TECHNICAL INFORMATION
0.6/1 KV CABLES
ELECTRICAL PARAMETER
(COPPER CONDUCTOR)
Nominal DC DC AC Inductive
IMPEDANCE
Cross Resistance Resistance Resistance Reactance
(Z)
Section 20° C 90° C 90° C (X)
(mm²)
Ohm/km Ohm/km Ohm/km Ohm/km Ohm/km
1.5 12.1 15.43 15.43 15.43 0.106
2.5 7.41 9.45 9.45 9.45 0.099
4 4.61 5.88 5.88 5.88 0.093
6 3.08 3.93 3.93 3.93 0.088
10 1.83 2.33 2.33 2.33 0.084
16 1.15 1.47 1.47 1.47 0.080
25 0.727 0.927 0.927 0.93 0.080
35 0.524 0.668 0.668 0.67 0.078
50 0.387 0.493 0.493 0.50 0.074
70 0.268 0.342 0.342 0.35 0.073
95 0.193 0.246 0.246 0.26 0.072
120 0.153 0.195 0.195 0.21 0.071
150 0.124 0.158 0.158 0.17 0.071
185 0.0991 0.126 0.126 0.14 0.071
240 0.0754 0.096 0.096 0.12 0.070
300 0.0601 0.077 0.077 0.10 0.070
400 0.0470 0.060 0.060 0.09 0.069
500 0.0366 0.0467 0.0467 0.08 0.069
630 0.0283 0.0361 0.0361 0.08 0.068
800 0.0221 0.0282 0.0282 0.07 0.068
1000 0.0176 0.0224 0.0224 0.07 0.068
1
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
TECHNICAL INFORMATION
0.6/1 KV CABLE
VOLTAGE DROP (V/A/km)
2
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
TECHNICAL INFORMATION
0.6/1 KV CABLES
SHORT CIRCUIT CURRENT (KA)
A. Permissible short circuit currents for copper conductors with XLPE insulation
1.5 0.5 0.4 0.3 0.3 0.3 0.3 0.2 0.2 0.2 0.2 0.1 0.1 0.1
2.5 0.8 0.7 0.6 0.5 0.5 0.4 0.4 0.4 0.4 0.3 0.2 0.2 0.2
4 1.3 1.0 0.9 0.8 0.7 0.7 0.6 0.6 0.6 0.4 0.3 0.3 0.3
6 1.9 1.6 1.4 1.2 1.1 1.0 1.0 0.9 0.9 0.6 0.5 0.4 0.4
10 3.2 2.6 2.3 2.0 1.8 1.7 1.6 1.5 1.4 1.0 0.8 0.7 0.6
16 5.1 4.2 3.6 3.2 3.0 2.7 2.6 2.4 2.3 1.6 1.3 1.1 1.0
25 8.0 6.5 5.7 5.1 4.6 4.3 4.0 3.8 3.6 2.5 2.1 1.8 1.6
35 11.2 9.1 7.9 7.1 6.5 6.0 5.6 5.3 5.0 3.5 2.9 2.5 2.2
50 16.0 13.1 11.3 10.1 9.2 8.5 8.0 7.5 7.2 5.1 4.1 3.6 3.2
70 22.4 18.3 15.8 14.2 12.9 12.0 11.2 10.6 10.0 7.1 5.8 5.0 4.5
95 30.4 24.8 21.5 19.2 17.5 16.2 15.2 14.3 13.6 9.6 7.8 6.8 6.1
120 38.4 31.3 27.1 24.3 22.2 20.5 19.2 18.1 17.2 12.1 9.9 8.6 7.7
150 48.0 39.2 33.9 30.3 27.7 25.6 24.0 22.6 21.5 15.2 12.4 10.7 9.6
185 59.2 48.3 41.8 37.4 34.2 31.6 29.6 27.9 26.5 18.7 15.3 13.2 11.8
240 76.7 62.7 54.3 48.5 44.3 41.0 38.4 36.2 34.3 24.3 19.8 17.2 15.3
300 95.9 78.3 67.8 60.7 55.4 51.3 48.0 45.2 42.9 30.3 24.8 21.5 19.2
400 127.9 104.4 90.4 80.9 73.8 68.4 64.0 60.3 57.2 40.4 33.0 28.6 25.6
500 159.9 130.5 113.1 101.1 92.3 85.5 79.9 75.4 71.5 50.6 41.3 35.8 32.0
630 201.4 164.5 142.4 127.4 116.3 107.7 100.7 95.0 90.1 63.7 52.0 45.0 40.3
800 255.8 208.9 180.9 161.8 147.7 136.7 127.9 120.6 114.4 80.9 66.0 57.2 51.2
1000 319.8 261.1 226.1 202.2 184.6 170.9 159.9 150.7 143.0 101.1 82.6 71.5 64.0
3
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
B. Permissible short circuit current for copper conductors with PVC Insulation
4
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
TECHNICAL INFORMATION
0.6/1 KV CABLES
CURRENT CARRYING CAPACITY
(AMPERE)
Operating Conditions:
Ambient Temperature: 30°C
Ground Temperature: 20°C
Depth of Laying: 0.5m
Thermal Resistivity of soil: 1.2°C m/W
5
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
TECHNICAL INFORMATION
0.6/1 KV CABLES
CURRENT CARRYING CAPACITY
(AMPERE)
Operating Conditions:
Ambient Temperature: 30°C, Ground Temperature: 20°C
Depth of Laying: 0.5m, Thermal Resistivity of soil: 1.2°C m/W
6
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
TECHNICAL INFORMATION
0.6/1 KV CABLES
FACTORS FOR CURRENT CARRYING CAPACITY
C. Rating Factors for Depth of Laying for cables laid Direct in Ground or in Ducts
Depth of
Cables Laid Direct in Ground Cable Laid in Ducts
Laying
Up to 50 70 mm² to Above 300
Meter Single Core Multi Core
mm² 300 mm² mm²
0.50 1.00 1.00 1.00 1.00 1.00
0.60 0.99 0.99 0.97 0.98 0.98
0.80 0.97 0.96 0.95 0.95 0.98
1.00 0.95 0.93 0.92 0.93 0.96
1.25 0.94 0.92 0.89 0.90 0.95
1.50 0.93 0.90 0.87 0.89 0.94
1.75 0.92 0.89 0.86 0.88 0.94
2.00 0.91 0.88 0.85 0.87 0.93
2.50 0.90 0.87 0.84 0.86 0.93
3.00 0.89 0.85 0.82 0.85 0.92
7
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
Number of systems
side by side 1 2 3 1 2 3
2 cm d 2d
2 cm 2d
d
Laying on the ground
systems
above each
other 1 2 3 1 2 3
Arranged on
frameworks or at
walls
0.94 0.91 0.89 0.89 0.86 0.84
8
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
0.95 0.90 0.88 0.85 0.84 0.90 0.84 0.80 0.75 0.73
Number of
troughs
1 0.95 0.90 0.88 0.85 0.84 0.95 0.84 0.80 0.75 0.73
Laying on
cable 2 0.90 0.85 0.83 0.81 0.80 d
0.95 0.80 0.76 0.71 0.69
troughs 3 0.88 0.83 0.81 0.79 0.78 0.95 0.78 0.74 0.70 0.68
(restricted
6 0.86 0.81 0.79 0.77 0.76 d 0.95 0.76 0.72 0.68 0.66
air
circulation) 2 cm
Number of
grills
1 1.00 0.98 0.96 0.93 0.92 0.95 0.84 0.80 0.75 0.73
Laying on 2 1.00 0.95 0.93 0.90 0.89 d 0.95 0.80 0.76 0.71 0.69
cable grills
(unrestricted 3 1.00 0.94 0.92 0.89 0.88 0.95 0.78 0.74 0.70 0.68
d
air 6 1.00 0.93 0.90 0.87 0.86 0.95 0.76 0.72 0.68 0.66
circulation) 2 cm
Number
of cables
above
each
other 1 2 3 6 9 1 2 3 6 9
Arranged on 2 cm
frameworks or at
walls 1.00 0.93 0.90 0.87 0.86 0.95 0.78 0.73 0.68 0.66
9
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
TECHNICAL INFORMATION
0.6/1 KV CABLES
RATING FACTORS FOR VARIATION IN THERMAL RESISTIVITY OF SOIL
B) FOR SINGLE AND THREE PHASE OF SINGLE CORE CABLES LAID DIRECT IN THE GROUND
10
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
11
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
TECHNICAL INFORMATION
0.6/1 KV CABLES
FACTORS FOR CURRENT CARRYING CAPACITY
For cable installation in other conditions, the current rating can be determined by the use of various
rating factors given here under:
INSTALLATION IN GROUND
A. Factors for grouping in soil
Single core cables in flat formation
Clearance between systems: 7 cm
Insulation
Type Thermal Resistivity of the soil
0.7 1.0 1.5 2.5 0.7-2.5
k.m/W
12
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
B. Factors for variation in ambient temperature and thermal resistivity of the soil.
Thermal
Resistivity of the 0.7 1.0 1.5 2.5
Soil k.m/W
Insulation
Type Load Factor fl 0.7 1.0 0.7 1.0 0.7 1.0 0.7-1.0
Soil Temperature
°C fi
10 1.16 1.05 1.05 0.98 0.95 0.91 0.86
15 1.14 1.03 1.02 0.95 0.92 0.89 0.84
20 1.12 1.00 1.00 0.93 0.9 0.86 0.81
XLPE 25 0.98 0.90 0.87 0.84 0.78
30 0.95 0.88 0.84 0.81 0.75
35 0.82 0.78 0.72
40 0.68
10 1.19 1.06 1.06 0.97 0.94 0.89 0.83
15 1.17 1.03 1.03 0.94 0.91 0.86 0.79
20 1.14 1.01 1.00 0.91 0.87 0.83 0.76
PVC 25 0.97 0.88 0.84 0.79 0.72
30 0.94 0.85 0.80 0.76 0.68
35 0.77 0.72 0.63
40 0.59
13
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
14
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
15
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
TECHNICAL INFORMATION
0.6/1 KV CABLES
Armour D.C. Resistance per km of cable @ 20° C
Aluminium
Nominal Wire Galvanized Steel Wire Armour
Cross armour
Section Single core Two Core Three core Four Core Five core
(mm²) Ohm/km Ohm/km Ohm/km Ohm/km Ohm/km
Circular Circular Shaped Circular Shaped Circular Shaped Circular
1.5 - 10.2 - 9.5 - 8.8 - 8.2
2.5 - 8.8 - 8.2 - 7.7 - 6.8
4 - 7.9 - 7.5 - 6.8 - 6.2
6 - 7.0 - 6.7 - 4.3 - 3.9
10 - 6.0 - 4.0 - 3.7 - 3.4
16 - 3.7 - 3.5 - 3.1 - 2.2
25 - 3.2 3.7 2.3 2.5 2.1 2.3 1.8
35 - 2.2 2.6 2.1 2.3 1.9 2.0 1.6
50 1.3 2.0 2.3 1.8 2.0 1.3 1.8 1.1
70 0.75 1.4 2.0 1.3 1.8 1.2 1.2 0.94
95 0.67 1.2 1.4 1.2 1.3 0.76 1.1 -
120 0.61 1.1 1.3 0.76 1.2 0.69 0.76 -
150 0.42 - 1.2 - 0.78 - 0.68 -
185 0.38 - 0.82 - 0.71 - 0.61 -
240 0.34 - 0.73 - 0.63 - 0.54 -
300 0.31 - 0.67 - 0.58 - 0.49 -
400 0.22 - 0.59 - 0.52 - 0.35 -
500 0.20 - - - - - - -
630 0.18 - - - - - - -
800 0.13 - - - - - - -
1000 0.12 - - - - - - -
16
MIDDLE EAST SPECIALIZED CABLES CO. (MESC)
TECHNICAL INFORMATION
0.6/1 KV CABLES
MINIMUM INSTALLATION RADIUS
MINIMUM BENDING
TYPE OF CABLE
RADIUS
Circular conductors -
8xD
armoured or unarmoured
Shaped conductors -
10 x D
armoured or unarmoured
The maximum tension must not be exceeded when pulling a cable into ducts and conduits:
The jacket required to pull the cable in a straight duct can be calculated as follows:
Ts = L x w x f
Ts = Tension required to pull cable, Kg.
L = Length of cable, m
w = Weight of cable, Kg/m
f = Coefficient of friction
Coefficient of friction
Jacket Material
Duct Material
PE PVC Rubber
Asbestos Cement 0.56 0.56 0.68
Rigid PVC 0.34 0.52 0.53
Metal 0.36 0.55 0.60
17