1 Scope

This specification provided by Hengtong Submarine Power Cable Co., Ltd covers the
application, construction, dimensions, performance and transportation drum of HV power
cable. The design, quotation, manufacture of cables is based on this specification as the
technical part of contract. Matters not mentioned in this specification shall be negotiated by
customer and supplier.

2 Application

Max. continuous operation temperature 90℃


Max. temperature at short circuit(≤5s) 250℃
Lowest recommended temperature during installation 0℃

3 Referent Standards

Document Document title

ISO 9001 Quality Management Systems-Requirements

OHSAS 18001 Occupational health and safety management system

ISO 14001 Environment Management System

Power cables with extruded insulation and their accessories for rated
IEC 60840-2011 voltages above 30kV(Um=36kV) up to 150kV(Um=170kV)-Test
methods and requirements

Electric cables-Calculation of the current rating-


IEC 60287-1-1-2014 Part 1-1: Current rating equations (100% load factor) and calculation
of losses-General
Electric cables-Calculation of the current rating-
IEC 60287-2-1-2015
Part 2-1: Thermal resistance-Calculation of thermal resistance

Calculations of thermally permissible short circuit currents, taking


IEC 60949-2008
into account non-adiabatic heating effects.

Page 2 of 5
Add:No.8,Tongda Road,Changshu,suzhou
City,Jiangsu Province China
Tel: +86-512-52266867
Fax: +86-512-52266808
Email: info@hengtonggroup.com

4 Diagram of Cable Construction

Nominal Diameter
No. Cable structure Description
thickness (Approx.)
Stranded circular milliken aluminum conductor
1 Conductor / 50.0
(class 2)
Conductor Semi-conducting tape and extruded
2 2×0.2+1.5 53.8
screen semi-conducting thermosetting compound

3 Insulation XLPE 16.0 85.8

Insulation Extruded semi-conducting thermosetting


4 1.5 88.8
screen compound

5 Water blocking Semi-conducting water swelling tape 0.5 89.8

Plain copper wire bound with copper tape,


6 Metallic screen 62/Φ1.4+0.1 92.8
open counter-helix

7 Water blocking Semi-conducting water swelling tape 0.5 95.3

Metal foil
8 Al-PE laminate foil 0.3 96.2
laminate

9 Outer sheath PE(Flame retardant) coated with graphite 4.5 105.2

Cable mark:ENEL ARE4H1H5E-87/150 kV 1600mm2-HTGD 160809 GME000246853 2020-09 xxxM


Reference standard: compliant with Enel SP_Global standard GSCH010 cable HV
GS Type code: GSCH010/016
Distribution Company and Country: Enel Romania
Country Code:330011

Unit:mm

Page 3 of 5
Add:No.8,Tongda Road,Changshu,suzhou
City,Jiangsu Province China
Tel: +86-512-52266867
Fax: +86-512-52266808
Email: info@hengtonggroup.com

5 Technical Particulars

No. Description unit Parameters

Mechanical Performance:

1 Min. bending radius during installation mm 2104

2 Min. bending radius installed mm 1578

3 Max. allowable pulling tension of conductor kN 64

4 Total weight of completed cable ——Approx kg/m 11.3

Electrical Performance:

1 Rated voltage of cable kV 150

2 Impulse lightning voltage of cable kV 750

3 Maximum DC resistance of conductor at 20℃ Ohm/km 0.0186

4 Maximum AC resistance of conductor at 90℃ Ohm/km 0.0241

5 Conductor to screen capacitance μF/km 0.298

6 Nominal electrical stress at conductor screen kV/mm 6.9

7 Nominal electrical stress at insulation screen kV/mm 4.3

8 Charge current A/km 8.1

9 Inductance per unit length mH/km 0.337

10 Screen short circuit capacity for 1s kA 12.0

11 Conductor short circuit capacity for 1s kA 151.2

12 Continuous current rating of trefoil formation

12.1 In air (40℃) A 1562


Buried soil at depth of 1500mm with thermal resistivity
12.2 A 1000
of 1.5degC.m/w and soil temperature of 20℃.
12.3 In duct A 1070

Page 4 of 5
Add:No.8,Tongda Road,Changshu,suzhou
City,Jiangsu Province China
Tel: +86-512-52266867
Fax: +86-512-52266808
Email: info@hengtonggroup.com

6 Packing

The cable is wound on the non-returnable steel drum. Both ends of cable are securely
fastened to drum and reliable sealed. The required marking is printed with a
weather-proof material on the outsides of drum according to customer’s requirement.
Packing with fumigated wood battens and using steel strip to fix. For different length of
cable, we provide different packing methods. The transportation drum drawing is
described as below.

a.Draft drum drawing b. Packing drawing

Delivery length Drum Dimensions(mm) Cable net Gross weight


Cable type
(m) D d B weight (kg) per drum(kg)

150kV 1C1600mm2 1026 4000 2000 2200 11593 14093

Note: The drum size & cable weight as above is estimated and final size & weight shall be
confirmed before shipment.

Page 5 of 5
Add:No.8,Tongda Road,Changshu,suzhou
City,Jiangsu Province China
Tel: +86-512-52266867
Fax: +86-512-52266808
Email: info@hengtonggroup.com

REFERENCE NUMBER:HT20030305UG-GV1

REPLACE:HT20030305UG-GV0

Technical Specification
For High Voltage Power Cable

Al/XLPE/CWS/APL/PE
87/150(170)kV 1C1600mm2

Revision Date Description Designed by Approved by

Technical
GV1 21st/7/2020
Specification

For customer/client signature

Page 1 of 5

You might also like