Medium Voltage Assemblies Medium Voltage Assemblies

Features/Products Xiria Xiria E FMX UX


Rated Voltage 3.6, 7.2, 12, 17.5 & 24kV 3.6, 7.2, 12, 17.5 & 24kV 12, 17.5 & 24KV 12, 17.5 & 24KV 36kV
50kA-3s
Max. Short time withstand 20kA-3s 20kA-1s & 3s 25kA-3s 31.5kA-3s
25kA-3s for 24kV
4000A
630A 630A 2000A 1250A / 2500A
Rated Current Busbars 2500A for 24kV
Single busbar Single busbar Single busbar Single busbar Single busbar
20kA-1s AFL 20kA-1s AFL 25kA-1s AFL AFLR 50kA-3s
Internal Arc AFLR 31.5kA-3s
(Against the Wall) (Arc Absorber Against the Wall) AFLR 25kA-3s for 24kV
200A / 500A 200A / 630A 1250, 1600 & 2000A 630A – 4000A
Circuit Breaker 1250A / 2500A
630A optional 630A, 800A 800A to 2500A for 24kV
Load Break Switch 630A 630A N/A NA Disconnecter Panel NA Disconnecter Panel
Fuse load-break switch N/A N/A N/A N/A N/A
Transformer panel N/A 200A N/A CB CB
Busbar sectionaliser, direct busbar panel N/A 630A 1250, 1600 & 2000A with CB CB + Riser CB + Riser
Add Xiria M 850 x 750 x 1305mm for
Metering panel Dedicated Metering Panel Included N/A Yes Yes
metering VT’s and CT’s.
Epoxy Resin Insulated around primary
Block type for metering or protection Epoxy Resin Insulated around primary Cast-resin insulated block-type in the Cast-resin insulated block-type in the
Current transformers conductors behind the cable cones for
available with equipment conductors behind the cable cones panel metering or protection panel metering or protection
protection
Cast-resin insulated voltage transformers for Cast-resin insulated voltage Cast-resin insulated voltage
For metering or protection available with
Voltage transformers Available only if Xiria M is used the voltage measurement on the cable side, or transformers voltage protection or transformers voltage protection or
equipment
on the busbar side. metering in the panel metering in the panel
Switching Vacuum Vacuum Vacuum Vacuum Vacuum
Insulation Air Air Air Air Air
Degree of Protection IP 31D IP 31D LV - IP3XD; HV - IP4X IP4X – IP42 IP2X - IP4X
Loss of Service Continuity category LSC2B - PM LSC2B - PM LSC2B - PM LSC2B - PM LSC2B - PM
Cable connections Front/Bottom Front/Bottom Front/Bottom Bottom, Top optional Bottom
Protection relays in panel Self-power Self-power relays in Panel No self-power option No self-power option No self-power option
Relays
Control Box w/aux power supply relays Control Box w/ aux power supply relays Aux power supply relays Aux power supply relays Aux power supply relays
Open/Close remotely breaker only, not for Open/Close remotely breaker only, not for Remote Operation CB, VT’s + earth switch
Motorized option Remote for all options Remote for all options
the selector switch, no earth switching the selector switch, no earth switching selector switch
Automation Remote, signaling, tripping & control Remote, signaling, tripping & control Remote, signaling, tripping & control Remote, signaling, tripping & control Remote, signaling, tripping & control
Ammeter, Short-circuit indicator, trip Ammeter, Short-circuit indicator, trip Ammeter, Short-circuit indicator, Ammeter, Short-circuit indicator,
Local options Ammeter, Short-circuit indicator, trip indicator
indicator indicator trip indicator trip indicator
600, 800, 1000mm x
Dimensions 760mm 2panles to 1810mm 5 panels 500 x 600 x 1305mm self-power relay 1200mm x 2600mm x 2930mm
500mm to 1325mm x 1450mm x 2100mm 1310 to 1570mm x
(W x D x H)(mm) x 600 x 1305mm 500 x 770 x 1705mm relay top control box (height includes arc chamber)
2200/2320 to 2860mm
CB: Protection of transformers & cables CB: Protection of transformers & cables Primary distribution, fixed space, Primary and secondary Primary
Applications LBS: for ring cable connection LBS: for ring cable connection fully motorized
ARC Absorber available

6 Power Distribution product guide Nov 2017 Power Distribution product guide Nov 2017 7
Medium Voltage Assemblies
Air Insulated Switchgear
Xiria
Xiria ring main units are characterised by their high level of
operational safety and are suitable for applications up to 24 kV.
Xiria units can be supplied in two-, three-, four- or five-panel
versions. Both the primary part of the unit and the mechanisms
are housed in a fully enclosed housing which protects the system
against environmental influences.
There is a choice of two basic panel versions in our product range:
• A vacuum load break switch for ring cable connections.
• A vacuum circuit-breaker for protecting transformers and cable
connections.
Both versions can be supplied in a unit in any desired combination
and order.
Xiria is an extremely well designed and modern system. For
example, when developing the system we intentionally opted
for protection in the form of a circuit-breaker combined with an
electronic relay. This is a modern, safe and flexible alternative to
fuse protection.
In addition it also makes Xiria very easy to use in an automated
distribution network. These specific features make Xiria an easy-
to-use system that responds perfectly to changing electricity
distribution requirements, both now and in the future.

Maintenance-free
All the live primary parts and mechanisms in a Xiria unit are installed in a fully enclosed housing. This prevents dust, moisture
and other environmental influences from affecting the operation of the unit. The switching mechanism has been designed
with a minimum number of parts, and is specifically intended for switching after a long period of inactivity – precisely the
way it happens in practice. What is more, the mechanism does not use any lubricants, which also benefits its operational
safety. As it is maintenance-free, Xiria significantly cuts inspection and maintenance costs without adversely affecting the
operational safety of your distribution network. Which is something to look forward to in today’s liberalised energy market.

Intrinsically safe
When carrying out operational actions and work on the cables, it is vital to have unambiguous status indications. When it
comes to the safety of the operating personnel, Eaton leaves nothing to chance. That is why Xiria is fitted with directly visible
isolation by means of inspection windows in the front which makes the isolating distance between the cable and the busbar
system directly visible. A visible, short-circuit proof earthing can take place via the load break switch or circuit-breaker.
Xiria is designed with a fully enclosed metal housing combined with single-phase insulation of all primary live parts. This
reduces the risk of an internal fault to an absolute minimum, thus providing a high degree of safety and availability. The
KEMA-tested arc-proof housing also offers additional protection for operating personnel.

Compact
Xiria is one of the smallest ring main units of its kind. This high degree of compactness is a direct result of the combination
of technologies used by Eaton – electrical field control, solid insulation and the use of extremely compact vacuum
interrupters. This compactness offers direct financial benefits in new buildings and when refurbishing existing transformer
stations because of the minimal floor area required.

Ready for automated networks


Xiria is completely ready for use in fully-automated networks. There are various options available for the system, depending
on the level of remote signalling and remote control required. These options are modular, so they can be quickly and easily
added in the future. In this way Xiria anticipates future developments in automation and operational control, so you can
be sure that you will not be left with control, display and communication standards that are too specific or possibly even
obsolete.

Clean and green


Xiria is made exclusively of environmentally-friendly materials. The insulation medium is clean, dry air and the switching
medium is vacuum. Thus Xiria responds to the demand for sustainability in energy distribution. The unit is easy to dismantle
at the end of its service life as the materials used are clearly labeled and can be reused. This facilitates recycling and avoids
excessive costs and environmental taxes when the unit is decommissioned.

8 Power Distribution product guide Nov 2017


Medium Voltage Assemblies
Air Insulated Switchgear
Xiria
3.6kV 7.2kV 12kV 17.5kV 24kV
Rated voltage kV 3.6 7.2 12 17.5 24
Impulse withstand voltage kV 40 60 75/95 95 125
Power frequency
kV 10 20 28 38 50
withstand voltage
Rated frequency Hz 50/60 50/60 50/60 50/60 50/60
Internal arc resistance kA-s 20-1 20-1 20-1 16-1 16-1
Busbar system
Rated normal current A 630 630 630 630 630
Rated short-time
kA-s 20-3 20-3 20-3 16-3 16-3
withstand current
Rated peak withstand current kA 50 50 50 40 40
Circuit-breaker
Rated normal current A 200/630 200/630 200/630 200/630 200/630
Rated breaking current kA 20 20 20 16 16
Rated short-circuit
kA 50 50 50 40 40
making current
Rated short-time
kA-s 20-3 20-3 20-3 16-3 16-3
withstand current
Load break switch
Rated normal current A 630 630 630 630 630
Rated mainly active load
A 630 630 630 630 630
breaking current at cos. phi 0.7
Rated short-circuit
kA 50 50 50 40 40
making current
Rated short-time
kA-s 20-3 20-3 20-3 16-3 16-3
withstand current

Main dimensions Xiria complies with the following international standards


IEC 62271-1 Common specifications
IEC 62271-200 Metal-enclosed switchgear
IEC 62271-304 Severe climatic conditions
IEC 62271-100 Circuit-breakers (M1/E2)
IEC 60265-1 Switches (M1/E3)
IEC 62271-102 Disconnector/Earthing switch (M0)
1305 mm
1305 mm
IEC 62271-102 Earthing via vacuum bottle (E2)
IEC 60529 Degree of protection
IEC 60044-1 Current transformers
EN 50181 Cable cones
Classification according to IEC 62271-200

760 mm760 mm 1110 mm


1110 mm1460 mm
1460 mm1810 mm
1810 mm
2-panel
2-panel
version,
version, 430 kg430 kg 550 kg550 kg 660 kg660 kg 600 mm
600 mm
weight: 350 kg350 kg
weight:

Power Distribution product guide Nov 2017 9


Medium Voltage Assemblies
Air Insulated Switchgear
Xiria E
The Xiria E switchgear is designed around Eaton's proven vacuum
interrupters, which require no maintenance and are certified for 30,000
operation cycles. All live parts in the available panels are single pole
insulated. The used materials are shaped specifically to provide optimum
insulation combined with excellent thermal characteristics. In addition,
the insulation is configured to provide effective control over electric fields
around the used components, thereby minimizing any risk of internal arcing.
Within the Xiria E panels both the primary parts and the mechanisms
are housed in a fully enclosed housing which protects the whole system
against environmental influences.
The use of vacuum interrupters and solid insulation means that the Xiria E
is environmentally friendly. These technologies ensure that this system is a
conservational alternative to switchgear systems using Sulfur Hexafluoride
(SF6) gas for insulation. The cost of ownership is also significantly reduced,
as no regular testing of gas pressure or other routine maintenance is
needed and there is no high end-of-life cost associated with ultimately
disposing of the equipment.
When it comes to the safety of the operating personnel the Xiria E design
leaves nothing to chance. All parts are fully enclosed by an internal arc
tested safe metal housing. Besides that the panels in the system are
provided with direct visible indication of the integrated earthing and ON/
OFF-position by means of inspection windows in the front.

Vacuum circuit-breaker
The vacuum circuit-breaker uses a simple and reliable spring charging mechanism for operation of the
vacuum interrupters. The mechanism contains a low number of moving parts and makes no use of lubricants.
It is completely housed in a sealed for life enclosure and therefore needs no maintenance.
• With environmental friendly vacuum interrupters • Manual or motor-operated
• Simple spring charging mechanism • Position indication by means of inspection
• No use of lubricants windows and mechanical indicators
• Housed in a sealed for life enclosure • Auxiliary contacts for Open/Closed position

2-position change-over switch


All panels are equipped with a change-over switch positioned in the same sealed for life enclosure as the
circuit-breaker. The change-over switch consists of three shafts connected to the busbars or earthing points.
Since it is mechanically interlocked the change-over switch can only be operated when the circuit breaker is
in the open position.
• Manual-operated switch with 2 positions • Auxiliary contacts for service / earthed positions
(service / earthed) • Position indication by means of inspection
• Maintenance free windows and mechanical indicators
• Housed in sealed for life enclosure • Mechanically interlocked with the vacuum circuit-
breaker

Busbar
The busbars in the panel are housed in the same sealed for life enclosure as the circuit-breaker and change-
over switch. To prevent a possible internal arc all busbars are single phase insulated.
• Single phase insulated • Simple and robust construction
• Air insulated • Easy to couple
• Housed in a sealed for life enclosure

Preventing an internal arc


Eaton's proven technologies have been integrated in the design and development of the Xiria in order to
ensure that the switchgear is safe and has high operational reliability throughout its complete lifetime. Within
the Xiria design there are different technologies used to prevent an open arc.
Single pole insulated primary parts Use of Electrical Field control
All high voltage parts are single pole insulated. The Engineers designed the whole construction of
insulation materials used for this are Polycarbonate primary parts, housed in the sealed for life tank,
and Thermo - plastic elastomer (TPE), both high- based on Eaton's key technology for electrical field
quality materials with optimal insulation characteristic control. By means of special shapes and dimensions
resulting in minimised dimensions. the possibility of an open arc is minimized.

10 Power Distribution product guide Nov 2017


Medium Voltage Assemblies
Air Insulated Switchgear
Xiria E
3.6 kV 7.2 kV 12 kV 17.5 kV 24 kV
Rated voltage kV 3.6 7.2 12 17.5 24
Impulse withstand voltage kV 40 60 75 / 95 95 125
Power frequency withstand voltage kV-1m 10 20 28 / 38 / 42 38 50
Rated frequency Hz 50/60 50/60 50/60 50/60 50/60
Loss of service continuity LSC2B LSC2B LSC2B LSC2B LSC2B
Internal arc resistance kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1
Internal arc resistance with absorber kA - s 16 - 1 16 - 1 16 - 1 16 - 1 16 - 1
Internal arc resistance cable comp. alternative kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1
Degree of protection in service IP31D IP31D IP31D IP31D IP31D
Degree of protection with doors/covers open IP2X IP2X IP2X IP2X IP2X
Ambient air temperature range °C -25 +40 -25 +40 -25 +40 -25 +40 -25 +40
Busbar system - 630A
Rated short-time withstand current kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1
Rated short time withstand current alternative kA - s 20 - 3 20 - 3 20 -3 20 - 3 20 - 3
Rated peak withstand current kA 50 50 50 50 50
Load break switches - 630A
Rated active load break current A 630 630 630 630 630
Rated short-circuit making current kA 50 50 50 50 50
Rated short-time withstand current kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1
Rated short-time withstand current alternative kA - s 20 - 3 20 - 3 20 -3 20 - 3 20 - 3
Rated Cable Charging Breaking Current A 31.5 31.5 31.5 31.5 31.5
Mechanical Endurance Class M2 5000 x M2 5000 x M2 5000 x M2 5000 x M2 5000 x
Mechanical Endurance Class as Earth Switch M0 M0 M0 M0 M0
Mechanical Endurance Class Disconnector M0 M0 M0 M0 M0
Electrical Endurance Class E3 E3 E3 E3 E3
Electrical Endurance Class as Earth Switch E2 E2 E2 E2 E2
Circuit-breakers - 630A
Rated breaking current kA 20 20 20 20 20
Rated short-circuit making current kA 50 50 50 50 50
Rated Capacitive Switching Current Class C2 C2 C2 C2 C2
Rated Cable Charging Breaking Current A 31.5 31.5 31.5 31.5 31.5
DC Time Constant msec 45 45 45 45 45
DC Component % <20 <20 <20 <20 <20
Transformer panel - 200A
Rated breaking current kA 20 20 20 20 20
Rated short-circuit making current kA 50 50 50 50 50
Rated Capacitive Switching Current Class C2 C2 C2 C2 C2
Rated Cable Charging Breaking Current A 31.5 31.5 31.5 31.5 31.5
DC Time Constant msec 45 45 45 45 45
DC Component % <20 <20 <20 <20 <20

Main dimensions XiriaE complies with the following international standards


IEC 62271-1 Common specifications for high-voltage
switchgear and control gear standards
IEC 62271-100 High-voltage alternating-current circuit-breakers
IEC 62271-102 Alternating current disconnectors and earthing
switches
IEC 62271-103 High-voltage switches
IEC 62271-200 A.C. metal-enclosed switchgear and control
gear for rated voltages above 1 kV and up to
and including 52 kV
IEC 62271-304 Additional requirements for enclosed
switchgear and control gear from 1 kV to 72.5
kV to be used in severe climatic conditions
IEC 60529 Degrees of protection provided by enclosures
IEC 60044-1 Instrument transformers - Part 1: Current
transformers
IEC 60044-2 Instrument transformers - Part 2: Inductive
voltage transformers
EN 50181 Plug-in type bushings above 1 kV up to 36 kV
ISO 9001-2000 Quality
ISO 14001 Environmental management

Depth: 760

Power Distribution product guide Nov 2017 11


Medium Voltage Assemblies
4069D Magnefix AU_A4 07-03-13 14:57 Pagina 3

Air Insulated Switchgear


Magnefix
Eaton has more than fifty years experience in manufacturing insulation enclosed switchgear and is
recognised throughout the world as being a specialist in the field of epoxy resin based insulation
technology. More than 200,000 Magnefix switchboards have been supplied to satisfied customers
all over the world.
Magnefix was first introduced onto the market more than 50 years ago. Especially the smart
design, safe and robust construction and easy operation have made Magnefix “timeless”. New
developments are still being carried out and research into new applications and technologies is
continuing unabated. Eaton’s engineers are continuously working on improvements in the design
and efficiency, and Magnefix users can count on maximum support and the associated service.
Magnefix is applied in, decentralised transformer stations, high rise buildings, consumer
connections, wind turbine connections and for the electrical supply to signalling and protection
equipment along railway tracks.
Magnefix in walk-in and compact type transformer stations.
Extremely compact Protected against atmospheric
Epoxy resin is not only a high quality insulating and climatic influences
material but due to its high mechanical The epoxy resin insulation ensures protection
high temperatures), high insulation breakdown factor,
strength, also an excellent construction against atmospheric and climatic influences.
material. This combination veryproduces
low moisturea veryabsorption, high creepage
In addition, currentis vibration proof and
the material
resistance,
compact design. The compact construction high mechanical strength and complete
shock proof and does not age. Magnefix is
and full insulation enclosed design of Magnefix
homogeneity. highly
The cable boxes forreliable
PILC andandXLPE
has atype
very long life-cycle.
equipment enables it to cables
be installed
are made in very
of synthetic materials. Magnefix
small spaces. This results in considerable Fully tested
switchgear is provided withEachdouble insulation
Magnefix at points is extensively
switchboard
savings in building costs.
accessible to operating personnel. This additional
mechanically and electrically tested before
Safe and reliable insulation is manufactured and it leaves
testedthe factory. The test
independently of procedures
Magnefix is a fully insulation enclosed
the primary type of
insulation. carried out are not only in accordance with
switchgear. All live parts are surrounded by the routine tests as specified in the relevant
insulating material in such a way that touching IEC publications, each switchboard is also
• Protected against atmospheric and climatic
is impossible. subjected to additional discharge tests.
influences Consequently, Eaton can guarantee the quality
Insulation The epoxy resin insulation ensures protection
and reliability against
of each Magnefix switchboard
The primary insulation ofatmospheric
the Magnefix andsystem
climatic influences.
supplied.
consists of epoxy resin with powdered
In addition, the material is vibration proof and shock
quartz as filling material. This ensures a very Earthing
The characteristics low dielectric loss factorproof
(alsoand
withdoes
highnot age. Magnefix
Before is highlyconnected
a cable reliable andto a Magnefix
has a very
temperatures), high insulation long life-cycle. switchboard can be earthed, the switch caps
breakdown
• Extremely compact factor, very low moisture absorption, high of the unit must be removed. Only then
creepage
Epoxy resin is not only a high quality insulating current resistance,
material • Fully high mechanical
tested is it possible to fit the earthing caps. The
but due to its high mechanical strength,strength
also an and complete homogeneity.
Each MagnefixThe switchboardMagnefix unit can
is extensively only be energized again
mechanically
cable boxes for PILC and XLPE type cables after the earthing caps have been removed.
excellent construction material. This combination and electrically tested before it leaves the factory.
are made of synthetic materials. Magnefix The earthing caps are designed to make
produces a very compact design. The compact
switchgear is provided withThe test
double procedures
insulationcarriedinadvertent
out are notearthing
only in of the busbars impossible.
construction and full insulation enclosedatdesign
pointsof accordance
accessible to operating with the routine tests as specified in the
personnel.
Magnefix equipment enables it to be installed in very insulationrelevant
This additional IEC publications,
is manufactured and each switchboard is also
994069D Magnefix AU_A4 07-03-13 14:58 Pagina 5
tested
small spaces. This results in considerable independently
savings in ofsubjected
the primary to insulation.
additional discharge tests. Consequently,
building costs. Eaton can guarantee the quality and reliability of each
Magnefix switchboard supplied.
• Safe and reliable Cable units
Magnefix is a fully insulation enclosedThe type
Magnefix typeof of the
fixed portion MD4 cable unit contains three • Earthing
terminals to which the cables can be connected. It also
switchgear. All live parts are surrounded
containsby
A Magnefix insulating
the switchboard
corresponding typeeach
busbar contacts, MD4Before
fitted a cable
usually connected
comprises to a Magnefix
a number of cableswitchboard
units to which the main cables
with an arcing chamber, the fixed main and arcing
are connected
material in such a way that touching is impossible.
contacts (switch-disconnectors),
and the magnets and pole plates. can be plus one the
earthed, or more
switchprotected tee-off
caps of the unit units
mustto bewhich the transformer
cablesTheare
arcingconnected
chambers and main and
be replaced when necessary.
(switch-disconnectors
arcing contacts can
removed. Only combined
then is itwith fuse-links).
possible A cable
to fit the unit consists of a fixed
earthing
• Insulation portion
The and three
switch caps containremovable switch-caps.
main and arcing contacts, The fixed portion is made of epoxy resin, in which the conduc-
caps. The Magnefix unit can only be energized again
tors are embedded.
opening springs, springs for ensuring the correct

The primary insulation of the Magnefix system consists


contact pressure and a ferromagnetic plate. These
switches have a double break per phase.
after the earthing caps have been removed. The
The epoxy
of epoxy resin with powdered quartz resinmaterial.
as filling switch caps, in earthing which the capsmoving main andtoarcing
are designed make contacts are located, are held in the
inadvertent
1
closed position by high-strength permanent magnets. The latter are not subject to variation, so that the
This ensures a very low dielectric loss factor (also 4with
2
earthing of the busbars impossible.
contacts are always MAGNEtically FIXed. The various units can be mounted on either a floor frame or a
MD4
wall frame.
Cross-section of a cable unit
1 Busbar contact
2 Fixed main contact
3 Cable terminals
Magnefix type MD4 4 Switch cap with main
and arcing contacts
3
Construction
A Magnefix switchboard type MD4 usually comprises
a number of cable units to which the main cables are
connected (switch-disconnectors), plus one or more Fuse-protected tee-off
protected tee-off units to which the transformer cables The fuse-protected tee-off is used for connection
are connected (switch-disconnectors combined with of the transformer and consists of a switch-disconnector
fuse-links). A cable unit consists of a fixed portion and and a fuse unit. The switch-disconnector connects the
three removable switch-caps. The fixed portion is made fuse unit to the busbar system. The fuse unit consists of
of epoxy resin, in which the conductors are embedded. a fixed portion with three terminals for the cables, and
The epoxy resin switch caps, in which the moving main three removable fuse holders. The latter are suitable for
and arcing contacts are located, are held in the closed fuse-links with dimensions in accordance with
position by high-strength permanent magnets. The latter DIN 43625-12kV. A mechanical interlock between the
are not subject to variation, so that the contacts are switch caps of the switch-disconnector and the fuse
always MAGNEtically FIXed. The various units can be holders makes it impossible to fit or remove a fuse
mounted on either a floor frame or a wall frame. holder before the corresponding switch cap has been
withdrawn. Fuse links can therefore only be fitted or 3
removed when the protected tee-off is switched off. In
addition, the contacts on the transformer side of the
fuse holder are deeply recessed, so that accidental
12 Power Distribution product guide touching is impossible. Nov 2017

1 2
3
Magnefix
Assembly arrangements
It is possible to assemble switchboards with a wide
electrical con
interconnec
Assembly It is possible to assemble switchboards with a wide electrical connections bet
interconnect
variety of combinations for various applications. Tie connection
It
994069D Magnefix AU_A4 07-03-13 14:58 Pagina 8 is Assembly
possible to assemble
variety of switchboards
combinations for with a
variouswide
applications. interconnect
Tie
rods ensure that the units and the insulated side plates
the busbar
connection
electrical c
systi
connect
busbar
994069D Magnefix AU_A4 07-03-13 14:58 Pagina 8 variety ofIt combinations
rods are
ensure
is possible to for various
that the
assemble
clamped applications.
unitsatand
thethe
switchboards
together Tie
insulated
rightwith side connection
Silverplates
a wide
tension. is busbar
completely
plated interconnect syste
the b
insulation.
994069D Magnefix
994069D AU_A4 07-03-13
Magnefix AU_A4 14:58 Pagina
07-03-13 8 Pagina 8
14:58 rods ensure
varietythat
areofthe unitsconductors-
clamped and the
combinations
tubular forinsulated
together at thebusbar
various
the side
right plates Silver
tension.
applications.
system- provide busbar
Tie plated
the system is surrroun
insulation.
connection is com

994069D Magnefix AU_A4 07-03-13 14:58 Pagina 8


are clamped
Medium Voltage Assemblies
rods together
ensure
tubular conductors-
are clampedthe
at the
tubular that theright
conductors- tension.
unitsthe
and
busbaratsystem-
together
theSilver
busbar
the right
plated
system-
insulated
provide
tension.
provide
side theinsulation.
plates
theSilver plated
busbar system is
insulation.
tubular conductors- the busbar system- provide the

Air Insulated Switchgear The basic units for assembly of Magnefix switchgear
Magnefix Magnefix arrangements The basic units for assembly of Magnefix switchgear
Magnefix arrangements The basic units for assembly of Magnefix switchgear
Assembly Magnefix arrangements
Magnefix
Assembly arrangements electrical
The basic units for assemblyconnections between
of Magnefix the units and
switchgear
It is Magnefix
possible toarrangements
assemble switchboards with a wideAssembly variety Itofiscombinations
possible to assemble switchboards with a wide electrical connections interconnect between
the busbarthe units and Each busbar
contacts.
for various applications. Tie rods ensure that the units Assembly andAssembly
It is possible the to insulated
varietyassemble switchboards
of combinations with a applications.
for various wide Tie interconnect
electrical theconnections
connections
electrical busbar
connection iscontacts.
between the units
between
completely Each busbar
and
the unitsand
insulated, andthe entire
sideAssembly
plates are clamped together at the right tension. variety
It is
electrical Itofiscombinations
possible
Silver to
connections assemble
possible
plated
rods between for
totubular
ensure various
switchboards
the
assemble
that units
the applications.
andwith
switchboards
units a wide
and the Tie a wide
with
insulated connection
interconnect
side plates is completely
the busbar
interconnect
busbar the
system insulated,
contacts.
busbar Eachand
contacts.
is surrrounded the
busbarbyentire
Each busbar
epoxy resin
It is possible to assemble switchboards with a wide interconnect
rods of
variety theare
ensure
variety busbar
that
combinations thecontacts.
ofclamped units
combinations Each
and
for together
variousthe
for busbar
insulated
applications.
various
at side
Tie plates
applications.
the right tension. Tie plated
Silver busbar connection
connection system is surrrounded
is completely insulated,
is completely
insulation. byinsulated,
epoxy
and theresin
entire
and the entire
conductors- the busbar system- provide
variety of combinations for various applications. Tie
the electrical
connection
connections
is completely
between
insulated, and the entire
rodsareensure
clamped
rods thattogether
the units
ensure
tubular that atthe
theunits
and
conductors- right
the thetension.
insulated
and the
busbar Silver
side
insulated
system- plated
plates
side plates
provide the insulation.
busbar system
busbarissystem
surrrounded by epoxy by
is surrrounded resin
epoxy resin
the rods
units andthat
ensure interconnect
the units and the the busbar
insulated side contacts.
plates Each
busbar busbar
system
aretubular
clamped
connection
is surrrounded
conductors-
are together
clamped thethe
at by
busbar
together
is
epoxy
right theresin
system-
at tension. provide
rightSilver
tension. the
plated
Silver platedinsulation.insulation.
completely
are clampedinsulated, and
together at the rightthe entire
tension. Silverbusbar
plated system is surrounded
insulation.
tubular conductors- theby
tubular conductors- epoxy
busbar thesystem-
busbarprovide
system-the provide the
Cable Cable unit Fuse protected Busbar
resin insulation.
tubular conductors- the busbar system- provide the
unit for top tee-off sectionaliser
Cable Cable connection
unit Fuse protected Busbar
Cable unit Cable unit for Fuse protected Circuit breaker
Circuit-breaker
Magnefix MD4 & MF switchgear comply with the following IEC The basic units for assembly of Magnefix
publications Cableunit
Cable switchgear for top
unit connection
top Fuse protected tee-off tee-off
protected Busbar
tee-off
sectionaliser
Busbar c
connection protected tee-off
The basic units for assembly of Magnefix switchgear
unit Cablefor top Cable unit tee-off Fuse protected sectionaliser Busbarconnection Busbar co
Common specifications The
for high-voltage
basicThe
units for switchgear
basic assembly and of Magnefix
of Magnefix
units for assembly switchgear connection for top
switchgear
Circuit-breaker
sectionaliser unit
IEC60694
The basic/ units
IEC62271-1
for assembly of Magnefix switchgear
unit tee-off
Circuit-breaker protected tee-off
connecti
controlgear standards connection unit
protected tee-off
Circuit-breaker
IEC60056 / IEC62271-100 High-voltage alternating-current circuit-breakers protected tee-off
IEC60129 / IEC62271-102 Alternating current disconnectors and earthing switches Ring main unit
IEC60265 / IEC62271-103 High-voltage switches This is the most commo
twomain
Ring or more
unitcable units
A.C. insulation-enclosed switchgear and controlgear for
IEC60466 / IEC62271-201 Ring main unitThis is the most common
rated voltages above 1 kV and up to and including 52 kV Application
Ring
This is the main
most
two orunit
common
more
Compact arrangemen
cable unitsstaa
transformer
IEC60529 Degrees of protection provided by enclosures
Cable Cable unit Fuse protected Busbar Busbar two
Blind or moreStand-alone
cable units
medium and fuse
Coupling
mostvoltage prote
distribu
4069DMagnefix
069D MagnefixAU_A4
AU_A407-03-13
07-03-1314:58
14:58Pagina
Pagina1313 Coupling Busbar Busbar Blind connection This is the
Stand-alone
Application
common arra
unit unit for topprotected tee-off sectionaliser connection connection fuse unit unit
IEC60185 / IEC60044-1 Instrument transformers - Cable
Part 1: Current
Cable transformers
Fuse
unit
Busbar
sectionaliser Ring Busbar
main
connectionunit. unit
Blind
block
Stand-alonetwo or
Application fuse
Coupling
more
unit cable units and fu
Cable Cable unit Fuse protected connection
Cableunit
Busbar Busbar
Cable
Cable for top CableBlind
unit Fuse tee-offStand-alone
unit protectedFuse protected Coupling sectionaliserBusbar Busbar
Busbar connection Busbar unit
connection
Blind block
Stand-alone
Blind Compact
fuse unitStand-alone
Coupling transformer sta
unit Coupling
unit for top tee-off sectionaliser
unit connection
unitforconnection
top connection
for top tee-off fuse unit
tee-off unit Circuit-breaker
sectionaliser sectionaliser unit connection
connection connection Compact
block connection
fuse unit transformer
fuse medium
Application
unit
unit stations
voltage
unit and swi
distribut
connection unit block Circuit-breaker protected tee-off
connection connection unit unitblock block mediumCompact voltage distribution
transformernetworks.
stations
Magnefix type Circuit-breaker MD4 protected tee-off MF Ring main unit.
Circuit-breakerCircuit-breaker
Ring main unit. Cable unit for
medium voltage distribution top connene
protected tee-off
Rated values protected tee-off
protected tee-off
Ring main unit.
For connecting cables to
Voltage switch-disconnector as d
kV 3.6 7.2 12 3.6 7.2 12 15
Cable unittop
but with for terminals
top conne is
Impulse withstand voltage kV 40/46 60/70 75/85 40/46 60/70 75/85 Cable95/110 unit forFortopconnecting
connection cables to
Standards
Standards
Power frequency withstand voltage kV 10/12 20/23 28/32 Ring10/12main unit
Ring main unit
20/23
This is the most common arrangement
28/32 For connecting 38/45
and consists
Application:
Cableswitch-disconnector
unit for to
cables toptheconnection
top side
Ideally suitable for Magn
of
as do
Ring main unit switch-disconnector
but withastop
For connecting described
terminals
cables to unde
theist
Frequency This isHz the most50-60
common arrangement 50-60 and consists 50-60of Ring
This 50-60
main unit
is Ring
the mainorcommon
most
two unit
more50-60
Ring main
cable
unit with
arrangement top
units and 50-60
connection.
and
fuseconsists
protected of 50-60
tee-offs.
various levels of apartme
but with top terminals is available.
switch-disconnector as describ
Magnefix
Magnefix
Busbar MD4MD4and
system andMF MFswitchgear
switchgearcomplycomplywith withthe the
two following
following
or more IEC IECpublications
cable publications
units and fuse protected tee-offs. two
This is or more
theThis
most iscable
common
the unitscommon
most and fusearrangement
arrangement protected tee-offs.
and consists and ofconsists of Application:
Application but with top terminals is availa
IEC60694/ IEC62271-1
IEC60694 / IEC62271-1 Commonspecifications
Common specificationsforforhigh-voltage
high-voltageswitchgear
switchgearand andcontrolgear
controlgearstandards
standards two or more twocableor more units and units
cable fuse protected tee-offs.Application:
and fuse protected tee-offs. Ideally suitable for Magne
Normal current A
Application 400 400 400 630 Compact
Application 630
transformer 630
stations and Ideally630
switching points
suitable infor Magnefix
various
Application: levels ofswitchboa
apartme
IEC60056/ IEC62271-100
IEC60056 / IEC62271-100 High-voltage
High-voltagealternating-current
alternating-current circuit-breakers
circuit-breakers
Ring main unit with top connection. Terminal station
Compact transformer stations and switching points in Application
Compact transformervoltage
Application stations and switching points in
Short-time withstand current 1 s. kA 14.4 14.4 14.4 20
Ring main unitmedium 20
with top connection. distribution
20 networks. various 20 levels
Ideallyofsuitable
apartment
This buildings,
for Magnefix
arrangement compr so
IEC60129/ IEC62271-102
IEC60129 / IEC62271-102 AlternatingAlternatingcurrent
currentdisconnectors
disconnectors
medium voltage andearthing
and earthingswitches
distribution switches
networks.
Ring main unit. medium
Compact voltage transformer
transformer
Compact distribution
stations and networks.
switching
stations points in points in
and switching
Peak withstand current Ring main unit with top connection. various levels of apartment bu
IEC60265/ IEC62271-103
Ring
IEC60265 / IEC62271-103 High-voltage
main unit. High-voltageswitches
switches kA 31 Ring main unit. 31 31 medium 50 voltage
medium voltage 50
distribution networks.
distribution 50
networks. 50 Application
Switch-disconnector
IEC60466/ IEC62271-201
/ IEC62271-201 A.C. A.C.insulation-enclosed
insulation-enclosedswitchgear switchgearand andRing main unit.
Ring main
controlgear unit. Terminal
Transformerstation
stations at t
IEC60466 controlgear forforrated
ratedvoltages
voltagesabove above1 kV
1 kVand
andupuptotoand
andincluding
including5252kVkV
Terminal station Forarrangement
This example for wind compritur
Normal
IEC60529
IEC60529 current Degrees of protection
Degrees of protection provided providedA by enclosures
by 400
enclosures 400 400 450 Cable unit450 for top connection 450 450
Cable unit for top connection Terminal station
This arrangement comprises a fuse pro
IEC60185
Mainly
IEC60185 / IEC60044-1
active
/ IEC60044-1 load breaking Instrument
Instrument transformers- Part
current
transformers - Part
A1: 1:Current
Current
400 transformers 400
transformers 400 Cable 450 unit for Fortop connection
connecting cables to the
450 station.
Terminal 450 top side of a switchboard,
450 Application
a
For connecting cables to the top side of a switchboard, a This arrangement comprises a
Cable unitCable
For connectingforswitch-disconnector
top
unitconnection
for top
cables connection
to the topas side of a switchboard,
described underApplication Transformer stations at th
ring amain unit,
Short-circuit making current peak value switch-disconnector kA 31 as described under 31 ring main unit, 31 50
Forswitch-disconnector
connecting cables 50 50 50
Transformer stations
For
a example
a Application at thefor endwindof feed
tur
8 with to
For connecting
but ascables
top described
the toptoside
terminals theunder
isof
top ring of
side
available. main
a switchboard, unit,
a switchboard,
but with top terminals is available.
Short-time
Classification
Classification withstand
accordingtoto
according current
IEC 1 s.
IEC62271-201
62271-201 kA 14.4 14.4 14.4 but 20 with top terminals
switch-disconnector as 20
switch-disconnector is available.
described under ring
as described 20under
main ring Formain
unit, 20unit,
example for windstations
Transformer turbine at connecti
the en
Application: Application: For example for wind turbine c
Earth fault
Protection breaking
grade current
againstelectric
electricshock
shock PA/PB1 but with top but terminals
with Terminal isstation.
available.
top terminals is available.
Protection grade against PA/PB1 A 240 240 240 240
Application: 240
Ideally suitable for Magnefix 240switchboards erected 240 on
Ideally suitable for Magnefix switchboards erected on Terminal station.
Loss
Loss Of
CableRingOf Service
Service
charging Continuity
Continuity
breaking LSC LSC 1 1
connection. current
main unit with top various Alevels of25 apartment buildings, 25
Ring main unit with
office 25
top connection.
blocks etc.
Application:
Ideally suitable
Application:
25 8 Terminal for
various Magnefix
levels switchboards
25 of apartment25 erected on
buildings, office 25 blocks etc.
station.
PartitionClass
Partition Class PIPI Ring main unit with top connection. various
Ideally levelsfor
suitable
Ideally of Magnefix
apartment
suitable buildings,
switchboards
for Magnefix office
erected
switchboards blockson etc. on
erected
Circuit-breaker 8
IAC applicable Ring main unitRing
Notapplicable withmain
top unit
connection.
with top connection. various levelsvarious of apartment buildings,buildings,
levels of apartment office blocks etc.
office blocks etc.
IAC Not 8
Normal current A 400 400 400 - - - -
Degreeofofprotection
Degree protection IP IP2X2X station
Terminal Terminal station
Short-time withstand current 1 s. kA 14.4 14.4
This arrangement comprises a fuse protected tee-off. 14.4 -
Terminal station - - -
This arrangement comprises a fuse protected tee-off.
Short-circuit
Above summary breaking
gives current
for some
Above summary gives for some subjects theApplication peak
subjects value the oldkA and the14.4
new
old and the new standards. standards. 14.4 14.4 Terminal station
This- arrangement
Terminal station-
comprises -
a fuse protected tee-off. -
Application
This arrangement comprisescomprises a fuse protected tee-off. tee-off.
DC component
Magnefix
Magnefix switchgearisistested
switchgear testedaccording
accordingtotothe theIEC%IECstandard
Transformer 20 at
standard
stations asas end of 20
applicable
applicable
the atatthe
feeder thetime
cables. time20ofofthe
thetype
typetests.
tests. - This Transformer
Application
arrangement
- stations a fuse protected
at the- end of feeder cables. -
Fuse-links For example for wind turbine connections. Application
Transformer stations
Application
For example at the
for end
wind of feeder
turbine cables.
connections.
For example
Transformer for wind
stations
Transformer turbine
atstations
the endatof connections.
thefeeder
end of cables.
feeder cables.
Normal current A 57.7 57.7 57.7 57.7 57.7 57.7 57.7
Dimensions(mm)
Dimensions (mm)
Terminal station.

Terminal station.
Terminal station. For example for wind turbine connections.
For example for wind turbine connections.

Main
8 dimensions Terminal station.
8 Terminal station.
45 45 BB 45 45 8 BB
Magnefix type MD4 Magnefix type MF
36 36 36 36 8 8 3636 105105105105 244244 3636
91 9191 91 230230 230230 4545 4545 4545 4545
45
45

1517
1517

1517
1517

89 89130130 130130
962
754 962

911
911
754

122122 124124
252
63
252
63

MD4 - B = C x 91 + T x 230 + 72
MF - B = C x 105 + T x 244 + 72
15 15 ø 11
ø 11 caca
45 45 27 27 11 3535 322322 3535 (C = number of cable units,
B-52
B-52 35 35 322322 35 35 1515 B-52
B-52 601601 T = number of protected tee-offs)
526526
Magnefix
Magnefix type
type MD4.
MD4. Magnefix
Magnefix type
type MF.
MF.
Power Distribution product guide Nov 2017 13
Dimensions(mm)
Dimensions (mm) Magnefixtype
Magnefix typeMD4
MD4 Magnefixtype
Magnefix typeMF
MF
Unitwidths
Unit widths
54012BR04 Power Xpert FMX AU_A4 07-03-13 14:49 Pagina 4

Medium Voltage Assemblies


FMX Smart, Innovative Design Air Insulated Switchgear
offers Economic and Reliable Solution Power Xpert FMX
Power Xpert® FMX is Eaton's IEC single busbar, solid- and air-insulated
medium voltage switchgear system, for use up to 24 kV. The system provides
Power Xpert® FMX is Eaton's IEC single busbar, solid- and reliable switching, protection, metering and distribution of electrical energy.
air-insulated medium voltage switchgear system, for use
up to 24 kV. The system provides reliable switching, The modern design system uses Eaton's state of the art technology and is
6054012BR04 P ower Xpert FMX AU _A4 07-03-13 14:50 P agina 7
protection, metering and distribution of electrical energy. manufactured in accordance with the highest quality standards. Within the
The modern design system The system uses only system our engineers have integrated Eaton core technologies, such as
uses Eaton's state of the art
technology and is manufactured
environmentally friendly
technology and materials. vacuum technology, solid insulation and electrical field control. More than a
Main Components
in accordance with the highest Since the type FMX system
quality standards. Within the is based on vacuum technology century of experience in design and production of medium voltage systems
system our engineers have and solid insulation, the system
integrated Eaton core is the latest environmentally has gone into the product. Type FMX switchgear features a reliable and
technologies, such as vacuum friendly "green" switchgear on
technology, solid insulation and the market. compact system design, which benefits from the best practices incorporated
electrical field control. More
than a century of experience in
design and production of
The new system incorporates
highly innovative technology,
Vacuum circuit-breaker
in Eaton's current range of MV systems. The system is tested according the
by implementing an electro-
medium voltage systems has
gone into the product.
magnetic mechanism for the latest standard IEC 62271.
The vacuum circuit-breaker uses a simple and reliable
circuit-breaker control, and it
Type FMX switchgear features electromagnetic mechanism for operation of the vacuum
a reliable and compact system
introduces an integrated cable
test facility outside of the high The system uses only environmentally friendly technology and materials. Since
interrupters. The construction of the mechanical linkage between
design, which benefits from
the best practices incorporated
voltage compartment.
the type FMX system is based on vacuum technology and solid insulation, the
the actuator and the drive rod of each of the three vacuum
interrupters is reduced in complexity, compared to a conventional
in Eaton's current range of
MV systems. The system is
tested according the latest
spring-charged mechanism. system is the latest environmentally friendly "green" switchgear on the market.
standard IEC 62271. Features
The new system incorporates highly innovative technology, by implementing
• Environmentally friendly vacuum interrupters
• Electromagnetic mechanism with controller
an electro - magnetic mechanism for the circuit-breaker control, and it
• introduces
Mechanical lever for hand-operated operation (switch off) an integrated cable test facility outside of the high voltage
• Mechanical position indicator for Open /compartment.
Closed position
• Auxiliary contacts for Open / Closed position
6054012BR04 P ower Xpert FMX AU _A4 07-03-13 14:50 P agina 7
Vacuum circuit-breaker
Complete Range up to 2000 A
The FMX comprises a complete In combination with Eaton's low governmental buildings and
The vacuum circuit-breaker uses a simple and reliable electromagnetic mechanism for operation
• Infrastructure projects
range up to 2000 A, with metal- voltage switchgear, busbar infrastructure projects. of the vacuum interrupters. The construction of the mechanical linkage between the actuator and
(tunnels, subways,

Main Components
enclosed modular compact
panels of a minimal 500 mm
width. Both the 12 and 24 kV
trunking, UPS products, project
management and service
capabilities, the FMX can be part
The design makes the FMX
system especially suitable for
applications where a reliable,
airports, etc.)
the drivechange-over
rod of each
• Hospitals
Two-position of the three vacuum interrupters is reduced in complexity, compared to a
switch
versions use the same compact
housing.
of a state of the art, complete
solution.
safe, economic (e.g. compact)
and clean (e.g. non-toxic) conventional spring-charged mechanism.
• Process
All panels
industry
are equipped
• Cement industry with a change-over switch consisting of
FMX completes the range of environment is necessary. interconnected contact pins moving in the horizontal plane. Since
• Mining industry
Eaton medium voltage switch- Application Areas • Environmentally friendly vacuum interrupters
it is mechanically interlocked, the change-over switch can only be • Mechanical position indicator for Open /
gear, being an extension to the The FMX is ideally suited for Some applications are: Vacuumwhencircuit-breaker
• Automotive
operated theindustry
circuit-breaker is in the open position.
successful products MMS
(double busbar), Unitole (with-
applications in main feeder • Utilities (main- and sub- •• Petrochemical
Electromagnetic
plants
mechanism with controller Closed position
stations, sub-distribution distribution stations) The• vacuum
Features circuit-breaker
Textile and paper industryuses a simple and reliable
drawable switchgear), SVS
(single busbar secondary switch-
stations and specific customer
requirements in (process) • Commercial and
electromagnetic mechanism for operation of the vacuum
• Mechanical lever for hand-operated
• Food
• Motor industry
or manually-operated
interrupters. The constructionswitch
of thewith two positions
mechanical linkage between
• Auxiliary contacts for Open / Closed position
gear) and Xiria (ring main unit). industry, commercial and governmental buildings
(Service
the Data/centres
• actuatorEarthed)
and the drive rod of each of the three vacuum
operation (switch off)
interrupters is reduced in complexity, compared
• Interconnected contact pins moving in the horizontal to a conventional
plane
spring-charged mechanism.
• Contact pins epoxy resin insulated and located in the busbar
compartment
2-position change-over switch
Features
• Auxiliary contacts for Service / Earthed positions
• Environmentally friendly vacuum interrupters
All panels are equipped with a change-over switch consisting of interconnected contact pins moving
• Mechanical position indicators
• Electromagnetic mechanism with controller
in the horizontal plane. Since it is mechanically interlocked, the change-over switch can only be
• Interlocked with the vacuum circuit-breaker
• Mechanical lever for hand-operated operation (switch off)
4 •operated when
Mechanical position the
indicator circuit-breaker
for Open / Closed position is in the open position.
• Auxiliary contacts for Open / Closed position
• Motor or manually-operated switch with two • Contact pins epoxy resin insulated and
positions (Service / Earthed) located in the busbar compartment
• Interconnected contact pins moving in the • Auxiliary contacts for Service / Earthed
Busbarshorizontal plane positions
Two-position change-over switch
•Allofpanels
bars
Mechanical
standardised withposition
a change-over
cross-sections.
indicators
The busbars in the panel are constructed from high-quality aluminium
are equipped The shape switch consisting
of the busbar has of
• Interlocked with the vacuum circuit-breaker
interconnected
been contact
designed to attain pins moving
optimal in the
electrical fieldhorizontal
control. plane. Since
it is mechanically interlocked, the change-over switch can only be
operated when the circuit-breaker is in the open position.
Busbar
Features
• Busbars constructed from high-quality aluminium
Features
The busbars in the panel are constructed from high-quality aluminium bars of standardised cross-
• Branch of busbars made of copper or aluminium
• Motor or manually-operated switch with two positions
sections. The shape of the busbar has been designed to attain optimal electrical field control.
• Aluminium
(Service /parts are coated with galvanic silver layer
Earthed)
• Contact surfaces are
• Interconnected treated
contact with
pins Penetrox
moving in the horizontal plane

• Housed Busbars constructed from high-quality
• Contactin busbar ductresin
pins epoxy covering the full
insulated andwidth of the
located panel
in the busbar • Housed in busbar duct covering the full
• Aircompartment
aluminium; Branch of busbars made of
insulated
• Auxiliary contacts forcompartment
Service / Earthed positions
width of the panel
• Situated in fully closed complying with
•IP4X copper or aluminium; Aluminium parts are
degree ofposition
Mechanical protection
indicators • Air insulated
coated
• Interlocked with
with the galvanic
vacuum silver layer
circuit-breaker
• Situated in fully closed compartment
• Contact surfaces are treated with Penetrox complying with IP4X degree of protection
7

Safe in use Reliable and safe in Environmentally friendly Low total cost of User friendly
• Capacitive voltage operation • Minimised number of ownership • Cable connection and
detection system for • Complete Busbars
design components Low initial costs due to: user interfaces for
verification of safe certified inThe
accordance
busbars in the panel are constructed from high-quality aluminium
• Environmentally-
bars of standardised cross-sections. The shape of the busbar has
• Panels minimum operation on the front
isolation from supply with IEC been designed to attain optimal electrical
friendly materials used
field control. 500 mm width side of the unit
• Operation only • Arc fault tested
Features in in the design • Integrated arc channel • Ergonomic cable
possible with closed accordance with
• Busbars constructed from high-quality aluminium
• No use of SF6-gas with absorbers connection height of
• Branch of busbars made of copper or aluminium
cable compartment IEC 62271-200
• Aluminium parts are coated withfor switching
galvanic silver layer and • 12 kV and 24 kV 750 mm from floor
• Cable testing via • Single pole insulated
• Contact surfaces are treated withinsulation
Penetrox (green panels in the same level
• Housed in busbar duct covering the full width of the panel
integrated cable test primary parts within
• Air insulated
switching) housing • Cable (secondary)
facility outside high one compartment • Minimal
• Situated in fully closed compartment complyingnumber
with of No costs during service entry points on both
voltage compartments •
IP4X degree of protection
Ferro-resonance transition points in due to: sides of the low
• Voltage transformers protected voltage the primary design • Long-life, using epoxy voltage compartment
can be (dis) transformers enables low energy resin as insulation top plate
connected from the • Integrated (internal) loss during operation 7 medium • Facility for (dis)
primary circuit, with arc absorbers • Only re-usable and/or • Maintenance-free connecting the voltage
closed high voltage recyclable materials circuit breaker transformers, easily
compartments used (electromagnetic accessible from the
mechanism and front without entering
vacuum interrupters the HV compartment

14 Power Distribution product guide Nov 2017


Medium Voltage Assemblies
Air Insulated Switchgear
Power Xpert FMX
12 kV 17.5 kV 24 kV
Rated Voltage kV 12 17.5 24
Lightning Impulse withstand voltage kV 75 95 125
Power frequency withstand voltage kV 28 38 50
Rated frequency Hz 50 50 50
Internal arc class AFL 25 kA - 1 s AFL 25 kA - 1 s AFL 25 kA - 1 s
Loss of service continuity category LSC2B LSC2B LSC2B
Partition class PM PM PM
Earthing circuit kA - s 25-3 25-3 25-3
Compartment circuit-breaker/cable Interlock-controlled Interlock-controlled Interlock-controlled
54012BR04
6054012BR04
3-13 6054012BR04
14:51 Power
Power
PaginaXpert
17 Power
Xpert
FMX AU_A4
FMX
XpertAU_A4
FMX
07-03-13
AU_A4
07-03-13
14:51
07-03-13
14:51
Pagina
14:51
Pagina
17 Pagina
17 17 Tool-based / Tool-based / Tool-based /
Compartment busbar
3-13 14:51 Pagina 17
non-accessible non-accessible non-accessible
Degree of protection HV compartments (optional) IP4X IP4X IP4X
Degree of protection LV compartment IP3XD IP3XD IP3XD
Temperature classification Minus 5 °C indoor Minus 5 °C indoor Minus 5 °C indoor
Product
Product Product
Range Range Range
Busbar system
Rated normal current A 2000 2000 2000
Rated short-time withstand current kA - s 25-3 25-3 25-3
tion Rated peak withstand OptionOption current
Option
Option kAOption 63OptionOption Option Option63
Option Option 63
tion Circuit-breaker - incoming feeder
Option and sectionalizer Option
Rated normal current A 1250 - 1600 - 2000 1250 - 1600 - 2000 1250 - 1600 - 2000
Rated short-circuit breaking current kA 25 25 25
Rated short-circuit making current kA 63 63 63
Rated short-time withstand current kA - s 25-3 25-3 25-3
Circuit-breaker - outgoing feeder
Rated normal current A 630 - 800 630 - 800 630 - 800
Rated short-circuit breaking current kA 25 25 25
Rated
Option short-circuit
Option Option
Option Option making current OptionOption Option kA Option Option
Option 63 63 63
Rated
Option short-time Option withstand current kA - s 25-3 25-3 25-3
Class E2, C2 E2, C2 E2, C2
Operating cycles at short-circuit current 100 100 100
Option Option Option
Option
Single capacitor bank switching OptionOption OptionA 400 400 400
Mechanism
Option
Rated operating sequence A C+P
Class M2 M2 M2
eaker panel Opening Circuit-breaker
timeCircuit-breaker
Circuit-breaker
panel panelpanel
Busbar sectionalizer panel ms 50Busbar Busbar sectionalizer
Busbar sectionalizer
sectionalizer
panel panel50panel 50
eaker panel DC component Busbar sectionalizer panel % 35 35 35
Closing time ms 70 70 70
Number of operations actuator 30,000 30,000 30,000
Number of operations interrupter 30,000 30,000 30,000
Auxiliary voltage V 24, 48, 60,110, 220 VDC 24, 48, 60,110, 220 VDC 24, 48, 60,110, 220 VDC
2 cables Circuit-breaker
Circuit-breaker
Circuit-breaker
3 cables Change-over
Change-over
Change-over
Capacitive 2 cables2 cables2 cables
Voltage 3 cables3 cables3 cables
Voltage Capacitive
Capacitive
Current VoltageVoltage
Capacitive
110/230 VACVoltage Current110/230
VoltageVoltageVoltage Current CurrentVAC 110/230 VAC
switch switch
voltage switch transformer
detection transformervoltagevoltage
detection
voltage
transformer transformer
detection transformer
detection transformer
transformer transformer transformer
transformer transformer
transformer
2 cables Mechanism
3 cables change-over
Capacitive
system switch
at Voltage
the cable Voltage
at the busbar system Current at the cable
system system at the cable at cable
at the the busbar
at the busbar
at the busbar
Opening time transformer
voltage detection (disconnectable) transformer
(disconnectable) stransformer (disconnectable)
< 20 (disconnectable)
(disconnectable) (disconnectable)< 20
(disconnectable)
(disconnectable) < 20
system at the cable at the busbar
Closing time (disconnectable) (disconnectable) s < 20 < 20 < 20
Number of operations change-over switch 1,000 1,000 1,000
Dimensions Class
Dimensions
Dimensions (mm) (mm) (mm) M0 M0 M0

Main dimensions
CB 630
CBA630CB
CBA630
630 A
A 1325 mm wide
CB 1600 A CB 800
CBA800CB
CBA800
800 A
A CB 1600
CB
CB 1600
A CB A
1600 A
1600 A BS
1200 mm wide1600 A BS 1600 A FMX complies BSwith
BS 1600 A BSthe
1600 1600following
A A international standards
CB 2000 A CB 1250
CB 1250
A CB 1250
A
1250 AA BSCB 2000
1250CB
A 2000
CB A CB A
A
2000 A BSBS
BS 1250 A1250
BS 1250
AA
2000 BS BS
A
1250 A A
2000 BS 2000
IEC 62271-1 Common
BS 2000
A 2000 Aspecifications
BS A
CB 1600 A BS 1600 A
CB 2000 A BS 1250 A BS 2000 A IEC 62271-100 Circuit-breakers (E2, M2, C2)
IEC 62271-102 Disconnectors and earthing switches (E2, M0)
IEC 62271-200 Metal enclosed switchgear and controlgear
IEC 60044-1 Current transformers
IEC 60044-2 Voltage transformers
IEC 60529 Degrees of protection (IP Code)
IEC 61850 Communication networks and systems in substations
IEC 61243-5 Live working - Voltage detectors - Part 5: Voltage
2100

2100

2100

detecting systems

Depth: 1450 mm
Extra panel height: 500 mm for busbar side voltage transformers, 150 mm for
busbar venting box, 500 mm for busbar side cooling box on 2000 A panels.
1000 500 500 500 1000 1000 1000
1200 1200
13251200 1200 1325 1325 1325

1000Depth:Depth:
1450 Depth:
mm 1450 mm
1450 mm 1200 1325

bar side voltage Extra height:


Extra transformers,
panel
Extra height:
panel panel
500 height:
150 mm
mm500for
mm
for 500
formm
busbar
busbar for voltage
busbar
side busbar
ventingside
box,side
500 voltage
voltagemm for transformers,
transformers,
transformers,
150 mm
busbar 150for
side mm150
formm
busbar
cooling boxfor
onbusbar
busbar
venting box,Aventing
venting
2000 500
box,
mm
panels.box,
500for
mm500
formm
busbar for cooling
busbar
side busbar sideon
side cooling
box cooling
box
2000onbox onA2000
A2000
panels. A panels.
panels.
Power Distribution product guide Nov 2017 15
bar side voltage transformers, 150 mm for busbar venting box, 500 mm for busbar side cooling box on 2000 A panels. 17 17 17 17

17
Medium Voltage Assemblies
Air Insulated Switchgear
Power Xpert UX 3.6kV - 24 kV
Eaton understands that real estate is a valuable resource. The available
space must be optimized to ensure building and land costs are minimized,
without compromise to the solution design or functionality.
The footprint of Eaton’s Power Xpert UX switchgear is one of the most
compact of all systems available on the market. 12/17.5kV vacuum circuit
breaker (VCB) panels with rated current of 630/1250A up to 31.5kA are
only 600mm wide and 1320mm deep – up to 37% less floor area than
similar switchgear solutions on the market. Along with a compact footprint,
the Power Xpert UX system offers flexible design options for the most
demanding of applications.
The Power Xpert UX platform has three high-voltage compartments
separated by earthed metal barriers, providing the highest loss of service
continuity classification LSC2B and partition class PM; The busbar
compartment, the switch device compartment and the cable compartment.
For personnel safety, the Power Xpert UX system is designed with a
number of comprehensive mechanical interlocks according to IEC62271-
200 for safe and reliable operation of the switchgear. Additional electrical or
mechanical key interlocks are available to secure safe and reliable operation
for busbar earthing and up or downstream interlocking
Eaton’s expertise in switchgear innovation, including cast-resin, vacuum circuit breaker and
contactor technologies, arc interruption and electrical field control have been integrated into the
design and development of Power Xpert UX. This ensures that the switchgear has the highest
levels of safety and operational reliability at all times.

Maximising performance and safety Best-in-class testing

ng with safety innovation


• Safety first No matter where the system is produced around the world, the same rigorous testing is provided as
• Ensuring maximum uptime standard. You can count on Eaton’s commitment to quality, beginning in the design phase with full
3rd party type testing to all relevant IEC standards, right through to factory and on site acceptance
• Flexibility in small foot print testing. In addition to compliance to ISO 9001, all manufacturing locations must adhere to Eaton’s
nologies that offer best-in-class operation and quality system to ensure the highest quality standards are delivered.
maintenance,
UX system is designed with safety in mind.
SF6-free design
switchgear innovation, including cast-resin, vacuum circuit breaker and
The
es, arc interruption and electrical field control have combination
been integratedofinto
vacuum
the interrupters for switching, cast-resin technology and clean air as the isolation
medium ensures
ment of Power Xpert UX. This ensures that the switchgear has the that the Power Xpert UX is an environmental friendly system. Without SF6 gas, plant
highest
operational reliability at all times. maintenance and operation is simplified and costly administration, SF6 gas management and end of life
disposal costs are minimized.

Vacuum circuit breaker technology


By designing a simple and efficient low energy springcharged mechanism with the minimum possible
Internal arc classification (IAC) AFLR
number of parts, the maintenance requirements normally associated with this type of mechanism are
ones up to 50kA for 1 second
minimized. The W-VACi breaker is virtually maintenance-free.

d isolated Internal arc classification


In the unlikely event of an (IAC) AFLR Theup to 50kA
system has for 1 second
been proven
uce the internal arc fault, the of
metal
nal faults In the unlikely event an internal by
arcindependent 3rd-party
fault, the metal enclosed design and robust construction
enclosedthe
enables design
Power andXpert
robust
UX systemtesting to provide an
to successfully internal
pass internal arcing tests in accordance with
on of arc construction enables the arc the
classification (IAC)ofofprotection
AFLR.
IEC 62271-200. This standard defines required level in the event of an internal arc
Power Xpert UX system to
fault, in all three primary compartments A = Protection for personnel Fully insulated and isolated current
up to 50kA for 1 second.
successfully pass internal
paths reduce the potential for internal faults through the creation of arc free zones.
arcing tests in accordance with F = Protection at the front
IEC 62271-200. This standard
defines the required leveldoors
of L = Protection at the sides
Racking behind closed
Fully insulated busbar system. protection in the event of an
behind To maximize operator safety PowerRXpert = Protection at the
UX enables rear
operation of the withdrawable switching device
Remote
internal operation
arc fault, in all three
from test to service and back to the test position, all behind closed doors. This ensures full internal arc
oors primary compartments up to
containment
For additional
50kA forsafety, at
fullall
1 second. times during operation.
remote
operation of the switchboard
erator safety is possible without the need
X enables Remote
to enter operation
the switch room.
withdrawable Operational safety andsafety,
auto- full remote operation of the switchboard is possible without the need to enter
For additional
eliability through accessibility of compartments
e from test to
k to the test
mation can be further enhanced
the switch room. Operational safety and automation can be further enhanced by including the remote
by including the remote racking
ind closed racking
option option for withdrawable switching devices and the option for remote operation of the integral
for withdrawable
ures full internal • switching devices and the
ersonnel
at all times
Busbar compartment:
Racking behind closed door. earthing switches. Full remote operation.
eration Tool-based / non-accessible option for remote operation of
n. the integral earthing switches.
e is • Switching device compart-
g access
ment: Interlock controlled
partments
design. • Cable compartment:

usthe24/7 temperature
Tool-based or monitoring
option for
y interlock controlled
to through permanently installed self-powered,
ction
ared sensors that continuously monitor the thermal
ts and cable connections. The monitoring system
on of hotspots at an early stage of development and
e maintenance data to prevent potential downtime. Interlock controlled access to the Interlock controlled access to the
16 Power Distribution product guide Nov 2017
switching device compartment. cable compartment.
diagnostics are essential to any reliable and safe network.

Medium Voltage Assemblies


Primary components
Air Insulated Switchgear
Power Xpert UX 3.6kV - 24 kV 24/7 thermal monitoring system
Eaton is one of the few global, fully integrated manufacturers of high-voltage switchgear. Utilizing
24/7corethermal monitoring
technologies of vacuum system
interruption and cast resin insulation, switching devices used within
the Power Xpert UX switchgear have outstanding performance including:
By determining potential reliability issues before By determining
they occur, potential The system
uptime can be increased provides
through valuable
planned
and •preventative maintenance. Eaton has reliability issues
partnered with before theya worlddata
Exertherm, forinpreventative
leader continuous main-
Optimal arc control • Insensitivity to environment
thermal monitoring, to provide •the Power Xpertoccur,UX uptime
system canwith
be increased tenance. Based
an optional continuous 24/7on real-time
temperature
• Virtually maintenance-free SF6 free
monitoring system. Hotspots in joints and through
cable planned andare
connections preven-
detected atdata,
an preventative
early stage of maintenance
development
• High electrical endurance • Long service tative
life maintenance. Eaton has can be scheduled to reduce
via permanently installed infrared sensors.

mary components
partnered with Exertherm, a unplanned downtime.
The system provides valuable data for preventative world leadermaintenance.
in continuous Based on real-time data, preventative
The thermal monitoring
maintenance can be scheduled to reduce unplanned thermal monitoring,
downtime. to The
provide
thermal monitoring system is modular
system is modular and can
and can be scaled to any size of installation. theLocal
Power or Xpert
remote UXmonitoring
system of the system is possible via local
e of the few global,display
Eaton’s
or web industry
connection. leading medium with voltage
an optional technology
continuous
be scaled to any size of
fully integrated manufacturers of high-voltage switchgear. Utilizing installation. Local or remote
24/7 temperature
ologies of vacuum interruption and cast resin insulation, switching devices used within monitoring
monitoring of the system is
Xpert UX switchgear have outstanding performance including: system. Hotspots in joints Panel mounted alarm module Self-powe
Primaryand components possible via local display or
cable connections are connects via MODBUS to the infrared s
web connection.
rc control • Insensitivity to environment
Eaton isdetected at an early stage of integrated manufacturers of high-voltagesystem data cards mounted within

onents
one of the few global, fully switchgear. Utilizing
maintenance-free • SF6 free development
core technologies of via permanently
vacuum interruption and cast resin insulation, switchingthe switchgear
devices used forwithin
local orthe
remote
installed infrared sensors. alarm and data logging.
trical endurance • Long service life Power Xpert UX switchgear have outstanding performance including:
• Optimal arc control • High electrical endurance • SF6 free
• Virtually maintenance-free • Insensitivity to environment • Long service life
acturers of high-voltage switchgear. Utilizing
s industry
sin leadingdevices
insulation, switching mediumused voltage
within technology
Vacuum circuit breakers - Type W-Vaci
formance including:
• Type tested in accordance with IEC62271-100 • Full range of accessories
Vacuum circuit breakers Vacuum contactors Vacuum contactors Earthing switch
nvironment • 12/17.5kV up to 4000A 50kA/3sec. • Optional remote racking capability
Type W-VACi Type W-SLC Type W-SLN
• Type tested in accordance • Tested
• inWide
SmartPX downtime avoidance
• 24kV up to 2500A 31.5kA/3sec.
accordance
rangewith
AC or• Tested
of in accordance
DC auxiliary
• Electrical or mechanical key interlocking options
with
Type tested in accordance
control •


with IEC62271-100
12/17.5kV up to 4000A •
and maintenance
IEC 62271-106
voltages
Mid-mount type
IEC 62271-106
Roll-on floor type

system with IEC62271-102
12/17.5kV up to 50kA/3sec. •
50kA/3sec. 130kA peak
• 3.6/7.2/12kV ratings 3.6/7.2kV ratings

• 24kV up to 2500A Vacuum Eaton’s SmartPX
contactors

- Type isW-SLC
an Modern• operations require
24kV up to 31.5kA/3sec.
Pump 2

• Contactor switching • Contactor


advanced intelligent system switching increasingly effective
Cell ID: A2 [A] 0
31.5kA/3sec. 80kA peak
up to 400A
• Tested up to 400A
for in accordance
control with IEC 62271-106 to •avoid
Wide range of AC or DC auxiliary control
Device Address 4

m voltage technology motor and power strategies process


40

Wide range of AC or DC • Optional remote operating


Cell Name: Pump 2

Morevoltages
30
Maximum fuse/contactor • Maximum fuse/contactor
Tap Picture to Reset

auxiliary control voltages



distribution.
• Mid-mount type The system downtime. capability and more
real-time data•Flexibility in arc control power transformer
20
combination: 200A combination: 400A
provides an extensive range is On-board
required tocontactor
Average Current (A) 22.0

circuit breakers Vacuum contactors Vacuum contactors ratingsEarthing switch


10
witchgear. Utilizing • Full range of accessories
• 3.6/7
• Breaking .2/12kV
capacity with fuse • Breaking capacity with develop
fuse
Average Voltage (V) 6000.0

vices used within


• Optional remote racking up to 50kA
of protection, monitoring
up to 50kA
and channel
algorithms that
option solutions Average Power (kW) 229.0
0
15:44:04 15:45:04 15:46:04

-VACi Type W-SLC


capability
Type• W-SLN
Contactor
controlswitching
functions,upeither
to 400A
locally monitor the system’s health
Thermal Capacity Used (%) 0.0
02-02-17 02-02-17 02-02-17

• Wide range of AC or DC
or voltages • Wide range of AC or DC
via afuse/contactor
network. It can be and predict •• Arc
Optional
problems. channels remotewith
provided
Rather racking capability Alarm Text Alarm On Alarm Off

• Electrical or mechanical key • Maximum


auxiliary combination: 200A Current Phase A (A) 20.0 Average Current High Li... 15:44:41 02-02-17 15:45:43 02-02-17

ed in accordance • Tested in accordance with • Tested incontrol


accordance
used in a with auxiliary
stand-alone
control voltages
• Type tested in accordance
mode or than overloading

integrated arc absorber
the system’s
Electrical or mechanical key interlocking options
Current Phase B (A) 22.0

interlocking options technology for venting gases


62271-100 IEC 62271-106 • IEC •62271-106
On-board Breaking
contactor capacity
control
integrated intowith fuse
• with
On-board
other up to 50kA
IEC62271-102
contactor
systems control
network with more inside data,
the switch room,
Current Phase C (C)

Voltage VAB (V)


24.0

6000.0

V up to 4000A • Mid-mount type


power transformer
• Roll-on floor type
option power transformer option
• 12/17.5kV up to 50kA/3sec. without the need to exhaust Voltage VBC (V) 6000.0

such as DCS and SCADA. The the SmartPX system stores


to the outside
Voltage VCA (V) 6000.0

c. • Optional remote racking • 130kA


Suitablepeak
for integration in
• 3.6/7.2/12kV ratings Vacuum
• 3.6/7.2kV
capability
ratingscontactors
SmartPX system- Type
is W-SLN
capable
400mm wide Slimline
and analyzes local data and
• Different heights of arc
Ground Fault Current (A)

Current Unbalance (%)


0.0

0.0
Alarms
o 2500A • 24kV up to 31.5kA/3sec.
sends only relevant
of storing and analyzing data Widealarms
Ack All History
Enabled
• Contactor switching
• Tested
• Contactor switching
in accordance withpeak
IEC
contactor 62271-106
panel • channels range of AC or DC auxiliary control
Voltage Unbalance (%) 0.0
are available
sec. • Electrical 80kA
up to 400A up to 400Aor mechanical
to streamlinekey
corrective and and warnings •toFlexible
the upstream Analysis and

ge of AC or DC interlocking
• Roll-on options • Electrical or mechanical key
floor type maintenance
• Optional remote operating voltages solutions to connect Control
Arc channel with integral arc absorber. Lo
• Maximum fuse/contactor preventative
• Maximum fuse/contactor of
interlocking options system, through thepush
arc channel to the wall
ology
control voltages
combination: 200A
Flexibility combination:
in •arc3.6/7400A
capability
.2kV ratingselectrical equipment
connected notifications •and On-board
flange contactor
(via sides,
emails via front or rearcontrol power transformer
SmartPX logs and trends the total power, current
e of accessories of the installation), in case
• Breaking capacity with fuse • Breaking capacityby learningfuse load profiles
withswitching over LAN, WLAN or ofSMS.option used by the power distribution system and stores
remote racking up to 50kA channel solutions • Contactor
up to 50kA time and using that data to
up to 400A venting gases outside the
• switch
Suitableroom
for integration SmartPX softwarewide
in 400mm monitors the electrical parame
Slimline
• Wide range of AC or DC • Wide • range
Maximum
ofpredict
AC or DCfuse/contactor
dangerous trends. combination: 400A system and detects patterns that may lead to fut
• Arc channels provided with contactor panel
or mechanical key auxiliary control voltages auxiliary control voltages
• Breaking capacity with fuse up to 50kA
actors
ng options Vacuum contactors
• On-board contactor control
technology for
Earthing
integrated arc absorber
On-board
• venting
switch
contactor control
gases • Electrical or mechanical key interlocking options
Type W-SLN
power inside the switch
transformer option room,
power transformer option
without the need to exhaust
• Optional remote racking • Earthing
to the outside Suitable switch
for integration in
capability 400mm wide Slimline
ance with • Tested in accordance with heights
• Different •of•Type
arc Type
contactor tested
tested
panel in accordance with IEC62271-102
in accordance •Space
24kV saving
up to 31.5kA/3sec. 80kA peak
• Electrical or mechanical key
IECinterlocking
62271-106 options •with
channels are available
• Electrical orIEC62271-102
12/17 .5kV up key
mechanical to 50kA/3sec. 130kA peak •solutions
Optional remote operating capability
Roll-on floor type Flexible solutions to connect
interlocking options

• • 12/17.5kV up channel
Arc to 50kA/3sec.
with integral arc absorber. Low height arc channels.
the arc channel to the wall POWER XPERT UX High-voltage switchge
ngs
130kA peak
• 3.6/7.2kV ratings flange (via sides, front or rear Flexibility
Flexibility in arcin arc • Current and voltage
transformers located in
m contactors Earthing switch of the installation), in case
• 24kV up to 31.5kA/3sec. channel channel solutions
solutions the bus riser
hing Flexibility
• Contactor
10 in arc channel
switching of solutions
venting gases outside the
W-SLN POWER XPERT UX High-voltage switchgear system
switch room 80kA peak • Voltage transformer and
• upArctochannels
400A • Arc•channels
Arc channels
provided
provided
with with
provided with • Flexible solutions tointegrated
connect
integrated arc absorber the arc
arc absorber integral fault-making busbar
• Optional remote operating technology technology
for venting
for venting
gasesgases earthing combined in the
contactor
n accordance with integrated
• Maximum arc absorber technology
fuse/contactor
• Type tested in accordance channel to the wall flange (via sides, bus coupler
capability insideinside
the switch
the switch
room,room,
0A
71-106 combination:
forwith 400A inside the switch
IEC62271-102
venting gases front or rear of the installation),
without
without
the need
the need toin
to exhaust
exhaust
• Top mounted voltage
to thetooutside
the outside
loor type
y with fuse • room, without

Breaking the
capacity need
with to exhaust
12/17.5kV up to 50kA/3sec.
fuse case of venting• Different
gases outside
• Different
heights
heights the
of arcof arc
transformers Top mounted voltage transformers. To
130kA peak bu
V ratings to to
up the50kA
outside switch room channels channels
are available
are available •Top with
Arc channel mounted integral
integral fault
arc absorber Low height arc channels.
• 24kV up to 31.5kA/3sec. • Flexible
• Flexible
solutions
solutions
to connect
to connect making busbar earthing
or switching •• Wide
Different heights of DC
arc channels are Arc channel
Arc channel
with integral
with integral
arc absorber.
arc absorber. Low height
Low height
arc channels.
arc channels.
C0Aor DC 80kA peak
range of AC or the arc
thechannel
arc channel
to thetowall
the wall
• Multiple sets of current
voltages
m fuse/contactor
available
auxiliary control
• Optional Space saving
remote voltages
operating
flangeflange
(via sides,
(via sides,
of theofinstallation),
front front
the installation),
or rear
in case
or rear
in case transformers per phase

solutions
capability of venting
of venting
gasesgases
outsideoutside
the the
• Fixed/removable and
ation: 400A
tor control • On-board contactor control switchswitch
room room
withdrawable voltage
ger optionwith fuse
capacity power transformer option transformers
kA POWER XPERT UX Space saving solutions • Current and voltage
High-voltage switchgear system • On board control power
racking • Suitable for integration
nge of AC or DC • Current and voltage
in
transformers located in
400mm wide Slimline the transformers
bus riser • Top mounted voltage transformers transformer (contactor)
control voltages
located in the bus riser
contactor panel • Voltage transformer and • Multiple sets of current transformers
dhanical
contactorkeycontrol integral
ransformer option •• Electrical
Voltage transformer andfault-making
integral busbar per phase
ons or mechanical earthingkey
combined in the SpaceSpace savingsaving
fault-makingoptions
interlocking busbar busearthing
coupler • Fixed/removable and withdrawable
for integration in solutions
solutions
wide Slimline combined in the• bus couplervoltage
Top mounted voltage transformers
or panel • Current
• Current
and voltage
and voltage Top mounted integral fault-making
• Top mounted integral transformers
fault making Top mounted voltage transformers. Top mounted integral fault-making
al or mechanical key • On board controltransformers
power transformer
transformers
located
located
in in busbar earthing.
busbar earthing.
the bus
theriser
bus riser
king options busbar earthing • Top mounted integral fault (contactor) Current and voltage transformers
making busbar earthing • Voltage
• Voltage
transformer
transformer
and and located in the
integral
integral
fault-making
fault-making
busbarbusbar Multiple sets of bus riser.
current transformers Cu
• Multiple sets of current earthing
earthing
combined
combined
in thein the per phase. in
transformers per phase bus coupler
bus coupler
• Top• mounted
Top mounted
voltage
voltage
Power Distribution product guide Nov 2017 17
• Fixed/removable and transformers
transformers Top mounted
Top mounted
voltage
voltage
transformers.
transformers. Top mounted
Top mounted
integral
integral
fault-making
fault-making
withdrawable voltage busbarbusbar
earthing.
earthing.
• Top• mounted
Top mounted
integral
integral
fault fault
transformers makingmaking
busbar
busbar
earthing
earthing
Medium Voltage Assemblies
Air Insulated Switchgear
Power Xpert UX 3.6kV - 24 kV
3.6 kV 7.2 kV 12 kV 17.5 kV
Electrical data
24 kV
Rated voltage kV 3.6 7.2 12 17.5 System 24
Impulse withstand voltage kV 40 60 75 95 125
Rated voltage
Power frequency withstand voltage kV 10 20 28 38 50 voltage
Impulse withstand
Rated frequency Hz 50/60 50/60 50/60 50/60 Power frequency
50/60withstand voltage
Busbar system Rated frequency
Rated normal current A 630 … 4000 630 … 4000 630 … 4000 Busbar system
630 … 4000 630 … 2500
Rated short time withstand current kA/s 25 … 50/3 25 … 50/3 25 … 50/3 Rated normal
25 … 50/3 20current
… 31.5/3
Rated short time withstand current
Rated peak withstand current kA 63 … 125 63 … 125 63 … 125 63 … 125 50 … 80
Rated peak withstand current
Circuit-breaker type W-VACi
Circuit-breaker type W-VACi
Rated nominal current A 630 … 4000 (FC) 630 … 2500
Rated nominal current
Rated breaking current kA 25 … 50/3 25 … 50/3 25 … 50/3 25 … 50/3 20 … 31.5/3
Rated breaking current
Rated short-circuit making current kA 63 … 125 63 … 125 63 … 125 63 … 125 50 … making
Rated short-circuit 80 current
Rated short time withstand current kA/s 25 … 50/3 25 … 50/3 25 … 50/3 25 … 50/3
Rated short 20
time… 31.5/3 current
withstand
Contactor type W-SLC Contactor type W-SLC
Rated nominal current A 400 400 400 - - current
Rated nominal
Rated current contactor / fuse combination A Max. 200 Max. 200 Max. 200 - - contactor / fuse combination
Rated current
Rated breaking current kA 50 (limited by the fuse) - Rated breaking
- current
Rated short time withstand current kA/s 6/1 6/1 6/1 - Rated short -time withstand current
Rated peak withstand current
Rated peak withstand current kA 15.6 15.6 15.6 - -
Earthing switch Earthing switch
Rated short-circuit making current
Rated short-circuit making current kA 63 … 130 63 … 130 63 … 130 63 … 130 50 … 80
Rated short time withstand current
Rated short time withstand current kA/s 25 …50/3 25 …50/3 25 …50/3 25 …50/3 20 … 31.5/3
Contactor type W-SLN (Slimline)
Contactor type W-SLN (Slimline)
Rated nominal current
Rated nominal current A 400 400 400 - - contactor / fuse combination
Rated current
Rated current contactor / fuse combination A Max. 400 (double fuse) - - current
Rated breaking
Rated breaking current kA 50 (limited by the fuse) - Rated short -time withstand current
Rated short time withstand current kA/s 6/1 6/1 6/1 - Rated peak -withstand current
Rated peak withstand current kA 15.6 15.6 15.6 - Earthing switch
-
Earthing switch Rated short-circuit making current kA 15.6 15.6 15.6 - Rated short-circuit
- making current
Rated short time withstand current
Rated short time withstand current kA/s 6/1 6/1 6/1 - -
Internal arc Internal arc
Internal arc classification AFLR
Internal arc classification AFLR kA/s Up to 50/1 Up to 50/1 Up to 50/1 Up to 50/1 Up to 31.5/1
Enclosure data
Enclosure data
Degree of protection
Degree of protection IP4X (IP41, IP42 or IP44 as an option)
Loss of service continuity category
Loss of service continuity category LSC2B Partition class
Partition class PM Standard color
Standard color RAL7035

Main dimensions Ma
System Width A (mm) Height B (mm) Height C1) (mm) Depth D (mm) Syste

3.6/7.2kV 3.6/7.2
Slimline contactor 400 2200 2760 1770 Slimlin
3.6/7.2/12kV 3.6/7.2
Mid-mount contactor panel 600 2200 2760 1320 Mid-m
3.6/7.2/12/17.5kV 3.6/7.2
630A - 25kA 600 2200 2760 1320 630A -
1250A - 25/31.5kA 600 2200 2760 1320 1250A
2000A - 25/31.5kA 800 2200 2760 1320 2000A
2500A
2500A - 25/31.5kA 800 2200 2760 1320
1250A
B
C

1250A - 40/50kA 800 2200 2760 1500


2000A
2000A - 40/50kA 800 2200 2760 1500 3150A
3150A - 25/31.5/40/50kA 1000 2200 2760 1500
24kV
24kV 1250A
1250A - 20/25/31.5kA 800 2320 2880 1570 2000A
2000A - 20/25/31.5kA 1000 2320 2880 1570 2500A
2500A - 20/25/31.5kA 1000 2320 2880 1570 1) Tota
For t

18 Power Distribution product guide Nov 2017


Medium Voltage Assemblies
Air Insulated Switchgear
Power Xpert UX 36kV
Eaton’s Power Xpert UX™ 36 IEC high-voltage switchgear is
designed for your most critical applications.
At Eaton, our focus is on developing the latest in power
distribution, control and protection technologies that optimize
the performance of your installation, while keeping your
personnel and equipment safe from harm. With over 90 years
of experience in high-voltage switching and vacuum technology,
our customers can depend on our expertise to provide the right
equipment for the most demanding of applications.
Designed to be fully scalable, the Power Xpert UX 36 enables
you to create a fit-for-purpose high-voltage switchgear system.
With ratings up to 2500A and 31.5kA, this system provides
reliable power distribution for applications.
The Power Xpert UX 36 is free of SF6, which eliminates
recording and re-filling, SF6 inspections at end-of-life and
disposal costs, reducing your total cost of ownership.

The integral arc-chamber


Evacuates the gases associated with an internal arc. Optional standard parts are available to
extend the arc chamber; flanges and grilles are available to exhaust the gases outside the
switchgear room. Internal Arc Classification of AFLR – 31.5kA – 1 sec.

The low voltage compartment


Segregated with earthed metal partitions with ample
space for control and protection devices. A fully
segregated horizontal wireway connects all the low-voltage
compartments.

The switching device compartment


Fully segregated by earthed metal partitions, with its
own pressure relief channel into the arc chamber,
the compartment provides all the safety interlocking
mechanisms required for safe and reliable operation of the
vacuum circuit breaker.

The busbar compartment


Busbars are totally enclosed in their own earthed metal compartment, which vents into the arc chamber.
Fully insulated along their entire length, the busbars are type tested for ratings up to 2500, 31.5kA for 3
seconds. Earthed metal partitions segregate switchgear sections.

The cable compartment


Ample cable termination provision is provided for up to 6 single core cables per phase to enter the
bottom of the switchgear and are terminated with compression lugs onto copper tails provided in the
bottom of each panel.

Safety and reliability through accessibility of compartments


Ensuring safety of personnel whether in operation or maintenance is essential and is further enhanced in
the Power Xpert UX 36 by providing a level of accessibility that limits unauthorized access.
IEC62271-200 defines the accessibility classification for each of the power sections in the switchgear.
The system has the following accessibility definitions:
• • Busbar: tool-based/non-accessible
• • Circuit breaker: interlocked controlled
• • Cable: tool-based or option for interlocked controlled

Vacuum switching Vacuum circuit breaker


With over 90 years of experience in the field, Eaton is a world By designing a simple, modular, efficient and low energy spring-
leader in vacuum switching technology. charged mechanism with the fewest possible number of parts
for the vacuum circuit breaker, normal maintenance requirements
SF6-free design are dramatically reduced. The 360W-VACi breaker is virtually
The combination of vacuum interrupters for switching, cast- maintenance-free.
resin technology, and clean air as the insulation medium, makes
the system environmentally friendly and helps maintain quality LSC2B-PM construction
throughout the product lifecycle. Because there is no SF6 The construction of the system ensures maximum uptime as
gas, plant maintenance and operation is simplified and costly personnel can safely perform maintenance on the cable compartment
administration, gas management and end-of-life disposal costs with live busbars or the switching device compartment with live
are minimized. busbars and cables.

Power Distribution product guide Nov 2017 19


Medium Voltage Assemblies
Air Insulated Switchgear
Power Xpert UX 36kV
The flexibility to design and configure the Power Xpert UX 36 to your specific needs
helps to ensure it is built for your applications.
Standard configurations for power distribution and control are readily available within
the Power Xpert UX 36 product range. Standard VCB ratings of 1250A, 2500A at
36kV meet the requirements of virtually all applications.

Special configurations
In addition to VCB panels, the Power Xpert UX 36 offers a range of panels with
specialized configurations, increasing the flexibility of the switchgear. One of these
configurations is the equipped riser panel, which allows for a busbar-connected
voltage transformer (VT) and control transformers (CT) to be mounted in the riser.
This can reduce the overall length of the lineup reducing the cost of the building.

Primary components
Eaton power control and protection components are among the best in the world. The Power Xpert UX 36 is designed specifically
around these components and provides a best-in-class power distribution system. Fully third-party type tested to meet even the
most arduous of applications.

Vacuum circuit breaker type 360W-VACi Truck-mounted fused voltage transformer Earthing switch
• Type tested in accordance with • Fused transformer truck arranged to • Tested in accordance with IEC 62271-102
IEC 62271-100 mount into either an equipped riser or an • Fully type tested within Power Xpert UX
• 36kV Ratings auxiliary (metering) panel 36 switchgear with ratings of 31.5kA-3s
• 1250A • Arranged for mounting 3 single-phase • 2,000 mechanical operations M1 class
• 2500A cast resin transformers with integral • Optional remote operation
primary fuse protection
• With Isc ratings of 31.5kA-3s
• Wide range of ratings and classes of VT
• Full range of field mountable accessories, are available
shunt trip, UVR, motorized mechanism,
auxiliary contacts

Secondary components
Safe and reliable operation of any switchgear relies heavily on a clear, uncomplicated control and protection system. Clarity of operation is
key to the design of the control and protection systems in the Power Xpert UX 36.

Clear, uncluttered low voltage compartment


• Clear monitoring and simple operation provide added safety and security to the installation
• Ample space for protection relays
• Space for circuit metering
• VCB local Open/Close switch
• Contactor On/Off pushbutton control
• LED indicators provide clear VCB or contactor position and Open/Close status
• Earth switch Open/Close status LED indicator

Voltage detection system (VDS)


• In accordance with IEC 61243-5, voltage detection systems shown here provide additional
operator and maintenance personnel safety
• Capacitive sensors in the cable compartment provide the power to the monitor mounted on the
door of the low voltage compartment door
• Voltage detection systems provide visual indication that voltage is present at the monitored
location, whether that is the cable or a busbar location
Other manufacturer’s systems can be integrated within the Power Xpert UX 36.

20 Power Distribution product guide Nov 2017


Medium Voltage Assemblies
Air Insulated Switchgear
Power Xpert UX 36kV 36 kV
Rated voltage kV 36
Lightning impulse withstand voltage kV 170
Power frequency withstand voltage kV 70
Rated frequency Hz 50/60
Internal arc class AFLR
Loss of service continuity category LSC2B
Partition class PM
Earthing circuit kA - 3 s 31.5
Accessibility of compartments
Circuit breaker compartment Interlock-controlled
Busbar compartment Tool-based/non-accessible
Cable compartment Tool-based or interlock-controlled
External degree of protection IP4X (IP41 as an option)
Internal degree of protection IP2X
Installation Indoor
Temperature classification C
o
-5 to +40
Relative humidity (max) % 95
Busbar system
Rated normal current A 1250, 2500
Rated short-time withstand current kA - 3 s 31.5
Rated peak withstand current kA 82
Circuit breaker ratings
Rated normal current A 1250, 2500
Rated short-circuit breaking current kA 31.5
Rated short-circuit making current kA 82
Rated short-time withstand current kA - 3 s 31.5
Class E2, M2, C2
Breaking number of short-circuit current 30
Auxiliary voltage V AC110/220 - DC110/220
Mechanism
Rated operating sequence A O - 0.3s - CO - 15s - CO
Class M2
Number of operations >10,000
Number of operations interrupter >10,000

Main dimensions

Panel width (A) 1200mm


36 kV
Max. rating 1250A, 2500A
Depth 2600
Height (A) 2400
Height including arc chamber (B) 2950

Power Distribution product guide Nov 2017 21


Medium Voltage Assemblies
Gas Insulated Switchgear
RVAC Ring Main Unit
RVAC RMUs are fully sealed and insulated switchgears developed by ECPS
exclusively for the cable system, and have been extensively applied in the urban grid
system across the country since introduction in 1995 with their excellent operating
performance.
RVAC RMU’s are characterized by the following:
• Insulation using SF6 gas
• Three position SF6 Switch as the breaking device in the load switch unit to break
rated current
• Vacuum arc-extinguishing chamber as the breaking device in the circuit breaker unit
to break short-circuit current.
• Based on the design principles of all insulation and omniseal, all primary parts of
a RVAC RMU are fully enclosed in the SS main case, free from condensation and
foreign materials. The main case has the protection grade of IP67 and is equipped
with Cooper touchable waterproof cable joints to protect against occasional floods
in flood-prone areas
Currently, the development of a grid system is focused on application of ecological
resources, requiring a medium-voltage switchgear which is characterised by energy
conservation, low operating cost, reliable performance and flexible configuration.
Featuring long service life, compact structure and re-usability, the RVAC RMUs have
become a role model economically and ecologically.
With rapid development of urbanization, the improvement and perfection of buried
cable system has loomed large in terms of equipment and many other aspects. Ring
main units (RMU), as the main equipment for protection and sectional isolation of the
buried cable system, have been widely used in the urban grid system with their safe
and reliable performance, compact and pleasant appearance, and outstanding cost
performance.
As the leader in the distribution switch gear field, Eaton Cooper Power Systems
(ECPS) started design and production of high-quality distribution switchgears as early
as 1942, with over 2,000,000 switchgears in proper operation throughout the world
up to now.

Vacuum technology features


• As the leader in the vacuum technology field, Eaton carries forward the innovation of
vacuum Westinghouse and HOLEC arc-extinguishing chambers
• Eaton is the first enterprise to develop proprietary technologies for
copper-chromium alloy contactor and inner shield
• The arc-extinguishing chamber developed by Eaton for contactor has a long service life of
2,500,000 operations
• Almost all of global high-end electrical equipment manufacturers are our purchasers of our
arc-extinguishing chambers.

SF6 gas insulated system


• All primary HV components are enclosed in SF6 gas tank, free from ambient conditions and
maintenance and ensuring full insulation
• The main case has the protection grade of IP67 and is equipped with Cooper prefab
shielded touchable cable accessories, allowing for long-term operation underwater or at
other extreme conditions.
• Advanced gas shielded welding and the pressure seal system with the leak rate of ≤1‰/a
is available, ensuring a service life of 30 years

Load break switch


The load switch is a three-position switch for opening, closing and grounding.
The movable blade at the opening position provides enough insulation distance. Opening and
closing of master switch and grounding switch can be available respectively with one operating
handle, and master switch and grounding switch
are mechanically interlocked.
• Arch-extinguishing with deionised metal grating for load switch ensures excellent breaking
performance;
• The operating mechanism controls moving speed of contactor of the load switch so that
the switch on and off speed of the load switch will not vary with operators.

22 Power Distribution product guide Nov 2017


Medium Voltage Assemblies
Gas Insulated Switchgear
RVAC Ring Main Unit
Rated voltage kV 12 24
Power frequency withstand voltage (1min)
Phase to phase/Phase to earth kV 42 50
Between isolating distance 48 60
Lightning impulse withstand voltage (BIL)
Phase to phase/Phase to earth kV 75 125
Between isolating distance 85 145
Rated frequency Hz 50 50
Internal arc classification (IAC) kA-s AFLR 20-1 AFLR 20-1
Degree of protection in service IP3X IP3X
Degree of protection with doors/covers open IP2X IP2X
Busbar system
Rated normal current A 630 630
Rated short-time withstand current kA-s 20-4 20-4
Rated peak withstand current kA 50 50
Load break switches panel
Rated normal current A 630 630
Rated short-circuit making current kA 50 50
Rated short-time withstand current kA-s 20-Apr 20-Mar
Mechanical endurance class (Lood break switch) M1 5000 M1 5000
Mechanical endurance class (Earthing switch) M1 2000 M1 3000
Electrical endurance class
E3 E3
(active load breaking capacity 630A)
Circuit-breakers panel
Rated normal current A 630 630
Rated breaking current kA 20 20
Rated short-circuit making current kA 50 50
Rated capacitive switching current class C2 C2
Mechanical endurance class (Circuit-breakers) M2 10000 x M1 3000
Mechanical endurance class (Earthing switch) M1 2000 M1 3000
Electrical endurance class E2 E2
Rated short-time withstand current kA-s 20-4 20-4
Mechanism type O - 0.3s - CO - 180s - CO O - 0.3s - CO - 180s - CO
Switch-fuse combination panel
Normal current of load-break switch A 630 630
Normal current with fuses A 125 125
Rated breaking current kA 31.5 31.5
Rated short-circuit making current kA 80 80
Rated transfer current A 1750 900
For others, please contact local Eaton sales representative.

Main dimensions
Type V RVAC complies with the following international standards
Depth: 12 kV 800mm
24 kV 870mm Common specifications for high-voltage
IEC62271-1
Type K Type T switchgear and controlgear
High-voltage switches for rated voltages
IEC62271-103
above 1kV up to and including 52 kV
High-voltage alternating current
IEC62271-102
disconnectors and earthing switches
A.C. metal-enclosed switchgear and
IEC62271-200 controlgear for rated voltages above 1kV
and up to including 52kV
High-voltage alternating-current circuit
IEC62271-100
breakers
High-voltage alternating current switch-
IEC62271-105 fuse combinations for rated voltage above
1kV up to and including 52kV

Power Distribution product guide Nov 2017 23


Medium Voltage Assemblies
Components
W-VACi medium voltage vacuum circuit breakers
Eatons W-VACi compact MV vacuum circuit breakers with IEC ratings of 12 kV, 17.5 kV and 24 kV
are part of Eaton’s comprehensive global product portfolio. It serves both 50 Hz and 60 Hz end-
user segments of the electrical industry such as industrial, commercial, utility, mining, marine
and off-shore. The W-VACi circuit breakers are complemented by a full line of accessories and
compartment kits for panel builders. In addition, they fit in Eaton’s new IEC panel design, Power
Xpert® UX. UX is available in 600 mm, 800 mm and 1000 mm configurations.
• Fixed and withdrawable versions available • User friendly operation with easy access
• Eno SF6 - gas and minimal inspection
• Conformance to the latest IEC standards - • Compact and cost effective
IEC 62271-100 and IEC 62271-1 • Flexible with a full line of accessories and
• Numerous safety features for maximum OEM components
protection

Universal mechanism assembly (UMA)


Designed with reliability and long product life, the W-VACi circuit breaker utilizes a simple spring
charged, stored energy mechanism. With its simple and proven design, the universal mechanism
assembly has a life of up to 20,000 mechanical operations and does not require inspection up to
10,000 operating cycles. It includes special plating on metal components to increase mechanical life
and prevent corrosion.

Encapsulated pole unit (EPU)


The W-VACi IEC vacuum circuit breakers use Eaton vacuum interrupters that are embedded in
epoxy resin. Encapsulating the vacuum interrupter in epoxy resin results in circuit breaker pole units
that are extremely durable. Further, it protects the vacuum interrupter from mechanical impact and
climatic conditions such as moisture, humidity and dust.

Vacuum interrupter (VI)


At the heart of the W-VACi IEC circuit breaker portfolio is Eaton’s proven vacuum interruption
technology and eighty-year expertise in this field. The vacuum interrupter is where current making
and breaking occurs. It houses Eaton-designed high-performance copperchrome contacts, which
provide superior performance characteristics. The vacuum in the arc chamber protects the copper
contacts from adverse effects such as contamination and corrosion.

Description
Circuit breaker designation 12 kV 17.5 kV 24 kV
Rated voltage Ur kV 12 17.5 24
Rated frequency fr Hz 50 / 60 50 / 60 50 / 60
Rated normal current Ir A 630 / 800 / 1250 / 1600 / 2000 / 2500 / 3150 / 4000  800 / 1250 / 1600 / 2000 / 2500
Rated short-time withstand
Ik kA rms 25 / 26.3 / 31.5 / 40 / 50 25 / 31.5 / 40 / 50 20 / 25
current
Rated duration of short circuit tk s 3 3 3
Rated supply voltage V 24 - 48 - 60 - 110 - 125 - 220 - 250 VDC / 120 - 220 - 230 VAC
Pole-center distance mm 150 210 275 150 210 275 210 275
Upper-to-lower terminal spacing mm 205 / 275 310 310 205 / 275 275 310 310 310
 4000 A rating with forced cooling

Main dimensions W-VACi 24kV family


W-VACi 12kV and 17.5kV family Pole space 210 mm Pole space 275 mm
Pole space 150 mm Pole space 210 mm Pole space 275 mm

FRONT FRONT

SIDE SIDE

PLAN PLAN

24 Power Distribution product guide Nov 2017


time
• Leading vacuum technology
SL range 160-400 A
• Auxiliary contact and mechanical latch are provided.Acc
universal for any size of equipment.
• Fully meet global standards
• For special orders, configuration can be made, based
• Pass third-party
Medium certification
customers'Voltage
detailed
Mounting such as KEMA,CSA
Assemblies
cutout requirement, and
with factory pre-as
and all mounting accessories included.
• Long service life: over 300,000 electrical operations,
• Best quality: all contactors are manufactured and ass
Components 2,500,000 mechanical operations
ISO certified factories with leading technology develo
• Flexible level.
installation: standard control panel or pedest
SL medium voltage vacuum contactors
The “SL” family of medium voltage vacuum contactors is designed and engineered
mounting. Contactors can be mounted horizontally o
Field-adjustable options include coil voltage, AC/DC
specifically for the OEM, combining the highest ratings available in a cost-saving,• reduced-
size package that’s lighter and easier to install. “SL” Contactors are ideal for full andtime
reduced
voltage starting of squirrel-cage induction, wound-rotor, and synchronous motors. Other
applications include power and capacitor switching. They’re especially recommended • Auxiliary
for contact and mechanical latch are provided.Ac
heavy duty applications and harsh environments found in many industries includinguniversalmining, for any size of equipment.
Control terminal strip

pulp and paper, HVAC, petrochemical, and automotive.


• For special orders, configuration Auxiliary contact can be made, based
No adjustment or replacement of vacuum interrupters is required to achieve 300,000
electrical operations. With fewer moving parts the contactor enhances longevity and customers'
reliability detailed requirement,
Pedestal mounting device
with factory “SL” Contacto
“ pre-as
while decreasing maintenance, resulting in a mechanical life of 2.5 million operations. and all mounting accessories included.
• Best quality: all contactors are manufactured and ass
Field-Adjustable Settings
ISO certified factories with leading Coil control board technology deve
(at control end terminal strip) Ele
Field adjustable coil voltages & drop-out times enable the installer to adjust to specific
requirements and make last minute changes to standard units. level.
Auxiliary Contact Kits provide for up to six extra auxiliary contacts. Table 1—Control voltage setup
Control terminal strip
Switch No.
Mechanical Latch Kits available in many coil voltages with a wide range of AC and DC selections. Voltage
SW1 SW2 S
Mechanical Interlock Kit prevents unintentional energizing.
100-110Vac/dc OFF OFF O
Easy Installation
115-120 Vac/dc ON OFF O
The SL medium voltage vacuum contactor can be mounted in horizontal or vertical positions when
125 Vac/dc OFF OFF O
space is an issue. The built-in mounting tabs provide for pedestal mounts or panel mounting also.
200-220 Vac/dc OFF ON O
3 different altitude versions Design and Test Standards 230-250 Vac/dc ON ON O
 ow altitude rating of -3500 to -1001 meters.
L IEC #60470
/PUFfactory default value is 120/60VAC
Standard altitude rating of -1000 to +2000 meters. CSA T.I.L D-21, File
High altitude rating of +2001 to +4000 meters.
“SL”
“ Contact
#LR28548ANSI/NEMA ICS3, Part 2 Control terminal strip Mounting cutout
Control terminal strip

Technical specifications
Interrupting Induction Synchronous motor Transformer Capacitor switching
Contactor size Voltage, V
rating, kA motor, kW (1.0 PF), kW kVA * kVAR/A
2200 – 2500V 450 600 600 480/120
3000 – 3600V 675 750 800
① 640/120
The above ratings can be different, for 800A equipment. Please
160A 4.5 11 'JYFE5ZQF4-.FEJVN7PMUBHF$POUBDUPS—Nov 2011
3800 – 4800V 900 1050 1000 960/120
Table 1—Control voltage setup
6000 – 6900V 1350 1650 1600 1320/120
2200 – 2500V 600 750 750
Switch 600/150
No.
Voltage
200A
3000 – 3600V
4.5
825 950 1000 SW1800/150 SW2 S
3800 – 4800V 1100 1300 1250 1200/150
6000 – 6900V 1675 2050
100-110Vac/dc2000
OFF 1650/150 OFF O
2200 – 2500V 1100 1300 115-120 Vac/dc 1200 ON 1000/270 OFF O
3000 – 3600V 1500 1850 1600 1475/270
360A
3800 – 4800V
4.5
1850 2250
125 Vac/dc 2500 OFF 2150/270 OFF O
6000 – 6900V 3000 3750 200-220 Vac/dc 3200 OFF 2950/270 ON O
2200 – 2500V 1300 1500 1500 1200/295
3000 – 3600V 1675 1850
230-250 Vac/dc
2000
ON 1650/295 ON O
400A 8.5
3800 – 4800V 2250 2600 /PUFfactory default
2500 value is 120/60VAC
2400/295
6000 – 6900V 3350 4100 4000 3300/295
2200 – 2500V 2250 2600 2500 2400/550
3000 – 3600V 3000 3750 3500 3200/550
800A 13.2
3800 – 4800V 3750 4500 4500 4000/550
6000 – 6900V 6000 7500 6000 4800/550
* Ratings not applicable for back-to-back switching. Consult factory.

eight
g pound ① The above ratings can be different, for 800A equipment. Pleas
Main dimensions

.4 47 Current Mounting Length Width Height Weight


size (A) (B) (C) kg
1.4 47 160 Control panelor pedestal 406 387 221 21.4
200 Control panelor pedestal 406 387 221 21.4
1.4 47
360 Control panelor pedestal 406 387 221 21.4
2.2 49 400 Control panelor pedestal 406 387 221 22.2
800 Control panelor pedestal 378 430 466 43.2
3.2 95

Power Distribution product guide Nov 2017 25


Medium Voltage Assemblies
Components
Medium voltage generator circuit breakers
Eaton's Cutler-Hammer VCP-WG line of Vacuum Generator
breakers were designed and tested to the specific ANSI / IEEE
C.37.013 standard. These breakers are designed to handle the
rigorous and unique characteristics needed when applied in close
proximity to a Generator and Transformer configuration.

Ratings of our VCP-WG line include 5 and 15kV, 50, 63 and 75kA,
and up to 4000A continuous current with natural convection
cooling. Higher current ratings can be achieved with the use of
fan cooling packages.
Eaton has dedicated years of research, design, enhancement and
testing to create Cutler-Hammer VCP-WG Circuit Breakers that
meet, and even exceed, these rigorous service duty requirements
of generator circuit application defined by IEEE. VCP-W vacuum
circuit breakers incorporate many design features which have
been field proven with over 50 years of vacuum interrupter design
and manufacturing experience…coupled with over 75 years of
power circuit breaker design and manufacturing experience.

Eaton’s VCP-WG generator circuit breakers meet and even exceed service duty requirements set forth
by IEEE for generator circuit applications, including:
• Generator circuit configuration • Generator-source short-circuit faults
• High continuous current levels • Unique voltage conditions
• Unique fault current conditions • Very fast RRRV
• Transformer-source short-circuit faults • Out-of-phase switching

Fault Current Breaking capacity


Eaton’s VCP-WG Generator Circuit Breakers have a distinct feature to perform under out-of-phase con-
ditions when the generator and power system voltages are not in sync. The voltages across the open
contacts can be as high as twice the rated line-to-ground voltage of the system. The VCP-WG complies
with IEEE standard requirement and passes the test that the generator circuit breaker can switch under
specified out-of-phase conditions.

Versatility in Application
Eaton's Generator Vacuum Circuit Breakers are available in drawout (VCP-WG) or fixed (VCP-WRG)
configurations to provide superior performance and versatility. Many industrial and commercial power
systems now include small generators as a local source of power. New applications are arising as a
result of the de-regulation of the utility industry, and the construction of smaller packaged power plants.
Typical applications include:
• Small and mid-sized hydro power generator • Combined cycle/combustion turbines
• Electrical generators • Paper, Chemical and manufacture companies
• Power plant with backup power plant

Technical specifications
Description 50VCP-WG50 50VCP-WG63 50VCP-WG75 150VCP-WG50 150VCP-WG63 150VCP-WG75
Rated voltage kV 4.76 4.76 4.76 15 15 15
Power frequency withstand kV-1min 19 19 19 36 36 36
voltage
Impulse kVp 60 60 60 95 95 95
withstand voltage
1200, 2000, 1200, 2000, 1200, 2000, 1200, 2000, 1200, 2000, 1200, 2000,
Rated current A 3000 3000 3000, 4000 3000 3000 3000, 4000
Rated short circuit breaking kA 50 63 75 50 63 75
current
Ratings referenced to 60Hz.

Description
Rated voltage kV 5 15 27 38
Impulse withstand voltage kVp 60 95 125 170
1200, 2000, 1200, 2000, 1200, 2000, 3000
Main bus rating A 1200, 2000
3000, 4000 3000, 4000 Depending on kA Rating
1200, 1600, 2500 A
Circuit breaker rating A 1200, 2000, 3000 1200, 2000, 3000 1200, 2000
Depending on kA Rating
Short circuit interrupting capacity kA 29, 41, 63 18, 28, 37, 63 16, 22, 25, 40 16, 21, 25, 32, 40
Ratings referenced to 60Hz.

26 Power Distribution product guide Nov 2017