Professional Documents
Culture Documents
Paper_doc
Paper_doc
Paper_doc
Abstract
Most of the IT industries with microgrids are facing the impacts of harmonics on
lighting loads, UPS, Elevators and Air Handling Units with Variable Frequency Drives
offers different harmonic frequencies, thus reduces the equipment performance and
its life cycle. Many passive filters like single tuned filter, double tuned filter or
combination of both single and double tuned filters etc.., are implemented
practically in the industries. It requires a careful tuning, otherwise, the resonance
problems will arouse in the entire microgrid and leads to instability between the
generation and loads, thus the design of an optimized passive filter is still a
challenging problem for mitigating the harmonics. The Cuckoo Search Algorithm is
proposed in this paper to design the passive harmonic filter to reduce the Total
Harmonic Distortion and size of the filter, which provides better tuning than the
manual tuning. This algorithm performed on real time data from an IT industry with
Fluke analyzer and the filter design is carried out on AHU, UPS and lighting loads
using MATLAB simulation software and desired waveforms are presented.
1 Introduction
Most of the industries with microgrids aims in the distributed automation with in
system to improve the quality of service, reduce the operating cost and increases
the efficient use of energy and fast operation to the changing the energy
environment. Such industries uses Adjustable Speed Drives (ASD) and Variable
Frequency Drives (VFD) or Variable Voltage Variable Frequency Drives (VVVFD) for
controlling Air Handling Units (AHU) with Building Management Systems (BMS) as
specified in American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE) 135-2016, a Data Communication Protocol for Building
Automation and Control Networks (BACnet Standard), however, these drives are
the sources of harmonics, which affects the system performance.
The industry has the automated control of VVVFDs through automated Building
Management Systems, thus the frequency of motor operation depends upon the
load in the work place, ambient temperature and set points. The modern day
buildings are built with the support of BMS to accomplish the maintenance and save
energy, through the communication protocols for the purpose of monitoring and or
control. The BMS has excellent features like monitoring and controlling the
equipment, status of data equipment, scheduling loads and provides the Graphical
User Interface (GUI) for the easy access to the operator.
Due to the variations in the temperature, the set points will vary in AHU and leads
to variation of speed in VVVFDs, it is worth noting that in AHU based VFDs, the
power is proportional to Speed3, in addition, the energy saving strategies are more
significant, if the air volume is controlled with motor speed. The Figure 1 shows the
basic structure of VVVFD, AHU and loads associated with controllers. While
controlling the set points at various speeds, it would generate the harmonic
frequencies in the supply current and increases the temperature in the wingdings of
the motor, thus affects the performance of the drive. While the controlling of speed
of the drive, the voltage at the terminals of the load is varied and the power
consumption is varied. In the past many harmonic filters are designed to mitigate
or reduce the %THD, since they are simple and inexpensive in design. Some of the
passive filters like single tuned filters, double tuned filters, C-type filters and
combination of single and double tuned filters are used in parallel to the loads. The
single tuned filters will mitigate only the single dominant harmonic frequency,
where as the double tuned filter will remove any two dominant harmonic
frequencies with careful tuning. However, the voltage deviation and peak voltage
change due to distortion are analyzed and it is realized that the filter capacitor
charging and discharging varies from cycle to cycle and results to fluctuation of the
regulator and maloperation of the equipment. Therefore to reduce the voltage
fluctuations, %THD and size of the filter, an optimized filter design is very much
necessary, this ensures the performance of the equipment and reduces the energy
cost as per IEEE recommendations [1–3].
Most of the meta heuristic algorithms are based on the social deterministic rules
and randomness, behavior of the animal or insect groups, that imitate in the
nature. Most common practical problems from technical and non technical fields are
iterative, complex, discontinuous, multi-modal problems are solved with simple
initialization and calculations of meta heuristic algorithms. Some of the meta
heuristic algorithms are Particle Swarm Optimization (PSO) [4], Genetic Algorithm
(GA) [5], Artificial Bee Colony (ABC) [6–10], Ant Colony Optimization (ACO) [11]
and Grey Wolf Optimization (GWO) [12].
Methods
The analysis of harmonics are important on the power system and on the
equipment is needed to improve the voltage profile and enhances the life span of
the equipment. The proposed Cuckoo Search Algorithm (CSA) is used
to design the passive filter for the AHU based loads, UPS and
Lighting loads, which is found to effective and simple. The
harmonic data is captured from a AHU load with Fluke analyzer
and processed the waveforms in MATLAB software for the
analysis.
(i) Identify the capacitor size Qc in MVAr and the reactive power requirement of the
harmonic source.
(ii) The capacitance reactance is:
𝑘𝑉 2
𝑥𝑐 = (1)
𝑐𝑄
(iii) To filter the hn harmonic, the inductive reactance should have a value of
xc
xL = (2)
Hn
𝑘𝑉 2 𝑘𝑉 2
𝑄𝐹𝑖𝑙𝑡𝑒𝑟 = = x
(𝑥𝐿 − 𝑥𝑐 )2 ( c − 𝑥𝑐 )2
Hn
Hn 2
𝑄𝐹𝑖𝑙𝑡𝑒𝑟 = (5)
(H n 2 −1)𝑄 2
xc
𝑍𝐹𝐻 = 𝑅 + 𝑗(Hn 𝑥𝐿 − ) (6)
Hn
xc 2
𝑍𝐹𝐻 = 𝑅 2 + (Hn 𝑥𝐿 − ) (7)
Hn
3 System Specifications
The VVVFD is operated at 35Hz and the current waveforms are shown in Figure. 2
and is obtained from Harmonic analyzer shows that the %ITHD is approximately
53.2%. In this case study, the VVVFD is operated at 35Hz, the overall %ITHD is
said to be 53.2% and the system demands 1.449kW, which is higher than the
previous operating frequency of 30Hz. The pressure in the air duct is slightly lesser
than the previous case, since the room temperature reduced. This value of pressure
difference is fed to the controller of VVVFD, thus increases the speed of the motor
and hence the amount of air supplied to the area.
Fig. 2 Current waveforms at 35Hz operation on RYB phases
The Table 1 shows the harmonic and system demand at various operating
frequencies of VVVFD. As the frequency increases, the demand increases linearly
and the %ITHD decreases. When the VVVFD is operated at 35 Hz of frequency the
dominating harmonic is 5th harmonic, which is 65%. The system parameters are
shown in Table 2 at 35 Hz operating frequency.
Voltage AB BC CA
V RMS 234 232.3 233.7
V PK 355 351.6 354.1
V CF 1.5 1.5 1.5
% THD 3.5 3.5 3.5
Freq 50
Current A B C
A RMS 7.4 7.2 7.5
A PK 14.8 13.7 14.8
A CF 2 1.9 2
%THD 53.2 59 55.1
%TDD – – –
K 11.8 13.7 12.4
Factor
Power A B C
kw 1.499 1.419 1.512
kva 1.73 1.679 1.76
kvar 0.864 0.898 0.901
PF 0.866 0.845 0.859
DPF 0.999 0.996 0.995
– Lag Lag
where THDI and Qf are the Total Harmonic Distortion (THD) and Quality factor to
represent filter size respectively. ω1 and ω2 are the coefficients objective function.
THD(Base) is the base THD and QMax is the size of maximum filter installed.
100 2
%𝑇𝐻𝐷 = 𝐻
ℎ 𝐼𝑖ℎ (12)
𝐼𝑖1
where h is the Harmonic order and I1 i is the Fundamental RMS current. The
filter size is written as:
𝑘𝑉 2
𝑄𝐹𝑖𝑙𝑡𝑒𝑟 = (13)
(𝑥 𝐿 −𝑥 𝑐 )2
The accommodation between the filter size is much less important than the THD
reduction, however, to improve the voltage characteristics, the coefficient values of
equation (11) of the objective function are defined as ω1=65% and ω2=35%.
Fig. 3: 5th harmonic component of Current waveform before and after the passive
filter process
The IT industry has 3×400 kVA UPS which is made of semiconductor devices, which
is highly non-linear in nature. The UPS is used to support the data center, servers
and other associated computed equipment. The %iTHD of the UPS is evaluated with
a fluke harmonic analyzer 1750 is 22.9%, with 5th harmonic frequency as dominant.
The corresponding waveforms are shown in the Figure. The %iTHD is reduced to
15.3% after applying the single tuned filter using CSA, the corresponding
waveforms are shown in Fig 4.
7 Conclusions
When the VVVFD is connected to the AHU in auto mode, the operating frequencies
are 33 Hz to 37 Hz, the impacts of harmonics are noted. The CSA optimization is
effective in the designing of harmonic passive filter for the dominating harmonic
component 5th harmonic are reduced and simulated waveforms are shown. The
passive filters are also designed for the dominant 5th harmonic frequencies with UPS
and 7th harmonic frequencies in lighting loads are evaluated and corresponding
waveforms are shown.
List of Abbreviations
References
[2] McGranaghan MF, Muller DR (1999) “Designing harmonic filters for adjustable
speed drives to comply with IEEE-519 harmonic limits”, IEEE transactions on
Industry Applications.
[3] Task force on Harmonics Modeling and Simulation (1996) Modulation and
simulation of propagation of harmonics in electric power networks part I: Concepts,
models and simulation techniques. IEEE Transaction on Power Delivery.
[5] R. Klempka, “Passive Power Filter Design Using Genetic Algorithm”, PRZEGLI,
ELEKTRO TECHNICZNY, , R.89 NR 5,2013, pp.294- 301.
[6] Avirup Maulik, Debapriya Das, “Optimal operation of microgrid using four
different optimization techniques”, Sustainable Energy Technologies and
Assessments,Volume 21,2017.
[7] D Karaboga, “An Idea based on honey bee swarm for numerical optimization”,
Techn. Rep. TR06, Erciyes Univ. Press, Erciyes, 2005.
[8] Choton K. Das, Octavian Bass, Ganesh Kothapalli, Thair S. Mahmoud, Daryoush
Habibi, “Optimal placement of distributed energy storage systems in distribution
networks using Artificial Bee Colony algorithm”, Applied Energy,Volume 232,2018.
[9] R. Sirjani and M. Kusaf, “Optimal design of passive harmonic filters using Bee
Colony Optimization”, IEEE, 2016 HONET-ICT, 2016, pp. 88-92, doi:
10.1109/HONET.2016.7753426.
[11] W. Wang, Y. Ling, 1. Zhang and Y.Wang, “Ant colony optimization algorithm
for design of analog filters”, IEEE Congress on Evolutionary Computation, Brisbane,
QLD, 2012, pp: 1-6.
[12] S. Mirjalili, S. M. Mirjalili and A. Lewis, “Wolf optimizer”, Adv. Eng. Softw., vol.
69, pp. 46-61, 2014.
[13] A.S. Joshi, Omkar Kulkarni, G.M. Kakandikar, V.M. Nandedkar, Cuckoo Search
Optimization- A Review,Materials Today: Proceedings, Volume 4, Issue 8, 2017,
Pages 7262-7269, ISSN 2214-7853, https://doi.org/10.1016/j.matpr.2017.07.055.
[14] S.Li, Yongan Li, Xiaodong Luo, Lilin Zeng and Zhengping He, “Multiobjective
optimal design for passive power filters in hybrid power filter system based on
multi-island particle swarm optimization”, Power Electronics and Motion Control
Conference (IPEMC), 2012 7th International, Harbin, China, 2012, pp. 2859-2863.