARM SIGNALS DDB TABLE


Ordinal Signal Name Source Type Response
Description
204 ALARM_9_2_SAV Software PFSO Self reset alarm
Sampled Value error.
205 9_2_SAV_CFG_ALARM Software PFSO Self reset alarm
This alarm is triggered when the LN name is less than 10 characters or greater than 34 characters.
206 QUALITY_BLOCK_ALARM Software PFSO Self reset alarm
Due to a quality issue, this alarm indicates that protection functions are blocked on all phases.
441 QUALITY_BLK_VA Software PFSO No response
Due to a quality issue, this alarm indicates that VA protection functions are blocked.
442 QUALITY_BLK_VB Software PFSO No response
Due to a quality issue, this alarm indicates that VB protection functions are blocked.
443 QUALITY_BLK_VC Software PFSO No response
Due to a quality issue, this alarm indicates that VC protection functions are blocked.
444 QUALITY_BLK_VSC1 Software PFSO No response
Due to a quality issue, this alarm indicates that VSC1 protection functions are blocked.
445 QUALITY_BLK_IA1 Software PFSO No response
Due to a quality issue, this alarm indicates that IA1 protection functions are blocked.
446 QUALITY_BLK_IB1 Software PFSO No response
Due to a quality issue, this alarm indicates that IB1 protection functions are blocked.
447 QUALITY_BLK_IC1 Software PFSO No response
Due to a quality issue, this alarm indicates that IC1 protection functions are blocked.
448 QUALITY_BLK_IM Software PFSO No response
Due to a quality issue, this alarm indicates that IM protection functions are blocked.
449 QUALITY_BLK_INSEN Software PFSO No response
Due to a quality issue, this alarm indicates that INSEN protection functions are blocked.
450 QUALITY_BLK_IA2 Software PFSO No response
Due to a quality issue, this alarm indicates that IA2 protection functions are blocked.
451 QUALITY_BLK_IB2 Software PFSO No response
Due to a quality issue, this alarm indicates that IB2 protection functions are blocked.
452 QUALITY_BLK_IC2 Software PFSO No response
Due to a quality issue, this alarm indicates that IC2 protection functions are blocked.
453 QUALITY_BLK_VSC2 Software PFSO No response
Due to a quality issue, this alarm indicates that VSC2 protection functions are blocked.

30 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

9.2 P446, P546, P841B ALARMS

Sampled Value global synchronisation alarm (GLOBALAV_SYN_FAIL)


This alarm is raised if the global synchronisation for Sampled Values has failed, inhibiting the current differential
function.

Inverse settings alarm (ALARM_INV_SETTING_SAV)


This alarm is raised if Phase Diff is set to Enabled but GPS Sync is set to GPS disabled.

9.2.1 ALARM SIGNAL SETTINGS


MENU TEXT Col Row Default Setting Available Setting
Description
Process Bus Alarm 18 45 Self Reset Self-Reset, Alarm Latched
This alarm shows there is an error on the Process Bus.
SAV Absence 18 51 00000000
This is a data cell with 8 binary flags. It shows the presence or absence of Sampled Values from each of the Merging Units the
IED is communicating with. There is a maximum of 8 Logical Nodes. The cell data for each Logical Node is continuously
refreshed.
0: No Sampled Values being received from the Merging Unit.
1: Sampled Values being received from the Merging Unit.
SAV No SmpSynch 18 52 00000000
This is a data cell with 8 binary flags. It indicates the healthiness of the Sampled Values being received from each of the
configured Merging Units.
0: Sampled Values received are synchronised and any loss of samples is within acceptable limits.
1: Sampled Values received are not synchronised (Setting :Synchro Alarm) or the Sampled Value delay exceeds the acceptable
value (Merging Unit Delay setting). The IED raises a 9-2 Sample Alarm when any one of the binary flags is 1.
00000000 00000000
SAV Questionable 18 54
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Questionable’ in the Sampled
Value frames for each of the analogue channels. The channel assignment depends on the IED.
00000000 00000000
SAV Invalid 18 55
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Invalid’ in the Sampled Value
frames for each of the analogue channels. The channel assignment depends on the IED.

9.2.2 ALARM SIGNALS DDB TABLE


Ordinal Signal Name Source Type Response
Description
340 ALARM_9_2_SAV Software PFSO Self reset alarm
Sampled Value error.
Alarm latched with protection
341 GLOBAL_SYN_FAIL Software PFSO
function
This alarm is raised if the global synchronisation for Sampled Values has failed, inhibiting the current differential function.
342 9_2_SAV_CFG_ALARM Software PFSO Self reset alarm
This alarm is triggered when the LN name is less than 10 characters or greater than 34 characters.
343 ALARM_INV_SETTING_SAV Software PFSO Self reset alarm
This alarm is raised if Phase Diff is set to Enabled but GPS Sync is set to GPS disabled.

Px4x-92LE-TM-EN-4 31
Chapter 3 - Operation

9.3 P645 ALARMS

9.3.1 ALARM SIGNAL SETTINGS


MENU TEXT Col Row Default Setting Available Setting
Description
Trust Ques Data 18 43 000000
This setting specifies how the Sampled Values are processed by the IED when the associated Quality tag is Questionable.
There are six binary flags (0 = No, 1 = Yes) which you can set, corresponding to the data quality attributes Out of Range, Bad
Reference, Oscillatory, Old Data, Inconsistent, and Inaccurate. Questionable data is treated as invalid if the flag is 0. To process
the data as good samples, the flag is changed to 1. The setting is common to all Logical Nodes in service.
SAV Absence 18 51 00000000
This is a data cell with 8 binary flags. It shows the presence or absence of Sampled Values from each of the Merging Units the
IED is communicating with. There is a maximum of 8 Logical Nodes. The cell data for each Logical Node is continuously
refreshed.
0: No Sampled Values being received from the Merging Unit.
1: Sampled Values being received from the Merging Unit.
SAV No SmpSynch 18 52 00000000
This is a data cell with 8 binary flags. It indicates the healthiness of the Sampled Values being received from each of the
configured Merging Units.
0: Sampled Values received are synchronised and any loss of samples is within acceptable limits.
1: Sampled Values received are not synchronised (Setting :Synchro Alarm) or the Sampled Value delay exceeds the acceptable
value (Merging Unit Delay setting). The IED raises a 9-2 Sample Alarm when any one of the binary flags is 1.
00000000 00000000
SAV Questionable 18 54
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Questionable’ in the Sampled
Value frames for each of the analogue channels. The channel assignment depends on the IED.
00000000 00000000
SAV Invalid 18 55
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Invalid’ in the Sampled Value
frames for each of the analogue channels. The channel assignment depends on the IED.

9.3.2 ALARM SIGNALS DDB TABLE


Ordinal Signal Name Source Type Response
Description
472 ALARM_9_2_SAV Software PFSO Self reset alarm
Sampled Value error.
473 9_2_SAV_CFG_ALARM Software PFSO Self reset alarm
This alarm is triggered when the LN name is less than 10 characters or greater than 34 characters.

9.4 P743 ALARMS

Sampled Value Synchronisation Alarm (SAV_SYNC_ALARM)


This alarm is raised if there is an error in Sampled Value synchronisation.

32 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

Merging Unit Quality Alarm (SAV_MU_ALARM)


This alarm is raised if any of the following conditions exist:
● One or more of the received Sampled Value frames are of ‘invalid’ quality.
● One or more of the receivedSampled Value frames are of ‘questionable’ quality and the IED is configured
not to accept such Sampled Value frames.
● One or more of the received Sampled Value frames have a test flag and the IED is configured to inhibit
protection functions when receiving frames with a test flag.
● One or more of the received Sampled Value frames does not have a test flag, and the IED is configured to
receive only frames with a test flag.
● Sampled Values received have a nominal frequency different to that set in the IED.

Process Bus Alarm (PROCESS_BUS_ALARM)


This alarm is raised if any of the following conditions exist:
● One or more of the expected Sampled Value frames are not received (absence of samples).
● One or more of the expected Sampled Value frames have reached the skew threshold.
● One or more of the expected Sampled Value frames have reached the jitter threshold (+/-10 microseconds).
● Loss Rate Level reached.

Quality Blocked Alarm (QUALITY_BLK_ALARM, QUALITY_BLK_PHASE_A, B and C)


These alarms are raised to indicate that protection functions are blocked. The P743 is a segregated Low busbar
protection IED, therefore if Phase A is marked with an ‘invalid’ quality flag, protection functions are blocked only on
that phase.

9-2 Configuration Alarm (9_2_SAV_CFG_ALARM)


This alarm is triggered when the LN1 name is less than 10 characters or greater than 34 characters.

9.4.1 ALARM SIGNAL SETTINGS


MENU TEXT Col Row Default Setting Available Setting
Description
IEC 61850-9.2LE 18 00
This column contains all the configure/setting measurement parameters relative to IEC 61850-9-2LE.
Process Bus Alarm 18 45 Self Reset Self-Reset, Alarm Latched
This alarm shows there is an error on the Process Bus.
SAV Absence 18 51 00000000
This is a data cell with 8 binary flags. It indicates the presence or absence of Sampled Values from each of the Merging Units
the IED is communicating with. There is a maximum of 8 Logical Nodes. The cell data for each Logical Node is continuously
refreshed. The P743 only uses bit 0 for LN 1
0: No Sampled Values being received from the Merging Unit.
1: Sampled Values being received from the Merging Unit.
SAV No SmpSynch 18 52 00000000
This is a data cell with 8 binary flags. It indicates the healthiness of the Sampled Values being received from each of the
Merging Units configured. The P743 only uses bit 0 for LN 1.
0: Sampled Values received are synchronised and any loss of samples is within acceptable limits.
1: Sampled Values received are not synchronised (Setting :Synchro Alarm) or the Sampled Value delay exceeds the acceptable
value (Merging Unit Delay setting). The IED raises a 9-2 Sample Alarm when any one of the binary flags is 1.

Px4x-92LE-TM-EN-4 33
Chapter 3 - Operation

9.4.2 ALARM SIGNALS DDB TABLE

Ordinal Signal Name Source Type Response


Description
272 SAV_SYNC_ALARM Software PFSO Self reset alarm event
Error in Sampled Value synchronisation.
273 SAV_MU_ALARM Software PFSO Self reset alarm event
Error in Sampled Value from Merging Unit.
274 PROCESS_BUS_ALARM Software PFSO Self reset alarm event
Process Bus error.
275 QUALITY_BLK_ALARM Software PFSO Self reset alarm event
Due to a quality issue, this alarm indicates that protection functions are blocked on all phases.
276 QUALITY_BLK_PHASE_A Software PFSO No response
Due to a quality issue on Phase A, this alarm indicates that protection functions are blocked on Phase A.
277 QUALITY_BLK_PHASE_B Software PFSO No response
Due to a quality issue on Phase B, this alarm indicates that protection functions are blocked on Phase B.
278 QUALITY_BLK_PHASE_C Software PFSO No response
Due to a quality issue on Phase C, this alarm indicates that protection functions are blocked on Phase C.
279 QUALITY_BLK_PHASE_N Software PFSO No response
Due to a quality issue on the Neutral phase, this alarm indicates that protection functions are blocked on the Neutral phase.
365 9_2_SAV_CFG_ALARM Software PFSO Self reset alarm event
This alarm is triggered when the LN1 name is less than 10 characters or greater than 34 characters.

9.5 P746 ALARMS

Sampled Value Synchronisation Alarm (SAV_SYNC_ALARM)


This alarm is raised if there is an error in Sampled Value synchronisation.

Merging Unit Quality Alarm (SAV_MU_ALARM)


This alarm is raised if any of the following conditions exist:
● One or more of the received Sampled Value frames are of ‘invalid’ quality.
● One or more of the receivedSampled Value frames are of ‘questionable’ quality and the IED is configured
not to accept such Sampled Value frames.
● One or more of the received Sampled Value frames have a test flag and the IED is configured to inhibit
protection functions when receiving frames with a test flag.
● One or more of the received Sampled Value frames does not have a test flag, and the IED is configured to
receive only frames with a test flag.
● Sampled Values received have a nominal frequency different to that set in the IED.

Process Bus Alarm (PROCESS_BUS_ALARM)


This alarm is raised if any of the following conditions exist:
● One or more of the expected Sampled Value frames are not received (absence of samples).
● One or more of the expected Sampled Value frames have reached the skew threshold.
● One or more of the expected Sampled Value frames have reached the jitter threshold (+/-10 microseconds).
● Loss Rate Level reached.

34 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

Quality Blocked Alarm (QUALITY_BLK_ALARM, QUALITY_BLK_PHASE_A, B and C)


These alarms are raised to indicate that protection functions are blocked. If Phase A is marked with an ‘invalid’
quality flag, protection functions are blocked only on that phase.

9-2 Configuration Alarm (9_2_SAV_CFG_ALARM)


This alarm is triggered when the LN1 name is less than 10 characters or greater than 34 characters.

9.5.1 ALARM SIGNAL SETTINGS


MENU TEXT Col Row Default Setting Available Setting
Description
IEC 61850-9.2LE 18 00
This column contains all the configure/setting measurement parameters relative to IEC 61850-9-2LE.
Synchro Alarm 18 03 Local 1 PPS No SYNC CLK, Local 1PPS, Global 1PPS
This setting is used for processing Sampled Value frames with an IEC 61850 Test mode flag. This setting is common to all Logical Nodes
configured in the IED.
Test Blocked: all channel data frames received with an IEC 61850 Test flag are treated as invalid. The IED blocks relevant protection functions
and issues a 9-2Sample Alarm.
Test Ignored: all channel data frames received with an IEC 61850 Test flag are treated as good so all protection functions remain active.
Test Only: all channel data received with an IEC 61850 Test flag are treated as good. Any channel data received without the Test flag are
treated as invalid. The IED blocks relevant protection functions and issues a 9-2 Sample Alarm.
Trust Ques Data 18 43 000000
This setting specifies how the Sampled Values are processed by the IED when the associated Quality tag is Questionable. There are six binary
flags (0 = No, 1 = Yes) which you can set, corresponding to the data quality attributes Out of Range, Bad Reference, Oscillatory, Old Data,
Inconsistent, and Inaccurate. Questionable data is treated as invalid if the flag is 0. To process the data as good samples, the flag is changed
to 1. The setting is common to all Logical Nodes in service.
SAV Absence 18 51 000000 0 or 1 for each flag
This is a data cell with 8 binary flags. It shows the presence or absence of Sampled Values from each of the Merging Units the IED is
communicating with. There is a maximum of 8 Logical Nodes. The cell data for each Logical Node is continuously refreshed.
0: No Sampled Values being received from the Merging Unit.
1: Sampled Values being received from the Merging Unit.
SAV No SmpSynch 18 52 000000
This is a data cell with 8 binary flags. It indicates the healthiness of the Sampled Values being received from each of the configured Merging
Units..
0: Sampled Values received are synchronised and any loss of samples is within acceptable limits.
1: Sampled Values received are not synchronised (Setting :Synchro Alarm) or the Sampled Value delay exceeds the acceptable value (Merging
Unit Delay setting). The IED raises a 9-2 Sample Alarm when any one of the binary flags is 1
SAV Test 18 53 00000000 00000000 00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Test mode flag for each analogue channel processed by the IED
(eg: VA, the A-phase voltage). The channel assignment depends on the IED.
SAV Questionable 18 54 00000000 00000000 00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Questionable’ in the Sampled Value frames for
each of the analogue channels. The channel assignment depends on the IED.
SAV Invalid 18 55 00000000 00000000 00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Invalid’ in the Sampled Value frames for each of
the analogue channels. The channel assignment depends on the IED.

9.5.2 ALARM SIGNALS DDB TABLE


Ordinal Signal Name Source Type Response
Description
508 9_2_SAV_CFG_ALARM Software PFSO Self reset alarm

Px4x-92LE-TM-EN-4 35
Chapter 3 - Operation

Ordinal Signal Name Source Type Response


Description
This alarm is triggered when the LN name is less than 10 characters or greater than 34 characters.
511 ALARM_9_2_SAV Software PFSO Self reset alarm
Sampled Value error.

36 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

10 P546

10.1 CURRENT DIFFERENTIAL FUNCTION


The feeder differential function uses a P546 at each end of the protected circuit. It can be configured in two-ended
or three-ended schemes depending on the application. The IEDs send local current information to the remote
ends. The decisions whether to trip are made locally after calculating the bias and differential currents based on
the received currents.
For the current differential function to work correctly, Sampled Values from each end of the feeder must be
synchronised to correspond to the same time instant. This also applies to any other quantities derived from
samples such as Fourier values. This is essential to properly evaluate bias and differential currents. Otherwise it
could result in false differential currents and unwanted operation of the differential scheme.
In a differential scheme with conventional P546 IEDs, either:
● time stamps plus current information are exchanged between the IEDs
● all the IEDs in the scheme are synchronised to 1 PPS GPS inputs.
When the IEDs in the scheme have an IEC 61850-9-2LE interface, the synchronisation must account for delays in
receiving Sampled Values over the Process Bus network. This is not important for conventional IEDs where the
primary CTs are directly wired to the IED’s analogue inputs. The following diagram shows P546 IEDs at both line
ends of the Process Bus. The Merging Units and the Sampled Value distribution networks at End A and End B are
independent of each other. Therefore the Sampled Values may arrive at the P546 IEDs with different delays.

IEC 61850 IEC 61850 IEC 61850 IEC 61850


MU 1 MU 2 MU 1 MU 2

IEC 61850
Process Bus Process Bus MU 3

IEC 61850-9-2LE IEC 61850-9-2LE

Feeder End A P546 P546 Feeder End B

End to End
Communications
1 PPS 1 PPS

P594 P594

E01036

Figure 6: Two-ended P546 scheme with IEC 61850-9-2LE IEDs at both feeder ends

To synchronise the Sampled Values across multiple P546 IEDs with IEC 61850-9-2LE interfaces, all must be
synchronised using a 1 PPS GPS signal from a P594/RT430. This applies for all IEDs in the scheme when one or
more of the feeder ends uses Sampled Value inputs.

Px4x-92LE-TM-EN-4 37
Chapter 3 - Operation

The following conditions are also necessary for the feeder differential function to work correctly:
● All P546 IEDs in the scheme must work in GPS Synchronised mode and must have 1 PPS GPS inputs from the
P594/RT430.
● At all line ends, the Merging Units in the feeder differential scheme must use a reference time clock for
synchronisation. For example, IEEE 1588 or GPS synchronised 1PPS.
● The GPS sources for the P546 IEDs and the Merging Units must be synchronised as they may not be
common.
● The first Sampled Value frame from the Merging Units for each second has a sequence count of 0. This
corresponds to a zero time offset from the start of the second.
The P546 uses the sample count in the Sampled Value frames, plus its own 1PPS GPS synchronisation input, to
calculate delays in the Process Bus. The P546 then phase shifts the current vectors to time-align them before
performing bias and differential currents calculations. The delay is recalculated every second to adapt to any
changes in the Process Bus, enhancing the security of the protection scheme.

IEC 61850
MU 2

Process Bus
P594

1 PPS
IEC 61850
MU 1
P546
IEC 61850-9-2LE

End to End
P546 Communications

1 PPS

P594
P546

1 PPS

P594
E01037

Figure 7: Conventional and non-conventional P546 IEDs combined in a current differential scheme

The current differential scheme is inhibited at all feeder ends if any of the following conditions occur:
● The Sampled Value frames received at the P546 are not 1 PPS GPS synchronised.
● The 1PPS input to the P546 is not GPS synchronised.
● There is a delay of 100 ms or more between the receipt of a Sampled Value frame with SmpCnt 0, and the 1
PPS input pulse to the P546 indicating the start of the second.

38 Px4x-92LE-TM-EN-4
Chapter 3 - Operation

When the GPS synchronisation recovers in any of these cases, the current differential scheme inhibit is removed on
the next occurrence of the ‘SmpCnt 0’ in the Sampled Value frames.
The P546 uses a special setting for commissioning tests with IEC 61850-9-2LE using local 1 PPS synchronisation.
See the Configuration chapter.

Px4x-92LE-TM-EN-4 39
Chapter 3 - Operation

40 Px4x-92LE-TM-EN-4
CHAPTER 4

APPLICATION EXAMPLES
Chapter 4 - Application Examples

42 Px4x-92LE-TM-EN-4
Chapter 4 - Application Examples

1 APPLICATION EXAMPLES
This chapter provides typical examples of applications for the product.
This chapter contains the following sections:
Application Examples 43
Overview 44
Bay Architecture 45
Station and Process Bus Arrangement 47
Voltage Input Switching 48
P441SV, P442, P444 50
P446 52
P546 54
P645 58
P743 60
P746 62
P841B 63

Px4x-92LE-TM-EN-4 43
Chapter 4 - Application Examples

2 OVERVIEW
The IEC 61850-9-2LE interface allows measurement signals to be transferred on a common bus, known as the
Process Bus. These signals may originate from standard CTs and VTs, or from NCITs. Information from both types
of measurement devices is sampled by merging units and is transferred on the Process Bus.
In a fully digital substation, digital interfaces are used for all items of primary plant. This includes the switchgear
such as circuit breakers, isolators and earth switches, in addition to the CTs and VTs. In the present MiCOM
implementation, IEC 61850-8-1 GOOSE messages on the Station Bus port can be used to receive binary status
information from the switchgear and send controls or commands. Additional IEC 61850-8-1 GOOSE messages can
be configured in the MiCOM IEDs which use the IEC 61850-9-2LE interface.

44 Px4x-92LE-TM-EN-4
Chapter 4 - Application Examples

3 BAY ARCHITECTURE
The following diagram shows an example of substation Ethernet architecture adapted to a substation Process Bus.
IED 1 and IED 2 are used for protection BCU is the Bay Controller. This would be typical of transmission bays. In this
example, each IED receives Sampled Values from a separate Analogue Merging Unit (AMU). Each Merging Unit is
connected to a separate CT. The IEDs and AMUs are connected point-to-point. Point-to-point connections do not
need switches but need one Merging Unit for each IED. Alternatively Sampled Values could be shared from one
Merging Unit to several IEDs using an Ethernet Switch.
The diagram also shows a network architecture for digital signals. The IEDs and Switchgear Control Units (SCU)
have redundant interfaces such as the IEC 62439 Parallel Redundancy Protocol. The network uses two Ethernet
switches to create two independent LANs. For example, a trip signal or control command from IED 1 reaches SCU
1 through both LANs. This ensures redundancy to trip or control the CB.
In this example, the Sampled Value network is completely independent of the network for IEC 61850-8-1 GOOSE.
This is analogous to conventional protection schemes where the AC wiring between CTs, VTs and IED inputs is fully
independent from DC wiring for binary inputs or outputs, and interlocks.
IEC 61850-8-1 PRP

IEC 61850-8-1 PRP

IEC 61850-8-1 PRP


IEC 61850-9-2LE

IEC 61850-9-2LE

IEC 61850-9-2LE
IED 2
IED 1

BCU

D
A

GPS receiver D
B B
Switch Switch Switch
A C
Switch
IEC 61850-8-1 PRP

IEC 61850-8-1 PRP


IEC 61850-9-2LE

IEC 61850-9-2LE

IEC 61850-9-2LE

SCU 1

SCU 2
AMU 1

AMU 2

AMU 3

CB

E01074

Figure 8: Example of Bay Architecture with IEC 61850-9-2LE IEDs

Px4x-92LE-TM-EN-4 45
Chapter 4 - Application Examples

Key:
A: 1 PPS distribution to IED 1 and Analogue Merging Units.
B: Point-to-point connections for Sampled Values.
C: Sampled values for other bay functions such as busbar protection or bay control units.
D: Network with redundancy for tripping or control signals.
E: Status and trips, physical signals.
AMU: Analogue Merging Unit with CT and VT inputs, and an IEC 61850-9-2LE output.
SCU: Switchgear Control Unit with binary inputs and outputs, and a redundant IEC 61850-8-1 GOOSE interface.
BCU: Bay Controller Unit (E.g. C264)

46 Px4x-92LE-TM-EN-4
Chapter 4 - Application Examples

4 STATION AND PROCESS BUS ARRANGEMENT


The system architecture can be arranged so that different types of information are organised into groups. For
example, GOOSE messages can be sent to one segment (Process Bus) and reports to another (Station Bus).
Separating Process Bus data from Station Bus data prevents them from interfering with each other so the
bandwidth can be optimised.
The following diagram shows an Ethernet switch which routes the reports received from the IED to the clients on
the Station Bus. The reports are not present on the Process Bus segment of the network. The switch filters out the
IEC 61850 GOOSE messages that are not relevant for the Station Bus, such as the switchgear status from the SCU,
or trip commands from the IED to the SCU.
For further information on how to filter MAC multicast addresses, see the switch documentation.

Switch
IEC 61850-8-1 PRP

IEC 61850-9-2LE

F
IED

E01075

Figure 9: Integration of an IED with the Station Bus

Key:
E: Station Bus. Reports, waveform records.
F: Process Bus. IEC 61850 GOOSE.

Px4x-92LE-TM-EN-4 47
Chapter 4 - Application Examples

5 VOLTAGE INPUT SWITCHING


The following diagram shows an example of three-phase voltage switching. In this case the feeders do not have
individual voltage transformers. Therefore the feeder protection uses the voltage available from busbar voltage
transformers for distance protection and other voltage-dependent functions.
Merging Units convert Voltages VT1 and VT2 to Sampled Values. Protection devices can then use the two
independent IEC 61850-9.2LE Sampled Value data streams. In the example, the P446 is configured to receive both
data streams. This is set in the IEC 61850-9.2LE setting menu, with the VT Switch Mode enabled. By default the IED
uses VA1 VB1 VC1 for voltage-dependent functions. If VT1 fails, the operator can switch the voltage input to VA2
VB2 VC2 (VT2). This is done by changing the status of the DDB VABC Select x.
The check synchronising voltages can be switched. This is useful in breaker-and-a-half schemes or other busbar
arrangements where the VT is used for a voltage check. A feeder may not be on the busbar and may be on one of
the other bays in service when the synchronizing check is needed.

VT1 VT2

IEC 61850 IEC 61850


Merging Unit 1 Merging Unit 2

SV frame with SV frame with


VA1 VB1 VC1 VA2 VB2 VC2

To feeder protection P446

E01051

Figure 10: Example of three-phase voltage switching

The following diagram shows an application of switching the check synchronizing voltage. VT1 provides the main
three-phase voltage VA VB VC for Feeder 1. The VTs on feeders on the busbar VT2, VT3 and VT4 can be configured
as Vcs1, Vcs2 and Vcs3 respectively. These can be made available to the Feeder 1 protection as Vsc1/Vsc2 using
the appropriate DDBs.

48 Px4x-92LE-TM-EN-4
Chapter 4 - Application Examples

FEEDER 1 FEEDER 2 FEEDER 3 FEEDER 4

VT1 VT2 VT3 VT4

E01052

Figure 11: Application of switching the check synchronizing voltage

Px4x-92LE-TM-EN-4 49
Chapter 4 - Application Examples

6 P441SV, P442, P444


An IED which has an IEC 61850-9-2LE interface is intended for use in applications where CT and VT measurements
have been converted to Sampled Values. See the Ordering Options for the hardware and software versions of the
IED. Also see the IED's technical manual for descriptions of its protection and non protection functions.

This CT can be used either for residual


* current from protected line or mutual
current from parallel line.

I ** This VT can be used either for check


sync or residual voltage.

I4TH
*
IM

Neutral current
from parallel line
IEC 61850-9-2LE
if present
IED
V

IEC 61850-8-1

V4TH
**
IEC 61850-8-1 Interface

IEC 61850-9-2LE Interface

E01055
Figure 12: Overview of functionality

6.1 SAMPLED VALUE DISTRIBUTION


The IED provides up to eight Logical Nodes for receiving the Sampled Values. This allows several different
arrangements of Merging Units in the substation. There are seven analogue input groups on the IED. These are:
[IA1 IB1 IC1] [IA2 IB2 IC2] [VA VB VC] [INSEN] [IM] [Vsc1] [Vsc2]
In the following diagram, the IED receives Sampled Values from two merging units. The IED has two Logical Nodes,
one receiving the analogue input groups [IA1 IB1 IC1] and [VA VB VC], the other receiving input groups [IA2 IB2 IC2]
and [Vsc1].

50 Px4x-92LE-TM-EN-4
Chapter 4 - Application Examples

IA1, IB1, IC1


Merging
Unit 1
VA, VB, VC
IED with
Ethernet
IEC 61850 9-2LE
Switch
Interface
IA2, IB2, IC2
Merging
Unit 2
VSC1

E01038
Figure 13: IED receiving Sampled Values from two merging units

In the following diagram, the IED receives Sampled Values from four merging units. The number of merging units
can vary depending on application requirements, such as the substation layout and the inputs required by the IED.

IA1, IB1, IC1


Merging
Unit 1
INSEN

Merging
Unit 2
VA, VB, VC IED with
Ethernet
IEC 61850 9-2LE
Switch
Interface
IA2, IB2, IC2
Merging
Unit 3
Vsc1

IM
Merging
Unit 4
Vsc2
E01039
Figure 14: IED receiving Sampled Values from four merging units

Px4x-92LE-TM-EN-4 51
Chapter 4 - Application Examples

7 P446
An IED which has an IEC 61850-9-2LE interface is intended for use in applications where CT and VT measurements
have been converted to Sampled Values. In this way the P546 with an IEC 61850-9-2LE interface can be used as a
P543, P544, P545 or P546 in applications using Sampled Values. However, unlike the P543 and P545, the P546 can
be used on plain feeders only and does not cover transformer feeder applications.
See the Ordering Options for the hardware and software versions of the IED. Also see the IED's technical manual
for descriptions of its protection and non protection functions.

BUS 1

* Alternatively VSC2 could be


used for residual voltage,
selected using setting.

VSC1

I1

I2

LINE V
IEC 61850-9-2LE
VSC2 IED
*
IEC 61850-8-1

IM

Neutral current
LINE IEC 61850-8-1 Interface
from parallel line
if present
IEC 61850-9-2LE Interface

IN SEN

BUS 2

E01048
Figure 15: Overview of P546 functionality

7.1 SAMPLED VALUE DISTRIBUTION


The IED provides up to eight Logical Nodes for receiving the Sampled Values. This allows several different
arrangements of Merging Units in the substation. There are seven analogue input groups on the IED. These are:
[IA1 IB1 IC1] [IA2 IB2 IC2] [VA VB VC] [INSEN] [IM] [Vsc1] [Vsc2]
In the following diagram, the IED receives Sampled Values from two merging units. The IED has two Logical Nodes,
one receiving the analogue input groups [IA1 IB1 IC1] and [VA VB VC], the other receiving input groups [IA2 IB2 IC2]
and [Vsc1].

52 Px4x-92LE-TM-EN-4
Chapter 4 - Application Examples

IA1, IB1, IC1


Merging
Unit 1
VA, VB, VC
IED with
Ethernet
IEC 61850 9-2LE
Switch
Interface
IA2, IB2, IC2
Merging
Unit 2
VSC1

E01038
Figure 16: IED receiving Sampled Values from two merging units

In the following diagram, the IED receives Sampled Values from four merging units. The number of merging units
can vary depending on application requirements, such as the substation layout and the inputs required by the IED.

IA1, IB1, IC1


Merging
Unit 1
INSEN

Merging
Unit 2
VA, VB, VC IED with
Ethernet
IEC 61850 9-2LE
Switch
Interface
IA2, IB2, IC2
Merging
Unit 3
Vsc1

IM
Merging
Unit 4
Vsc2
E01039
Figure 17: IED receiving Sampled Values from four merging units

Px4x-92LE-TM-EN-4 53
Chapter 4 - Application Examples

8 P546
An IED which has an IEC 61850-9-2LE interface is intended for use in applications where CT and VT measurements
have been converted to Sampled Values. In this way the P446 with an IEC 61850-9-2LE interface can be used as a
P443 or P446 in applications using Sampled Values.
See the Ordering Options for the hardware and software versions of the IED. Also see the IED's technical manual
for descriptions of its protection and non protection functions.

BUS 1

* Alternatively VSC2 could be


used for residual voltage,
selected using setting.

VSC1

I1

I2

LINE V
IEC 61850-9-2LE
VSC2 IED
*
IEC 61850-8-1

IM

Neutral current
LINE IEC 61850-8-1 Interface
from parallel line
if present
IEC 61850-9-2LE Interface

IN SEN

BUS 2

E01048
Figure 18: Overview of P546 functionality

8.1 SAMPLED VALUE DISTRIBUTION


The IED provides up to eight Logical Nodes for receiving the Sampled Values. This allows several different
arrangements of Merging Units in the substation. There are seven analogue input groups on the IED. These are:
[IA1 IB1 IC1] [IA2 IB2 IC2] [VA VB VC] [INSEN] [IM] [Vsc1] [Vsc2]
In the following diagram, the IED receives Sampled Values from two merging units. The IED has two Logical Nodes,
one receiving the analogue input groups [IA1 IB1 IC1] and [VA VB VC], the other receiving input groups [IA2 IB2 IC2]
and [Vsc1].

54 Px4x-92LE-TM-EN-4
Chapter 4 - Application Examples

IA1, IB1, IC1


Merging
Unit 1
VA, VB, VC
IED with
Ethernet
IEC 61850 9-2LE
Switch
Interface
IA2, IB2, IC2
Merging
Unit 2
VSC1

E01038
Figure 19: IED receiving Sampled Values from two merging units

In the following diagram, the IED receives Sampled Values from four merging units. The number of merging units
can vary depending on application requirements, such as the substation layout and the inputs required by the IED.

IA1, IB1, IC1


Merging
Unit 1
INSEN

Merging
Unit 2
VA, VB, VC IED with
Ethernet
IEC 61850 9-2LE
Switch
Interface
IA2, IB2, IC2
Merging
Unit 3
Vsc1

IM
Merging
Unit 4
Vsc2
E01039
Figure 20: IED receiving Sampled Values from four merging units

8.2 CURRENT DIFFERENTIAL SCHEMES


Schemes with IEDs which use the IEC 61850-9-2LE interface can be two or three-ended. This is the same as with
conventional P546 relays. The schemes always require GPS synchronisation with 1 PPS inputs from P594/RT430s to
IEDs at all feeder ends.
The IEC 61850-9-2LE standard allows IEDs with Sampled Value inputs to be mixed with IEDs with conventional
inputs. This allows protected feeders to link an existing substation which has conventional equipment with a
substation where the current transformers are all non-conventional or the relays have Sampled Value inputs.

Px4x-92LE-TM-EN-4 55
Chapter 4 - Application Examples

IEC 61850 IEC 61850 IEC 61850 IEC 61850


MU 1 MU 2 MU 1 MU 2

IEC 61850
Process Bus Process Bus MU 3

IEC 61850-9-2LE IEC 61850-9-2LE

Feeder End A P546 P546 Feeder End B

End to End
Communications
1 PPS 1 PPS

P594 P594

E01036

Figure 21: Two-ended scheme with Sampled Value unputs

56 Px4x-92LE-TM-EN-4
Chapter 4 - Application Examples

IEC 61850
MU 2

Process Bus
P594

1 PPS
IEC 61850
MU 1
P546
IEC 61850-9-2LE

End to End
P546 Communications

1 PPS

P594
P546

1 PPS

P594
E01037

Figure 22: Three-ended scheme with analogue and Sampled Value unputs

The current differential protection requires GPS 1 PPS synchronisation and is inhibited if synchronisation is lost at
any one feeder end. Therefore we recommend you enable appropriate backup protection in the IEDs to ensure
faults are covered if the GPS signal fails. This backup protection should use only Local 1 PPS synchronisation of the
Sampled Value inputs.

Note:
Use a P594 with version D firmware to meet the requirements of Local 1 PPS and Global 1 PPS signals for sample
synchronisation.

Px4x-92LE-TM-EN-4 57
Chapter 4 - Application Examples

9 P645
An IED which has an IEC 61850-9-2LE interface is intended for use in applications where CT and VT measurements
have been converted to Sampled Values. In this way the P645 with an IEC 61850-9-2LE interface can be used as a
P642, P643 or P645 in applications using Sampled Values.
See the Ordering Options for the hardware and software versions of the IED. Also see the IED's technical manual
for descriptions of its protection and non protection functions.

I-HV

IN-HV

IEC 61850-9-2LE
IN-LV P645

IEC 61850-8-1
I-LV

IN-TV
IEC 61850-8-1 Interface

IEC 61850-9-2LE Interface


I-TV

I-TV

E01047

Figure 23: Overview of P645 functionality

9.1 SAMPLED VALUE DISTRIBUTION


The IED provides up to eight Logical Nodes for receiving the Sampled Values. This allows several different
arrangements of Merging Units in the substation. There are ten analogue input groups on the IED. These are:
[IA1 IB1 IC1] [IA2 IB2 IC2] [IA3 IB3 IC3] [IA4 IB4 IC4] [IA5 IB5 IC5] [IY1] [IY2] [IY3] [VA VB VC] [VFLUX]
The following diagrams show two possible arrangements for the P645. In the first diagram, the IED receives
Sampled Values from three different merging units. The HV winding currents and the optional three-phase voltage
input are received from MU1, the LV winding currents from MU2 and the tertiary currents from MU3. The winding
neutral currents, where required for functions such as restricted earth fault, can also be received through the
same merging units. In the second diagram, the IED receives Sampled Values from five different merging units.

58 Px4x-92LE-TM-EN-4
Chapter 4 - Application Examples

IA1, IB1, IC1


Merging
IY1
Unit 1
VA, VB, VC

IA3, IB3, IC3 IED with


Merging Ethernet
IEC 61850 9-2LE
Unit 2 Switch
IY2 Interface

IA5, IB5, IC5


Merging
Unit 3
IY3
E01042
Figure 24: IED receiving sampled from three merging units

IA1, IB1, IC1


Merging
Unit 1
IY1

IA2, IB2, IC2 Merging


Unit 2

IA3, IB3, IC3 IED with


Merging Ethernet
IEC 61850 9-2LE
Unit 3 Switch
IY2 Interface

IM IC4
IA4, IB4, Merging
Unit 4

IA5, IB5, IC5


Merging
Unit 5
E01043
Figure 25: IED receiving Sampled Values from five merging units

Px4x-92LE-TM-EN-4 59
Chapter 4 - Application Examples

10 P743
The P743 with the IEC 61850 interface board is intended for low impedance decentralised busbar protection
schemes using a P741. In this type of scheme the P743 is commonly named the Peripheral Unit and the P741 is
named the Central Unit Protection.
See the Ordering Options for the hardware and software versions of the IED. Also see the IED's technical manual
for descriptions of its protection and non protection functions.

10.1 SAMPLED VALUE DISTRIBUTION

Caution:
The following requirements are mandatory to maintain performance of the protection functions and
to reduce risks of maloperation.

● The Ethernet connection between the Merging Unit and the P743 must be point to point (no external switch
between Merging Units and the P743).
● The Merging Unit must acquire the measurement [IA, IB, IC, IN].
● The Merging Unit must be connected to a GLOBAL 1 PPS signal.
● Each P743 is connected to a separate Merging Unit. The time difference between signals from each Merging
Unit must not exceed 10 microseconds.
● At 50 Hz the Merging Unit acquires values every 250 microseconds +/-10 microseconds and transmits
Sampled Value frames on the Process Bus every 250 microseconds +/-10 microseconds.
● At 60 Hz the Merging Unit acquires values every 208.3 microseconds +/-10 microseconds and transmits
Sampled Value frames on the Process Bus every 208.3 microseconds +/-10 microseconds.
The following diagram shows a typical application where all P743 IEDs are Peripheral Units. IEDs can also be
connected to a dedicated IEC 61850 8.1 network.

60 Px4x-92LE-TM-EN-4
Chapter 4 - Application Examples

Global 1 PPS

IA, IB, IC, IN P743 with


Merging
Feeder 1 IEC 61850 9-2LE
Unit 1
interface board

P743 with
IA, IB, IC, IN Merging
IEC 61850 9-2LE
Feeder 2 Unit 2
interface board

P743 with
IA, IB, IC, IN Merging
IEC 61850 9-2LE
Feeder 3 Unit 3
interface board
P741
P743 with
IA, IB, IC, IN Merging
IEC 61850 9-2LE
Feeder 4 Unit 4
interface board

P743 with
IA, IB, IC, IN Merging
IEC 61850 9-2LE
Feeder 5 Unit 5
interface board

IA, IB, IC, IN Merging P743 with


Bus Coupler Unit 6 IEC 61850 9-2LE
interface board
E01045

Figure 26: Typical application of P743 with P741

Px4x-92LE-TM-EN-4 61
Chapter 4 - Application Examples

11 P746
The P746 with the IEC 61850-9-2LE interface is intended for applications where a Sampled Value interface is
required. The IED only supports applications with a maximum of six CT inputs. This is the one-box mode. The P746
with the IEC 61850-9-2LE interface does not support the three-box mode. The IED is based on P746 firmware
version 03 with MiCOM P40 Cyber-security. See the relevant relay's technical manual for descriptions of its
protection and non-protection functions.

11.1 SAMPLED VALUE DISTRIBUTION


The following diagram shows a typical P746 application where all six three-phase current inputs are used. Where
required, the optional voltage input can be combined in one of the six merging units shown or it can use a
separate dedicated merging unit.

IA1, IB1, IC1


Merging
Unit 1
VA, VB, VC

IA2, IB2, IC2


Merging
Unit 2

IA3, IB3, IC3 Merging


Unit 3 IED with
Ethernet
IEC 61850 9-2LE
Switch
IA4, IB4, IC4 Interface
Merging
Unit 4

IA5, IB5, IC5 Merging


Unit 5

IA6, IB6, IC6


Merging
Unit 6
E01044
Figure 27: IED receiving sampled from six merging units

62 Px4x-92LE-TM-EN-4
Chapter 4 - Application Examples

12 P841B
An IED which has an IEC 61850-9-2LE interface is intended for use in applications where CT and VT measurements
have been converted to Sampled Values. In this way the P841B with an IEC 61850-9-2LE interface can be used as
a P841A in applications using Sampled Values.
See the Ordering Options for the hardware and software versions of the IED. Also see the IED's technical manual
for descriptions of its protection and non protection functions.

BUS 1

* Alternatively VSC2 could be


used for residual voltage,
selected using setting.

VSC1

I1

I2

LINE V
IEC 61850-9-2LE
VSC2 IED
*
IEC 61850-8-1

IM

Neutral current
LINE IEC 61850-8-1 Interface
from parallel line
if present
IEC 61850-9-2LE Interface

IN SEN

BUS 2

E01048
Figure 28: Overview of P546 functionality

12.1 SAMPLED VALUE DISTRIBUTION


The IED provides up to eight Logical Nodes for receiving the Sampled Values. This allows several different
arrangements of Merging Units in the substation. There are seven analogue input groups on the IED. These are:
[IA1 IB1 IC1] [IA2 IB2 IC2] [VA VB VC] [INSEN] [IM] [Vsc1] [Vsc2]
In the following diagram, the IED receives Sampled Values from two merging units. The IED has two Logical Nodes,
one receiving the analogue input groups [IA1 IB1 IC1] and [VA VB VC], the other receiving input groups [IA2 IB2 IC2]
and [Vsc1].

Px4x-92LE-TM-EN-4 63
Chapter 4 - Application Examples

IA1, IB1, IC1


Merging
Unit 1
VA, VB, VC
IED with
Ethernet
IEC 61850 9-2LE
Switch
Interface
IA2, IB2, IC2
Merging
Unit 2
VSC1

E01038
Figure 29: IED receiving Sampled Values from two merging units

In the following diagram, the IED receives Sampled Values from four merging units. The number of merging units
can vary depending on application requirements, such as the substation layout and the inputs required by the IED.

IA1, IB1, IC1


Merging
Unit 1
INSEN

Merging
Unit 2
VA, VB, VC IED with
Ethernet
IEC 61850 9-2LE
Switch
Interface
IA2, IB2, IC2
Merging
Unit 3
Vsc1

IM
Merging
Unit 4
Vsc2
E01039
Figure 30: IED receiving Sampled Values from four merging units

64 Px4x-92LE-TM-EN-4
CHAPTER 5

COMMISSIONING INSTRUCTIONS
Chapter 5 - Commissioning Instructions

66 Px4x-92LE-TM-EN-4
Chapter 5 - Commissioning Instructions

1 CHAPTER OVERVIEW
This chapter contains the following sections:
Chapter Overview 67
General Guidelines 68
Commissioning Test Equipment 69
Check Connections 70
IED Configured with One Logical Node 71
IED Configured with Two or More Logical Nodes 72
Logical Node Names 73
P546 74
P645, P746 75
P743 76

Px4x-92LE-TM-EN-4 67
Chapter 5 - Commissioning Instructions

2 GENERAL GUIDELINES

Warning:
Before working on the equipment, check the device ratings and read the appropriate
Safety Information chapter.

Connect the device to the network. Check the Link and Activity LEDs are functioning. Check the IP address is
correct.
This section shows typical network connections.

68 Px4x-92LE-TM-EN-4
Chapter 5 - Commissioning Instructions

3 COMMISSIONING TEST EQUIPMENT


This is a typical list of equipment required for testing the IEC 61850-9-2LE interface in the IED.
● IED test kit capable of generating 2 or 3 sets of IEC 61850-9-2LE Sampled Values and GOOSE data sets.
Or conventional current or voltage source with Merging Unit to generate Sampled Values
● Ethernet switch(es)
● Fibre optic cables

Px4x-92LE-TM-EN-4 69
Chapter 5 - Commissioning Instructions

4 CHECK CONNECTIONS
1. De-energise the IED.
2. Visually inspect the connectors, and check the external wiring is correct.

70 Px4x-92LE-TM-EN-4
Chapter 5 - Commissioning Instructions

5 IED CONFIGURED WITH ONE LOGICAL NODE


The settings for the IEC 61850-9-2LE interface are in the IED menu IEC 61850-9-2LE. See the Settings chapter.
1. If necessary, isolate or block any outgoing trips from the IED. If physical contacts from the IED are wired in
the scheme, from the main IED menu select Test Mode.
2. Connect the IED's IEC 61850-9-2LE port to the Sampled Value source. If necessary this can be routed
through an Ethernet switch.
3. In the IED menu setting IEC 61850-9-2LE > Physical Link, select Fibre Optic for receiving Sampled
Values.
4. Check that the Logical Node name in the IED matches the name in the Sampled Value source (test kit or
Merging Unit). Make any changes in the source Logical Node names. This prevents mismatches in Logical
Node names when the IED is put into service when testing existing schemes.
5. Set the IED Synchro Alarm to No SYNC CLK so the IED accepts Sampled Value frames with or without
synchronisation.
6. Generate Sampled Value frames with the rated current and voltage as required in the IED’s Logical Node
configuration.
7. In the MEASUREMENTS menu, check the magnitudes and phase angles are displayed correctly. The display
may be in primary or secondary values. Also the IED’s CT ratio or VT ratio settings affect the display. A
typical accuracy of 1% can be expected for magnitudes.
8. Change the Logical Node name configured in the test kit. Check the data cell SAV Absence displays '0' for
the Logical Node configured in the IED. Check that all MEASUREMENTS displays for voltage or current are
zero.
9. Depending on the scheme, use the Synchro Alarm setting to return the IED to service. Re-enable the IED trip
outputs.

Px4x-92LE-TM-EN-4 71
Chapter 5 - Commissioning Instructions

6 IED CONFIGURED WITH TWO OR MORE LOGICAL NODES


The settings for the IEC 61850-9-2LE interface are in the IED menu IEC 61850-9-2LE.
1. If necessary, isolate or block any outgoing trips from the IED. If physical contacts from the IED are wired in
the scheme, from the main IED menu select Test Mode.
2. Connect the IED's IEC 61850-9-2LE port to an Ethernet switch, which is connected to the Sampled Value
sources. In the IED menu setting IEC 61850-9-2LE then Physical Link, select Fibre Optic for receiving
Sampled Values.
3. Check that the Logical Node name in the IED matches the name in the Sampled Value source (test kit or
Merging Unit). Make any changes in the source Logical Node names. This prevents mismatches in Logical
Node names when the IED is put into service when testing existing schemes.
4. Set the IED Synchro Alarm to Local 1PPS so the IED accepts Sampled Value frames with local or global
synchronisation.
5. Check that the Sampled Value source (test kit or Merging Unit) is GPS synchronised.
6. Check the receipt of Sampled Value frames one by one for each Logical Node configured in the IED.

Repeat the following steps for each Logical Node, configuring them one by one in the Sampled Value source(s).
1. Generate Sampled Value frames with the rated current and voltage as required in the IED’s Logical Node
configuration. You can check the receipt of Sampled Value frames for the configured Logical Node.
2. In the MEASUREMENTS menu, check the magnitudes and phase angles are displayed correctly. The display
may be in primary or secondary values. Also the IED’s CT ratio or VT ratio settings affect the display. A
typical accuracy of 1% can be expected for magnitudes.
3. Change the Logical Node name configured in the test kit. Check the data cell SAV Absence displays '0' for
the Logical Node configured in the IED. Check that all MEASUREMENTS displays for voltage or current are
zero.

If the GPS signal is lost, repeat the following steps for each Logical Node.
1. Check the data cell 9-2 Sample Alarm.
2. Turn off the GPS to the Sampled Value source and turn it on again. Binary flags for respective Logical Node
should indicate '1' for loss of GPS and return to '0' when the GPS is healthy.
3. Depending on the scheme, use the Synchro Alarm setting to return the IED to service. Re-enable the IED trip
outputs. If the RJ45 port was used for testing, change the setting IEC 61850-9-2LE then Physical Link to
Fibre Optic.

72 Px4x-92LE-TM-EN-4
Chapter 5 - Commissioning Instructions

7 LOGICAL NODE NAMES


Each Logical Node must be identified by a unique name that allows it to receive Sampled Values from a specific
Merging Unit.
Rename the Logical Nodes used for the application. Use between 10 and 34 characters for each Merging Unit
Logical Node name. Each Logical Node name must be exactly the same as the one set in the Merging Unit that
broadcasts it.

Px4x-92LE-TM-EN-4 73
Chapter 5 - Commissioning Instructions

8 P546

8.1 COMISSIONING THE GPS FUNCTIONALITY


The P546 needs a 1PPS GPS input to function correctly. See the IED manual for GPS synchronisation tests. Use a
P594 with version D firmware to comply with IEC 61850-9-2LE requirements for Local 1PPS and Global 1PPS
signals.

8.1.1 STRENGTH OF P594 OPTICAL SIGNAL AT IED


1. Put the P594 in Test Cycle Mode. See the P594 manual.
2. Check the optical fibre cable to the P594 transmitter is connected corrrectly.
3. Disconnect the other end of the cable from the IED and measure the received signal strength.
4. Record the value. It should be -16.8 dBm to -25.4 dBm.
5. Reconnect the optical fibre to the IED.

8.1.2 CHECKING THE GPS SYNCHRONISATION SIGNAL AT THE IED


1. In the P594 menu, set Test Cycle Mode to Disable.
2. Connect the transmit fibre from the P594 to the IED's GPS port.
3. At the IED, set PROT COMMS/IM64 > GPS Sync Enabled to Enable. This enables GPS synchronisation.
4. Select MEASUREMENTS 4 > Channel Status. If the IED receives the GPS synchronisation signal, the display
reads **11******** (where * is a don’t care state for this test). This means both the Local GPS and Remote
GPS are received.
5. To check the GPS failure condition, disconnect the fibre from the P594 and check the display reverts to
**00********.
6. Reconnect the fibre and check the display reads **11********.

8.1.3 COMMISSIONING MODE


Global synchronisation is needed for a current differential scheme to function correctly. The protection function is
blocked if global synchronisation is not present. As IED test kits may not be able to generate Sampled Value
frames with global synchronisation, the IED has a commissioning mode which allows the differential function to be
tested with local synchronisation alone.
1. In the COMMISSIONING menu, set SAV Test Mode to Local Sync Only. The current differential
protection function then operates for Sampled Value frames received with both Local 1 PPS and Global 1
PPS synchronisation.
2. Test the current differential protection function using a test kit synchronised to GPS, sending Sampled Value
frames with Local 1 PPS synchronisation.
3. When the commissioning tests are complete, set the SAV Test Mode to Disabled before the IED is
returned to service. The current differential protection operates only with Global 1 PPS synchronisation.
4. Check the Merging Unit's maximum delay and if necessary adjust the Merging Unit's delay setting.

74 Px4x-92LE-TM-EN-4
Chapter 5 - Commissioning Instructions

9 P645, P746

9.1 DIFFERENTIAL PROTECTION FUNCTION TESTING


In conventional IEDs, differential protection such as transformer differential protection can be tested using a single
three-phase current source. When testing IEDs with an IEC 61850-9-2LE interface, the test equipment should be
able to generate at least two Logical Nodes. If the IEDs receive Sampled Value frames corresponding to one
configured Logical Node only, a 9-2 Sample Alarm is raised. Single end infeed cases can be simulated by making
the current magnitudes zero in one of the Logical Nodes.

Px4x-92LE-TM-EN-4 75
Chapter 5 - Commissioning Instructions

10 P743

10.1 CURRENT DIFFERENTIAL COMMISSIONING MODE


Global synchronisation is needed for a current differential scheme to function correctly. The protection function is
blocked if global synchronisation is not present. As IED test kits may not be able to generate Sampled Value
frames with global synchronisation, the IED has a commissioning mode which allows the differential function to be
tested with local synchronisation alone.
1. In the COMMISSION TESTS menu, set SAV SynTst to Local Sync Only. The current differential protection
function then operates for Sampled Value frames received with both Local 1 PPS and Global 1 PPS
synchronisation.
2. Test the current differential protection function using a test kit synchronised to GPS, sending Sampled Value
frames with Local 1 PPS synchronisation.
3. When the commissioning tests are complete, set the SAV SynTst to Disabled before the IED is returned to
service. The current differential protection operates only with Global 1 PPS synchronisation.
4. Check the Merging Unit's maximum delay and if necessary adjust the Merging Unit's delay setting.

76 Px4x-92LE-TM-EN-4
CHAPTER 6

TECHNICAL SPECIFICATIONS
Chapter 6 - Technical Specifications

78 Px4x-92LE-TM-EN-4
Chapter 6 - Technical Specifications

1 CHAPTER OVERVIEW
This chapter describes the technical specifications of the product.
This chapter contains the following sections:
Chapter Overview 79
Interfaces 80

Px4x-92LE-TM-EN-4 79
Chapter 6 - Technical Specifications

2 INTERFACES

2.1 100 BASE FX TRANSMITTER CHARACTERISTICS

Parameter Sym Min. Typ. Max. Unit


Output Optical Power BOL 62.5/125 µm -19
PO -16.8 -14 dBm avg.
NA = 0.275 Fibre EOL -20
Output Optical Power BOL 50/125 µm -22.5
PO -20.3 -14 dBm avg.
NA = 0.20 Fibre EOL -23.5
10 %
Optical Extinction Ratio
-10 dB
Output Optical Power at Logic "0" State PO -45 dBm avg.

Conditions: TA = 0°C to 70°C

2.2 100 BASE FX RECEIVER CHARACTERISTICS

Parameter Sym Min. Typ. Max. Unit


Input Optical Power Minimum at
PIN Min. (W) -33.5 –31 dBm avg.
Window Edge
Input Optical Power Minimum at
PIN Min. (C) -34.5 -31.8 Bm avg.
Eye Center
Input Optical Power Maximum PIN Max. -14 -11.8 dBm avg.

Conditions: TA = 0°C to 70°C

80 Px4x-92LE-TM-EN-4
CHAPTER 7

SETTINGS AND RECORDS


Chapter 7 - Settings and Records

82 Px4x-92LE-TM-EN-4
Chapter 7 - Settings and Records

1 CHAPTER OVERVIEW
IEDs which use the IEC 61850-9-2LE interface have additional settings, each depending on the IED.
This chapter contains the following sections:
Chapter Overview 83
P441SV, P442, P444 84
P446, P546, P841B 89
P645 94
P743 97
P746 100

Px4x-92LE-TM-EN-4 83
Chapter 7 - Settings and Records

2 P441SV, P442, P444

2.1 SETTINGS TABLE


IEDs which have the IEC 61850-9-2LE interface have additional settings in the IEC 61850-9.2LE submenu. This
allows them to be configured to the system and application.
To display the primary values whether CTs, VTs or NCITs are used, set Remote Values in the MEASURE’T SET UP
column to Primary.
MENU TEXT Col Row Default Setting Available Setting
Description
IEC 61850-9.2LE 18 00
This column contains all the configure/setting measurement parameters relative to IEC61850-9-2LE.
Physical Link 18 01 Fibre Optic Copper, Fibre Optic
This setting specifies the physical connection between the IED and the Process Bus network. The RJ45 copper port is for service use only and
should not be used as a permanent connection.
AntiAias Filter 18 02 Enabled Disabled, Enabled
This setting activates or deactivates the anti-aliasing filter, which conditions the Sampled Values from the Process Bus network.
Synchro Alarm 18 03 Local 1PPS No SYNC CLK, Local 1PPS, Global 1PPS
This setting specifies the type of Sampled Value synchronisation expected by the IED, depending on the application.
Global 1PPS: the Sampled Values are synchronised with a global area clock (GPS like clock). The IED issues an alarm (‘9-2 Sample Alarm’) when it
receives Sampled Value frames without Global 1PPS.
Local 1PPS: the Sampled Values are synchronised with a local area clock signal at the substation. Sampled Value frames received with Global
or Local synchronisation are acceptable with this setting. The IED issues the alarm '9-2 Sample Alarm' if the Sampled Value frames received
have no synchronisation.
No SYNC CLK: the Sampled Values do not need to be synchronised. With this setting the IED ignores the synchronisation flag in the Sampled
Value frames.
9.2 Test Mode 18 04 Test Blocked Test Blocked, Test Ignored, Test Only
This setting is used for processing Sampled Value frames with an IEC 61850 Test mode flag. This setting is common to all Logical Nodes
configured in the IED.
Test Blocked: all channel data frames received with an IEC 61850 Test flag are treated as invalid. The IED blocks relevant protection functions
and issues a ‘9-2 Sample Alarm’.
Test Ignored: all channel data frames received with an IEC 61850 Test flag are treated as good so all protection functions remain active.
Test Only: all channel data received with an IEC 61850 Test flag are treated as good. Any channel data received without the Test flag are
treated as invalid. The IED blocks relevant protection functions and issues a ‘9-2 Sample Alarm’.
Merge Unit Delay 18 05 1 ms
When Sampled Values are received at the IED from different Merging Units, they may not arrive simultaneously due to differences in Merging
Unit performance or different network path delays. This setting specifies the maximum time delay expected, starting at the reception of the
Sampled Value frame from the first Merging Unit to the reception of the Sampled Value frame from the last Merging Unit for each sample
count. Signal processing starts at the end of the Merging Unit delay and if a frame is not received in that specified time, an alarm appears.
(9-2 Sample Alarm).
The IED has a search command to measure and display the maximum Sampled Value frame delay. The Merging Unit Delay can be set based on
the result of the search, which is displayed on the IED.
VT Switch Mode 18 06 Disabled Disabled, Enabled
If VT Switching Mode is enabled, you can configure the IED to switch between different VT inputs. These can be single-phase or three-phase
inputs and are received as Sampled Values. The corresponding setting cells are visible when VT Switching Mode is enabled. Switching is
controlled either using opto or virtual inputs. These can be assigned in the IED's Programmable Scheme Logic. If you do not need to use VT
switching for voltage based protection functions or check synchronising, disable it.
LN Count 18 11 1
This setting specifies the number of Logical Nodes in use for receiving the Sampled Values required by the IED. The default value varies with
the product. Modify the LN Count to match the number of Merging Units relevant for the IED in each specific application. The default LN Count
is model dependent.

84 Px4x-92LE-TM-EN-4
Chapter 7 - Settings and Records

MENU TEXT Col Row Default Setting Available Setting


Description
LN1 Name to LN9
18 12 MiCOM Logical Node 1 to 9
Name
Each Logical Node must be identified by a unique name that allows it to receive Sampled Values from a specific Merging Unit. The default
name for LN1 is ‘MiCOM Logical Node 1’. You can edit this ASCII text string using between 10 and 34 characters to match the Merging Unit’s
Logical Node (sample value identifier) name . The same applies for LN2 to 9. The Logical Node name is the system-wide unique identification
‘MsvID’ defined in the Merging Unit control block MSVCB according to IEC 61850-9-2 Ed 1.0. The number of Logical Nodes available is variable,
as set in LN Count. For example, with an LN Count of 3, LN1 Name, LN2 Name and LN3 Name should be set to match those of the
corresponding Merging Units.
Rename the Logical Nodes used for the application. Use between 10 and 34 characters to match each MU Logical Node name. Each Logical
Node name must be exactly the same as the one set in the Merging Unit that broadcasts it.
IA1 IB1 IC1 18 31 LN1 Unused, LN1, LN2, LN3,…,LN 9
Three-phase current inputs to the IED.
IA2 IB2 IC2 18 32 Unused Unused,LN1, LN2, LN3,…,LN 9
Three-phase current inputs to the IED.
INsen 18 33 Unused Unused,LN1, LN2, LN3,…,LN 9
Current input with sensitive range for SEF/REF functions. This single-phase current signal is recovered from the neutral current in the IEC
61850-9-2LE frame of the LN assigned.
IM 18 34 Unused Unused,LN1, LN2, LN3,…,LN 9
Current input for neutral current from a parallel feeder. This single-phase current signal is recovered from the neutral current in the IEC
61850-9-2LE frame of the LN assigned.
VA VB VC 18 35 LN1 Unused,LN1, LN2, LN3,…,LN 9
Three-phase voltage inputs to the IED. The default setting Logical Node 1 indicates that only one LN is configured. This cell is visible only when
VT Switch Mode [18 06] is disabled.
Vsc1 18 36 Unused Unused,LN1, LN2, LN3,…,LN 9
This single-phase voltage is recovered from the phase(s) assigned in the IED setting. It may be assigned to Van, Vbn, Vcn, Vab, Vbc or Vca in the
settings. The IEC 61850-9-2LE interface uses the appropriate phase(s) from the Sampled Value frame received on the Logical Node configured
for Vsc1. The IED raises an Illegal Channel Map alarm if the same Logical Node is assigned to both [VA VB VC] and Vsc1. This cell is visible only
when VT Switch Mode is disabled.
Vsc2 18 37 Unused Unused, LN1, LN2, LN3,…,LN 9
This single-phase voltage is recovered from the phase(s) assigned in the IED setting. It may be assigned to Van, Vbn, Vcn, Vab, Vbc or Vca in the
settings. The IEC 61850-9-2LE interface uses the appropriate phase(s) from the Sampled Value frame received on the Logical Node configured
for Vsc2. The IED raises an Illegal Channel Map alarm if the same Logical Node is assigned to both [VA VB VC] and Vsc2. This cell is visible only
when VT Switch Mode is disabled.
VA1 VB1 VC1 18 38 LN1 Unused, LN1, LN2, LN3,…,LN 9
One of the two Sampled Value inputs for selection of three-phase voltage for use by functions in the relay, such as distance protection or
overvoltage protection. This cell is visible only when VT Switch Mode is enabled.
VA2 VB2 VC2 18 39 Unused Unused, LN1, LN2, LN3,…,LN 9
The second of the two Sampled Value inputs for selection of three-phase voltage for use by functions in the relay, such as distance protection
or overvoltage protection. This cell is visible only when VT Switch Mode is enabled.
Vcs1 18 3A Unused Unused, LN1, LN2, LN3,…,LN 9
The first of the three Sampled Value inputs for selection of single-phase voltage for check synchronising function. This cell is visible only when
VT Switch Mode is enabled.
This single-phase voltage is recovered from the phase(s) assigned in the IED setting. It can be assigned to Van, Vbn, Vcn, Vab, Vbc or Vca in the
settings. The IEC 61850-9-2LE interface uses the appropriate phase(s) from the Sampled Value frame. These are received on the Logical Node
which is configured for Vcs1.
Vcs2 18 3B Unused Unused, LN1, LN2, LN3,…,LN 9

Px4x-92LE-TM-EN-4 85
Chapter 7 - Settings and Records

MENU TEXT Col Row Default Setting Available Setting


Description
The second of the three Sampled Value inputs for selection of single-phase voltage for check synchronising function. This cell is visible only
when VT Switch Mode is enabled.
This single-phase voltage is recovered from the phase(s) assigned in the IED setting. It can be assigned to Van, Vbn, Vcn, Vab, Vbc or Vca in the
settings. The IEC 61850-9-2LE interface uses the appropriate phase(s) from the Sampled Value frame. These are received on the Logical Node
which is configured for Vcs2.
Vcs3 18 3C Unused Unused, LN1, LN2, LN3,…,LN 9
The third Sampled Value inputs for selection of single-phase voltage for check synchronising function. This cell is visible only when VT Switch
Mode is enabled.
This single-phase voltage is recovered from the phase(s) assigned in the IED setting. It can be assigned to Van, Vbn, Vcn, Vab, Vbc or Vca in the
settings. The IEC 61850-9-2LE interface uses the appropriate phase(s) from the Sampled Value frame. These are received on the Logical Node
which is configured for Vcs3.
MUs Delay Search 18 41 No No, Yes
The IED has a search command to measure and display the maximum Sampled Value frame delay. The Merging Unit Delay can be set based on
the result of the search, which is displayed on the IED.
MUs Delay Max 18 42 0
When sampled values are received at the IED from different Merging Units, they may not arrive simultaneously due to differences in Merging
Unit performance or different network path delays. This setting specifies the maximum time-delay expected, starting at the reception of the
sampled value frame from the "first" Merging Unit to the reception of the sampled value frame from the last Merging Unit for each sample
count. Signal processing starts at the end of the Merging Unit delay and if a frame is not received in that specified time, a synchronisation
alarm appears.
Trust Ques Data 18 43 000000 0 or 1 for each flag
This setting specifies how the Sampled Values are processed by the IED when the associated Quality tag is ‘Questionable’. There are six binary
flags (0 = No, 1 = Yes) which can be set by the user, corresponding to the data quality attributes ‘Out of Range’, ‘Bad Reference’, ‘Oscillatory’,
‘Old Data’, ‘Inconsistent’ and ‘Inaccurate’. Questionable data is treated as invalid if the flag is ‘0’. To process the data as good samples, the flag
is changed to ‘1’. The setting is common to all Logical Nodes in service.
Loss Rate Level 18 44 10%
This setting is related to Process Bus network performance, in particular, the possibility of loss of samples. The set threshold is an upper limit
for the loss of Sampled Values from any of the Logical Nodes configured in the IED, calculated every cycle. If the loss rate level exceeds the set
value, the IED generates the ‘9-2 Sample Alarm’ and the related protection functions are inhibited. 1.25% corresponds to the loss of 1 out of the
80 samples expected every cycle, averaged over one second. The loss rate calculation and threshold check is performed independently for
each Logical Node configured.
SAV Absence 18 51 000000000 0 or 1 for each flag
This is a data cell with 9 binary flags. It indicates the presence or absence of Sampled Values from each of the Merging Units the IED is
communicating with. There is a maximum of 9 Logical Nodes. The cell data for each Logical Node is continuously refreshed.
0: Sampled Values being received from the Merging Unit.
1: No Sampled Values being received from the Merging Unit.
SAV No SmpSynch 18 52 000000000 0 or 1 for each flag
This is a data cell with 9 binary flags. It indicates the healthiness of the Sampled Values being received from each of the configured Merging
Units:
0: Sampled Values received are synchronised and any loss of samples is within acceptable limits.
1: Sampled Values received are not synchronised (Setting : Synchro Alarm) or the Sampled Value delay exceeds the acceptable value (Merging
Unit Delay setting). The IED raises a ‘SAV No SmpSynch’ when any one of the binary flags is ‘1’.
00000000 00000000
SAV Test 18 53 0 or 1 for each flag
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Test mode flag for each analogue channel processed by the IED
(eg: VA, the A-phase voltage). The channel assignment depends on the IED.
00000000 00000000
SAV Questionable 18 54 0 or 1 for each flag
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Questionable’ in the Sampled Value frames for
each of the analogue channels. The channel assignment depends on the IED.

86 Px4x-92LE-TM-EN-4
Chapter 7 - Settings and Records

MENU TEXT Col Row Default Setting Available Setting


Description
00000000 00000000
SAV Invalid 18 55 0 or 1 for each flag
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Invalid’ in the Sampled Value frames for each of
the analogue channels. The channel assignment depends on the IED.
Frame Loss Data 18 70
This column contains all the configure/setting measurement parameters relative to frame loss data.
Frame Loss Rate 18 71 Enabled Disabled, Enabled
Enables the frame loss rate counter
LN1 – LN9
18 72 – 7A 0
Loss Rate Sec
These data cells indicate the percentage of SV frames missing during the past second, for LNx
LossRate Reset 18 90 No No, Yes
Resets the frame loss rate counter
Reset Time 18 91 0
This data cell is the time stamp of the most recent instance of Frame Loss Rate counter
LN1 – LN9 FrmLoss
18 92 – 9A 0
Cuml
These data cells indicate the number of frames lost since last reset for LN 1…9; the most recent reset time available in the IED menu.
LN1 - LN9 Error
18 B1 to 9 0
Second
Frame Error Seconds is a cumulative value since the last reset per LN. If the Frame Loss Rate exceeds 1.25% (one sample per cycle on average
for one second) the IED records this as an Error Second.
VA VB VC 18 D1 VA1 VB1 VC1, VA2 VB2 VC2
This data cell displays the three-phase voltage input in use by the relay. This cell is visible only when VT Switch Mode is enabled.
Vsc1 18 D2 Vcs1, Vcs2, Vcs3
This data cell displays the single-phase voltage in use by the System Check function as Vsc1. This cell is visible only when VT Switch Mode is
enabled.
Vsc2 18 D3 Vcs1, Vcs2, Vcs3
This data cell displays the single-phase voltage in use by the System Check function as Vsc2. This cell is visible only when VT Switch Mode is
enabled.

2.2 DDB TABLE


IEDs which have the IEC 61850-9-2LE interface have additional DDBs so they can be configured to the system and
application.
Ordinal Signal Name Source Type Response
Description
204 ALARM_9_2_SAV Software PFSO Self reset alarm
Sampled Value error.
205 9_2_SAV_CFG_ALARM Software PFSO Self reset alarm
This alarm is triggered when the LN name is less than 10 characters or greater than 34 characters.
206 QUALITY_BLOCK_ALARM Software PFSO Self reset alarm
Due to a quality issue, this alarm indicates that protection functions are blocked on all phases.
441 QUALITY_BLK_VA Software PFSO No response
Due to a quality issue, this alarm indicates that VA protection functions are blocked.

Px4x-92LE-TM-EN-4 87
Chapter 7 - Settings and Records

Ordinal Signal Name Source Type Response


Description
442 QUALITY_BLK_VB Software PFSO No response
Due to a quality issue, this alarm indicates that VB protection functions are blocked.
443 QUALITY_BLK_VC Software PFSO No response
Due to a quality issue, this alarm indicates that VC protection functions are blocked.
444 QUALITY_BLK_VSC1 Software PFSO No response
Due to a quality issue, this alarm indicates that VSC1 protection functions are blocked.
445 QUALITY_BLK_IA1 Software PFSO No response
Due to a quality issue, this alarm indicates that IA1 protection functions are blocked.
446 QUALITY_BLK_IB1 Software PFSO No response
Due to a quality issue, this alarm indicates that IB1 protection functions are blocked.
447 QUALITY_BLK_IC1 Software PFSO No response
Due to a quality issue, this alarm indicates that IC1 protection functions are blocked.
448 QUALITY_BLK_IM Software PFSO No response
Due to a quality issue, this alarm indicates that IM protection functions are blocked.
449 QUALITY_BLK_INSEN Software PFSO No response
Due to a quality issue, this alarm indicates that INSEN protection functions are blocked.
450 QUALITY_BLK_IA2 Software PFSO No response
Due to a quality issue, this alarm indicates that IA2 protection functions are blocked.
451 QUALITY_BLK_IB2 Software PFSO No response
Due to a quality issue, this alarm indicates that IB2 protection functions are blocked.
452 QUALITY_BLK_IC2 Software PFSO No response
Due to a quality issue, this alarm indicates that IC2 protection functions are blocked.
453 QUALITY_BLK_VSC2 Software PFSO No response
Due to a quality issue, this alarm indicates that VSC2 protection functions are blocked.
1133 9_2_VABC_SELECT_X PSL PFSI VT Switch
Switches 3 phase voltage between 2 Sampled Value frames.
1134 9_2_VSC1_SELECT_X1 PSL PFSI VT Switch
Used to select single phase voltage VSC1 associated with System Check function.
1135 9_2_VSC1_SELECT_1X PSL PFSI VT Switch
Used to select single phase voltage VSC1 associated with System Check function.
1136 9_2_VSC2_SELECT_X1 PSL PFSI VT Switch
Used to select single phase voltage VSC2 associated with System Check function.
1137 9_2_VSC2_SELECT_1X PSL PFSI VT Switch
Used to select single phase voltage VSC2 associated with System Check function.

88 Px4x-92LE-TM-EN-4
Chapter 7 - Settings and Records

3 P446, P546, P841B

3.1 SETTINGS TABLE


IEDs which have the IEC 61850-9-2LE interface have additional settings in the IEC 61850-9.2LE submenu. This
allows them to be configured to the system and application.
To display the primary values whether CTs, VTs or NCITs are used, set Remote Values in the MEASURE’T SET UP
column to Primary.
MENU TEXT Col Row Default Setting Available Setting
Description
IEC 61850-9.2LE 18 00
This column contains all the configure/setting measurement parameters relative to IEC61850-9-2LE.
Physical Link 18 01 Fibre Optic Copper, Fibre Optic
This setting specifies the physical connection between the IED and the Process Bus network. The RJ45 copper port is for service use only and
should not be used as a permanent connection.
AntiAias Filter 18 02 Enabled Disabled, Enabled
This setting activates or deactivates the anti-aliasing filter, which conditions the Sampled Values from the Process Bus network.
Synchro Alarm 18 03 Local 1PPS No SYNC CLK, Local 1PPS, Global 1PPS
This setting specifies the type of Sampled Value synchronisation expected by the IED, depending on the application.
Global 1PPS: the Sampled Values are synchronised with a global area clock (GPS like clock). The IED issues an alarm (‘9-2 Sample Alarm’) when it
receives Sampled Value frames without Global 1PPS.
Local 1PPS: the Sampled Values are synchronised with a local area clock signal at the substation. Sampled Value frames received with Global
or Local synchronisation are acceptable with this setting. The IED issues the alarm '9-2 Sample Alarm' if the Sampled Value frames received
have no synchronisation.
No SYNC CLK: the Sampled Values do not need to be synchronised. With this setting the IED ignores the synchronisation flag in the Sampled
Value frames.
9.2 Test Mode 18 04 Test Blocked Test Blocked, Test Ignored, Test Only
This setting is used for processing Sampled Value frames with an IEC 61850 Test mode flag. This setting is common to all Logical Nodes
configured in the IED.
Test Blocked: all channel data frames received with an IEC 61850 Test flag are treated as invalid. The IED blocks relevant protection functions
and issues a ‘9-2 Sample Alarm’.
Test Ignored: all channel data frames received with an IEC 61850 Test flag are treated as good so all protection functions remain active.
Test Only: all channel data received with an IEC 61850 Test flag are treated as good. Any channel data received without the Test flag are
treated as invalid. The IED blocks relevant protection functions and issues a ‘9-2 Sample Alarm’.
Merge Unit Delay 18 05 1 ms
When Sampled Values are received at the IED from different Merging Units, they may not arrive simultaneously due to differences in Merging
Unit performance or different network path delays. This setting specifies the maximum time delay expected, starting at the reception of the
Sampled Value frame from the first Merging Unit to the reception of the Sampled Value frame from the last Merging Unit for each sample
count. Signal processing starts at the end of the Merging Unit delay and if a frame is not received in that specified time, an alarm appears.
(9-2 Sample Alarm).
The IED has a search command to measure and display the maximum Sampled Value frame delay. The Merging Unit Delay can be set based on
the result of the search, which is displayed on the IED.
VT Switch Mode 18 06 Disabled Disabled, Enabled
If VT Switching Mode is enabled, you can configure the IED to switch between different VT inputs. These can be single-phase or three-phase
inputs and are received as Sampled Values. The corresponding setting cells are visible when VT Switching Mode is enabled. Switching is
controlled either using opto or virtual inputs. These can be assigned in the IED's Programmable Scheme Logic. If you do not need to use VT
switching for voltage based protection functions or check synchronising, disable it.
LN Count 18 11 1
This setting specifies the number of Logical Nodes in use for receiving the Sampled Values required by the IED. The default value varies with
the product. Modify the LN Count to match the number of Merging Units relevant for the IED in each specific application. The default LN Count
is model dependent.

Px4x-92LE-TM-EN-4 89
Chapter 7 - Settings and Records

MENU TEXT Col Row Default Setting Available Setting


Description
LN1 Name to LN9
18 12 MiCOM Logical Node 1 to 9
Name
Each Logical Node must be identified by a unique name that allows it to receive Sampled Values from a specific Merging Unit. The default
name for LN1 is ‘MiCOM Logical Node 1’. You can edit this ASCII text string using between 10 and 34 characters to match the Merging Unit’s
Logical Node (sample value identifier) name . The same applies for LN2 to 9. The Logical Node name is the system-wide unique identification
‘MsvID’ defined in the Merging Unit control block MSVCB according to IEC 61850-9-2 Ed 1.0. The number of Logical Nodes available is variable,
as set in LN Count. For example, with an LN Count of 3, LN1 Name, LN2 Name and LN3 Name should be set to match those of the
corresponding Merging Units.
Rename the Logical Nodes used for the application. Use between 10 and 34 characters to match each MU Logical Node name. Each Logical
Node name must be exactly the same as the one set in the Merging Unit that broadcasts it.
IA1 IB1 IC1 18 31 LN1 Unused, LN1, LN2, LN3,…,LN 9
Three-phase current inputs to the IED.
IA2 IB2 IC2 18 32 Unused Unused,LN1, LN2, LN3,…,LN 9
Three-phase current inputs to the IED.
INsen 18 33 Unused Unused,LN1, LN2, LN3,…,LN 9
Current input with sensitive range for SEF/REF functions. This single-phase current signal is recovered from the neutral current in the IEC
61850-9-2LE frame of the LN assigned.
IM 18 34 Unused Unused,LN1, LN2, LN3,…,LN 9
Current input for neutral current from a parallel feeder. This single-phase current signal is recovered from the neutral current in the IEC
61850-9-2LE frame of the LN assigned.
VA VB VC 18 35 LN1 Unused,LN1, LN2, LN3,…,LN 9
Three-phase voltage inputs to the IED. The default setting Logical Node 1 indicates that only one LN is configured. This cell is visible only when
VT Switch Mode [18 06] is disabled.
Vsc1 18 36 Unused Unused,LN1, LN2, LN3,…,LN 9
This single-phase voltage is recovered from the phase(s) assigned in the IED setting. It may be assigned to Van, Vbn, Vcn, Vab, Vbc or Vca in the
settings. The IEC 61850-9-2LE interface uses the appropriate phase(s) from the Sampled Value frame received on the Logical Node configured
for Vsc1. The IED raises an Illegal Channel Map alarm if the same Logical Node is assigned to both [VA VB VC] and Vsc1. This cell is visible only
when VT Switch Mode is disabled.
Vsc2 18 37 Unused Unused, LN1, LN2, LN3,…,LN 9
This single-phase voltage is recovered from the phase(s) assigned in the IED setting. It may be assigned to Van, Vbn, Vcn, Vab, Vbc or Vca in the
settings. The IEC 61850-9-2LE interface uses the appropriate phase(s) from the Sampled Value frame received on the Logical Node configured
for Vsc2. The IED raises an Illegal Channel Map alarm if the same Logical Node is assigned to both [VA VB VC] and Vsc2. This cell is visible only
when VT Switch Mode is disabled.
VA1 VB1 VC1 18 38 LN1 Unused, LN1, LN2, LN3,…,LN 9
One of the two Sampled Value inputs for selection of three-phase voltage for use by functions in the relay, such as distance protection or
overvoltage protection. This cell is visible only when VT Switch Mode is enabled.
VA2 VB2 VC2 18 39 Unused Unused, LN1, LN2, LN3,…,LN 9
The second of the two Sampled Value inputs for selection of three-phase voltage for use by functions in the relay, such as distance protection
or overvoltage protection. This cell is visible only when VT Switch Mode is enabled.
Vcs1 18 3A Unused Unused, LN1, LN2, LN3,…,LN 9
The first of the three Sampled Value inputs for selection of single-phase voltage for check synchronising function. This cell is visible only when
VT Switch Mode is enabled.
This single-phase voltage is recovered from the phase(s) assigned in the IED setting. It can be assigned to Van, Vbn, Vcn, Vab, Vbc or Vca in the
settings. The IEC 61850-9-2LE interface uses the appropriate phase(s) from the Sampled Value frame. These are received on the Logical Node
which is configured for Vcs1.
Vcs2 18 3B Unused Unused, LN1, LN2, LN3,…,LN 9

90 Px4x-92LE-TM-EN-4
Chapter 7 - Settings and Records

MENU TEXT Col Row Default Setting Available Setting


Description
The second of the three Sampled Value inputs for selection of single-phase voltage for check synchronising function. This cell is visible only
when VT Switch Mode is enabled.
This single-phase voltage is recovered from the phase(s) assigned in the IED setting. It can be assigned to Van, Vbn, Vcn, Vab, Vbc or Vca in the
settings. The IEC 61850-9-2LE interface uses the appropriate phase(s) from the Sampled Value frame. These are received on the Logical Node
which is configured for Vcs2.
Vcs3 18 3C Unused Unused, LN1, LN2, LN3,…,LN 9
The third Sampled Value inputs for selection of single-phase voltage for check synchronising function. This cell is visible only when VT Switch
Mode is enabled.
This single-phase voltage is recovered from the phase(s) assigned in the IED setting. It can be assigned to Van, Vbn, Vcn, Vab, Vbc or Vca in the
settings. The IEC 61850-9-2LE interface uses the appropriate phase(s) from the Sampled Value frame. These are received on the Logical Node
which is configured for Vcs3.
MUs Delay Search 18 41 No No, Yes
The IED has a search command to measure and display the maximum Sampled Value frame delay. The Merging Unit Delay can be set based on
the result of the search, which is displayed on the IED.
MUs Delay Max 18 42 0
When sampled values are received at the IED from different Merging Units, they may not arrive simultaneously due to differences in Merging
Unit performance or different network path delays. This setting specifies the maximum time-delay expected, starting at the reception of the
sampled value frame from the "first" Merging Unit to the reception of the sampled value frame from the last Merging Unit for each sample
count. Signal processing starts at the end of the Merging Unit delay and if a frame is not received in that specified time, a synchronisation
alarm appears.
Trust Ques Data 18 43 000000 0 or 1 for each flag
This setting specifies how the Sampled Values are processed by the IED when the associated Quality tag is ‘Questionable’. There are six binary
flags (0 = No, 1 = Yes) which can be set by the user, corresponding to the data quality attributes ‘Out of Range’, ‘Bad Reference’, ‘Oscillatory’,
‘Old Data’, ‘Inconsistent’ and ‘Inaccurate’. Questionable data is treated as invalid if the flag is ‘0’. To process the data as good samples, the flag
is changed to ‘1’. The setting is common to all Logical Nodes in service.
Loss Rate Level 18 44 10%
This setting is related to Process Bus network performance, in particular, the possibility of loss of samples. The set threshold is an upper limit
for the loss of Sampled Values from any of the Logical Nodes configured in the IED, calculated every cycle. If the loss rate level exceeds the set
value, the IED generates the ‘9-2 Sample Alarm’ and the related protection functions are inhibited. 1.25% corresponds to the loss of 1 out of the
80 samples expected every cycle, averaged over one second. The loss rate calculation and threshold check is performed independently for
each Logical Node configured.
SAV Absence 18 51 000000000 0 or 1 for each flag
This is a data cell with 9 binary flags. It indicates the presence or absence of Sampled Values from each of the Merging Units the IED is
communicating with. There is a maximum of 9 Logical Nodes. The cell data for each Logical Node is continuously refreshed.
0: Sampled Values being received from the Merging Unit.
1: No Sampled Values being received from the Merging Unit.
SAV No SmpSynch 18 52 000000000 0 or 1 for each flag
This is a data cell with 9 binary flags. It indicates the healthiness of the Sampled Values being received from each of the configured Merging
Units:
0: Sampled Values received are synchronised and any loss of samples is within acceptable limits.
1: Sampled Values received are not synchronised (Setting : Synchro Alarm) or the Sampled Value delay exceeds the acceptable value (Merging
Unit Delay setting). The IED raises a ‘SAV No SmpSynch’ when any one of the binary flags is ‘1’.
00000000 00000000
SAV Test 18 53 0 or 1 for each flag
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Test mode flag for each analogue channel processed by the IED
(eg: VA, the A-phase voltage). The channel assignment depends on the IED.
00000000 00000000
SAV Questionable 18 54 0 or 1 for each flag
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Questionable’ in the Sampled Value frames for
each of the analogue channels. The channel assignment depends on the IED.

Px4x-92LE-TM-EN-4 91
Chapter 7 - Settings and Records

MENU TEXT Col Row Default Setting Available Setting


Description
00000000 00000000
SAV Invalid 18 55 0 or 1 for each flag
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Invalid’ in the Sampled Value frames for each of
the analogue channels. The channel assignment depends on the IED.
Frame Loss Data 18 70
This column contains all the configure/setting measurement parameters relative to frame loss data.
Frame Loss Rate 18 71 Enabled Disabled, Enabled
Enables the frame loss rate counter
LN1 – LN9
18 72 – 7A 0
Loss Rate Sec
These data cells indicate the percentage of SV frames missing during the past second, for LNx
LossRate Reset 18 90 No No, Yes
Resets the frame loss rate counter
Reset Time 18 91 0
This data cell is the time stamp of the most recent instance of Frame Loss Rate counter
LN1 – LN9 FrmLoss
18 92 – 9A 0
Cuml
These data cells indicate the number of frames lost since last reset for LN 1…9; the most recent reset time available in the IED menu.
LN1 - LN9 Error
18 B1 to 9 0
Second
Frame Error Seconds is a cumulative value since the last reset per LN. If the Frame Loss Rate exceeds 1.25% (one sample per cycle on average
for one second) the IED records this as an Error Second.
VA VB VC 18 D1 VA1 VB1 VC1, VA2 VB2 VC2
This data cell displays the three-phase voltage input in use by the relay. This cell is visible only when VT Switch Mode is enabled.
Vsc1 18 D2 Vcs1, Vcs2, Vcs3
This data cell displays the single-phase voltage in use by the System Check function as Vsc1. This cell is visible only when VT Switch Mode is
enabled.
Vsc2 18 D3 Vcs1, Vcs2, Vcs3
This data cell displays the single-phase voltage in use by the System Check function as Vsc2. This cell is visible only when VT Switch Mode is
enabled.

3.2 DDB SIGNALS TABLE


IEDs which have the IEC 61850-9-2LE interface have additional DDBs so they can be configured to the system and
application.
Ordinal English Text Source Description
340 9-2 Sample Alarm Software Abnormal state of IEC 61850-9-2LE sample.
The IEC 61850-9-2LE sample Global sync has failed,
341 C Diff Sync Fail Software
inhibiting the current differential function.
This alarm highlights discrepancies in assignments of
analogue channels in the IED. For example, if you assign
342 9-2LE Cfg Alarm Software
two current inputs to the same Logical Node, the IED
raises an Illegal Channel Map alarm.
This DDB issues an alarm when Phase Diff is set to
343 Invalid Setting Software
'Enabled' but GPS Sync is set to 'GPS Disabled'.
991 VABC Select x PSL Switch three-phase voltage between two designated LNs
992 Vsc1 Select x1 PSL Switch Vsc1 between three designated LN – Bit 1

92 Px4x-92LE-TM-EN-4
Chapter 7 - Settings and Records

Ordinal English Text Source Description


993 Vsc1 Select 1x PSL Switch Vsc1 between three designated LN – Bit 0
994 Vsc2 Select x1 PSL Switch Vsc2 between three designated LN – Bit 1
995 Vsc2 Select 1x PSL Switch Vsc2 between three designated LN – Bit 0
1792-1823 Virtual Input 33-64 Software These are additional virtual Inputs.
These are additional virtual inputs that provide Quality
1824-1855 Quality VIP 33 -64 Software
attributes.
These are are additional virtual inputs that indicate if the
1856-1887 PubPres VIP 33 -64 Software
publisher is present.
1888-1919 Virtual Output33-64 PSL These are additional GOOSE outputs.

Px4x-92LE-TM-EN-4 93
Chapter 7 - Settings and Records

4 P645

4.1 SETTINGS TABLE


IEDs which have the IEC 61850-9-2LE interface have additional settings in the IEC 61850-9.2LE submenu. This
allows them to be configured to the system and application.
To display the primary values whether CTs, VTs or NCITs are used, set Remote Values in the MEASURE’T SET UP
column to Primary.
MENU TEXT Col Row Default Setting Available Setting
Description
IEC 61850-9.2LE 18 00
This column contains all the configure/setting measurement parameters relative to IEC61850-9-2LE.
Physical Link 18 01 Fibre Optic Copper, Fibre Optic
This setting specifies the physical connection between the IED and the Process Bus network. The RJ45 copper port is for service use only and
should not be used as a permanent connection.
AntiAias Filter 18 02 Enabled Disabled, Enabled
This setting activates or deactivates the anti-aliasing filter, which conditions the Sampled Values from the Process Bus network.
Synchro Alarm 18 03 Local 1PPS No SYNC CLK, Local 1PPS, Global 1PPS
This setting specifies the type of Sampled Value synchronisation expected by the IED, depending on the application.
Global 1PPS: the Sampled Values are synchronised with a global area clock (GPS like clock). The IED issues an alarm (‘9-2 Sample Alarm’) when it
receives Sampled Value frames without Global 1PPS.
Local 1PPS: the Sampled Values are synchronised with a local area clock signal at the substation. Sampled Value frames received with Global
or Local synchronisation are acceptable with this setting. The IED issues the alarm '9-2 Sample Alarm' if the Sampled Value frames received
have no synchronisation.
No SYNC CLK: the Sampled Values do not need to be synchronised. With this setting the IED ignores the synchronisation flag in the Sampled
Value frames.
9-2 Test Mode 18 04 Test Blocked Test Blocked, Test Ignored, Test Only
This setting is used for processing Sampled Value frames with an IEC 61850 Test mode flag. This setting is common to all Logical Nodes
configured in the IED.
Test Blocked: all channel data frames received with an IEC 61850 Test flag are treated as invalid. The IED blocks relevant protection functions
and issues a ‘9-2 Sample Alarm’.
Test Ignored: all channel data frames received with an IEC 61850 Test flag are treated as good so all protection functions remain active.
Test Only: all channel data received with an IEC 61850 Test flag are treated as good. Any channel data received without the Test flag are
treated as invalid. The IED blocks relevant protection functions and issues a ‘9-2 Sample Alarm’.
Merge Unit Delay 18 05 1 ms
When Sampled Values are received at the IED from different Merging Units, they may not arrive simultaneously due to differences in Merging
Unit performance or different network path delays. This setting specifies the maximum time delay expected, starting at the reception of the
Sampled Value frame from the first Merging Unit to the reception of the Sampled Value frame from the last Merging Unit for each sample
count. Signal processing starts at the end of the Merging Unit delay and if a frame is not received in that specified time, an alarm appears.
(9-2 Sample Alarm).
The IED has a search command to measure and display the maximum Sampled Value frame delay. The Merging Unit Delay can be set based on
the result of the search, which is displayed on the IED.
LN Count 18 11 8
This setting specifies the number of Logical Nodes in use for receiving the Sampled Values required by the IED. The default value varies with
the product. Modify the LN Count to match the number of Merging Units relevant for the IED in each specific application. The default LN Count
is model dependent.
LN1 Name to LN8 Name 18 12 MiCOM Logical Node 1 to 8

94 Px4x-92LE-TM-EN-4
Chapter 7 - Settings and Records

MENU TEXT Col Row Default Setting Available Setting


Description
Each Logical Node must be identified by a unique name that allows it to receive Sampled Values from a specific Merging Unit. The default
name for LN1 is ‘MiCOM Logical Node 1’. You can edit this ASCII text string using between 10 and 34 characters to match the Merging Unit’s
Logical Node (sample value identifier) name . The same applies for LN2 to 8. The Logical Node name is the system-wide unique identification
‘MsvID’ defined in the Merging Unit control block MSVCB according to IEC 61850-9-2 Ed 1.0. The number of Logical Nodes available is variable,
as set in LN Count. For example, with an LN Count of 3, LN1 Name, LN2 Name and LN3 Name should be set to match those of the
corresponding Merging Units.
Rename the Logical Nodes used for the application. Use between 10 and 34 characters to match each MU Logical Node name. Each Logical
Node name must be exactly the same as the one set in the Merging Unit that broadcasts it.
IA1 IB1 IC1 - IA5 IB5 IC5 18 31 - 35 LN1 - 5 Unused, LN1, LN2, LN3,…,LN 8
Three-phase current inputs to the IED for HV, LV and TV windings.
IY1 - IY3 18 36 - 38 LN6 - LN8 Unused, LN1, LN2, LN3,…,LN 8
The single-phase current signals IY1, IY2 and IY3 for REF function. These are recovered from the neutral current in the IEC 61850-9-2LE frame of
the assigned LN
VA VB VC 18 39 LN1 Unused, LN1, LN2, LN3,…,LN 8
The three-phase voltage input [VA VB VC] used for overflux element W1. The IED raises an Illegal Channel Map alarm if the same Logical Node
is assigned to both [VA VB VC] and VFLUX.
VFLUX 18 3A LN2 Unused,LN1, LN2, LN3,…,LN 8
The single phase input VFLUX is used for overflux element W2. The IED raises an Illegal Channel Map alarm if the same Logical Node is
assigned to both [VA VB VC] and VFLUX.
MUs Delay Search 18 41 No No, Yes
The IED has a search command to measure and display the maximum Sampled Value frame delay. The Merging Unit Delay can be set based on
the result of the search, which is displayed on the IED.
MUs Delay Max 18 42 0
When sampled values are received at the IED from different Merging Units, they may not arrive simultaneously due to differences in Merging
Unit performance or different network path delays. This setting specifies the maximum time-delay expected, starting at the reception of the
sampled value frame from the "first" Merging Unit to the reception of the sampled value frame from the last Merging Unit for each sample
count. Signal processing starts at the end of the Merging Unit delay and if a frame is not received in that specified time, a synchronisation
alarm appears.
Trust Ques Data 18 43 000000 0 or 1 for each flag
This setting specifies how the Sampled Values are processed by the IED when the associated Quality tag is ‘Questionable’. There are six binary
flags (0 = No, 1 = Yes) which can be set by the user, corresponding to the data quality attributes ‘Out of Range’, ‘Bad Reference’, ‘Oscillatory’,
‘Old Data’, ‘Inconsistent’ and ‘Inaccurate’. Questionable data is treated as invalid if the flag is ‘0’. To process the data as good samples, the flag
is changed to ‘1’. The setting is common to all Logical Nodes in service.
Loss Rate Level 18 44 10%
This setting is related to Process Bus network performance, in particular, the possibility of loss of samples. The set threshold is an upper limit
for the loss of Sampled Values from any of the Logical Nodes configured in the IED, calculated every cycle. If the loss rate level exceeds the set
value, the IED generates the ‘9-2 Sample Alarm’ and the related protection functions are inhibited. 1.25% corresponds to the loss of 1 out of the
80 samples expected every cycle, averaged over one second. The loss rate calculation and threshold check is performed independently for
each Logical Node configured.
SAV Absence 18 51 00000000 0 or 1 for each flag
This is a data cell with 8 binary flags. It indicates the presence or absence of Sampled Values from each of the Merging Units the IED is
communicating with. There is a maximum of 8 Logical Nodes. The cell data for each Logical Node is continuously refreshed.
0: Sampled Values being received from the Merging Unit.
1: No Sampled Values being received from the Merging Unit.
SAV No SmpSynch 18 52 00000000 0 or 1 for each flag
This is a data cell with 8 binary flags. It indicates the healthiness of the Sampled Values being received from each of the Merging Uniured:
0: Sampled Values received are synchronised and any loss of samples is within acceptable limits.
1: Sampled Values received are not synchronised (Setting : Synchro Alarm) or the Sampled Value delay exceeds the acceptable value (Merging
Unit Delay setting). The IED raises a ‘9-2 Sample Alarm’ when any one of the binary flags is ‘1’.

Px4x-92LE-TM-EN-4 95
Chapter 7 - Settings and Records

MENU TEXT Col Row Default Setting Available Setting


Description
00000000 00000000
SAV Test 18 53 0 or 1 for each flag
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Test mode flag for each analogue channel processed by the IED
(eg: VA, the A-phase voltage). The channel assignment depends on the IED.
00000000 00000000
SAV Questionable 18 54 0 or 1 for each flag
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Questionable’ in the Sampled Value frames for
each of the analogue channels. The channel assignment depends on the IED.
00000000 00000000
SAV Invalid 18 55 0 or 1 for each flag
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Invalid’ in the Sampled Value frames for each of
the analogue channels. The channel assignment depends on the IED.
Frame Loss Data 18 70
This column contains all the configure/setting measurement parameters relative to frame loss data.
Frame Loss Rate 18 71 Enabled Disabled, Enabled
Enables the frame loss rate counter
LN1 - LN8
18 72 - 79 0
LossRate Sec
These data cells indicate the percentage of SV frames missing during the past second, for LNx.
LossRate Reset 18 90 No No, Yes
Resets the frame loss rate counter
Reset Time 18 91 0
This data cell is the time stamp of the most recent instance of Frame Loss Rate counter.
LN1 – LN8 FrmLoss Cuml 18 92 - 99 0
These data cells indicate the number of frames lost since last reset for LN 1…8, the most recent reset time available in the IED menu.
LN1 - LN8 Error Second 18 B1 to 8 0
Frame Error Seconds is a cumulative value since the last reset per LN. If the Frame Loss Rate exceeds 1.25% (one sample per cycle on average
for one second) the IED records this as an Error Second.

4.2 DDB SIGNALS TABLE


IEDs which have the IEC 61850-9-2LE interface have additional DDBs so they can be configured to the system and
application.
Ordinal English Text Source Description
472 9-2 Sample Alarm Software Abnormal state of IEC 61850-9-2LE sample.
This alarm highlights discrepancies in assignments of analogue
channels in the IED. For example, if you assign two current
473 9-2LE Cfg Alarm Software
inputs to the same Logical Node, the IED raises an Illegal
Channel Map alarm.
These are additional virtual inputs that provide Quality
1088-1119 Quality VIP 33 -64 Software
attributes.
These are are additional virtual inputs that indicate if the
1152-1183 PubPres VIP 33 -64 Software
publisher is present.
1754-1769 Virtual Output33-48 PSL These are additional GOOSE outputs

96 Px4x-92LE-TM-EN-4
Chapter 7 - Settings and Records

5 P743

5.1 SETTINGS TABLE


IEDs which have the IEC 61850-9-2LE interface have additional settings in the IEC 61850-9.2LE submenu. This
allows them to be configured to the system and application.
To display the primary values whether CTs, VTs or NCITs are used, set Remote Values in the MEASURE’T SET UP
column to Primary.
Menu Text Col Row Default Setting Available Options
Description
IEC 61850-9.2LE 18 00
Physical Link 18 01 Fibre Optic Copper, Fibre Optic
This setting specifies the physical connection between the IED and the Process Bus network. The RJ45 copper port is for service use only and
should not be used as a permanent connection.
Anti-Alias Filter 10 02 Enabled Disabled, Enabled
This setting activates or deactivates the anti-aliasing filter, which conditions the Sampled Values from the Process Bus network.
9-2 Test Mode 10 04 Test Blocked Test Blocked, Test Ignored, Test Only
This setting is used for processing Sampled Value frames with an IEC 61850 Test mode flag. This setting is common to all Logical Nodes
configured in the IED.
Test Blocked: all channel data frames received with an IEC 61850 Test flag are treated as invalid. The IED blocks relevant protection functions
and issues a ‘9-2Sample Alarm’.
Test Ignored: all channel data frames received with an IEC 61850 Test flag are treated as good so all protection functions remain active.
Test Only: all channel data received with an IEC 61850 Test flag are treated as good. Any channel data received without the Test flag are
treated as invalid. The IED blocks relevant protection functions and issues a ‘9-2Sample Alarm’.
LN1 Name 18 12 MiCOM Logic Node 1
Logical Node 1 must be identified by a unique name that allows it to receive Sampled Values from a specific Merging Unit. Rename the Logical
Node using between 10 and 34 characters to match the MU Logical Node name. The Logical Node name must be exactly the same as the one
set in the Merging Unit that broadcasts it.
Trust Ques Data 18 43 000000 0 or 1 for each flag
This setting specifies how the Sampled Values are processed by the IED when the associated Quality tag is ‘Questionable’. There are six binary
flags (0 = No, 1 = Yes) which can be set by the user, corresponding to the data quality attributes ‘Out of Range’, ‘Bad Reference’, ‘Oscillatory’,
‘Old Data’, ‘Inconsistent’ and ‘Inaccurate’. Questionable data is treated as invalid if the flag is ‘0’. To process the data as good samples, the flag
is changed to ‘1’. The setting is common to all Logical Nodes in service.
Loss Rate Level 18 44 10% 1.25% to 15%, in steps of 1.25%
This setting is related to Process Bus network performance, in particular, the possibility of loss of samples. The set threshold is an upper limit
for the loss of Sampled Values from any of the Logical Nodes configured in the IED, calculated every cycle. If the loss rate level exceeds the set
value, the IED generates the ‘9-2Sample Alarm’ and the related protection functions are inhibited. 1.25% corresponds to the loss of 1 out of the
80 samples expected every cycle, averaged over one second. The loss rate calculation and threshold check is performed independently for
each Logical Node configured.
ProcessBus Alarm 18 45 Self Reset

SAV Absence 18 51 00000000 0 or 1 for each flag


This is a data cell with 8 binary flags. It indicates the presence or absence of Sampled Values from each of the Merging Units the IED is
communicating with. There is a maximum of 8 Logical Nodes. The cell data for each Logical Node is continuously refreshed.
0: Sampled Values being received from the Merging Unit.
1: No Sampled Values being received from the Merging Unit.
SAV No SampSync 18 52 00000000 0 or 1 for each flag

Px4x-92LE-TM-EN-4 97
Chapter 7 - Settings and Records

Menu Text Col Row Default Setting Available Options


Description
This is a data cell with 8 binary flags. It indicates the healthiness of the Sampled Values being received from each of the Merging Units
configured:
0: Sampled Values received are synchronised and any loss of samples is within acceptable limits.
1: Sampled Values received are not synchronised (Setting : SynchroAlarm) or the Sampled Value delay exceeds the acceptable value (Merging
Unit Delay setting). The IED raises a ‘9-2 Sample Alarm’ when any one of the binary flags is ‘1’.
SAV Test 18 53 00000000 00000000 00000000 0 or 1 for each flag
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Test mode flag for each analogue channel processed by the IED
(eg: VA, the A-phase voltage). The channel assignment depends on the IED.
SAV Questionable 18 54 00000000 00000000 00000000 0 or 1 for each flag
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Questionable’ in the Sampled Value frames for
each of the analogue channels. The channel assignment depends on the IED.
SAV Invalid 18 55 00000000 00000000 00000000 0 or 1 for each flag
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Invalid’ in the Sampled Value frames for each of
the analogue channels. The channel assignment depends on the IED.
Jitter Status 18 56
Only the first bit is used.
Frame Loss Data 18 70

Frame Loss Rate 18 71 Enabled Enabled, Disabled

LN1 LossRate Sec 18 72

Loss Rate Reset 18 90 No Yes, No

Last Reset Time 18 91

LN1 FrmLoss Points 18 92


Logical node 1 counts how many frames are lost from the time of reset.
LN1 Error Second 18 B1
Counter for error seconds.

5.2 DDB SIGNALS TABLE


IEDs which have the IEC 61850-9-2LE interface have additional DDBs so they can be configured to the system and
application.
Ordinal Signal Name Source Type Response
Description
112 to
VIRTUAL_TC 1-16 PSL PFSI Protection Event Log
127
Virtual output - allows your to control a binary signal which can be mapped using the SCADA protocol output to other devices
272 SAV_SYNC_ALARM Software PFSO Self reset alarm event
Error in Sampled Value synchronisation.
273 SAV_MU_ALARM Software PFSO Self reset alarm event
Error in Sampled Value from Merging Unit.
274 PROCESS_BUS_ALARM Software PFSO Self reset alarm event

98 Px4x-92LE-TM-EN-4
Chapter 7 - Settings and Records

Ordinal Signal Name Source Type Response


Description
Process Bus error.
275 QUALITY_BLK_ALARM Software PFSO Self reset alarm event
Due to a quality issue, this alarm indicates that protection functions are blocked on all phases.
276 QUALITY_BLK_PHASE_A Software PFSO No response
Due to a quality issue on Phase A, this alarm indicates that protection functions are blocked on Phase A.
277 QUALITY_BLK_PHASE_B Software PFSO No response
Due to a quality issue on Phase B, this alarm indicates that protection functions are blocked on Phase B.
278 QUALITY_BLK_PHASE_C Software PFSO No response
Due to a quality issue on Phase C, this alarm indicates that protection functions are blocked on Phase C.
279 QUALITY_BLK_PHASE_N Software PFSO No response
Due to a quality issue on the Neutral phase, this alarm indicates that protection functions are blocked on the Neutral phase.
365 9_2_SAV_CFG_ALARM Software PFSO Self reset alarm event
Error in 9-2 configuration.
368 to GOOSE Input
VIRTUAL TS 1-16 PFSI Protection Event Log
383 Command
Virtual Input received from GOOSE message
1152 to GOOSE Input
VIP_QUALITY_1 to 64 PFSO Protection Event Log
1215 Command
GOOSE virtual input - provides the Quality attributes of any data object in an incoming GOOSE message
1280 to GOOSE Input
VIP_PUB_PRES_1 to 64 PFSO Protection Event Log
1343 Command
GOOSE virtual input - indicates if the GOOSE publisher responsible for publishing the data that derives a virtual input is
present.

Px4x-92LE-TM-EN-4 99
Chapter 7 - Settings and Records

6 P746

6.1 SETTINGS TABLE


IEDs which have the IEC 61850-9-2LE interface have additional settings in the IEC 61850-9.2LE submenu. This
allows them to be configured to the system and application.
To display the primary values whether CTs, VTs or NCITs are used, set Remote Values in the MEASURE’T SET UP
column to Primary.
MENU TEXT Col Row Default Setting Available Setting
Description
IEC 61850-9.2LE 18 00
This column contains all the configure/setting measurement parameters relative to IEC 61850-9-2LE.
Physical Link 18 01 Fibre Optic Copper, Fibre Optic
This setting specifies the physical connection between the IED and the Process Bus network. The RJ45 copper port is for service use only and
should not be used as a permanent connection.
AntiAlais Filter 18 02 Enabled Disabled, Enabled
This setting activates or deactivates the anti-aliasing filter, which filters the Sampled Values from the Process Bus network.
Synchro Alarm 18 03 Local 1 PPS No SYNC CLK, Local 1PPS, Global 1PPS
This setting is used for processing Sampled Value frames with an IEC 61850 Test mode flag. This setting is common to all Logical Nodes
configured in the IED.
Test Blocked: all channel data frames received with an IEC 61850 Test flag are treated as invalid. The IED blocks relevant protection functions
and issues a 9-2Sample Alarm.
Test Ignored: all channel data frames received with an IEC 61850 Test flag are treated as good so all protection functions remain active.
Test Only: all channel data received with an IEC 61850 Test flag are treated as good. Any channel data received without the Test flag are
treated as invalid. The IED blocks relevant protection functions and issues a 9-2 Sample Alarm.

This setting is used for processing Sampled Value frames with an IEC 61850 Test mode flag. This setting is common to all Logical Nodes
configured in the IED.
Test Blocked: all channel data frames received with an IEC 61850 Test flag are treated as invalid. The IED blocks relevant protection functions
and issues a 9-2Sample Alarm.
Test Ignored: all channel data frames received with an IEC 61850 Test flag are treated as good so all protection functions remain active.
Test Only: all channel data received with an IEC 61850 Test flag are treated as good. Any channel data received without the Test flag are
treated as invalid. The IED blocks relevant protection functions and issues a 9-2 Sample Alarm.
Merge Unit Delay 18 05 1ms 0 to 3 ms, step 0.25 ms
When Sampled Values are received at the IED from different Merging Units, they may not arrive simultaneously due to differences in Merging
Unit performance or different network path delays. This setting specifies the maximum time delay expected, starting at the reception of the
Sampled Value frame from the first Merging Unit to the reception of the Sampled Value frame from the last Merging Unit for each sample
count. Signal processing starts at the end of the Merging Unit delay and if a frame is not received in that specified time, an alarm appears.
(9-2 Sample Alarm).
The IED has a search command to measure and display the maximum Sampled Value frame delay. The Merging Unit Delay can be set based on
the result of the search, which is displayed on the IED.
LN Count 18 11 6 1 to 8
This setting specifies the number of Logical Nodes in use for receiving the Sampled Values required by the IED. The default value varies with
the product. Modify the LN Count to match the number of Merging Units relevant for the IED in each specific application. The default LN Count
is model dependent.
LN1-8 Name 18 12 to 19 MiCOM Logical Node 1-8

100 Px4x-92LE-TM-EN-4
Chapter 7 - Settings and Records

MENU TEXT Col Row Default Setting Available Setting


Description
Each Logical Node must be identified by a unique name that allows it to receive Sampled Values from a specific Merging Unit. The default
name for LN1 is ‘MiCOM Logical Node 1’. You can edit this ASCII text string using between 10 and 34 characters to match the Merging Unit’s
Logical Node (sample value identifier) name . The same applies for LN2 to 8. The Logical Node name is the system-wide unique identification
‘MsvID’ defined in the Merging Unit control block MSVCB according to IEC 61850-9-2 Ed 1.0. The number of Logical Nodes available is variable,
as set in LN Count. For example, with an LN Count of 3, LN1 Name, LN2 Name and LN3 Name should be set to match those of the
corresponding Merging Units.
Rename the Logical Nodes used for the application. Use between 10 and 34 characters to match each MU Logical Node name. Each Logical
Node name must be exactly the same as the one set in the Merging Unit that broadcasts it.
IA1 IB1 IC1 - IA6 IB6 IC6 18 31 - 36 LN1 - LN6 Unused, LN1, LN2, LN3,…,LN 8
Three-phase current inputs to the IED
VA VB VC 18 37 LN1 Unused, LN1, LN2, LN3,…,LN 8
Three-phase voltage input to the IED
MUs Delay Search 18 41 No No, Yes
The IED has a search command to measure and display the maximum Sampled Value frame delay. The Merging Unit Delay can be set based on
the result of the search, which is displayed on the IED.
MUs Delay Max 18 42
When sampled values are received at the IED from different Merging Units, they may not arrive simultaneously due to differences in Merging
Unit performance or different network path delays. This setting specifies the maximum time-delay expected, starting at the reception of the
sampled value frame from the "first" Merging Unit to the reception of the sampled value frame from the last Merging Unit for each sample
count. Signal processing starts at the end of the Merging Unit delay and if a frame is not received in that specified time, a synchronisation
alarm appears.
Trust Ques Data 18 43 000000 0 or 1 for each flag
This setting specifies how the Sampled Values are processed by the IED when the associated Quality tag is Questionable. There are six binary
flags (0 = No, 1 = Yes) which you can set, corresponding to the data quality attributes Out of Range, Bad Reference, Oscillatory, Old Data,
Inconsistent, and Inaccurate. Questionable data is treated as invalid if the flag is 0. To process the data as good samples, the flag is changed
to 1. The setting is common to all Logical Nodes in service.
Loss Rate Level 18 44 0.1
This setting is related to Process Bus network performance, in particular, the possibility of loss of samples. The set threshold is an upper limit
for the loss of Sampled Values from any of the Logical Nodes configured in the IED, calculated every cycle. If the loss rate level exceeds the set
value, the IED generates the 9-2 Sample Alarm and the related protection functions are inhibited. 1.25% corresponds to the loss of 1 out of the
80 samples expected every cycle, averaged over one second. The loss rate calculation and threshold check is performed independently for
each configured Logical Node.
SAV Absence 18 51 000000 0 or 1 for each flag
This is a data cell with 8 binary flags. It shows the presence or absence of Sampled Values from each of the Merging Units the IED is
communicating with. There is a maximum of 8 Logical Nodes. The cell data for each Logical Node is continuously refreshed. The P743 only uses
bit 0 for LN 1
0: No Sampled Values being received from the Merging Unit.
1: Sampled Values being received from the Merging Unit.
SAV No SmpSynch 18 52 000000
This is a data cell with 8 binary flags. It indicates the healthiness of the Sampled Values being received from each of the configured Merging
Units. The P743 only uses bit 0 for LN 1.
0: Sampled Values received are synchronised and any loss of samples is within acceptable limits.
1: Sampled Values received are not synchronised (Setting :Synchro Alarm) or the Sampled Value delay exceeds the acceptable value (Merging
Unit Delay setting). The IED raises a 9-2 Sample Alarm when any one of the binary flags is 1
00000000 00000000
SAV Test 18 53 0 or 1 for each flag
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Test mode flag for each analogue channel processed by the IED
(eg: VA, the A-phase voltage). The channel assignment depends on the IED.
00000000 00000000
SAV Questionable 18 54 0 or 1 for each flag
00000000

Px4x-92LE-TM-EN-4 101
Chapter 7 - Settings and Records

MENU TEXT Col Row Default Setting Available Setting


Description
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Questionable’ in the Sampled Value frames for
each of the analogue channels. The channel assignment depends on the IED.
00000000 00000000
SAV Invalid 18 55 0 or 1 for each flag
00000000
This is a data cell with 24 binary flags. It indicates the status of the IEC 61850 Quality attribute ‘Invalid’ in the Sampled Value frames for each of
the analogue channels. The channel assignment depends on the IED.
Frame Loss Data 18 70
This column contains all the configure/setting measurement parameters relative to frame loss data.
Frame Loss Rate 18 71 Enabled Disabled, Enabled
Enables the frame loss rate counter
LN1-8 LossRate Sec 18 72-79
This data cell indicates the percentage of SV frames missing during the past second for each LN
LossRate Reset 18 90 No Yes, No
Resets the frame loss rate counter
Reset Time 18 91 0
This data cell is the time stamp of the most recent instance of Frame Loss Rate counter
LN1-8 FrmLoss Cuml 18 92-99 0
This data cell indicates the number of frames lost since the last reset for the LN, the most recent reset time available in the IED menu.
LN1-8 Error Second 18 B1-B8 0
Frame Error Seconds is a cumulative value since the last reset for the LN. If the Frame Loss Rate exceeds 1.25% (one sample per cycle on
average for one second) the IED records this as an Error Second.

6.2 DDB SIGNALS TABLE


IEDs which have the IEC 61850-9-2LE interface have additional DDBs so they can be configured to the system and
application.
Ordinal English Text Source Description
This alarm highlights discrepancies in assignments of
analogue channels in the IED. For example, if you assign
508 9-2LE Cfg Alarm Software
two current inputs to the same Logical Node, the IED
raises an Illegal Channel Map alarm.
511 9-2 Sample Alarm Software Abnormal state of IEC 61850-9-2LE sample.
These are are additional virtual inputs that indicate if the
586-599 PubPres VIP 115-128 Software
publisher is present.
663-715 Virtual Input 65-117 Software These are additional virtual Inputs.
These are additional virtual inputs that provide Quality
951-1007 Quality VIP 65-121 Software
attributes.
1044-1103 Virtual Output 33-92 PSL These are additional GOOSE outputs
These are are additional virtual inputs that indicate if the
1186-1267 PubPres VIP 33 -114 Software
publisher is present.
1484-1494 Virtual Input 118-128 Software These are additional virtual Inputs.
These are additional virtual inputs that provide Quality
1508-1614 Quality VIP 122-128 Software
attributes.
These are additional virtual inputs that provide Quality
1560-1591 Quality VIP 33 -64 Software
attributes.
Virtual Output
1678-1695 PSL These are additional GOOSE outputs
93-110

102 Px4x-92LE-TM-EN-4
Chapter 7 - Settings and Records

Ordinal English Text Source Description


Virtual Output
1722-1739 PSL These are additional GOOSE outputs
111-128
1888-1919 Virtual Input 33-64 Software These are additional virtual Inputs.

Px4x-92LE-TM-EN-4 103
Chapter 7 - Settings and Records

104 Px4x-92LE-TM-EN-4
APPENDIX A

ORDERING OPTIONS
Appendix A - Ordering Options

106 Px4x-92LE-TM-EN-4
Px4x Appendix A - Ordering Options

Variants Order No.


Compact Distance Protection with reclosing P441

Nominal Auxiliary Supply (Vx)


24 - 54Vdc 7
48 - 125Vdc (40 - 100Vac) 8
110 - 250 Vdc (100 - 240 Vac) 9

Current Rating (In) & Voltage Rating (Vn)


Dual Rated CT (1 & 5A : 100 - 120 V) 1
Non-conventional input transformers NCIT (IEC 61850-9-2 LE) not yet available A
Module Sum (∑1A / PXDB) 5
IEC 61850-9-2LE Sampled Analogue Values Ethernet board C

Hardware Options
Standard Version 1
Single Ethernet 100Mbit/s 6
Single Ethernet (100Mbit/s) plus IRIG-B (Modulated) A
Single Ethernet (100Mbit/s) plus IRIG-B (Un-modulated) B
Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B H
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Modulated IRIG-B J
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Un-modulated IRIG-B K
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B M
Redundant Ethernet PRP/HSR, 2 fibre ports + Modulated IRIG-B N
Redundant Ethernet PRP/HSR, 2 fibre ports + Unmodulated IRIG-B P
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 multi-mode fibre ports + Modulated/Un-Modulated IRIG-B R
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 copper ports RJ45 + Modulated/Un-Modulated IRIG-B S
Redundant Ethernet PRP/HSR/RSTP/Failover, 1 copper port RJ45 + 1 multi-mode fibre port + Modulated/Un-Modulated IRIG-B T
* HSR – contact GE for details

Software Options
With 3 phase tripping and 3 phase auto reclose: 8 inputs and 14 outputs B
With check synchronising B
With 1 phase tripping and 1 phase auto reclose: 8 inputs and 8 outputs Mounting Op R C

Protocol Options
K - Bus 1
Modbus 2
VDEW (IEC 60870-5-103) 3
DNP3.0 4
IEC61850 + Courier via rear RS485 port 6
IEC61850+IEC60870-5-103 via rear RS485 port 7

Mounting / Livery Change


Flush/Panel Mounting with Harsh Env.Coating, White Front Panel M
40TE Case (9-2LE models only) Flush/Panel Mounting with Harsh Env. Coating, White Front Panel R
Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel S
40TE Case (9-2LE models only) Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel U

Language
English, French, German, Spanish 0
English, French, German, Italian 4
Chinese, English or French via HMI, with English or French only via Communications port C

Software Version
Date and Application Dependant

Customer Specific Options


Standard Version 0
Customer Engineered Version A

Hardware Version
Model and Hardware Version Dependant

Px4x-92LE-TM-EN-4 A1
Appendix A - Ordering Options Px4x

Variants Order No.


Distance Protection P442 P442 **

Nominal auxiliary voltage


24-54 Vdc 7
48-125 Vdc (40-100 Vac) 8
110-250 Vdc (100-240 Vac) 9

In/Vn rating
Dual rated CT (1 & 5A : 100 - 120V) 1
Module Sum (∑1A / PXDB) 5
Non-conventional input transformers NCIT (IEC 61850-9-2 LE) C

Hardware options
Standard version 1
IRIG-B Only (Modulated) 2
IRIG-B input and Fibre optic converter (Courier, Modbus,IEC60870-5-103 or DNP3) 4
Ethernet 10Mbit/s 5
Single Ethernet 100Mbit/s 6
Second Rear Comms + InterMiCOM 7
IRIG-B (Modulated) + Second Rear Comms + InterMiCOM 8
Single Ethernet (100Mbit/s) plus IRIG-B (Modulated) Software version '31' and later (Suffix J) A
Single Ethernet (100Mbit/s) plus IRIG-B (Un-modulated) Software version '31' and later (Suffix J) B
IRIG-B (Un-modulated) Software version '31' and later (Suffix J) C
InterMiCOM + Courier Rear Port * E
InterMiCOM + Courier Rear Port + IRIG-B modulated * F
Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B H
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B M
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 multi-mode fibre ports + Modulated/Un-Modulated IRIG-B R
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 copper ports RJ45 + Modulated/Un-Modulated IRIG-B S
Redundant Ethernet PRP/HSR/RSTP/Failover, 1 copper port RJ45 + 1 multi-mode fibre port + Modulated/Un-Modulated IRIG-B T
* NB: Options available with Software version 45 & later (Design Suffix K)

Software options
16 Logic Inputs & 21 Relay Outputs B
16 Logic Inputs & 21 Relay Outputs (3 Fast trip) D
16 Logic Inputs & 21 Relay Outputs (6 Fast trip) E
16 Logic Inputs & 18 Relay Outputs (4 High Break) * C
* NB: Option C is only available with Design Suffix K & Software version 40 or later

Protocol options
K-Bus 1
Modbus 2
VDEW (IEC 60870-5-103) 3
DNP3.0 4
UCA2 + Courier via rear RS485 port (Ethernet hardware options [i.e. 6] only) 5
IEC61850 + Courier via rear RS485 port * 6
IEC61850 + IEC60870-5-103 via rear RS485 port * 7
DNP3 over Ethernet with Courier rear port K-Bus/RS485 protocol 8
* NB: IEC61850 Edition 2 available with '82' Software

Mounting
Flush/Panel Mounting with Harsh Env.Coating, White Front Panel M
Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel S

Language
English, French, German, Spanish 0
English, French, German, Italian 4
Chinese, English or French via HMI, with English or French only via Communications port C

Software version
Date and application dependant **

Customer specific options


Standard version 0
Customer engineered version: ENEL 1
Customer engineered version: TERNA 2
Customer engineered version: RTE 4
Customer engineered version: general A

Hardware version
Model and hardware version dependant *

A2 Px4x-92LE-TM-EN-4
Px4x Appendix A - Ordering Options

Variants Order No.


Distance Protection P444 P444 **

Nominal auxiliary voltage


24-54 Vdc 7
48-125 Vdc (40-100 Vac) 8
110-250 Vdc (100-240 Vac) 9

In/Vn rating
Dual rated CT (1 & 5A : 100 - 120V) 1
Module Sum (∑1A / PXDB) 5
Non-conventional input transformers NCIT (IEC 61850-9-2 LE) NEW BOARD C

Hardware options
Standard version 1
IRIG-B input 2
IRIG-B input and Fibre optic converter (IEC60870-5-103) 4
Ethernet 10Mbits 5
Single Ethernet 100Mbit/s 6
Rear Comms + InterMiCOM 7
Rear Comms + IRIB-B + InterMiCOM 8
Single Ethernet (100Mbit/s) plus IRIG-B (Modulated) Software version '31' and later (Suffix J) A
Single Ethernet (100Mbit/s) plus IRIG-B (Un-modulated) Software version '31' and later (Suffix J) B
IRIG-B (Un-modulated) (Software version '31' and later) C
InterMiCOM + Courier Rear Port * E
InterMiCOM + Courier Rear Port + IRIG-B modulated * F
Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B H
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Modulated IRIG-B J
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Un-modulated IRIG-B K
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B M
Redundant Ethernet PRP/HSR, 2 fibre ports + Modulated IRIG-B N
Redundant Ethernet PRP/HSR, 2 fibre ports + Unmodulated IRIG-B P
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 multi-mode fibre ports + Modulated/Un-Modulated IRIG-B R
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 copper ports RJ45 + Modulated/Un-Modulated IRIG-B S
Redundant Ethernet PRP/HSR/RSTP/Failover, 1 copper port RJ45 + 1 multi-mode fibre port + Modulated/Un-Modulated IRIG-B T
* NB: Options available with Software version 45 & later (Design Suffix K)
** For HSR – contact GE for details

Models
1 & 3 Pole tripping/reclosing with 24 inputs & 32 outputs B
1 & 3 Pole tripping/reclosing with 24 inputs & 34 ouputs (12 high break) C
1 & 3 Pole tripping/reclosing with 24 inputs & 32 outputs (4 fast output contacts) D
1 & 3 Pole tripping/reclosing with 24 inputs & 32 outputs (8 fast output contacts) E
1 & 3 Pole tripping/reclosing with 24 inputs & 46 outputs J
1 & 3 Pole tripping/reclosing with 24 inputs & 46 outputs (4 fast output contacts) K
1 & 3 Pole tripping/reclosing with 24 inputs & 46 outputs (8 fast output contacts) L
1 phase tripping and 1 phase auto reclose: 8 inputs and 8 outputs Mounting Option ‘R’ R

Protocol options
K-Bus 1
Modbus 2
VDEW (IEC 60870-5-103) (RS485 or Fibre Optic) 3
DNP3.0 4
UCA2 5
IEC61850 + Courier via rear RS485 port * 6
IEC61850 + IEC60870-5-103 via rear RS485 port * 7
DNP3 over Ethernet with Courier rear port K-Bus/RS485 protocol 8
* NB: IEC61850 Edition 2 available with '82' Software

Mounting
Flush/Panel Mounting with Harsh Env.Coating, White Front Panel M
19" Rack Mounting with Harsh Env. Coating, White Front Panel N
Flush/panel mounting with harsh environment coating P
19" Rack mounting with harsh environmental coating Q
40TE Case (9-2LE models only) Flush/Panel Mounting with Harsh Env. Coating, White Front Panel R
Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel S
19" Rack Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel T
40TE Case (9-2LE models only) Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel U

Language
English, French, German, Spanish 0
English, French, German, Italian 4
Chinese, English or French via HMI, with English or French only via Communications port C

Software version
Date and application dependant

Customer specific options


Standard version 0
Customer engineered version: ENEL 1
Customer engineered version: TERNA 2
Customer engineered version: RTE 4
Customer engineered version: General A

Hardware version
Model and hardware version dependant *

Px4x-92LE-TM-EN-4 A3
Appendix A - Ordering Options Px4x

Variants Order No.


Distance Protection P446 P446 **
Distance & Autoreclose for 2 Circuit Breakers

Nominal auxiliary voltage


24-54 Vdc 7
48-125 Vdc (40-100 Vac) 8
110-250 Vdc (100-240 Vac) 9

In/Vn rating
In = 1A/5A ; Vn = 100-120Vac 1
IEC 61850-9-2LE Sampled Analogue Values Ethernet board * C

* Only available with '74'/'80' Software

Hardware options Protocol Compatibilty


Nothing 1, 3 & 4 1
IRIG-B Only (Modulated) 1, 3 & 4 2
IRIG-B (Modulated) & Fibre Optic Converter 1, 3 & 4 4
Ethernet (100Mbit/s) 6, 7 & 8 6
Second Rear Comms + InterMiCOM 1, 3 & 4 7
IRIG-B (Modulated) + Second Rear Comms + InterMiCOM 1, 3 & 4 8
Ethernet (100Mbit/s) plus IRIG-B (Modulated) 6, 7 & 8 A
Ethernet (100Mbit/s) plus IRIG-B (Un-modulated) 6, 7 & 8 B
IRIG-B (Un-modulated) 1, 3 & 4 C
InterMiCOM + Courier Rear Port 1, 3 & 4 E
InterMiCOM + Courier Rear Port + IRIG-B modulated 1, 3 & 4 F
Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B 6, 7 & 8 H
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Modulated IRIG-B 6, 7 & 8 J
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Un-modulated IRIG-B 6, 7 & 8 K
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B 6, 7 & 8 M
Redundant Ethernet PRP/HSR, 2 fibre ports + Modulated IRIG-B 6, 7 & 8 N
Redundant Ethernet PRP/HSR, 2 fibre ports + Unmodulated IRIG-B 6, 7 & 8 P
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 multi-mode fibre ports + Modulated/Un-Modulated IRIG-B 6, 7 & 8 R
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 copper ports RJ45 + Modulated/Un-Modulated IRIG-B 6, 7 & 8 S
Redundant Ethernet PRP/HSR/RSTP/Failover, 1 copper port RJ45 + 1 multi-mode fibre port + Modulated/Un-Modulated IRIG-B 6, 7 & 8 T

* HSR – contact GE for details

Product Options
24 inputs and 32 outputs (8 input and 8 outputs Mounting Opt R) B
24 inputs and 8 standard plus 12 high break outputs C
24 inputs and 16 standard plus 8 high break outputs D
As B + 850nm dual channel (8 input and 8 outputs Mounting Opt R) F
As C + 850nm dual channel G
As D + 850nm dual channel H
As B + 1300nm SM single channel (8 input and 8 outputs Mounting Opt R) J
As C + 1300nm SM single channel K
As D + 1300nm SM single channel L
As B + 1300nm SM dual channel (8 input and 8 outputs Mounting Opt R) N
As C + 1300nm SM dual channel O
As D + 1300nm SM dual channel P
As B + 1300nm MM single channel (8 input and 8 outputs Mounting Opt R) R
As C + 1300nm MM single channel S
As D + 1300nm MM single channel T
As B + 1300nm MM dual channel (8 input and 8 outputs Mounting Opt R) V
As C + 1300nm MM dual channel W
As D + 1300nm MM dual channel X
As B + 850nm MM + 1300mn SM (8 input and 8 outputs Mounting Opt R) Z
As D + 850nm MM + 1300mn SM 1
As B + 1300mn SM + 850nm MM (8 input and 8 outputs Mounting Opt R) 2
As D + 1300mn SM + 850nm MM 3
As B + 850nm MM + 1300mn MM (8 input and 8 outputs Mounting Opt R) 4
As D + 850nm MM + 1300mn MM 5
As B + 1300mn MM + 850nm MM (8 input and 8 outputs Mounting Opt R) 6
As D + 1300mn MM + 850nm MM 7

Protocol options Hardware Compatibilty


K-Bus 1, 2, 3, 4, C, E & F 1
IEC60870-5-103 1, 2, 3, 4, C, E & F 3
DNP3.0 1, 2, 3, 4, C, E & F 4
IEC61850 + Courier via rear RS485 port 6, A, B, G, H, J, K, L, M, N, P 6
IEC61850+IEC60870-5-103 via rear RS485 port 6, A, B, G, H, J, K, L, M, N, P 7
DNP3.0 Over Ethernet with Courier rear port K-Bus/RS485 protocol 6, A, B, G, H, J, K, L, M, N, P 8

Mounting
Flush/Panel Mounting with Harsh Env.Coating, White Front Panel M
19" Rack Mounting with Harsh Env. Coating, White Front Panel N
Flush/panel mounting with harsh environment coating P
19" Rack mounting with harsh environmental coating Q
40TE Case (9-2LE models only) Flush/Panel Mounting with Harsh Env. Coating, White Front Panel R
Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel S
19" Rack Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel T
40TE Case (9-2LE models only) Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel U

Language
English, French, German, Spanish 0
English, French, German, Russian 5
English, Italian, Polish and Portuguese * 7
Chinese, English or French via HMI, with English or French only via Communications port C
* Available with '75'/'76'/'82' software

Software version
Date and application dependant **

Customer specific options


Standard version 0
Customer version A

A4 Px4x-92LE-TM-EN-4
Px4x Appendix A - Ordering Options

Hardware version
Extended main processor (XCPU2) With Function Keys & Tri-colour LEDs K
Main processor (CPU3) 40TE P
As K plus increased main processor memory (XCPU3), Cyber Security M

Px4x-92LE-TM-EN-4 A5
Appendix A - Ordering Options Px4x

Variants Order No.


Current Differential (Optional Distance) P546 **
Nominal auxiliary voltage
24-54 Vdc 7
48-125 Vdc (40-100 Vac) 8
110-250 Vdc (100-240 Vac) 9

In/Vn rating
In = 1A/5A ; Vn = 100-120Vac 1
IEC 61850-9-2LE Sampled Analogue Values Ethernet board * C

* Only available with '74'/'80' Software

Hardware options Protocol Compatibilty


Standard - None 1, 2, 3 & 4 1
IRIG-B Only (Modulated) 1, 2, 3 & 4 2
IRIG-B (Modulated) & Fibre Optic Converter 1, 2, 3 & 4 4
Ethernet (10Mbit/s) * 5 5
Ethernet (100Mbit/s) 5, 6, 7 & 8 6
Second Rear Comms 1, 2, 3 & 4 7
IRIG-B (Modulated) + Second Rear Comms 1, 2, 3 & 4 8
Ethernet (100Mbit/s) plus IRIG-B (Modulated) ** 6, 7 & 8 A
Ethernet (100Mbit/s) plus IRIG-B (Un-modulated) ** 6, 7 & 8 B
IRIG-B (Un-modulated) ** 1, 2, 3 & 4 C
InterMiCOM + Courier Rear Port **** 1, 2, 3 & 4 E
InterMiCOM + Courier Rear Port + IRIG-B modulated **** 1, 2, 3 & 4 F
Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B *** 6, 7 & 8 H
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Modulated IRIG-B *** 6, 7 & 8 J
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Un-modulated IRIG-B *** 6, 7 & 8 K
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B *** 6, 7 & 8 M
Redundant Ethernet PRP/HSR, 2 fibre ports + Modulated IRIG-B *** 6, 7 & 8 N
Redundant Ethernet PRP/HSR, 2 fibre ports + Unmodulated IRIG-B *** 6, 7 & 8 P
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 multi-mode fibre ports + Modulated/Un-Modulated IRIG-B 6, 7 & 8 R
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 copper ports RJ45 + Modulated/Un-Modulated IRIG-B 6, 7 & 8 S
Redundant Ethernet PRP/HSR/RSTP/Failover, 1 copper port RJ45 + 1 multi-mode fibre port + Modulated/Un-Modulated IRIG-B 6, 7 & 8 T

* Only on Suffix G or J Relays


** Only on Suffix K & M relays
*** Only on Suffix K & M relays with software versions 45/55 & later
**** Only on Suffix K or M relays with 47/57 Software, replaces hardware options '7' & '8'
***** For HSR – contact GE for details

Product Options
Ch1=850nm multi-mode, Ch2=850nm multi-mode, 24 Inputs 32 Standard Outputs (8 inputs, 8 outputs mounting option R) A
Ch1=1300nm single-mode, Ch2=not fitted (2 Terminal only), 24 Inputs & 32 Standard outputs (8 inputs, 8 outputs mounting option R) B
Ch1=1300nm single-mode, Ch2=1300nm single-mode, 24 inputs & 32 Standard Outputs (8 inputs, 8 outputs mounting option R) C
Ch1=1300nm multi-mode, Ch2=not fitted (2 Terminal only), 24 Inputs & 32 Standard Outputs (8 inputs, 8 outputs mounting option R) D
Ch1=1300nm multi-mode, Ch2=1300nm multi-mode 24 Inputs & 32 Standard Outputs (8 inputs, 8 outputs mounting option R) E
Ch1=1550nm single-mode, Ch2=not fitted (2 Terminal only) 24 Inputs & 32 Standard Outputs (8 inputs, 8 outputs mounting option R) F
Ch1=1550nm single-mode, Ch2=1550nm single-mode, 24 Inputs & 32 Standard Outputs (8 inputs, 8 outputs mounting option R) G
Ch1=850nm multi-mode, Ch2=1300nm single-mode, 24 Inputs & 32 Standard Outputs (8 inputs, 8 outputs mounting option R) H
Ch1=850nm multi-mode, Ch2=850nm multi-mode, 24 Inputs & 8 Standard + 12 High Break Outputs *** I
Ch1=850nm multi-mode, Ch2=1300nm multi-mode, 24 Inputs and 32 Standard Outputs * (8 inputs, 8 outputs mounting option R) J
Ch1=850nm multi-mode, Ch2=1550nm single-mode 24 Inputs & 32 Standard Outputs * (8 inputs, 8 outputs mounting option R) K
Ch1=1300nm single-mode, Ch2=850nm multi-mode 24 Inputs & 32 Standard Outputs * (8 inputs, 8 outputs mounting option R) L
Ch1=1300nm multi-mode, Ch2=850nm multi-mode, 24 Inputs & 32 Standard Outputs * (8 inputs, 8 outputs mounting option R) M
Ch1=1300nm single-mode, Ch2=not fitted (2 Terminal only) 24 Inputs & 8 Standard + 12 High Break Outputs *** N
Ch1=1300nm single-mode, Ch2=1300nm single-mode + 24 Inputs & 8 Standard + 12 High Break Outputs *** O
Ch1=1300nm multi-mode, Ch2=not fitted (2 Terminal only) + 24 Inputs & 8 Standard + 12 High Break Outputs *** P
Ch1=1300nm multi-mode, Ch2=1300nm multi-mode + 24 Inputs & 8 Standard + 12 High Break Outputs *** Q
Ch1=1550nm single-mode, Ch2=850nm multi-mode, 24 Inputs & 32 Standard Outputs * (8 inputs, 8 outputs mounting option R) R
Ch1=850nm multi-mode, Ch2=850nm multi-mode, 24 Inputs & 16 Standard + 8 High Break Outputs ** S
Ch1=1300nm single-mode, Ch2=not fitted (2 Terminal only), 24 Inputs & 16 Standard + 8 High Break Outputs ** T
Ch1=1300nm single-mode, Ch2=1300nm single-mode, 24 Inputs & 16 Standard + 8 High Break Outputs ** U
Ch1=1300nm multi-mode, Ch2=not fitted (2 Terminal only) 24 Inputs & 16 Standard + 8 High Break Outputs ** V
Ch1=1300nm multi-mode, Ch2=1300nm multi-mode, 24 Inputs & 16 Standard + 8 High Break Outputs ** W
Ch1=1550nm single-mode, Ch2=not fitted (2 Terminal only) 24 Inputs & 16 Standard + 8 High Break Outputs ** X
Reserved - was used for RWE special Y
Ch1=1550nm single-mode, Ch2=1550nm single-mode, 24 Inputs & 16 Standard + 8 High Break Outputs ** Z
Ch1=850nm multi-mode, Ch2=1300nm single-mode, 24 Inputs & 16 Standard + 8 High Break Outputs ** 0
Ch1=850nm multi-mode, Ch2=1300nm multi-mode, 24 Inputs & 16 Standard + 8 High Break Outputs ** 1
Ch1=850nm multi-mode, Ch2=1550nm single-mode, 24 Inputs & 16 Standard + 8 High Break Outputs ** 2
Ch1=1300nm single-mode, Ch2=850nm multi-mode, 24 Inputs & 16 Standard + 8 High Break Outputs ** 3
Ch1=1300nm multi-mode, Ch2=850nm multi-mode, 24 Inputs & 16 Standard + 8 High Break Outputs ** 4
Ch1 1550nm single-mode, Ch2 850nm multi-mode, 24 Inputs & 16 Standard + 8 High Break Outputs ** 5
Reserved for future single channel 6
Reserved for future single channel 7
Ch1=1550nm single-mode, Ch2=not fitted (2 Terminal only), 24 Inputs & 8 Standard + 12 High Break Outputs *** 8
Ch1=1550nm single-mode, Ch2=1550nm single-mode, 24 Inputs & 8 Standard + 12 High Break Outputs *** 9

* Only Available with Suffix G, J, K & M Relays


** Only Available with Suffix K or M Relays
*** Only on Suffix K or M relays with software versions 45/55 & later

Protocol options Hardware Compatibilty


K-Bus 1, 2, 3, 4, C, E & F 1
Modbus * 1, 2, 3, 4, 2
IEC60870-5-103 (VDEW) 1, 2, 3, 4, C, E & F 3
DNP3.0 1, 2, 3, 4, C, E & F 4
UCA2 ** 5&6 5
IEC61850 + Courier via rear RS485 port *** 6, A, B,G, H, J, K, L, M, N, P 6
IEC61850 + IEC60870-5-103 via rear RS485 port *** 6, A, B,G, H, J, K, L, M, N, P 7
DNP3.0 Over Ethernet with Courier rear port K-Bus/RS485 protocol **** 6, A, B,G, H, J, K, L, M, N, P 8

* Only on Suffix B, G or J Relays


** Only on Suffix G or J Relays
*** Only On Suffix K or M Relays

A6 Px4x-92LE-TM-EN-4
Px4x Appendix A - Ordering Options

**** Only available On Suffix K or M relays with software versions 44/54 & later

Mounting
Flush/Panel Mounting with Harsh Env.Coating, White Front Panel M
19" Rack Mounting with Harsh Env. Coating, White Front Panel N
40TE Case (9-2LE models only) Flush/Panel Mounting with Harsh Env. Coating, White Front Panel R
Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel S
19" Rack Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel T
Flush/panel mounting with harsh environment coating P
Rack mounting with harsh environmental coating Q
40TE Case (9-2LE models only) Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel U

Language
English, French, German, Spanish 0
English, French, German, Russian * 5
English, Italian, Polish and Portuguese *** 7
Chinese, English or French via HMI, with English or French only via Communications port ** C

* Design Suffix G, J, K or M only


** Design Suffix K or M & 42/52 software and later only
*** Design Suffx M with 65/66/75/76/81/82 software

Software version
Without Distance 4/6/8*
With Distance 5/7/8*

Customer specific options


Standard version 0
Customer version A

Hardware version
Phase 2 Enhanced Coprocessor, wide range opto B
Enhanced Main Processor (CPU2) with hotkeys G
As G plus dual characteristic optos J
Extended main processor (XCPU2) With Function Keys & Tri-colour LEDs K
Main processor (CPU3) 40TE P
As K plus increased main processor memory (XCPU3), Cyber Security M

Px4x-92LE-TM-EN-4 A7
Appendix A - Ordering Options Px4x

Variants Order Number


P645 Transformer Protection P645 **
Vx Aux Rating :
24 - 54Vdc 7
48 - 125Vdc (40 - 100Vac) 8
110 - 250 Vdc (100 - 240 Vac) 9
In/Vn Rating :
HV-LV In = 1A/5A, Vn = (100/120V) (18CT/1VT) Standard CT 1
HV-LV In = 1A/5A, Vn = (100/120V) (18CT/4VT) Standard CT 2
HV-LV In = 1A/5A, Vn = (100/120V) (18CT/1VT) Sensitive CT 3
HV-LV In = 1A/5A, Vn = (100/120V) (18CT/4VT) Sensitive CT 4
IEC 61850-9-2LE Sampled Analogue Values Ethernet board * C

* Only available with '12'/'20'/'22' Software on 80TE/40TE models


Hardware Options :
Standard : no options 1
IRIG-B (Modulated) only 2
IRIG-B (Modulated) & Fibre Optic Converter 4
Ethernet (100Mbit/s) 6
Second Rear Comms Port (Courier EIA232/EIA485/k-bus) 7
Second Rear Comms Port + IRIG-B (modulated) (Courier EIA232/EIA485/k-bus) 8
Ethernet (100Mbit/s) plus IRIG-B (Modulated) A
Ethernet (100Mbit/s) plus IRIG-B (Un-modulated) B
IRIG-B (Un-modulated) C
Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B H
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Modulated IRIG-B J
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Un-modulated IRIG-B K
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B M
Redundant Ethernet PRP/HSR, 2 fibre ports + Modulated IRIG-B N
Redundant Ethernet PRP/HSR, 2 fibre ports + Unmodulated IRIG-B P
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 multi-mode fibre ports + Modulated/Un-Modulated IRIG-B R
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 copper ports RJ45 + Modulated/Un-Modulated IRIG-B S
Redundant Ethernet PRP/HSR/RSTP/Failover, 1 copper port RJ45 + 1 multi-mode fibre port + Modulated/Un-Modulated IRIG-B T

Product Specific Options :


Size 12 (60TE) case, 16 optos + 16 relays A
Size 12 (60TE) case, 16 optos + 16 relays + RTD B
Size 12 (60TE) case, 16 optos + 16 relays + CLIO (mA I/O) C
Size 12 (60TE) case, 24 optos + 16 relays D
Size 12 (60TE) case, 16 optos + 24 relays E
Size 16 (80TE) case, 24 optos + 24 relays or Size 8 (40TE) 8 optos 8 relays Mounting Opt R F
Size 16 (80TE) case, 24 optos + 24 relays + RTD G
Size 16 (80TE) case, 24 optos + 24 relays + CLIO (mA I/O) H
Size 16 (80TE) case, 24 optos + 24 relays + RTD + CLIO (mA I/O) J
Size 12 (60TE) case, 16 optos + 20 relays (including 4 high break) K
Size 16 (80TE) case, 24 optos + 20 relays (including 4 high break) L
Size 16 (80TE) case, 24 optos + 20 relays (including 4 high break) + RTD M
Size 16 (80TE) case, 24 optos + 20 relays (including 4 high break) + CLIO (mA I/O) N
Size 16 (80TE) case, 24 optos + 20 relays (including 4 high break) + RTD + CLIO (mA I/O) P
Size 16 (80TE) case, 16 optos + 24 relays (including 8 high break) Q
Size 16 (80TE) case, 16 optos + 24 relays (including 8 high break) + RTD R
Size 16 (80TE) case, 16 optos + 24 relays (including 8 high break) + CLIO (mA I/O) S
Size 16 (80TE) case, 16 optos + 24 relays (including 8 high break) + RTD + CLIO (mA I/O) T
Size 16 (80TE) case, 40 optos + 24 relays U
Size 16 (80TE) case, 40 optos + 16 relays + RTD V
Size 16 (80TE) case, 40 optos + 16 relays + CLIO (mA I/O) W
Size 16 (80TE) case, 40 optos + 8 relays + RTD + CLIO (mA I/O) X
Size 16 (80TE) case, 40 optos + 20 relays (including 4 High Break) Y
Size 16 (80TE) case, 40 optos + 12 relays (including 4 High Break) + RTD Z
Size 16 (80TE) case, 40 optos + 12 relays (including 4 High Break) + CLIO (mA I/O) 1
Protocol Options :
K-Bus/Courier 1
Modbus 2
IEC60870-5-103 3
DNP3.0 4
IEC 61850 over Ethernet and Courier via rear K-Bus/RS485 6
IEC61850 over ethernet with CS103 rear port RS485 protocol ** 7
DNP3.0 over Ethernet and Courier via rear K-Bus/RS485 8
** 91 Software only
Mounting Options :
Flush/Panel Mounting with Harsh Env.Coating, White Front Panel M
19" Rack Mounting with Harsh Env. Coating, White Front Panel N
40TE Case (9-2LE models only) Flush/Panel Mounting with Harsh Env. Coating, White Front Panel R
Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel S
19" Rack Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel T
40TE Case (9-2LE models only) Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel U
Language Options :
English, French, German, Spanish 0
English, French, German, Russian 5
Chinese, English or French via HMI, with English or French only via Communications port C
Software Version Options :
Unless specified the latest version will be delivered **
Settings Files Options :
Default 0
Customer Specific A
Design Suffix :
Factory determined

A8 Px4x-92LE-TM-EN-4
Px4x Appendix A - Ordering Options

Variants Order Number


Busbar Protection Peripheral Unit (60TE) P743
Vx Aux Rating
48 - 125Vdc (40 - 100Vac) 8
110 - 250Vdc (100 - 240Vac) 9

Hardware Options
Without CT Input 0
With In = 1/5A CT Input 1
IEC 61850-9-2LE Sampled Analogue Values Ethernet board * C

Hardware Options
Standard - None 1
Ethernet (100 Mbits/s) without IRIG-B 6
2nd Rear Port & InterMiCOM & IRIG-B (Modulated) E
Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B H
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Modulated IRIG-B J
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Un-modulated IRIG-B K
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B M
Redundant Ethernet PRP/HSR, 2 fibre ports + Modulated IRIG-B N
Redundant Ethernet PRP/HSR, 2 fibre ports + Unmodulated IRIG-B P
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 multi-mode fibre ports + Modulated/Un-Modulated IRIG-B R
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 copper ports RJ45 + Modulated/Un-Modulated IRIG-B S
Redundant Ethernet PRP/HSR/RSTP/Failover, 1 copper port RJ45 + 1 multi-mode fibre port + Modulated/Un-Modulated IRIG-B T

Product Specific
16 Relays Outputs and 24 Status Inputs ** A
16 Relays Outputs, 4 High Break and 16 Status Inputs B
8 Relays Outputs, 4 High Break and 24 Status Inputs C
8 Relays Outputs, 8 High Break and 16 Status Inputs D

Protocol Options
K-Bus/Courier
1
IEC60870-5-103 (Via KITZ274)
Courier (K-Bus), IEC60870-5-103 via KITZ274 (Supplied as Courier. KITZ274 to be ordered)
6
Additional IEC61850

Mounting
Flush/Panel Mounting with Harsh Env.Coating, White Front Panel M
Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel S

Language
Multilingual - English, French, German, Spanish 0
Multilingual - English, French, German, Russian 5

Software Issue
Unless specified the latest version will be delivered **

Customisation
Default 0
Customer specific A
Central Networks Version 5

Design Suffix

Px4x-92LE-TM-EN-4 A9
Appendix A - Ordering Options Px4x

Variants Order Number


P746 Busbar Protection Relay P746 **
Vx Aux Rating :
24 - 54Vdc 7
48 - 125Vdc (40 - 100Vac) 8
110 - 250 Vdc (100 - 240 Vac) 9

In/Vn Rating :
CT1 - CT18 In = 1A/5A, Vn = (100/120V) (18CT/3VT) 1
CT1 - CT18 In = 1A/5A, Vn = (380/480V) (18CT/3VT) 2
IEC 61850-9-2LE Sampled Analogue Values Ethernet board * C

* Only available with '12' Software

Hardware Options :
Standard : no options 1
IRIG-B (Modulated) only 2
IRIG-B (Modulated) & Fibre Optic Converter 4
Ethernet (100Mbit/s) 6
2nd Rear Comms port 7
2nd Rear comms port + IRIG-B (Modulated) 8
Ethernet (100Mbit/s) plus IRIG-B (Modulated) A
Ethernet (100Mbit/s) plus IRIG-B (Un-modulated) B
IRIG-B (Un-modulated) C
Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B H
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Modulated IRIG-B J
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Un-modulated IRIG-B K
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B M
Redundant Ethernet PRP/HSR, 2 fibre ports + Modulated IRIG-B N
Redundant Ethernet PRP/HSR, 2 fibre ports + Unmodulated IRIG-B P
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 multi-mode fibre ports + Modulated/Un-Modulated IRIG-B R
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 coper ports RJ45 + Modulated/Un-Modulated IRIG-B S
Single Ethernet PRP/HSR/RSTP/Failover, 1 multi-mode fibre port & 1 coper port RJ45 + Modulated/Un-Modulated IRIG-B T

Product Specific Options :


Size 16 Case, 16 optos + 16 Relays A
Size 16 Case, 16 optos + 8 Relays + 8 High Break Relays B
Size 16 Case, 16 optos + 32 Relays C
Size 16 Case, 16 optos + 24 Relays + 4 High Break Relays D
Size 16 Case, 24 optos + 24 Relays E
Size 16 Case, 24 optos + 16 Relays + 8 High Break Relays F
Size 16 Case, 24 optos + 8 Relays + 12 High Break Relays G
Size 16 Case, 32 optos + 24 Relays H
Size 16 Case, 32 optos + 16 Relays + 8 High Break Relays J
Size 16 Case, 40 optos + 24 Relays K
Size 16 Case, 32 optos + 32 Relays L

Protocol Options :
K-Bus/Courier 1
Modbus 2
IEC60870-5-103 3
DNP3.0 4
IEC 61850 over Ethernet and Courier via rear K-Bus/RS485 6
IEC61850 over ethernet with CS103 rear port RS485 protocol ** 7
DNP3.0 over Ethernet with Courier rear port K-Bus/RS485 8
** Available with Hardware options R, S, T
Mounting Options :
Flush/Panel Mounting with Harsh Env.Coating, White Front Panel M
19" Rack Mounting with Harsh Env. Coating, White Front Panel N
Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel S
19" Rack Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel T
Panel Mounting, with harsh environment coating P
Rack Mounting, with harsh environment coating Q

Language Options :
English, French, German, Spanish 0
English, French, German, Russian 5
Chinese, English or French via HMI, with English or French only via Communications port C

Software Version Options :


Unless specified the latest version will be delivered **

Settings Files Options :


Default 0
Customer Specific A

Design Suffix :
Factory Determined

A10 Px4x-92LE-TM-EN-4
Px4x Appendix A - Ordering Options

Variants Order No.


Multi-functional line terminal IED P841 **
Nominal auxiliary voltage
24-54 Vdc 7
48-125 Vdc (40-100 Vac) 8
110-250 Vdc (100-240 Vac) 9

In/Vn rating + Main Functionality


Model A: Autoreclose for one CB (60TE) Dual rated CT(1/5A :100-120V) 1
Model B: Autoreclose for one/two CB (80TE) Dual rated CT(1/5A :100-120V) 3
Model B: Autoreclose for one/two CB (80TE) With Ed.1 & IEC 61850-9-2LE Sampled Analog. Values Ethernet board *
C
Model B: Autoreclose for one/two CB (40TE) With Ed.2 & IEC 61850-9-2LE Sampled Analog. Values Ethernet board **

* Only available with '74' Software ** Only available with '80' Software

Hardware options Protocol


Nothing 1, 3 & 4 1
IRIG-B Only (Modulated) 1, 3 & 4 2
IRIG-B (Modulated) & Fibre Optic Converter 1, 3 & 4 4
Ethernet (100Mbit/s) 6, 7 & 8 6
Second Rear Comms 1, 3 & 4 7
IRIG-B (Modulated) + Second Rear Comms 1, 3 & 4 8
Ethernet (100Mbit/s) plus IRIG-B (Modulated) 6, 7 & 8 A
Ethernet (100Mbit/s) plus IRIG-B (Un-modulated) 6, 7 & 8 B
IRIG-B (Un-modulated) 1, 3 & 4 C
InterMiCOM + Courier Rear Port * 1, 3 & 4 E
InterMiCOM + Courier Rear Port + IRIG-B modulated * 1, 3 & 4 F
Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B 6, 7 & 8 H
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Modulated IRIG-B 6, 7 & 8 J
Redundant Ethernet RSTP, 2 multi-mode fibre ports + Un-modulated IRIG-B 6, 7 & 8 K
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B 6, 7 & 8 M
Redundant Ethernet PRP/HSR, 2 fibre ports + Modulated IRIG-B 6, 7 & 8 N
Redundant Ethernet PRP/HSR, 2 fibre ports + Unmodulated IRIG-B 6, 7 & 8 P
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 multi-mode fibre ports + Modulated/Un-Modulated IRIG-B 6, 7 & 8 R
Redundant Ethernet PRP/HSR/RSTP/Failover, 2 copper ports RJ45 + Modulated/Un-Modulated IRIG-B 6, 7 & 8 S
Redundant Ethernet PRP/HSR/RSTP/Failover, 1 copper port RJ45 + 1 multi-mode fibre port + Modulated/Un-Modulated IRIG-B 6, 7 & 8 T

* Only with 47/ 57 Software & later, replaces hardware options '7' & '8'

** For HSR – contact GE for details


Product Options
16 Inputs & 14 Standard Outputs (60TE only) A
16 Inputs & 7 Standard + 4 High Break Outputs (60TE only) B
24 Inputs & 32 Standard Outputs (80TE) 8 inputs, 8 outputs mounting option 'R' (40TE) C
24 Inputs & 16 Standard + 8 High Break Outputs (80TE only) D
24 Inputs & 8 Standard + 12 High Break Outputs (80TE only) E

Protocol options Hardware Compatibilty


K-Bus 1, 2, 3, 4, C, E & F 1
IEC60870-5-103 1, 2, 3, 4, C, E & F 3
DNP3.0 1, 2, 3, 4, C, E & F 4
IEC61850 + Courier via rear RS485 port 6, A, B, G, H, J, K, L, M, N, P 6
IEC61850+IEC60870-5-103 via rear RS485 port 6, A, B, G, H, J, K, L, M, N, P 7
DNP3.0 Over Ethernet with Courier rear port K-Bus/RS485 protocol 6, A, B, G, H, J, K, L, M, N, P 8

Mounting
Flush/Panel Mounting with Harsh Env.Coating, White Front Panel M
19" Rack Mounting with Harsh Env. Coating, White Front Panel N
40TE Case (9-2LE models only) Flush/Panel Mounting with Harsh Env. Coating, White Front Panel R
Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel S
19" Rack Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel T
40TE Case (9-2LE models only) Flush/Panel Mounting with Harsh Env. Coating, with USB Port, Black and Silver Front Panel U
Q
U

Language
English, French, German, Spanish 0
English, French, German, Italian (Not yet available!) 4
English, French, German, Russian 5
English, Italian, Polish and Portuguese 7
Chinese, English or French via HMI, with English or French only via Communications port C

Software version
Autoreclose for single Circuit Breaker (60TE) 4/6/8*
Autoreclose for two Circuit breakers (80TE) 5/7/8*

Customer specific options


Standard version 0
Customer version A

Hardware version
Extended main processor (XCPU2) With Function Keys & Tri-colour LEDs K
Main processor (CPU3) 40TE P
As K plus increased main processor memory (XCPU3), Cyber Security M

Px4x-92LE-TM-EN-4 A11
Appendix A - Ordering Options Px4x

A12 Px4x-92LE-TM-EN-4
APPENDIX B

WIRING DIAGRAMS
Appendix B - Wiring Diagrams

120 Px4x-92LE-TM-EN-4
Px4x-92LE Appendix B – Wiring Diagrams

CORTEC DRAWING-
MODEL EXTERNAL CONNECTION DIAGRAM TITLE ISSUE
OPTION* SHEET
All COMMS OPTIONS MICOM Px40 PLATFORM 10Px4001-1 K

P441 I/O Option C DISTANCE PROTECTION 40TE WITH NCIT 8 OPTO INPUTS & 8 RELAY OUTPUTS 10P44102-1 D

P442 I/O Option E DISTANCE PROTECTION 60TE WITH NCIT 16 INPUTS, 21 STANDARD RELAYS (6 OPTIONAL FAST TRIP ) 10P44204-1 D

P444 I/O Option J COMMS OPTION P444 MICOM PX40 PLATFORM NCIT 10P44404-1 E

I/O Option C DISTANCE WITH NCIT 80TE 24 OPTOS 34 RELAYS (12 HIGH BREAK) 10P44406-1 E

I/O Option R DISTANCE PROTECTION 40TE WITH 8 OPTO INPUTS & 8 RELAY OUTPUTS 10P44407-1 C

P446 I/O Option 4 DISTANCE 40TE WITH NCIT 8 OPTO INPUTS, 8 RELAY OUTPUTS 10P44607-1 E

I/O Option 4 DISTANCE 40TE WITH NCIT 8 OPTO INPUTS & 8 RELAY OUTPUTS 10P44607-2 D

P546 I/O Option 4 CURRENT DIFFERENTIAL 40TE WITH NCIT 8 OPTO INPUTS, 8 RELAY OUTPUTS 10P54610-1 E

I/O Option 4 CURRENT DIFFERENTIAL RELAY 40TE WITH NCIT 8 OPTO INPUTS & 8 RELAY OUTPUTS 10P54610-2 D

P645 I/O Option F 5 BIAS INPUT TRANSFORMER DIFFERENTIAL SAMPLE ANALOGUE VALUE 8 INPUTS & 8 OUTPUTS WITH NCIT 10P64521-1 F

P743 I/O Option A BUSBAR PROTECTION PERIPHERAL UNIT P743 (60TE) WITH NCIT 10P74307-1 D

I/O Option B BUSBAR PROTECTION PERIPHERAL UNIT P743 (60TE) WITH NCIT 10P74308-1 D

I/O Option C BUSBAR PROTECTION PERIPHERAL UNIT P743 (60TE) WITH NCIT 10P74309-1 D

I/O Option D BUSBAR PROTECTION PERIPHERAL UNIT P743 (60TE) WITH NCIT 10P74310-1 D

P746 I/O Option A BUSBAR PROTECTION (80TE) WITH 16 I/P & 16 O/P NCIT 10P74612-1 E

I/O Option D BUSBAR PROTECTION (80TE) WITH 16 I/P & 28 O/P (4 O/P ARE HIGH BREAK) NCIT 10P74615-1 E

I/O Option E BUSBAR PROTECTION (80TE) WITH 24 I/P & 24 O/P NCIT 10P74616-1 E

I/O Option F BUSBAR PROTECTION (80TE) WITH 24 I/P & 24 O/P (8 O/P ARE HIGH BREAK) NCIT 10P74617-1 E

I/O Option G BUSBAR PROTECTION WITH 24 I/P & 20 O/P (12 O/P ARE HIGH BREAK) NCIT 10P74618-1 E

I/O Option H BUSBAR PROTECTION (80TE) WITH 32 I/P & 24 O/P NCIT 10P74619-1 E

I/O Option J BUSBAR PROTECTION (80TE) WITH 32 I/P & 24 O/P (8 O/P ARE HIGH BREAK) NCIT 10P74620-1 E

I/O Option K BUSBAR PROTECTION (80TE) WITH 40 I/P & 24 O/P NCIT 10P74621-1 E

I/O Option L BUSBAR PROTECTION (80TE) WITH 32 I/P & 32 O/P NCIT 10P74622-1 E

I/O Option C BUSBAR PROTECTION (80TE) WITH 16 I/P & 32 O/P WITH NCIT 10P74614-1 E

P841 I/O Option C AUTORECLOSE 80TE WITH NCIT 24 INPUTS AND 32 OUTPUTS 10P84106-1 E

I/O Option C AUTORECLOSE 80TE WITH NCIT 24 INPUTS AND 32 OUTPUTS 10P84106-2 C

I/O Option D AUTORECLOSE 80TE WITH NCIT 24 INPUTS, 16 STANDARD RELAYS & 8 HIGH BREAK RELAYS 10P84107-1 E

I/O Option D AUTORECLOSE 80TE WITH NCIT 24 INPUTS, 16 STANDARD RELAYS & 8 HIGH BREAK RELAYS 10P84107-2 C

I/O Option E AUTORECLOSE 80TE WITH NCIT 24 INPUTS, 8 STANDARD RELAYS & 12 HIGH BREAK RELAYS 10P84108-1 E

I/O Option E AUTORECLOSE 80TE WITH NCIT 24 INPUTS, 8 STANDARD RELAYS & 12 HIGH BREAK RELAYS 10P84108-2 C

I/O Option C AUTORECLOSE 40TE WITH NCIT 8 OPTO INPUTS, 8 RELAY OUTPUTS 10P84111-1 E

I/O Option C AUTORECLOSE 40TE WITH NCIT 8 OPTO INPUTS, 8 RELAY OUTPUTS 10P84111-2 D

* When selecting applicable connection diagram(s), it may be helpful to reference the appropriate model’s CORTEC.

Px4x-92LE-TM-EN-4 B1
MiCOM P441 (PART) MiCOM P441 (PART) F11
WATCHDOG
F12 CONTACT
D1 F13
- WATCHDOG
OPTO 1 F14 CONTACT
D2
+
D3 E1
-
D4 OPTO 2 E2 RELAY 1
+
D5 E3
- E4 RELAY 2
D6 OPTO 3
+ E5
RJ45
D7 E6 RELAY 3
-
TX+ 1 OPTO 4
D8 E7
TX- 2 +
E8 RELAY 4
RX+ 3 D9
100 BASE-TX - E9
4 D10 OPTO 5
SLOT C IEC 61850-9-2 LE SK6 + E10 RELAY 5
5 D11
(SAMPLE ANALOGUE VALUE ONLY) - E11
RX- 6 OPTO 6 RELAY 6
D12 E12
7 +
E13
8 D13
- E14
D14 OPTO 7 RELAY 7
+ E15
D15 E16
-
100 BASE-FX D16 OPTO 8 E17
TX + RELAY 8
IEC 61850-9-2 LE E18
SLOT C D17
COMMON
(SAMPLE ANALOGUE VALUE ONLY) RX D18 CONNECTION

COMMS
SLOT A
NOTE 2.

F17
-
SEE DRAWING
EIA485/
KBUS 10Px4001.
F18
PORT +
F16
SCN

F1 *
AC OR DC -
x AUX SUPPLY F2
+
CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

NOTES .

1. PIN TERMINAL (P.C.B. TYPE)


2. FOR COMMS OPTIONS SEE DRAWING 10Px4001

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT CONNECTION DIAG DISTANCE PROTECTION 40TE WITH NCIT
E 8 OPTO INPUTS & 8 RELAY OUTPUTS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P44102 2 ST16 1WT, UK
Sht:
MiCOM P442 (PART) MiCOM P442 (PART)
G11
WATCHDOG
CONTACT G12
B1
- G13 E1
OPTO 1 WATCHDOG
B2 CONTACT G14 E2 RELAY 8 **
+
B3 NOTE 3 E3
- D1
OPTO 2 E4 RELAY 9 **
B4 ** RELAY 15 D2
+
E5
B5 D3
- E6 RELAY 10 **
OPTO 3 ** RELAY 16 D4
RJ45 B6 E7
+ D5
TX+ 1 B7 ** RELAY 17 E8 RELAY 11
- D6
TX- 2 OPTO 4 E9
B8 D7
RX+ 3 + E10
B9 RELAY 18 D8
4 - E11
100 BASE-TX SK6 D9 RELAY 12
5 B10 OPTO 5
+ E12
IEC 61850-9-2 LE 6 D10
RX- E13
B11 D11
(SAMPLE ANALOGUE VALUE ONLY) 7 - RELAY 19
OPTO 6 E14 RELAY 13
8 B12 D12
+ E15
B13 D13
- E16
OPTO 7 RELAY 20 D14
B14 E17
+ D15 RELAY 14
TX E18
B15 D16
100 BASE-FX -
B16 OPTO 8 D17
RX + RELAY 21
IEC 61850-9-2 LE D18 F1
B17
(SAMPLE ANALOGUE VALUE ONLY) COMMON F2 RELAY 1
B18 CONNECTION F3
COMMS
NOTE 2. F4 RELAY 2
C1
- F5
C2 OPTO 9 RELAY 3
+ F6
G17 F7
C3 -
-
OPTO 10 SEE DRAWING F8 RELAY 4
C4 EIA485/
+ 10Px4001. F9
KBUS G18
C5 PORT + F10
-
C6 OPTO 11 G16 F11
+ RELAY 5
SCN F12
C7
-
OPTO 12 F13
C8
+ F14 RELAY 6
C9 F15
-
C10 OPTO 13 F16
+
C11 F17 RELAY 7
- F18
C12 OPTO 14
+
C13
-
C14 OPTO 15
+ G1 *
-
C15 AC OR DC
- x AUX SUPPLY G2
OPTO 16 +
C16 CASE
+
EARTH
C17
COMMON
C18 CONNECTION
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
** FAST TRIP RELAY (OPTIONAL)

NOTES .

1. PIN TERMINAL (P.C.B. TYPE)


2. FOR COMMS OPTIONS SEE DRAWING 10Px4001
3. OPTO INPUTS 1 & 2 MUST BE USED FOR SETTING GROUP CHANGES
IF THIS OPTION IS SELECTED IN THE RELAY MENU.

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAG DIST. PROT'N 60TE WITH NCIT
D 16 INPUTS, 21 STANDARD RELAYS (6 OPTIONAL FAST TRIP )
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P44204 2 ST16 1WT, UK
Sht:
MiCOM P444 (PART) MiCOM P444 (PART)
N11 J1
WATCHDOG RELAY 25
CONTACT N12 J2
D1
- N13 J3
D2 OPTO 1 WATCHDOG RELAY 26
+ CONTACT N14 J4
D3 NOTE 1 J5
- M1
J6 RELAY 27
D4 OPTO 2 RELAY 1 M2
+ J7
D5 M3 RELAY 28
- RELAY 2 J8
OPTO 3 M4
D6 J9
+ M5
D7 J10 RELAY 29
RELAY 3 M6
-
OPTO 4 J11
D8 M7
+ J12 RELAY 30
D9 RELAY 4 M8
- J13
OPTO 5 M9
D10 RELAY 5 J14
+ M10 RELAY 31
D11 J15
- M11
OPTO 6 RELAY 6 J16
D12 M12
RJ45 + J17
M13 RELAY 32
D13 J18
TX+ 1 - M14
D14 OPTO 7 RELAY 7
TX- 2
+ M15 H1
RX+ 3 D15 RELAY 33
M16 H2
4 -
100 BASE-TX SK6 D16 OPTO 8 M17 H3
5 + RELAY 8
IEC 61850-9-2 LE M18 H4 RELAY 34
RX- 6 D17
COMMON H5
7 D18 L1
CONNECTION H6 RELAY 35
8 * * RELAY 9 L2
E1 H7
- L3
E2 OPTO 9 RELAY 10 H8 RELAY 36
+ ** L4
H9
TX E3 L5
- RELAY 11 H10
100 BASE-FX E4 OPTO 10 ** L6
+ H11 RELAY 37
L7
IEC 61850-9-2 LE RX E5 H12
- * * RELAY 12 L8
E6 OPTO 11 H13
L9
+ H14
E7 RELAY 13 L10 RELAY 38
- H15
OPTO 12 L11
E8 H16
+ RELAY 14 L12
E9 H17 RELAY 39
- L13
OPTO 13 H18
E10 L14 OPTIONAL
+ RELAY 15
E11 L15 G1 DEPENDANT ON
- L16 RELAY 40 MODEL VERSION
G2
E12 OPTO 14
+ L17 G3
RELAY 16
E13 L18 G4 RELAY 41
-
E14 OPTO 15 G5
+ K1
G6 RELAY 42
E15 * * RELAY 17 K2
- G7
E16 OPTO 16 K3
+ G8 RELAY 43
* * RELAY 18 K4
E17 G9
NOTES COMMON K5
E18 CONNECTION RELAY 19 G10
** K6
1. OPTO INPUTS 1 AND 2 MUST BE USED FOR SETTING GROUP CHANGES G11 RELAY 44
F1 K7
IF THIS OPTION IS SELECTED IN THE RELAY MENU. - G12
F2 OPTO 17 * * RELAY 20 K8
+ G13
2. FOR COMMS OPTIONS SEE DRAWING 10Px4001. K9
F3 RELAY 21 G14
- K10 RELAY 45
F4 OPTO 18 G15
+ K11
RELAY 22 G16
F5 K12
- G17 RELAY 46
F6 OPTO 19 K13
+ G18
RELAY 23 K14
F7
- K15
F8 OPTO 20 K16
+ * N1
F9 RELAY 24 K17 - AC OR DC
- K18 N2 x AUX SUPPLY
F10 OPTO 21 +
+
F11
- COMMS
F12 OPTO 22 NOTE 2.
+
F13
-
F14 OPTO 23 N17
-
+
F15 EIA485/ SEE DRAWING
- KBUS 10Px4001.
F16 OPTO 24 N18
PORT +
+ CASE
F17 N16 EARTH
COMMON SCN
F18 CONNECTION

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY


* * FAST TRIP RELAY (OPTIONAL) 10P44404-1D

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: COMMS OPTION P444
E MICOM PX40 PLATFORM NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P44404 ST16 1WT, UK
Sht:
G1
-
G2 OPTO 1 MiCOM P444 (PART)
+
G3 NOTE 2 K3
- P11 -
WATCHDOG
G4 OPTO 2 CONTACT P12 RELAY 17
+ K4
P13 +
G5 WATCHDOG
- P14 K7
OPTO 3 CONTACT -
G6 +
N1 RELAY 18
G7 K8 HIGH BREAK
- RELAY 1 N2 +
G8 OPTO 4 CONTACTS
+ N3 K11 - NOTE 4
G9 RELAY 2 N4 RELAY 19
-
OPTO 5 N5 K12
G10 +
+ RELAY 3 N6 K15
G11 -
- N7
OPTO 6 RELAY 20
G12 + RELAY 4 N8 K16
+
G13 N9
- RELAY 5
G14 OPTO 7 N10
+ J1
N11
G15 RELAY 6 J2 RELAY 21
- N12
G16 OPTO 8 J3
+ N13
J4 RELAY 22
G17 RELAY 7 N14
RJ45 COMMON J5
N15
G18 CONNECTION J6 RELAY 23
TX+ 1 N16
F1 J7
2 - RELAY 8 N17
TX- J8
F2 OPTO 9 N18 RELAY 24
RX+ 3 + J9
F3 J10
4 -
100 BASE-TX SK6 OPTO 10 M3
F4 - J11
5 + RELAY 25
IEC 61850-9-2 LE RELAY 9 J12
F5 M4
RX- 6 -
OPTO 11
+ J13
7 F6 + M7
- J14 RELAY 26
8 F7 RELAY 10 J15
-
F8 OPTO 12 HIGH BREAK M8 J16
+ +
CONTACTS M11 J17
F9 NOTE 4 RELAY 27
-
-
OPTO 13 RELAY 11 J18
F10
+ M12
TX + H1
F11
- M15 H2 RELAY 28
100 BASE-FX OPTO 14 -
F12 + RELAY 12 H3
IEC 61850-9-2 LE RX F13 M16 RELAY 29
- + H4
F14 OPTO 15 H5
+
H6 RELAY 30
F15 L3
-
-
H7
F16 OPTO 16 RELAY 13
+ L4 H8 RELAY 31
+
F17 H9
COMMON L7
F18 CONNECTION
- H10
RELAY 14 H11
E1 HIGH BREAK L8 RELAY 32
- + H12
OPTO 17 CONTACTS L11
E2 NOTE 4 H13
+ -
E3 RELAY 15 H14
- L12 RELAY 33
OPTO 18 H15
E4
+
+ L15 H16
E5
-
- RELAY 16 H17 RELAY 34
E6 OPTO 19 L16 H18
+ +
E7
-
E8 OPTO 20
+ * P1
COMMS -
E9 AC OR DC
- NOTE 3 P2 x AUX SUPPLY
E10 OPTO 21 +
+
E11
-
E12 OPTO 22 NOTES
+ P17
-
E13 1. PIN TERMINAL (P.C.B. TYPE)
- EIA485/ SEE DRAWING
E14 OPTO 23 KBUS 10Px4001.
+ 2. OPTO INPUTS 1 AND 2 MUST BE USED FOR SETTING GROUP CHANGES P18
PORT +
IF THIS OPTION IS SELECTED IN THE RELAY MENU.
E15
- P16
E16 OPTO 24 3. FOR COMMS OPTIONS SEE DRAWING 10Px4001. SCN
+ CASE
E17 4. TO OBTAIN HIGH BREAK DUTY, CONTACTS MUST BE EARTH
COMMON
E18 CONNECTED WITH THE CORRECT POLARITY.
CONNECTION
5. COPPER PORT IS FOR SERVICE ONLY, NOT
MiCOM P444 (PART) RECOMMENDED FOR PERMANENT CONNECTION * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT. CONNECTION DIAGRAM P444 DISTANCE WITH NCIT 80TE
E 24 OPTOS 34 RELAYS (12 HIGH BREAK)
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: 07/05/2012 Chkd: N.ROBINSON certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P44406 ST16 1WT, UK
Sht:
MiCOM P446 (PART) MiCOM P446 (PART)
F11
WATCHDOG
F12 CONTACT
D1
- F13
OPTO 1 WATCHDOG
D2 F14 CONTACT
+
D3 NOTE 3
-
OPTO 2 E1
D4
+ E2 RELAY 1
D5 E3
-
D6 OPTO 3 E4 RELAY 2
RJ45 +
E5
TX+ 1 D7
- E6 RELAY 3
TX- 2 OPTO 4
D8 E7
100 BASE-TX RX+ 3 +
E8 RELAY 4
4 D9
SLOT C IEC 61850-9-2 LE SK6 -
OPTO 5 E9
5 D10
(SAMPLE ANALOGUE VALUE ONLY) + E10 RELAY 5
RX- 6
D11 E11
7 -
OPTO 6 E12 RELAY 6
8 D12
+ E13
D13 E14
- RELAY 7
D14 OPTO 7 E15
100 BASE-FX +
TX E16
D15
SLOT C IEC 61850-9-2 LE - E17
OPTO 8 RELAY 8
(SAMPLE ANALOGUE VALUE ONLY) D16 E18
RX +
D17
COMMON
D18 CONNECTION
SLOT A COMMS
NOTE 2.

F17
-
SEE DRAWING
EIA485/
TX1 KBUS 10Px4001.
F18
PORT +
F16
RX1 SCN
FIBRE OPTIC
SLOT B
COMMUNICATION
TX2

RX2

F1 *
-
AC OR DC
x AUX SUPPLY F2
+
CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

NOTES .
1. PIN TERMINAL (P.C.B. TYPE)
2. FOR COMMS OPTIONS SEE DRAWING 10Px4001

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT CONN DIAG - DISTANCE 40TE WITH NCIT
E 8 OPTO INPUTS, 8 RELAY OUTPUTS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P44607 2 ST16 1WT, UK
Sht:
CUSTOMER SETTING DEFAULT SETTING D1
-
Not Used OPTO 1 D2 F11
+ WATCHDOG
D3 MiCOM P446 F12 CONTACT
- (PART) F13
Block CB1/2 AR OPTO 2 D4 WATCHDOG
+ F14 CONTACT DEFAULT SETTING CUSTOMER SETTING
D5
- E1
L3 Aid 1 Receive OPTO 3 D6 E2 RELAY 1 R1 Trip Z1
+
D7 E3
-
OPTO 4 E4 RELAY 2 R2 Any Start
L4 Aid 1 COS/LGS D8
+ E5
D9
- E6 RELAY 3 R3 Any Trip
L5 Reset LEDs OPTO 5 D10
+ E7
D11 RELAY 4 R4 General Alarm
- E8
MCB/VTS OPTO 6 D12 E9
+
D13 E10 RELAY 5 R5 IM64 1
-
CB1 Healthy OPTO 7 D14 E11
+ E12 RELAY 6 CB1 Fail Trip
D15
- E13
CB2 Healthy OPTO 8 D16
+ E14 RELAY 7 Control Close CB1
D17
E15
COMMON
CONNECTION D18 E16
E17 Control Trip CB1
RELAY 8
E18

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT CONN DIAG DISTANCE 40TE WITH NCIT
D 8 OPTO INPUTS & 8 RELAY OUTPUTS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 2 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P44607 ST16 1WT, UK
Sht:
MiCOM P546 (PART) MiCOM P546 (PART)
F11
WATCHDOG
F12 CONTACT
D1
- F13
OPTO 1 WATCHDOG
D2 F14 CONTACT
+
D3
-
D4 OPTO 2
+
D5 E1
- E2 RELAY 1
D6 OPTO 3
RJ45 + E3
TX+ 1 D7 E4 RELAY 2
-
TX- 2 OPTO 4 E5
D8
RX+ 3 + E6 RELAY 3
100 BASE-TX
4 D9 E7
SLOT C IEC 61850-9-2 LE SK6 -
5 D10 OPTO 5 E8 RELAY 4
(SAMPLE ANALOGUE VALUE ONLY) +
RX- 6 E9
D11
7 - E10 RELAY 5
D12 OPTO 6
8 + E11
D13 E12 RELAY 6
-
OPTO 7 E13
D14
+ E14
100 BASE-FX RELAY 7
TX
D15 E15
SLOT C IEC 61850-9-2 LE -
D16 OPTO 8 E16
(SAMPLE ANALOGUE VALUE ONLY) RX + E17
D17 RELAY 8
E18
COMMON
D18 CONNECTION
SLOT A COMMS
NOTE 2.

F17
-
SEE DRAWING
EIA485/
TX1 KBUS 10Px4001.
F18
PORT +
F16
RX1 SCN
FIBRE OPTIC
COMMUNICATION SLOT B
CURR DIFF
TX2

RX2

RX1 CONNECT TO P594


F1 *
-
AC OR DC
x AUX SUPPLY F2
+
CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

NOTES .

1. PIN TERMINAL (P.C.B. TYPE)


2. FOR COMMS OPTIONS SEE DRAWING 10Px4001

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT CONN DIAG. CURRENT DIFFERENTIAL 40TE WITH NCIT
E 8 OPTO INPUTS, 8 RELAY OUTPUTS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P54610 2 ST16 1WT, UK
Sht:
CUSTOMER SETTING DEFAULT SETTING D1
-
Not Used OPTO 1 D2 F11
+ WATCHDOG
D3 MiCOM P546 F12 CONTACT
- (PART) F13
Block CB1/2 AR OPTO 2 D4 WATCHDOG
+ F14 CONTACT DEFAULT SETTING CUSTOMER SETTING
D5
- E1
L3 Aid 1 Receive OPTO 3 D6 E2 RELAY 1 Diff Trip
+
D7 E3
-
OPTO 4 E4 RELAY 2 R7 Control Close CB1
L4 Aid 1 COS/LGS D8
+ E5
D9
- E6 RELAY 3 R3 Any Trip
L5 Reset LEDs OPTO 5 D10
+ E7
D11 RELAY 4
- E8 R4 General Alarm
MCB/VTS OPTO 6 D12 E9
+
D13 E10 RELAY 5 R5 IM64 1
-
CB1 Healthy OPTO 7 D14 E11
+ E12 RELAY 6 CB1 Fail Trip
D15
- E13
CB2 Healthy OPTO 8 D16
+ E14 RELAY 7
D17 R2 Signaling Fail
E15
COMMON
CONNECTION D18 E16
E17
RELAY 8 R8 Control Trip CB1
E18

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT CONN DIAG CURRENT DIFFERENTIAL RELAY 40TE WITH NCIT
D 8 OPTO INPUTS & 8 RELAY OUTPUTS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 2 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P54610 ST16 1WT, UK
Sht:
MiCOM P645SV (PART) MiCOM P645SV (PART)
F11
WATCHDOG
F12 CONTACT
D1
- F13
OPTO 1 WATCHDOG
D2 F14 CONTACT
+
D3
-
D4 OPTO 2 E1
+ RELAY 1
E2
D5
- E3
D6 OPTO 3 RELAY 2
RJ45 + E4
TX+ 1 D7 E5
- RELAY 3
TX- 2 OPTO 4 E6
D8
RX+ 3 + E7
100 BASE-TX
4 D9 E8 RELAY 4
SLOT C IEC 61850-9-2 LE SK6 -
5 D10 OPTO 5 E9
(SAMPLE ANALOGUE VALUE ONLY) + RELAY 5
RX- 6 E10
D11
7 - E11
D12 OPTO 6 E12 RELAY 6
8 +
E13
D13
- E14
OPTO 7 RELAY 7
D14 E15
100 BASE-FX
+
TX E16
D15
SLOT C IEC 61850-9-2 LE -
OPTO 8 E17
D16 RELAY 8
(SAMPLE ANALOGUE VALUE ONLY) RX + E18
D17
COMMON
D18 CONNECTION
SLOT A COMMS
NOTE 2.

F17
-
SEE DRAWING
EIA485/
KBUS 10Px4001.
F18
PORT +
F16
SCN

F1 *
-
AC OR DC
x AUX SUPPLY F2
+
CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

NOTES .

1. PIN TERMINAL (P.C.B. TYPE)


2. FOR COMMS OPTIONS SEE DRAWING 10Px4001

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT.CONN. DIAG. 5 BIAS INPUT TRANSFORMER DIFFERENTIAL
F SAMPLE ANALOGUE VALUE 8 INPUTS & 8 OUTPUTS WITH NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P64521 2 ST16 1WT, UK
Sht:
MiCOM P743 (PART)

C1 MiCOM P743 (PART)


-
C2 OPTO 9
+
C3 E1
-
OPTO 10 RELAY 9 E2
C4
+ E3
C5 - RELAY 10 E4 G11
C6 OPTO 11 E5 WATCHDOG
+ G12 CONTACT
RJ45 RELAY 11
C7 E6 G13
TX+ 1 - WATCHDOG
OPTO 12 E7 G14
TX- 2 C8 CONTACT
+ RELAY 12 E8
RX+ 3 C9
- E9
4
100 BASE-TX SK6 C10 OPTO 13 RELAY 13 E10
5 + F1
IEC 61850-9-2 LE E11
RX- 6 C11 F2 TRIP A
- RELAY 14 E12
(SAMPLE ANALOGUE VALUE ONLY) 7 OPTO 14
C12 F3
8 + E13
F4 TRIP B
C13 E14
- RELAY 15 F5
C14 OPTO 15 E15
+ F6 TRIP C
E16
TX C15 F7
- E17
100 BASE-FX OPTO 16 RELAY 16 F8 RELAY 4
C16 E18
+
RX F9
IEC 61850-9-2 LE C17
COMMON F10 RELAY 5
(SAMPLE ANALOGUE VALUE ONLY) C18 CONNECTION F11
B1 F12 RELAY 6
- TX1
OPTO 1 B2 D1 F13
+ -
OPTO 17 RX1 F14
B3 D2 FIBRE OPTIC RELAY 7
- + F15
OPTO 2 D3 COMMUNICATION
B4 - F16
+ CURR DIFF TX2
D4 OPTO 18 F17
B5 + RELAY 8
-
OPTO 3 D5 RX2 F18
B6 -
+
D6 OPTO 19
B7 +
-
OPTO 4 B8 D7
+ -
D8 OPTO 20
B9 + *
- G1 COMMS
OPTO 5 D9 AC OR DC -
B10 - NOTE 3
+ x AUX SUPPLY G2
D10 OPTO 21 +
B11 +
-
OPTO 6 B12 D11
+ -
D12 OPTO 22
B13 +
-
OPTO 7 B14 D13
+ -
D14 OPTO 23
B15 +
-
OPTO 8 B16 D15 CASE
+ -
OPTO 24 EARTH
B17 D16
+
COMMON
CONNECTION B18 D17
COMMON
D18 CONNECTION * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

NOTES .

1. PIN TERMINAL (P.C.B. TYPE)


2. FOR COMMS OPTIONS SEE DRAWING 10Px4001
2. COPPER PORT IS FOR SERVICE ONLY, NOT RECOMMENDED
FOR PERMANENT CONNECTION.

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: BUSBAR PROTECTION
D PERIPHERAL UNIT P743 (60TE) WITH NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74307 ST16 1WT, UK
Sht:
MiCOM P743 (PART)

C1
-
C2 OPTO 9
+ MiCOM P743 (PART)
C3
-
C4 OPTO 10
+ E1
C5 - RELAY 5 E2
C6 OPTO 11 E3
RJ45
+
RELAY 6 E4
C7 G11
TX+ 1 - WATCHDOG
OPTO 12 E5 G12
TX- 2 C8 CONTACT
+ RELAY 7 E6
RX+ 3
G13
C9 E7 WATCHDOG
4 - G14 CONTACT
100 BASE-TX SK6 C10 OPTO 13 RELAY 8 E8
5 +
IEC 61850-9-2 LE C11 E9
RX- 6
- RELAY 9 E10
(SAMPLE ANALOGUE VALUE ONLY) 7 OPTO 14
C12 F1
8 + E11
F2 RELAY 13
C13 RELAY 10 E12
- F3
C14 OPTO 15 E13
+ F4 RELAY 14
E14
TX C15 RELAY 11 F5
- E15
100 BASE-FX OPTO 16 F6 RELAY 15
C16 E16
+
RX F7
IEC 61850-9-2 LE C17 E17
COMMON RELAY 12 F8 RELAY 16
(SAMPLE ANALOGUE VALUE ONLY) C18 E18
CONNECTION F9
B1 F10 RELAY 17
-
OPTO 1 B2 F11
+ RELAY 18
F12
B3 TX1
- F13
OPTO 2 B4
+ RX1 F14
FIBRE OPTIC RELAY 19
B5 F15
- D3 COMMUNICATION
- F16
OPTO 3 B6 CURR DIFF TX2
+ RELAY 1 F17
B7 D4 RELAY 20
+ F18
- RX2
OPTO 4 B8 D7 -
+
B9 RELAY 2
- D8
OPTO 5 + HIGH BREAK
B10
+ D11 - CONTACTS
B11 G1 * COMMS
- RELAY 3 -
AC OR DC NOTE 3
OPTO 6 B12 D12 x AUX SUPPLY G2
+ + +
B13 D15 -
-
OPTO 7 B14 RELAY 4
+ D16
+
B15
-
OPTO 8 B16
+
B17
COMMON CASE
CONNECTION B18 EARTH

NOTES .
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
1. PIN TERMINAL (P.C.B. TYPE)
2. FOR COMMS OPTIONS SEE DRAWING 10Px4001
3. COPPER PORT IS FOR SERVICE ONLY, NOT RECOMMENDED
FOR PERMANENT CONNECTION.

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: BUSBAR PROTECTION
D PERIPHERAL UNIT P743 (60TE) WITH NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74308 ST16 1WT, UK
Sht:
MiCOM P743 (PART)

C1
-
C2 OPTO 9
+
C3 MiCOM P743 (PART)
-
C4 OPTO 10
+
C5 - E3
C6 OPTO 11 -
RJ45
+ RELAY 1
C7 E4
TX+ 1 - +
G11
2 C8 OPTO 12 E7 WATCHDOG
TX- + G12 CONTACT
-
RX+ 3 C9 RELAY 2 G13
4 - E8 WATCHDOG
100 BASE-TX SK6 C10 OPTO 13 HIGH BREAK + G14 CONTACT
5 + CONTACTS E11
IEC 61850-9-2 LE C11
-
RX- 6
- RELAY 3
(SAMPLE ANALOGUE VALUE ONLY) 7 OPTO 14 E12
C12
8 + + F1
C13 E15 RELAY 5
- - F2
C14 OPTO 15 RELAY 4 F3
+ E16
+ F4 RELAY 6
TX C15
- F5
100 BASE-FX C16 OPTO 16
+ F6 RELAY 7
IEC 61850-9-2 LE RX
C17 F7
COMMON RELAY 8
(SAMPLE ANALOGUE VALUE ONLY) C18 F8
CONNECTION
F9
B1
- F10 RELAY 9
OPTO 1 B2 D1
+ - F11
D2 OPTO 17 RELAY 10
B3 + F12
- TX1
OPTO 2 B4 D3 F13
+ -
OPTO 18 RX1 F14
B5 D4 FIBRE OPTIC RELAY 11
- + F15
OPTO 3 D5 COMMUNICATION
B6 - CURR DIFF F16
+ TX2
D6 OPTO 19 F17
B7 + RELAY 12
-
OPTO 4 D7 RX2 F18
B8 -
+
D8 OPTO 20
B9 +
-
OPTO 5 B10 D9
+ -
D10 OPTO 21
B11 + *
- G1 COMMS
OPTO 6 D11 AC OR DC -
B12 - NOTE 3
+ x AUX SUPPLY G2
D12 OPTO 22 +
B13 +
-
OPTO 7 B14 D13
+ -
D14 OPTO 23
B15 +
-
OPTO 8 B16 D15
+ -
D16 OPTO 24
B17 +
COMMON
CONNECTION B18 D17 CASE
COMMON EARTH
D18 CONNECTION

NOTES . * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

1. PIN TERMINAL (P.C.B. TYPE)


2. FOR COMMS OPTIONS SEE DRAWING 10Px4001
3. COPPER PORT IS FOR SERVICE ONLY, NOT RECOMMENDED
FOR PERMANENT CONNECTION.

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: BUSBAR PROTECTION
D PERIPHERAL UNIT P743 (60TE) WITH NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74309 ST16 1WT, UK
Sht:
MiCOM P743 (PART)

C1
-
C2 OPTO 9
+ MiCOM P743 (PART)
C3
-
C4 OPTO 10
+
C5 E3
- -
C6 OPTO 11 RELAY 5
RJ45
+ E4
C7 G11
+
TX+ 1 - E7 WATCHDOG
C8 OPTO 12 - G12 CONTACT
TX- 2 + RELAY 6 G13
RX+ 3 C9 E8 WATCHDOG
4 - HIGH BREAK + G14 CONTACT
100 BASE-TX SK6 C10 OPTO 13 CONTACTS E11
5 + -
IEC 61850-9-2 LE C11 RELAY 7
RX- 6
- E12
(SAMPLE ANALOGUE VALUE ONLY) 7 OPTO 14
C12
+ F1
8 + E15
F2 RELAY 9
C13
-
- RELAY 8 F3
C14 OPTO 15 E16
+ + F4 RELAY 10
TX C15 F5
-
100 BASE-FX OPTO 16 F6 RELAY 11
C16
+
RX F7
IEC 61850-9-2 LE C17
COMMON F8 RELAY 12
(SAMPLE ANALOGUE VALUE ONLY) C18 CONNECTION F9
B1 F10 RELAY 13
-
OPTO 1 B2 F11
+ RELAY 14
F12
B3 TX1
- F13
OPTO 2 B4
+ RX1 F14
FIBRE OPTIC RELAY 15
B5 F15
- D3 COMMUNICATION
- F16
OPTO 3 B6 CURR DIFF TX2
+ RELAY 1 F17
B7 D4 RELAY 16
+ F18
- RX2
OPTO 4 B8 D7 -
+
B9 RELAY 2
- D8
OPTO 5 + HIGH BREAK
B10
+ D11 - CONTACTS
B11 G1 * COMMS
- RELAY 3 -
AC OR DC NOTE 3
OPTO 6 B12 D12 x AUX SUPPLY G2
+ + +
B13 D15 -
-
OPTO 7 B14 RELAY 4
+ D16
+
B15
-
OPTO 8 B16
+
B17
COMMON CASE
CONNECTION B18 EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY


NOTES .

1. PIN TERMINAL (P.C.B. TYPE)


2. FOR COMMS OPTIONS SEE DRAWING 10Px4001
3. COPPER PORT IS FOR SERVICE ONLY, NOT RECOMMENDED
FOR PERMANENT CONNECTION.

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAGRAM: BUSBAR PROTECTION
D PERIPHERAL UNIT P743 (60TE) WITH NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74310 ST16 1WT, UK
Sht:
MiCOM P746 (PART) MiCOM P746 (PART)

G1
- P11
OPTO 1 G2 WATCHDOG
+ CONTACT P12
G3 P13
-
OPTO 2 WATCHDOG
G4 CONTACT P14
+
G5 N1
-
OPTO 3 RELAY 1 N2
G6
+ N3
G7
- RELAY 2 N4
OPTO 4 G8
+ N5
G9 RELAY 3 N6
-
OPTO 5 G10 N7
+
RELAY 4 N8
G11
- N9
OPTO 6 G12
+ RELAY 5 N10
G13 N11
-
OPTO 7 G14 RELAY 6 N12
+
G15 N13
-
OPTO 8 N14
G16 RELAY 7 SEE DRAWING
+ N15 COMMS OPTIONS
G17 10Px4001
COMMON N16
CONNECTION G18 N17
RELAY 8
F1 N18
-
OPTO 9 F2
+ RJ45 M1
F3 RELAY 9 M2
- 1 TX+
OPTO 10 F4 M3
+ 2 TX-
RELAY 10 M4
F5 3 RX+
- M5
OPTO 11 F6 4 100 BASE-TX P17
+ RELAY 11 M6 -
SK6
F7 5 IEC 61850-9-2 LE M7 SEE DRAWING EIA485/
-
OPTO 12 RX- RELAY 12 10Px4001 KBUS
F8 6 M8 P18
+ + PORT
F9 7 M9
- RELAY 13 P16
OPTO 13 8 M10 SCN
F10
+ M11
F11 RELAY 14 * P1
- M12 -
OPTO 14 F12 AC OR DC
+ M13 P2 x AUX SUPPLY
+
F13 M14
- TX RELAY 15
OPTO 15 100 BASE-FX M15
F14
+
M16
F15 IEC 61850-9-2 LE
- RX M17
OPTO 16 F16 RELAY 16
+ M18
F17
COMMON
CONNECTION F18

1. COPPER PORT IS FOR SERVICE ONLY, NOT


RECOMMENDED FOR PERMANENT CONNECTION

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY


Issue: Revision: Title:
CID006234 Outlines updated to GE Format EXT. CONNECTION DIAG: P746 BUSBAR PROTECTION (80TE)
E WITH 16 I/P & 16 O/P NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: 07/05/2012 Chkd: N.ROBINSON certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74612 ST16 1WT, UK
Sht:
MiCOM P746 (PART) MiCOM P746 (PART)

G1
- P11
OPTO 1 G2 WATCHDOG L1
+ P12 CONTACT RELAY 17 RJ45
L2
G3 P13
- L3 TX+
OPTO 2 WATCHDOG 1
G4 P14 CONTACT RELAY 18
+ L4 2 TX-
G5 N1 L5
- 3 RX+
OPTO 3 N2 RELAY 1 RELAY 19
G6 L6
+ N3 4 100 BASE-TX
G7 L7 SK6
- N4 RELAY 2 5 IEC 61850-9-2 LE
OPTO 4 RELAY 20 L8
G8 N5 RX-
+ L9 6
G9 N6 RELAY 3
- RELAY 21 L10 7
OPTO 5 G10 N7
+ L11 8
N8 RELAY 4
G11 RELAY 22 L12
- N9
OPTO 6 G12 L13
+ N10 RELAY 5
L14
G13 N11 RELAY 23
- L15
OPTO 7 RELAY 6
TX
G14 N12 100 BASE-FX
+ L16
G15 N13
- L17 IEC 61850-9-2 LE
N14 RELAY 24
OPTO 8 G16 RELAY 7 L18 RX
+ N15
G17
COMMON N16
CONNECTION G18 N17
RELAY 8 SEE DRAWING
F1 N18 COMMS OPTIONS
- 10Px4001
OPTO 9 F2
+ M1
F3 M2 RELAY 9
-
OPTO 10 F4 M3
+ RELAY 10
M4
F5 K3
- M5
OPTO 11 P17
-
F6 RELAY 11 -
+ M6 RELAY 25
F7 K4 SEE DRAWING EIA485/
- M7 +
OPTO 12 10Px4001 KBUS
F8 M8 RELAY 12 K7 P18
+ - + PORT
F9 M9 RELAY 26
- K8 M16
OPTO 13 M10 RELAY 13 SCN
F10 HIGH BREAK +
+ M11 K11
CONTACTS
F11 RELAY 14
- * P1
- M12 -
OPTO 14 RELAY 27 AC OR DC
F12 M13 K12 P2
+ + +
x AUX SUPPLY
F13 M14 K15
- RELAY 15
OPTO 15 M15
-
F14
+ RELAY 28
M16 K16
F15
- M17
+
OPTO 16 F16 RELAY 16
+ M18
F17
COMMON
CONNECTION F18

1. COPPER PORT IS FOR SERVICE ONLY, NOT


RECOMMENDED FOR PERMANENT CONNECTION

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT. CONNECTION DIAG: P746 BUSBAR PROTECTION (80TE)
E WITH 16 I/P & 28 O/P (4 O/P ARE HIGH BREAK) NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: 07/05/2012 Chkd: N.ROBINSON certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74615 ST16 1WT, UK
Sht:
MiCOM P746 (PART) MiCOM P746 (PART)

G1 E1
- - P11 L1
OPTO 1 G2 E2 OPTO 17 WATCHDOG
+ + CONTACT P12 L2 RELAY 17
G3 E3 P13 L3
-
WATCHDOG
-
OPTO 2 G4 E4 OPTO 18 P14 L4 RELAY 18
+ + CONTACT
G5 E5 N1 L5
-
RELAY 1 RELAY 19
-
OPTO 3 OPTO 19 N2 L6
G6 E6
+ + N3 L7
G7 E7
- - RELAY 2 N4 L8 RELAY 20
OPTO 4 G8 E8 OPTO 20
+ + N5 L9
G9 E9 RELAY 3 N6 L10 RELAY 21
- -
OPTO 5 G10 E10 OPTO 21 N7 L11
+
RELAY 4 N8 L12 RELAY 22
+
G11 E11
- - N9 L13
OPTO 6 G12 E12 OPTO 22
+ RELAY 5 N10 L14
RELAY 23
+
G13 E13 N11 L15
- -
OPTO 7 G14 E14 OPTO 23 RELAY 6 N12 L16
+ +
G15 E15 N13 L17
- RELAY 24
N14
-
OPTO 8 OPTO 24 L18
G16 E16 RELAY 7
+ + N15
G17 E17
COMMON COMMON N16
CONNECTION G18 E18 CONNECTION N17
RELAY 8
F1 N18
-
OPTO 9 F2 SEE DRAWING
+ M1 COMMS OPTIONS
RELAY 9 10Px4001
F3 M2
-
OPTO 10 RJ45 M3
F4
+ TX+ RELAY 10
1 M4
F5
- 2 TX- M5
OPTO 11 F6 P17
+ RX+ RELAY 11 M6 -
3
F7 M7 SEE DRAWING EIA485/
- 4 100 BASE-TX
OPTO 12 SK6 RELAY 12 10Px4001 KBUS
F8 M8 P18
+ 5 IEC 61850-9-2 LE + PORT
F9 M9
- 6 RX- RELAY 13 P16
OPTO 13 M10
F10 SCN
+ 7 M11
F11 8 RELAY 14 *
- M12 P1 -
OPTO 14 F12 AC OR DC
+ M13 P2 x AUX SUPPLY
+
F13 M14
- RELAY 15
OPTO 15 F14 M15
+
TX M16
F15 100 BASE-FX
- M17
OPTO 16 F16 RELAY 16
+ IEC 61850-9-2 LE M18
F17 RX
COMMON
CONNECTION F18

1. COPPER PORT IS FOR SERVICE ONLY, NOT


RECOMMENDED FOR PERMANENT CONNECTION

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT. CONNECTION DIAG: P746 BUSBAR PROTECTION (80TE)
E WITH 24 I/P & 24 O/P NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: 07/05/2012 Chkd: N.ROBINSON certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74616 ST16 1WT, UK
Sht:
MiCOM P746 (PART) MiCOM P746 (PART)
L3 -

G1 E1 RELAY 17
- L4
OPTO 1
-
OPTO 17 P11 +
G2 E2 WATCHDOG
+ + CONTACT P12 L7 -
G3 E3 P13
- RELAY 18
WATCHDOG
-
OPTO 2 G4 E4 OPTO 18 P14 L8
+ + CONTACT + HIGH BREAK
G5 E5 N1 L11 CONTACTS
- -
RELAY 1
-
OPTO 3 OPTO 19 N2
G6 E6 RELAY 19
+ + N3 L12
G7 E7 +
- RELAY 2 N4 L15
-
OPTO 4 G8 E8 OPTO 20 -
+ + N5
G9 E9 RELAY 3 RELAY 20
- N6 L16
- +
OPTO 5 G10 E10 OPTO 21 N7
+ K3 -
RELAY 4 N8
+
G11 E11
- - N9 RELAY 21
OPTO 6 G12 E12 OPTO 22 K4
+ + RELAY 5 N10 +
G13 E13 N11 K7 -
- -
OPTO 7 G14 E14 OPTO 23 RELAY 6 N12 RELAY 22
+ + K8
G15 E15 N13 + HIGH BREAK
-
N14 K11
-
OPTO 8 OPTO 24 - CONTACTS
G16 E16 RELAY 7
+ + N15
G17 E17 RELAY 23
N16 K12
COMMON COMMON +
CONNECTION G18 E18 CONNECTION N17
RELAY 8 K15 -
F1 N18
- RELAY 24
OPTO 9 F2 K16
+ RJ45 M1 +
F3 RELAY 9 M2
- 1 TX+
OPTO 10 M3 SEE DRAWING
F4 2 TX- COMMS OPTIONS
+ RELAY 10 10Px4001
M4
F5 3 RX+
- M5
OPTO 11 F6 100 BASE-TX P17
4 RELAY 11 M6 -
+ SK6
F7 5 IEC 61850-9-2 LE M7 SEE DRAWING EIA485/
- 10Px4001
OPTO 12 RX- RELAY 12 KBUS
F8 6 M8 P18
+ + PORT
F9 7 M9
- P16
OPTO 13 RELAY 13 M10 SCN
F10 8
+ M11
F11 RELAY 14 * P1
- M12 -
OPTO 14 F12 AC OR DC
+ M13 P2 x AUX SUPPLY
+
F13 M14
- TX RELAY 15
OPTO 15 F14
100 BASE-FX M15
+
M16
F15 IEC 61850-9-2 LE
- RX M17
OPTO 16 F16 RELAY 16
+ M18
F17
COMMON
CONNECTION F18
1. COPPER PORT IS FOR SERVICE ONLY, NOT
RECOMMENDED FOR PERMANENT CONNECTION

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT. CONNECTION DIAG: P746 BUSBAR PROTECTION (80TE)
E WITH 24 I/P & 24 O/P (8 O/P ARE HIGH BREAK) NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: 07/05/2012 Chkd: N.ROBINSON certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74617 ST16 1WT, UK
Sht:
MiCOM P746 (PART) MiCOM P746 (PART)

G1 E1
- - P11
OPTO 1 G2 E2 OPTO 17 WATCHDOG
+ + CONTACT P12
G3 E3 L3 -
- P13
WATCHDOG
-
OPTO 2 G4 E4 OPTO 18 P14 RELAY 13
+ CONTACT L4
+
+
G5 E5 N1
- L7
RELAY 1 -
-
OPTO 3 OPTO 19 N2
G6 E6
+ + N3 RELAY 14
G7 E7 L8
- - RELAY 2 N4 + HIGH BREAK
OPTO 4 G8 E8 OPTO 20
+ + N5 L11 - CONTACTS
G9 E9 RELAY 3 N6 RELAY 15
- -
OPTO 5 OPTO 21 N7 L12
G10 E10 +
+
RELAY 4 N8
+
G11 E11 L15 -
- - N9
OPTO 6 G12 E12 OPTO 22 RELAY 16
+ RELAY 5 N10 L16
+
+
G13 E13 N11
- K3 -
-
OPTO 7 G14 E14 OPTO 23 RELAY 6 N12
+ + RELAY 17
G15 E15 N13 K4
- +
N14
-
OPTO 8 G16 E16 OPTO 24 RELAY 7
+ K7 -
+ N15
G17 E17 RELAY 18
COMMON COMMON N16
K8
CONNECTION G18 E18 CONNECTION N17 + HIGH BREAK
RELAY 8 K11
F1 N18 - CONTACTS
-
OPTO 9 F2 SEE DRAWING RELAY 19
COMMS OPTIONS
+ 10Px4001 K12
+
F3
- K15
OPTO 10 -
F4
+ RELAY 20
F5 RJ45 M3 K16
- - +
OPTO 11 F6 1 TX+ RELAY 9
+ P17
M4 -
F7 2 TX- +
- SEE DRAWING EIA485/
OPTO 12 RX+ M7
F8 3 - 10Px4001 KBUS
+ P18
4 100 BASE-TX RELAY 10 + PORT
F9 M8
- SK6
OPTO 13 5 HIGH BREAK + P16
F10 IEC 61850-9-2 LE SCN
+ CONTACTS M11
6 RX- -
F11
- RELAY 11 * P1
OPTO 14 F12
7 M12 -
+ + AC OR DC
8 P2 x AUX SUPPLY
F13 M15 +
- -
OPTO 15 F14 RELAY 12
+ M16
F15 +
-
OPTO 16 F16
+ TX
100 BASE-FX
F17
COMMON IEC 61850-9-2 LE
CONNECTION F18 RX

1. COPPER PORT IS FOR SERVICE ONLY, NOT


RECOMMENDED FOR PERMANENT CONNECTION
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAG: P746 BUSBAR PROTECTION
E WITH 24 I/P & 20 O/P (12 O/P ARE HIGH BREAK) NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: 07/05/2012 Chkd: N.ROBINSON certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74618 ST16 1WT, UK
Sht:
MiCOM P746 (PART) MiCOM P746 (PART)

G1 E1
- - P11 L1
OPTO 1 G2 E2 OPTO 17 WATCHDOG
+ + CONTACT P12 L2 RELAY 17
G3 E3 P13 L3
-
WATCHDOG
-
OPTO 2 G4 E4 OPTO 18 P14 L4 RELAY 18
+ + CONTACT
G5 E5 N1 L5
-
RELAY 1 RELAY 19
-
OPTO 3 OPTO 19 N2 L6
G6 E6
+ + N3 L7
G7 E7
- - RELAY 2 N4 L8 RELAY 20
OPTO 4 G8 E8 OPTO 20
+ + N5 L9
G9 E9 RELAY 3 N6 L10 RELAY 21
- -
OPTO 5 G10 E10 OPTO 21 N7 L11
+ RELAY 4 RELAY 22
N8 L12
+
G11 E11
- - N9 L13
OPTO 6 G12 E12 OPTO 22
+ RELAY 5 N10 L14
RELAY 23
+
G13 E13 N11 L15
- -
OPTO 7 G14 E14 OPTO 23 RELAY 6 N12 L16
+ +
G15 E15 N13 L17
- RELAY 24
N14
-
OPTO 8 OPTO 24 L18
G16 E16 RELAY 7
+ + N15
G17 E17
COMMON COMMON N16
CONNECTION G18 E18 CONNECTION N17
RELAY 8 RJ45
F1 D1 N18
- - 1 TX+
OPTO 9 F2 D2 OPTO 25
+ M1
+ 2 TX-
F3 D3 RELAY 9 M2
- - 3 RX+
OPTO 10 F4 D4 OPTO 26 M3
+ RELAY 10 4 100 BASE-TX
M4
+
F5 D5 SK6
- - M5 5 IEC 61850-9-2 LE
OPTO 11 F6 D6 OPTO 27
+ + RELAY 11 M6 6 RX-
F7 D7 M7 7
- -
OPTO 12 F8 D8 OPTO 28 RELAY 12 M8
+ + 8
F9 D9 M9
- RELAY 13 M10
-
OPTO 13 F10 D10 OPTO 29
+ + M11
F11 D11 RELAY 14
- M12
TX
-
OPTO 14 F12 D12 OPTO 30 100 BASE-FX
+ + M13
F13 D13 M14
- - RELAY 15 IEC 61850-9-2 LE
OPTO 15 F14 D14 OPTO 31 M15 RX
+
M16
+
F15 D15
- M17 SEE DRAWING
-
OPTO 16 F16 D16 OPTO 32 RELAY 16 COMMS OPTIONS
+ + M18 10Px4001
F17 D17
COMMON COMMON
CONNECTION F18 D18 CONNECTION P17
-
SEE DRAWING EIA485/
10Px4001 KBUS
P18
+ PORT
P16
SCN

* P1 -
AC OR DC
P2 x AUX SUPPLY
+

1. COPPER PORT IS FOR SERVICE ONLY, NOT


RECOMMENDED FOR PERMANENT CONNECTION
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
SEE DRAWING 10P74600 FOR RELAY CONNECTIONS TO SYSTEM
Issue: Revision: Title:
CID006234 Outlines updated to GE Format EXT. CONNECTION DIAG: P746 BUSBAR PROTECTION (80TE)
E WITH 32 I/P & 24 O/P NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: 07/05/2012 Chkd: N.ROBINSON certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74619 ST16 1WT, UK
Sht:
MiCOM P746 (PART) MiCOM P746 (PART)
P11 L3 -
G1 E1 WATCHDOG
- CONTACT P12
- RELAY 17
OPTO 1 G2 E2 OPTO 17 P13 L4
+ + WATCHDOG +
G3 E3 CONTACT P14 L7
- -
N1
-
OPTO 2 G4 E4 OPTO 18
+ RELAY 18
+ RELAY 1 N2 L8
G5 E5 + HIGH BREAK
- N3
L11
-
OPTO 3 G6 E6 OPTO 19 - CONTACTS
RELAY 2 N4
+ +
G7 E7 N5 RELAY 19
- L12
OPTO 4
-
OPTO 20 RELAY 3 N6 +
G8 E8
+ L15 -
N7
+
G9 E9
- - RELAY 4 N8 RELAY 20
OPTO 5 G10 E10 OPTO 21 L16
+ + N9 +
G11 E11 RELAY 5 N10
- -
OPTO 6 G12 E12 OPTO 22 N11 K3
+ -
RELAY 6
+
G13 E13 N12 RELAY 21
- K4
N13
-
OPTO 7 G14 E14 OPTO 23 +
+ + N14 K7
G15 E15 RELAY 7 -
- N15
RELAY 22
-
OPTO 8 G16 E16 OPTO 24
+ N16 K8
+ + HIGH BREAK
G17 E17 N17 K11
RELAY 8 - CONTACTS
COMMON COMMON N18
CONNECTION G18 E18 CONNECTION RELAY 23
F1 D1 M1 K12
- +
RELAY 9
-
OPTO 9 F2 D2 OPTO 25 M2 K15
+ -
+ M3
F3 D3 RELAY 24
- - RELAY 10 M4 K16
OPTO 10 F4 D4 OPTO 26 +
+ + M5 RJ45
F5 D5 RELAY 11 M6
- - 1 TX+
OPTO 11 F6 D6 OPTO 27 M7
+ 2 TX-
RELAY 12 M8
+
F7 D7
- 3 RX+
M9
-
OPTO 12 F8 D8 OPTO 28
+ + RELAY 13 M10 4 100 BASE-TX
F9 D9 SK6
- - M11 5 IEC 61850-9-2 LE
OPTO 13 F10 D10 OPTO 29 RELAY 14
+ + M12 6 RX-
F11 D11 M13 7
- -
OPTO 14 F12 D12 OPTO 30 M14
RELAY 15 8
+ + M15
F13 D13
- - M16
OPTO 15 F14 D14 OPTO 31
+ M17
+ RELAY 16
F15 D15 M18
-
OPTO 16
-
OPTO 32 TX
F16 D16 100 BASE-FX
+ +
F17 D17
IEC 61850-9-2 LE
COMMON COMMON RX
CONNECTION F18 D18 CONNECTION SEE DRAWING
COMMS OPTIONS
10Px4001 P17
-
SEE DRAWING EIA485/
10Px4001 KBUS
P18
+ PORT
P16
SCN

* P1 -
AC OR DC
P2 x AUX SUPPLY
+

1. COPPER PORT IS FOR SERVICE ONLY, NOT


RECOMMENDED FOR PERMANENT CONNECTION
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXTERNAL CONNECTION DIAG: P746 BUSBAR PROTECTION (80TE)
E WITH 32 I/P & 24 O/P (8 O/P ARE HIGH BREAK) NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: 07/05/2012 Chkd: N.ROBINSON certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74620 ST16 1WT, UK
Sht:
MiCOM P746 (PART) MiCOM P746 (PART)
G1 E9
- -
OPTO 1 G2 E10 OPTO 21
+ P11 L1
+ WATCHDOG
G3 E11 CONTACT P12 L2 RELAY 17
- -
OPTO 2 G4 E12 OPTO 22 P13 L3
+ WATCHDOG RELAY 18
+
CONTACT P14 L4
G5 E13
- - N1 L5
OPTO 3 G6 E14 OPTO 23
+ + RELAY 1 N2 L6 RELAY 19
G7 E15 N3 L7
- -
OPTO 4 G8 E16 OPTO 24 RELAY 2 N4 L8 RELAY 20
+ +
G9 E17 N5 L9
- RELAY 3 RELAY 21
OPTO 5 COMMON N6 L10
G10 E18 CONNECTION
+ N7 L11
G11 D1 RELAY 4 N8 L12 RELAY 22
- -
OPTO 6 G12 D2 OPTO 25
+ + N9 L13
G13 D3 RELAY 5 N10 L14
- - RELAY 23
OPTO 7 G14 D4 OPTO 26 N11 L15
+ + RELAY 6 N12 L16
G15 D5
- - N13 L17
OPTO 8 G16 D6 OPTO 27 RELAY 24
+ N14 L18
+ RELAY 7
G17 D7 N15
COMMON
-
G18 D8 OPTO 28 N16
CONNECTION
N17
+
F1 D9 RELAY 8
-
N18
-
OPTO 9 F2 D10 OPTO 29
+ SEE DRAWING
M1
+
F3 D11 COMMS OPTIONS
- RELAY 9 10Px4001
OPTO 10
-
OPTO 30 M2
F4 D12
+ + M3
F5 D13 RELAY 10 M4
- -
OPTO 11 F6 D14 OPTO 31 M5
+ + P17
F7 D15 RELAY 11 M6 -
-
SEE DRAWING
-
OPTO 12 OPTO 32 M7 EIA485/
F8 D16 10Px4001
+ RELAY 12 M8 KBUS
P18
+
F9 D17 + PORT
- M9
OPTO 13 COMMON
F10 D18 CONNECTION RELAY 13 P16
+ M10 SCN
F11 H1 M11
- -
OPTO 14 F12 H2 OPTO 33 RELAY 14 M12 * P1
+ -
+
M13 AC OR DC
F13 H3 P2 x AUX SUPPLY
- +
OPTO 15
-
OPTO 34 M14
F14 H4 RELAY 15
+ + M15
F15 H5 M16
- -
OPTO 16 F16 H6 OPTO 35 M17
+ + RELAY 16
F17 H7 M18
COMMON
-
F18 H8 OPTO 36
CONNECTION +
E1 H9
- -
OPTO 17 E2 H10 OPTO 37
+ +
E3 H11
- -
OPTO 18 E4 H12 OPTO 38
+ + RJ45
E5 H13
- - 1 TX+
OPTO 19 E6 H14 OPTO 39
+ + 2 TX-
E7 H15 RX+
- - 3
OPTO 20 E8 H16 OPTO 40
+ 4 100 BASE-TX
SK6
+
H17 5 IEC 61850-9-2 LE
COMMON
H18 CONNECTION 6 RX-
7
8

TX
100 BASE-FX

IEC 61850-9-2 LE
RX
1. COPPER PORT IS FOR SERVICE ONLY, NOT
RECOMMENDED FOR PERMANENT CONNECTION

POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY


Issue: Revision: Title:
CID006234 Outlines updated to GE Format EXT. CONNECTION DIAG: P746 BUSBAR PROTECTION (80TE)
E WITH 40 I/P & 24 O/P NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: 07/05/2012 Chkd: N.ROBINSON certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74621 ST16 1WT, UK
Sht:
MiCOM P746 (PART) P11 MiCOM P746 (PART)
WATCHDOG
CONTACT P12
G1 E9 P13
- WATCHDOG
P14 K1
-
OPTO 1 G2 E10 OPTO 21 CONTACT
+ + N1 K2 RELAY 25
G3 E11 RELAY 1 N2
- - K3
OPTO 2 G4 E12 OPTO 22 N3 RELAY 26
+ + K4
G5 E13 RELAY 2 N4 K5
- -
OPTO 3 OPTO 23 N5 K6 RELAY 27
G6 E14
+ RELAY 3 N6 K7
+
G7 E15
- - N7 K8 RELAY 28
OPTO 4 G8 E16 OPTO 24
+ + RELAY 4 N8 K9
G9 E17 N9 K10 RELAY 29
-
OPTO 5 COMMON RELAY 5
G10 E18 CONNECTION N10 K11
+
N11 K12 RELAY 30
G11 D1
- RELAY 6 N12 K13
-
OPTO 6 G12 D2 OPTO 25
+ + N13 K14
G13 D3 RELAY 31
- N14 K15
OPTO 7
-
OPTO 26 RELAY 7
G14 D4 N15 K16
+ +
G15 D5 N16 K17
- - RELAY 32
OPTO 8 OPTO 27 N17 K18
G16 D6 RELAY 8
+ + N18
G17 D7
COMMON
-
OPTO 28 M1
CONNECTION G18 D8
+ RELAY 9 M2
F1 D9
- - M3
OPTO 9 F2 D10 OPTO 29
+ + RELAY 10 M4
F3 D11 M5
- -
OPTO 10 F4 D12 OPTO 30 RELAY 11 M6 SEE DRAWING
+ COMMS OPTIONS
+
M7 10Px4001
F5 D13
- - RELAY 12 M8
OPTO 11 F6 D14 OPTO 31
+ + M9
F7 D15 RELAY 13 M10
- -
OPTO 12 F8 D16 OPTO 32 M11 P17
+ + -
F9 D17 RELAY 14 M12 SEE DRAWING
- EIA485/
OPTO 13 COMMON M13 10Px4001 KBUS
F10 D18 CONNECTION P18
+ M14 + PORT
F11 RELAY 15
- M15 P16
OPTO 14 F12 SCN
+ M16
F13 M17 * P1
- RELAY 16 -
OPTO 15 RJ45 M18 AC OR DC
F14
+ P2 x AUX SUPPLY
1 TX+ L1 +
F15
- RELAY 17 L2
OPTO 16 2 TX-
F16
+ 3 RX+ L3
F17 RELAY 18 L4
COMMON 4 100 BASE-TX
CONNECTION F18 SK6 L5
5 IEC 61850-9-2 LE RELAY 19
E1 L6
- 6 RX-
OPTO 17 L7
E2
+ 7 RELAY 20 L8
E3
- 8 L9
OPTO 18 E4
+ RELAY 21 L10
E5 L11
-
OPTO 19 E6 RELAY 22 L12
+
TX L13
E7 100 BASE-FX
- L14
OPTO 20 E8 RELAY 23
+ IEC 61850-9-2 LE L15
RX
L16
L17
1. COPPER PORT IS FOR SERVICE ONLY, NOT RELAY 24
SEE DRAWING 10P74600 FOR RELAY CONNECTIONS TO SYSTEM RECOMMENDED FOR PERMANENT CONNECTION L18

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY


Issue: Revision: Title:
CID006234 Outlines updated to GE Format EXT. CONNECTION DIAG: P746 BUSBAR PROTECTION (80TE)
E WITH 32 I/P & 32 O/P NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: 07/05/2012 Chkd: N.ROBINSON certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74622 ST16 1WT, UK
Sht:
MiCOM P746 (PART) MiCOM P746 (PART)

G1
- P11
OPTO 1 G2 WATCHDOG L1
+ P12 CONTACT RELAY 17 L2
G3 P13
- L3
OPTO 2 WATCHDOG RJ45
G4 P14 CONTACT RELAY 18
+ L4
G5 N1 1 TX+
- L5
OPTO 3 N2 RELAY 1 RELAY 19 2 TX-
G6 L6
+ N3 RX+
L7 3
G7
- N4 RELAY 2
OPTO 4 RELAY 20 L8 4 100 BASE-TX
G8 N5 SK6
+ L9 5
RELAY 3
IEC 61850-9-2 LE
G9 N6 RELAY 21
- L10 6 RX-
OPTO 5 G10 N7
+ L11
N8 RELAY 4 7
G11 RELAY 22 L12
- N9 8
OPTO 6 G12 L13
+ N10 RELAY 5
L14
G13 N11 RELAY 23
- L15
OPTO 7 G14 N12 RELAY 6
+ L16
G15 N13 TX
- L17 100 BASE-FX
N14 RELAY 24
OPTO 8 G16 RELAY 7 L18
+ N15 IEC 61850-9-2 LE
G17 K1 RX
COMMON N16
G18 RELAY 25 K2
CONNECTION N17
RELAY 8 K3
F1 N18
- RELAY 25
OPTO 9 K4
F2 M1 SEE DRAWING
+ K5 COMMS OPTIONS
10Px4001
F3 M2 RELAY 9
- RELAY 27 K6
OPTO 10 F4 M3
+ K7
M4 RELAY 10
F5 RELAY 28 K8
- M5
OPTO 11 F6 K9 P17
+ M6 RELAY 11 -
RELAY 29 K10
F7 M7 SEE DRAWING EIA485/
- K11
OPTO 12 RELAY 12 10Px4001 KBUS
F8 M8 RELAY 30 P18
+ K12 + PORT
F9 M9 K13
- RELAY 13 P16
OPTO 13 M10 SCN
F10 K14
+ M11 RELAY 31
F11 K15
- M12 RELAY 14 * P1
K16 -
OPTO 14 F12 AC OR DC
+ M13 P2
K17 +
x AUX SUPPLY
F13 M14 RELAY 32
- RELAY 15 K18
OPTO 15 F14 M15
+
M16
F15
- M17
OPTO 16 F16 RELAY 16
+ M18
F17
COMMON
CONNECTION F18

1. COPPER PORT IS FOR SERVICE ONLY, NOT


RECOMMENDED FOR PERMANENT CONNECTION

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT. CONNECTION DIAG: P746 BUSBAR PROTECTION (80TE)
E WITH 16 I/P & 32 O/P NCIT
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: 07/05/2012 Chkd: N.ROBINSON certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P74614 ST16 1WT, UK
Sht:
MiCOM P841 (PART) MiCOM P841 (PART)
G1 E1 L1 P11
- - RELAY 17 WATCHDOG
OPTO 17 L2 P12 CONTACT
OPTO 1 G2 E2
+ + L3 P13
G3 E3 RELAY 18 WATCHDOG
- - L4 P14 CONTACT
OPTO 2 G4 E4 OPTO 18 L5 N1
+ +
RELAY 19 L6 N2 RELAY 1
G5 E5
- - L7 N3
OPTO 3 G6 E6 OPTO 19
+ + RELAY 20 L8 N4 RELAY 2
G7 E7 L9 N5
- -
OPTO 4 G8 E8 OPTO 20 RELAY 21 L10 N6 RELAY 3
+ +
G9 E9 L11 N7
- - RELAY 22 L12 N8 RELAY 4
OPTO 5 G10 E10 OPTO 21
+ + L13 N9
G11 E11 L14 N10 RELAY 5
- - RELAY 23
OPTO 6 G12 E12 OPTO 22 L15 N11
+ + RELAY 6
G13 E13 L16 N12
- - L17 N13
OPTO 7 G14 E14 OPTO 23 RELAY 24
+ + L18 N14 RELAY 7
G15 E15 K1 N15
- - RELAY 25
OPTO 8 G16 E16 OPTO 24 K2 N16
+ + K3 N17
G17 E17 RELAY 8
RELAY 26 K4 N18
COMMON COMMON
CONNECTION G18 E18 CONNECTION K5
M1
F1 RELAY 27 K6
M2 RELAY 9
-
OPTO 9 F2 K7
M3
+ RELAY 28 K8
M4 RELAY 10
F3
- K9
OPTO 10 M5
F4 RELAY 29 K10
+ M6 RELAY 11
F5 K11
- M7
RELAY 30 K12
OPTO 11 F6 M8 RELAY 12
+ K13
P17 M9
F7 - EIA 485/ K14
- RELAY 31 M10 RELAY 13
OPTO 12 F8 NOTE 1 K15
+ M11
P18 K16 RELAY 14
+ KBUS PORT M12
F9 K17
- P16 RELAY 32 M13
OPTO 13 F10 SCN K18
+ M14 RELAY 15
F11 RJ45 M15
- * P1 TX+ 1
OPTO 14 F12 - M16
AC OR DC TX- 2
+ P2 x RX+ 3 M17
F13 + AUX SUPPLY RELAY 16
4
- 100 BASE-TX SK6 M18
5
OPTO 15 F14 IEC 61850-9-2 LE
RX- 6
+ 7
F15 8
-
OPTO 16 F16 48V DC FIELD CASE
+ EARTH
F17 TX
100 BASE-FX
COMMON
F18 IEC 61850-9-2 LE RX
CONNECTION

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY 1. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
2. PIN TERMINAL (PCB TYPE)
3. COPPER PORT IS FOR SERVICE ONLY, NOT
RECOMMENDED FOR PERMANENT CONNECTION
Issue: Status: Revision: Title:
EXT. CONN DIAG : AUTORECLOSE 80TE WITH NCIT
E Approved CID006234 - Outline update only
24 INPUTS AND 32 OUTPUTS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 23/12/19 Name: S Burton This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK. 2 ST16 1WT, UK
10P84106 Sht:
CUSTOMER SETTING DEFAULT SETTING G1
-
NOT USED OPTO 1 G2 P11
+ WATCHDOG
G3 P12 CONTACT
- P13
BAR OPTO 2 G4 WATCHDOG
+ P14 CONTACT DEFAULT SETTING CUSTOMER SETTING
G5
- N1
NOT USED OPTO 3 G6 N2 RELAY 1 NOT USED
+
G7 N3
-
OPTO 4 N4 RELAY 2 ANY START
NOT USED G8
+ N5
G9
- N6 RELAY 3 ANY TRIP
RESET LEDS OPTO 5 G10
+ N7
G11 RELAY 4 GENERAL ALARM
- N8
CB2 AUXA 52-B OPTO 6 G12 N9
+
G13 N10 RELAY 5 NOT USED
-
CB2 AUXB 52-B OPTO 7 G14 N11
+ N12 RELAY 6 CB1 FAIL 1 TRIP
G15
- N13
CB2 AUXC 52-B OPTO 8 G16
+ N14 RELAY 7
G17 CNTL CB1 CLOSE
N15
COMMON
CONNECTION G18 MiCOM P841 N16
F1 (PART) N17
- RELAY 8 CNTL CB1 TRIP
CB1 AUXA 52-B OPTO 9 F2 N18
+
F3 M1
-
OPTO 10 M2 RELAY 9 CB1 TRIP A
CB1 AUXB 52-B F4
+ M3
F5
- M4 RELAY 10 CB1 TRIP B
CB1 AUXC 52-B OPTO 11 F6
+ M5
F7 RELAY 11 CB1 TRIP C
- M6
MCB/VTS OPTO 12 F8 M7
+
F9 M8 RELAY 12 CB2 FAIL 2 TRIP
-
CB1 CLOSE MAN OPTO 13 F10 M9
+ M10 RELAY 13 CNTL CB2 CLOSE
F11
- M11
CB2 CLOSE MAN OPTO 14 F12
+ M12 RELAY 14 CNTL CB2 TRIP
F13
- M13
CB1 HEALTHY OPTO 15 F14 M14
+ RELAY 15 CB1 FAIL 2 TRIP
F15 M15
-
NOT USED OPTO 16 F16 M16
+ M17
F17 RELAY 16 CB2 FAIL 2 TRIP
COMMON M18
CONNECTION F18
L1
L2 RELAY 17 CB2 TRIP A
E1
- L3
CB2 HEALTHY OPTO 17 E2 RELAY 18 CB2 TRIP B
+ L4
E3 L5
- RELAY 19
NOT USED OPTO 18 E4 L6 CB2 TRIP C
+ L7
E5
- L8 RELAY 20 NOT USED
CB1 EXT TRIP A OPTO 19 E6
+ L9
E7 L10 RELAY 21 NOT USED
-
CB1 EXT TRIP B OPTO 20 E8 L11
+ L12 RELAY 22 NOT USED
E9
- L13
CB1 EXT TRIP C OPTO 21 E10
+ L14 RELAY 23 NOT USED
E11 L15
-
CB2 EXT TRIP A OPTO 22 E12 L16
+ L17
E13 RELAY 24 NOT USED
- L18
CB2 EXT TRIP B OPTO 23 E14
+ K1
E15 RELAY 25 NOT USED
- K2
CB2 EXT TRIP C OPTO 24 E16 K3
+
K4 RELAY 26 NOT USED
E17
COMMON K5
CONNECTION E18
K6 RELAY 27 VTS
K7
K8 RELAY 28 NOT USED
K9
K10 RELAY 29 AR CB1 LOCKOUT
K11
K12 RELAY 30 AR CB2 LOCKOUT
K13
K14 RELAY 31 ARIP
K15
K16
K17
RELAY 32 SUCCESS CLOSE
K18

Issue: Status: Revision: Title:


EXT. CONN DIAG : AUTORECLOSE 80TE WITH NCIT
C Approved CID006234 - Outline update only
24 INPUTS AND 32 OUTPUTS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 23/12/19 Name: S Burton This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 2 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK. - ST16 1WT, UK
10P84106 Sht:
MiCOM P841 (PART) MiCOM P841 (PART) P11
WATCHDOG
P12 CONTACT
E1 G1 L3 P13
- WATCHDOG
- - P14
OPTO 17 E2 G2 OPTO 1 RELAY 17 CONTACT
+ + L4 N1
+
E3 G3 N2 RELAY 1
- - L7
OPTO 18 OPTO 2 -
E4 G4 N3
+ + RELAY 18 RELAY 2
E5 G5 L8 N4
- - HIGH BREAK +
N5
OPTO 19 E6 G6 OPTO 3 CONTACTS L11
+ + - N6 RELAY 3
E7 G7 RELAY 19 N7
- - L12
OPTO 20 E8 G8 OPTO 4 + N8 RELAY 4
+ + L15
E9 G9 - N9
- - RELAY 20 N10 RELAY 5
OPTO 21 E10 G10 OPTO 5 L16
+ + + N11
E11 G11 K3 N12 RELAY 6
- - -
OPTO 22 E12 G12 OPTO 6 RELAY 21 N13
+ + K4
+ N14 RELAY 7
E13 G13
- - K7 N15
OPTO 23 E14 G14 OPTO 7 -
+ + N16
RELAY 22
E15 G15 K8 N17
- - HIGH BREAK + RELAY 8
OPTO 24 E16 G16 OPTO 8 CONTACTS N18
K11
+ + -
E17 G17 M1
RELAY 23
COMMON COMMON K12 M2 RELAY 9
CONNECTION E18 G18 CONNECTION +
K15 M3
- RELAY 10
F1 M4
- RELAY 24
K16 M5
F2 OPTO 9 +
+ M6 RELAY 11
P17 F3
- M7
-
EIA485/ F4 OPTO 10 M8 RELAY 12
KBUS NOTE 1 +
PORT P18 M9
F5
+ - RJ45 M10 RELAY 13
M16 F6 OPTO 11
SCN + TX+ 1 M11
F7 TX- 2 M12 RELAY 14
-
F8 OPTO 12 RX+ 3 M13
+ 4 M14
100 BASE-TX SK6 RELAY 15
5 M15
F9 IEC 61850-9-2 LE
- RX- 6
OPTO 13 M16
F10 7
+ M17
8 RELAY 16
P1 * F11 M18
- -
AC OR DC F12 OPTO 14
x P2
AUX SUPPLY + +
F13
- TX
F14 OPTO 15
+ 100 BASE-FX
F15 IEC 61850-9-2 LE RX
-
F16 OPTO 16
+
F17 CASE
EARTH
COMMON
F18
CONNECTION
1. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
2. PIN TERMINAL (PCB TYPE)
POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY 3. COPPER PORT IS FOR SERVICE ONLY, NOT
* RECOMMENDED FOR PERMANENT CONNECTION
Issue: Status: Revision: Title:
EXT. CONN DIAG : AUTORECLOSE 80TE WITH NCIT
E Approved CID006234 - Outline update only
24 INPUTS, 16 STANDARD RELAYS & 8 HIGH BREAK RELAYS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 23/12/19 Name: S Burton This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK. 2 ST16 1WT, UK
10P84107 Sht:
CUSTOMER SETTING DEFAULT SETTING G1
-
NOT USED OPTO 1 G2 P11
+ WATCHDOG
G3 P12 CONTACT
- P13
BAR OPTO 2 G4 WATCHDOG
+ P14 CONTACT DEFAULT SETTING CUSTOMER SETTING
G5
- N1
NOT USED OPTO 3 G6 SEE NOTE 1 SEE NOTE 1 N2 RELAY 1 AR LOCKOUT
+
G7 N3
-
OPTO 4 N4 RELAY 2 ANY START
NOT USED G8 SEE NOTE 1
+
G9 N5
- N6 RELAY 3 ANY TRIP
RESET LEDS OPTO 5 G10
+ N7
G11 RELAY 4 GENERAL ALARM
- N8
CB2 AUXA 52-B OPTO 6 G12 N9
+
G13 N10 RELAY 5 ARIP
-
CB2 AUXB 52-B OPTO 7 G14 N11
+ N12 RELAY 6 CB1 FAIL 1 TRIP
G15
- N13
CB2 AUXC 52-B OPTO 8 G16
+ N14 RELAY 7
G17 CNTL CB1 CLOSE
N15
COMMON
CONNECTION G18 MiCOM P841 N16
F1 (PART) N17
- RELAY 8 CNTL CB1 TRIP
CB1 AUXA 52-B OPTO 9 F2 N18
+
F3 M1
-
OPTO 10 M2 RELAY 9 CB1 TRIP A
CB1 AUXB 52-B F4
+
F5 M3
- M4 RELAY 10 CB1 TRIP B
CB1 AUXC 52-B OPTO 11 F6
+ M5
F7 RELAY 11 CB1 TRIP C
- M6
MCB/VTS OPTO 12 F8 M7
+
F9 M8 RELAY 12 NOT USED
-
CB1 CLOSE MAN OPTO 13 F10 M9
+ M10 RELAY 13 CNTL CB2 CLOSE
F11
- M11
CB2 CLOSE MAN OPTO 14 F12
+ M12 RELAY 14 CNTL CB2 TRIP
F13
- M13
CB1 HEALTHY OPTO 15 F14 M14
+ RELAY 15 CB2 FAIL 1 TRIP
F15 M15
-
NOT USED OPTO 16 F16 M16
+
F17 M17 RELAY 16 NOT USED
COMMON M18
CONNECTION F18
L3 -
E1 RELAY 17 CB1 TRIP A
- L4
+
CB2 HEALTHY OPTO 17 E2
+ L7 -
E3
- RELAY 18 CB1 TRIP B
NOT USED OPTO 18 E4 L8
+ +
HIGH BREAK
E5 L11 - CONTACTS
-
CB1 EXT TRIP A OPTO 19 E6 RELAY 19 CB1 TRIP C
+ L12
E7 +
- L15
CB1 EXT TRIP B OPTO 20 E8 -
+ RELAY 20 CB1 TRIP 3PH
E9 L16
- +
CB1 EXT TRIP C OPTO 21 E10 K3
+ -
E11 RELAY 21 CB2 TRIP A
- K4
CB2 EXT TRIP A OPTO 22 E12 +
+ K7
E13 -
- RELAY 22 CB2 TRIP B
CB2 EXT TRIP B OPTO 23 E14 K8
+ +
E15 HIGH BREAK
K11 -
- CONTACTS
CB2 EXT TRIP C OPTO 24 E16 RELAY 23 CB2 TRIP C
+ K12
E17 +
COMMON K15 -
CONNECTION E18
RELAY 24 CB2 TRIP 3PH
K16
+

NOTE 1:
ONLY FOR RELAYS WITH DISTANCE PROTECTION OPTION.
Issue: Status: Revision: Title:
EXT. CONN DIAG : AUTORECLOSE 80TE WITH NCIT
C Approved CID006234 - Outline update only
24 INPUTS, 16 STANDARD RELAYS & 8 HIGH BREAK RELAYS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 23/12/19 Name: S Burton This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 2 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK. - ST16 1WT, UK
10P84107 Sht:
MiCOM P841 (PART) MiCOM P841 (PART)
G1 E1 M3 P11
- - - WATCHDOG
OPTO 1 OPTO 17 P12 CONTACT
G2 E2 RELAY 9
+ + M4 P13
G3 E3 + WATCHDOG
- - P14 CONTACT
- M7
OPTO 2 G4 E4 OPTO 18 N1
+ + RELAY 10 N2 RELAY 1
G5 E5 M8
- - + N3
OPTO 3 OPTO 19 HIGH BREAK
G6 E6 M11
+ + CONTACTS - N4 RELAY 2
G7 E7 RELAY 11 N5
- -
OPTO 4 OPTO 20 M12 RELAY 3
G8 E8 + N6
+ +
G9 E9 - M15 N7
- - N8 RELAY 4
OPTO 5 G10 E10 OPTO 21 RELAY 12
+ + M16 N9
+
G11 E11 L3 N10 RELAY 5
- - -
OPTO 6 G12 E12 OPTO 22 N11
+ + RELAY 13
L4 N12 RELAY 6
G13 E13 +
- - N13
OPTO 7 G14 E14 OPTO 23 - L7
+ + N14 RELAY 7
G15 E15 RELAY 14
L8 N15
- - +
OPTO 8 G16 E16 OPTO 24 HIGH BREAK N13
+ + CONTACTS - L11
N14 RELAY 8
G17 E17
COMMON RELAY 15 N15
COMMON L12
CONNECTION G18 E18 CONNECTION +
F1 - L15
-
OPTO 9 F2 RELAY 16
+ L16
+
F3
- - K3
OPTO 10 F4
+ RELAY 17
F5 K4
- +
OPTO 11 F6 P17 K7
+ -
-
F7 EIA485/ RELAY 18
- NOTE 1 KBUS K8
OPTO 12 HIGH BREAK + RJ45
F8 P18 PORT
+ + CONTACTS K11
- 1 +TX
P16 RELAY 19 2
F9 -TX
- SCN K12
OPTO 13 + 3 +RX
F10
+ K15 4 100 BASE-TX
* - SK6
F11 P1 5 IEC 61850-9-2 LE
- - RELAY 20
OPTO 14 AC OR DC
F12 P2 x K16 6 -RX
+ + AUX SUPPLY + 7
F13
- 8
OPTO 15 F14
+
F15
-
OPTO 16 F16 TX
+ 100 BASE-FX
F17 CASE
EARTH RX
IEC 61850-9-2 LE
COMMON
CONNECTION F18

1. FOR COMMS OPTIONS SEE DRAWING 10Px4001.


2. PIN TERMINAL (PCB TYPE)
3. COPPER PORT IS FOR SERVICE ONLY, NOT
POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY RECOMMENDED FOR PERMANENT CONNECTION
*
Issue: Status: Revision: Title:
EXT. CONN DIAG : AUTORECLOSE 80TE WITH NCIT
E Approved CID006234 - Outline update only
24 INPUTS, 8 STANDARD RELAYS & 12 HIGH BREAK RELAYS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 23/12/19 Name: S Burton This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK. 2 ST16 1WT, UK
10P84108 Sht:
CUSTOMER SETTING DEFAULT SETTING G1
-
NOT USED OPTO 1 G2 P11
+ WATCHDOG
G3 P12 CONTACT
- P13
BAR OPTO 2 G4 WATCHDOG
+ P14 CONTACT DEFAULT SETTING CUSTOMER SETTING
G5
- N1
NOT USED OPTO 3 G6 N2 RELAY 1 AR LOCKOUT
+
G7 N3
-
OPTO 4 N4 RELAY 2 ANY START
NOT USED G8
+ N5
G9
- N6 RELAY 3 ANY TRIP
RESET LEDS OPTO 5 G10
+ N7
G11 RELAY 4 GENERAL ALARM
- N8
CB2 AUXA 52-B OPTO 6 G12 N9
+
G13 N10 RELAY 5 ARIP
-
CB2 AUXB 52-B OPTO 7 G14 N11
+ N12 RELAY 6 CNTL CB1 CLOSE
G15
- N13
CB2 AUXC 52-B OPTO 8 G16
+ N14 RELAY 7
G17 CNTL CB2 CLOSE
N15
COMMON
CONNECTION G18 MiCOM P841 N16
F1 (PART) N17
- RELAY 8 NOT USED
CB1 AUXA 52-B OPTO 9 F2 N18
+
F3
-
CB1 AUXB 52-B OPTO 10 F4
+
F5
-
CB1 AUXC 52-B OPTO 11 F6
+
F7
- M3
OPTO 12 F8 -
MCB/VTS
+ RELAY 9 CB1 TRIP A
F9 M4
- +
CB1 CLOSE MAN OPTO 13 F10
+ M7 -
F11
- RELAY 10 CB1 TRIP B
CB2 CLOSE MAN OPTO 14 F12 M8
+ +
HIGH BREAK
F13 M11
- - CONTACTS
CB1 HEALTHY OPTO 15 F14 RELAY 11 CB1 TRIP C
+ M12
F15 +
-
NOT USED OPTO 16 F16 M15 -
+
F17 RELAY 12 CB2 TRIP A
COMMON M16
F18 +
CONNECTION
L3 -
E1 RELAY 13 CB2 TRIP B
- L4
+
CB2 HEALTHY OPTO 17 E2
+ L7 -
E3
- RELAY 14 CB2 TRIP C
NOT USED OPTO 18 E4 L8
+ +
HIGH BREAK
E5 L11 - CONTACTS
-
CB1 EXT TRIP A OPTO 19 E6 RELAY 15 CB1 TRIP A
+ L12
E7 +
- L15
CB1 EXT TRIP B OPTO 20 E8 -
+ RELAY 16 CB1 TRIP B
E9 L16
- +
CB1 EXT TRIP C OPTO 21 E10 K3
+ -
E11 RELAY 17 CB1 TRIP C
- K4
CB2 EXT TRIP A OPTO 22 E12 +
+ K7
E13 -
- RELAY 18 CB2 TRIP A
CB2 EXT TRIP B OPTO 23 E14 K8
+ +
E15 HIGH BREAK
K11 -
- CONTACTS
CB2 EXT TRIP C OPTO 24 E16 RELAY 19 CB2 TRIP B
+ K12
E17 +
COMMON K15 -
CONNECTION E18
RELAY 20 CB2 TRIP C
K16
+

Issue: Status: Revision: Title:


EXT. CONN DIAG : AUTORECLOSE 80TE WITH NCIT
C Approved CID006234 - Outline update only
24 INPUTS, 8 STANDARD RELAYS & 12 HIGH BREAK RELAYS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 23/12/19 Name: S Burton This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 2 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK. - ST16 1WT, UK
10P84108 Sht:
MiCOM P841 (PART) MiCOM P841 (PART)
F11
WATCHDOG
F12 CONTACT
D1
- F13
OPTO 1 WATCHDOG
D2 F14 CONTACT
+
D3
-
D4 OPTO 2
+ E1
D5 E2 RELAY 1
-
D6 OPTO 3 E3
RJ45 +
E4 RELAY 2
TX+ 1 D7
- E5
TX- 2 OPTO 4
D8 E6 RELAY 3
RX+ 3 +
100 BASE-TX E7
4 D9
SLOT C IEC 61850-9-2 LE SK6 - E8 RELAY 4
5 D10 OPTO 5
(SAMPLE ANALOGUE VALUE ONLY) + E9
RX- 6 RELAY 5
D11 E10
7 -
D12 OPTO 6 E11
8 + RELAY 6
E12
D13 E13
-
D14 OPTO 7 E14
+ RELAY 7
100 BASE-FX TX E15
D15
SLOT C
- E16
IEC 61850-9-2 LE OPTO 8
D16 E17
RX + RELAY 8
(SAMPLE ANALOGUE VALUE ONLY) E18
D17
COMMON
D18 CONNECTION
SLOT A
COMMS
NOTE 2.

F17
-
SEE DRAWING
EIA485/
KBUS 10Px4001.
F18
PORT +
F16
SCN

F1 *
-
AC OR DC
x AUX SUPPLY F2
+
CASE
EARTH

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

NOTES .

1. PIN TERMINAL (P.C.B. TYPE)


2. FOR COMMS OPTIONS SEE DRAWING 10Px4001

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT CONN DIAG AUTORECLOSE 40TE WITH NCIT
E 8 OPTO INPUTS, 8 RELAY OUTPUTS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 1 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P84111 ST16 1WT, UK
Sht:
CUSTOMER SETTING DEFAULT SETTING D1
-
Not Used OPTO 1 D2 F11
+ WATCHDOG
D3 MiCOM P841 F12 CONTACT
- (PART) F13
Block CB1/2 AR OPTO 2 D4 WATCHDOG
+ F14 CONTACT DEFAULT SETTING CUSTOMER SETTING
D5
- E1
Init Close CB1 OPTO 3 D6 E2 RELAY 1 R1 Not Used
+
D7 E3
-
OPTO 4 E4 RELAY 2 R2 Any Start
Init Close CB2 D8
+ E5
D9
- E6 RELAY 3 R3 Any Trip
L5 Reset LEDs OPTO 5 D10
+ E7
D11 RELAY 4
- E8 R4 General Alarm
MCB/VTS OPTO 6 D12 E9
+
D13 E10 RELAY 5 R5 CB1 Fail1Trip
-
CB1 Healthy OPTO 7 D14 E11
+ E12 RELAY 6 R6 CB2 Fail1Trip
D15
- E13
CB2 Healthy OPTO 8 D16
+ E14 RELAY 7
D17 R7 CB1 Fail2Trip
E15
COMMON
CONNECTION D18 E16
E17
RELAY 8 R8 CB2 Fail2Trip
E18

Issue: Revision: Title:


CID006234 Outlines updated to GE Format EXT CONN DIAG AUTORECLOSE 40TE WITH NCIT
D 8 OPTO INPUTS, 8 RELAY OUTPUTS
Drg C
GE PROPRIETARY AND CONFIDENTIAL INFORMATION
Date: 4/30/2020 Name: S.J.BURTON This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express
Sht: 2 UK Grid Solutions Ltd
No:
condition that neither it nor the information contained therein shall be disclosed to others without the express written consent of GE, and that the information St Leonards Building
shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to Next - Harry Kerr Drive, Stafford.
Date: Chkd: certain restrictions under U.S. export control laws and regulations.© General Electric Company, GE CONFIDENTIAL UNPUBLISHED WORK.
10P84111 ST16 1WT, UK
Sht:
Imagination at work

Grid Solutions
St Leonards Building
Redhill Business Park
Stafford, ST16 1WT, UK
+44 (0) 1785 250 070
contact.centre@ge.com

© 2021 General Electric. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or
should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial
circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without
express written authority, is strictly prohibited.