Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

GSV4

Intruder alarm system Wiring manual

SAFETY WARNINGS
The device must be installed in a place with limited access.

The device must be connected to an AC power supply with Protective Earthing. Cable colours mean: Phase or Live line (L) - black
or brown cable, Neutral line (N) - blue cable, Protective Earth line (PE) - green cable with a vertical yellow dash. Double isolated
cables with minimum cross-sectional area of 0,75 mm2 for 230V power supply must be used.

The device uses two power supplies: main and back-up.


Main power supply: a power transformer with:
- primary winding: ~230V, 50 Hz;
- secondary winding: ~20V, 1.5A, 50Hz.
Back-up power supply: 12V, 7Ah/20HR capacity, rechargeable hermetically sealed Lead-Acid battery.

SECOLINK intruder alarm system GSV4 is compliant with EN 60950-1 safety requirements.
Power supplies described above must comply with the EN 60950-1 safety requirements.
All devices being connected with the intruder alarm system must comply with EN 60950-1 safety requirements.
Intruder alarm system is compliant with the essential requirements of Directives 1999/5/EC, 2004/108/EC, 2006/95/EC.
Intruder alarm system contains radio transceiver operating in GSM900/1800 bands.
Please read and follow these safety guidelines in order to maintain safety of operators and people around:
DO NOT use the intruder alarm system where it can interfere with other devices and cause any potential danger.
DO NOT use the intruder alarm system with medical devices.
DO NOT use the intruder alarm system in hazardous environment.
DO NOT expose the intruder alarm system to high humidity, chemical environment or mechanical impacts.
Additional automatic Two-Pole Circuit Breaker should be installed in an AC electric power circuit in order to protect against
over-current, short circuits and earthing faults.
The circuit breaker contact gap should be no less than 3mm, protective circuit breaker current must be in 0,5A - 2A range.
The circuit breaker should be placed close to the system's housing and should be easily accessed.
Power supply distribution board Power cable to the
alarm system Cabinet of the alarm system (device)

Automatic two-pole
circuit breaker
L N

Cable from power


distribution board
L N

Fig. 1. Automatic two-pole circuit breaker and power cable wiring diagram

The device installation and service should be performed by trained personnel with sufficient knowledge about the device and
general safety requirements for work with low voltage (up to 1000V) AC power lines. In the case of a device malfunction repair
works can be performed by qualified personnel only. If the system is malfunctioning, the end user should inform the qualified
personnel as soon as possible. User doesn't have right to repair the system.

Before performing any work of installation or service always disconnect the device from power supplies in sequence as described
below:
- cut off 230 V AC power line with the automatic Two-pole Circuit Breaker;
- disconnect 12V back-up battery by removing battery female plug from male socket BAT.
Two-pole Circuit-Beaker installation on flexible cables is forbidden.

Intruder alarm system comes with in-built LEDs. The LEDs blink when device is powered up.

General safety requirements:


- do not touch any part of the main power supply under voltage: transformer, a fuse block, connection wires;
- it is forbidden to perform any device installation or service work during lightning;
- use batteries according to manufacturer recommendations. The use of improper battery type may cause an explosion;
- battery replacement : be sure battery terminals are isolated, battery terminals short-wiring may cause an explosion.

It is not recommended to connect the device to a fully discharged battery. To avoid system malfunction use an adequate charger to
charge a new or discharged battery before connecting battery to the device.
Inoperative or expired batteries should be recycled according to the local rules or EU directives 2006/66/EC and 93/86/EEC.
Collection and separate utilization of waste battery is mandatory!

The connection to the mains supply must be made as per the local authorities rules and regulations.
The end of a stranded conductor shall not be consolidated by soft-soldering, insulated pins shall be used. Insulated pins shall be
connected in a manner that they are and with remain mechanically efficient.

Please act according to your local rules and do not dispose of your unusable alarm system or its components with other household
waste. This product utilization in EU is covered by European Directive 2002/96/EC.
1
GSV4
Intruder alarm system Wiring manual

Installation of GSV4

For correct operation GSV4 needs one GSV4 X1


Attention!
12V 7Ah rechargeable battery. The battery is
used as a back-up power supply in case of Do not cover ventilation
MODEM LED
temporal AC loss. This battery is also used holes of cabinet!
when alarm system consumes more power
than GSV4 can supply (~0,7 A). Excessive
consumption may happen when system
activates siren. Usually activation last only few SYSTEM LED

BAT

-PGM1
-PGM2
+BELL
minutes, so it does not discharge the battery.

+AUX
S1

COM

COM
20V
AC

Z1
Z2
Z3
Z4
Z5
Z6
USB
S2

Leave minimum 10 cm of free space between


Zones (see Wiring of zones) the ventilation hole and any other surface.
Heating of GSV4 can reduce maximum current
on +AUX and PGM outputs.
-PGM2
Black Calculated life expectancy for GSV4 at 40°C
12V batery -PGM1 ambient temperature: 9 years. Ambient
7Ah/20HR temperature over 40°C may reduce life
Red COM
+BELL expectancy.
Live Neutral Protective
wire wire Earth wire
L N PE
Fuse Mounting modules in cabinet
250mA Plastic stud GSV4 has to be fastened in cabinet (CAS8M) by using plastic
GSV4 studs. GSV4 mounting holes should correspond to cabinet's
board rear wall holes. Do not forget to fix the plastic studs in the rear
Automatic holes before fastening the cabinet on a wall.
Main Protective two-pole
Earthing terminal Cabinet
circuit AC power transformer:
breaker Primary winding: ~230V AC, 50Hz
Power supply Secondary winding: ~20V AC, 50Hz Template. Siren output programming
distribution board
In order to simplify security system programming, GSV4 is supplied to customers
Picture 2. Wiring of power supply and siren without battery with a pre-installed default template. It has 1 pre-programmed partition and 6 zones:
Zones:
Securing power cable to cabinet Z1 is preset to be used with an entry door magnetic contact;
Use cable ties to Z2 – with PIR motion detector in an entry/exit path;
Power cable to alarm system
secure power cable Z3, Z4, Z5 – for PIR detectors wiring;
to cabinet wall. Z6 – key-switch zone to arm/disarm and clear alarm.
PGM outputs:
Cabinet rear wall Cable ties +BELL is preset in the template to control a siren with no battery;
-PGM1 is preset to make activation (makes “minus”) of siren with back-up battery;
-PGM2 is preset to indicate system status (armed/disarmed).
Grounding cabinet and door
SECOLINK security system GSV4 may have different templates for different
countries. Check GSV4 sticker for a country’s prefix or pre-installed template code.
Protective Earth Example: GSV4_MY
wire PE
Note: in most templates +BELL is set for sirens with no
battery (picture 2). To use the siren with back-up battery
(picture 3) you need to change +BELL definition to Power
supply. Definition changing in software MASCAD is showed
on the right.
-PGM1
+BELL

Cabinet grounding
BAT

Use 3 - 15 kOhm resistor on siren


COM
20V

place
AC

Grounding terminals +BELL and -PGM if siren


place does not give enough voltage.
Main Protective
Earthing terminal 10kW

-PGM1 negative control


S
Maximum load ratings and electrical COM power supply
characteristics of GSV4 +BELL power supply

Maximum long term output current of GSV4: 0,7 A Picture 3. Installation of 3 wire type siren. Siren uses back-up battery
(I +AUX + I +BELL + I BAT. CHARGE 0,7 A )
Note: in case installation uses 2 wire siren with back-up
Maximum current out of +AUX: +0,25 A
battery (picture 4) installer needs to make changes as
Maximum current out of +BELL (without battery) +0,2 A showed on the right. This type sirens uses back-up battery to
Maximum current out of +BELL (with battery) +2,0 A sound alarm and makes alarm when power supply line
(+BELL) do not provide power from GSV4. Use Inversion of
Maximum current into -PGM1: -0,05 A
Status PGM attribute to program system for this operation.
Maximum current into -PGM2: -0,05 A
-PGM1
+BELL

Maximum battery charging current: +0,25 A


BAT

COM
20V
AC

GSV4 disconnects battery when it’s voltage less than: 9,5 V Note: check siren wiring manual from manufacturer.
Minimum AC voltage on AC 20V: ~16 V Switches or jumpers can be used to setup this type siren.
Maximum AC voltage on AC 20V: ~22 V
Note: higher than ~22 V voltage can damage GSV4. COM power supply
Maximum voltage on +AUX, +BELL outputs: +13,9 V +BELL positive control / power supply

Minimum voltage on +AUX, +BELL outputs: +12,0 V S


Maximum current of fast blowing fuse used in battery 3,15 A Picture 4. Installation of 2 wire type siren. Siren uses back-up battery
Maximum current of slow blowing fuse used in primary AC: 250 mA
Maximum AC power consumption 30 mA
2
GSV4
Intruder alarm system Wiring manual

Wiring of zones
Normally closed Normally closed Normally closed Normally open contact Normally open contact Normally open contact
contact contact with one contact with two (NO) with one resistor with two resistors
(NC) resistor resistors (NO/EOL) (NO/DEOL)
(NC/EOL) (NC/DEOL)

GSV4 GSV4 GSV4 GSV4 GSV4 GSV4


+AUX

+AUX

+AUX

+AUX

+AUX

+AUX
COM

COM

COM

COM

COM

COM

COM

COM

COM

COM

COM

COM
Z1

Z1

Z1

Z1

Z1

Z1
+AUX COM Z1 COM +AUX COM Z1 COM +AUX COM Z1 COM +AUX COM Z1 COM +AUX COM Z1 COM +AUX COM Z1 COM

1kW 1kW 1kW 1kW 1kW 1kW

12V T1 T2 NC C 12V T1 T2 NC C 12V T1 T2 NC C 12V T1 T2 NO C 12V T1 T2 NO C 12V T1 T2 NO C


T1
T2

NC
C

T1
T2

NC
C

T1
T2

NC
C

T1
T2

NO
C

T1
T2

NO
C

T1
T2

NO
C
Tamper Tamper Tamper Tamper Tamper Tamper
Detector Detector Detector Detector Detector Detector

Wiring of 4-wire smoke detector


Smoke detectors can be triggered by dust. Therefore, in order to prevent false alarms, it Zones settings:
to COM to COM is recommended to perform a fire alarm verification. For the verification certain system
settings must be activated.
6 Zone settings:
Zone definition: 24h smoke;
5

Attribute assigned to the zone: Fire verification ;


PGM output settings:
Fire (smoke) detector must be powered from PGM output +BELL. If +BELL is
2

occupied, the power to the detector should be supplied from +AUX via relay. The relay
PGM ouput settings:
4

3
should be controlled by -PGM1 or -PGM2 ;
PGM definition: Fire Power Supply;
to PGM / Zone selected to be as a fire zone must be marked as a trigger source for PGM output;
to zone relay PGM reset time must be set;
Terminals of smoke detector Global time settings:
Detector settle time must be set;
Note: smoke detectors, produ-
Fire zone verification time must be set;
ced by different manufacturers,
Operation: In order to check the triggered fire detector, the power supply of the detector
may have a different terminals
has to be turned OFF shortly and turned ON again. The length of the time period when Global time settings:
layout. For more information
the system turns OFF the PGM output can be set under the setting Reset time. When
check detector wiring manual
reset time expires, the system turns ON the PGM output again and waits for the detector
from manufacturer.
to settle (Detector settle time). Then the system checks the detector again for as long as
it was set under the Fire zone verification time. If the fire detector is triggered again, it
means the alarm was real.

Additional information
Wiring of relays System start-up with no 230V AC Restoring user PIN to default value
power In order to restore user’s PIN to default
GSV4 GSV4 Connect 12V battery with Jumper value, it is necessary to change some
G S V 4 b y u s i n g B AT settings:
-PGM1
+BELL

+AUX

Connect GSV4 with a computer via USB.


COM

connector. Use jumper to


close (for a short time) Download the project with the help of the
terminal pins. System will software MASCAD.
start to operate however Open a Users tab and select a user who
AC loss trouble will be forgot his/her PIN. Select the Temporary
+BELL COM +AUX -PGM1 PIN check-box. Default PIN is shown in
indicated.
brackets.
Save settings and upload them back to
Black GSV4.
D1 D1
Red
BAT

+BELL
COM
20V
AC

Relay Relay 12V batery


7Ah/20HR
NC NO NC NO
It is recommended to use diode to
supress voltage surges on relay.

Purpose of S1 and S2 buttons


GSV4 has two buttons: S1 and S2 on board. The purpose of each button depends on whether it’s module is working (powered) or not (not powered):
when the device is working, S1 and S2 buttons are used to enable service mode, register, download and upload the project in www.alarmserver.net. Pressing
each button certain amount of times corresponds to a specific function described in pictures below:
1 x S1 Enable service mode 2 x S1 Upload project to 3 x S1 Register system in 2 x S2 Download project from
(10 min.) www.alarmserver.net www.alarmserver.net www.alarmserver.net

when the device is not working, S1 button is used to start a firmware upgrade procedure. The firmware upgrade mode can be turned on by pressing and holding
S1 button and connecting USB cable at the same time. The software Firmware Upgrade Tool. V.1.xx is used to upgrade the firmware.

3
GSV4
Intruder alarm system Wiring manual

Additional information (continued)


Key-switch zone wiring
GSV4 has got a zone definition PGM control, which can be used to connect a key-switch.It is possible to program this zone to arm the system when the zone is
violated, and to disarm and clear the alarm when the zone is restored.
There is an example below of how to connect and program the key-switch zone. The zone input is programmed to arm the system in Away mode when the zone is
violated (NC) and to disarm the system when the zone is restored (NO). If there is an alarm in the system, it will be cleared together with a disarming action.

Wiring: Zone settings: Operation:


Normally open Normally closed
GSV4 contact contact
(NO) (NC)
COM
Z6

Z6 COM

System is disarmed System is armed in


Away mode

Wiring of LED. System status indication


GSV4 has got a PGM definition Full arm status, which can be used to indicate the system status (armed/disarmed). In this example LED is used to show the status.
The system turns LED on when it is armed and turns it off when the system is disarmed.

Wiring: PGM settings: Operation:


Turned Off Turned On
GSV4
-PGM2
+AUX

+AUX -PGM2 System is disarmed System is armed


1kW

Typical system installation example

GSV4 X1

MODEM LED

SYSTEM LED
BAT

-PGM1
-PGM2
+BELL

+AUX

S1
COM

COM
20V
AC

Z1
Z2
Z3
Z4
Z5
Z6

USB
S2

12V battery
7Ah/20HR

Metal cabinet CAS8M

You might also like