REV DATE PREPARED BY SIGN CHECKED BY SIGN APPROVED SIGN REASON FOR
BY
REVISION
Title:MEPL-PRC-OMD-MEL-008
MEENAKSHI ENERGY Page: Page 2 of 8
Date: 06/08/2016
PVT LTD Rev: A
Maintenance
Procedure Standard Procedure for Preventive
Maintenance maintenance of Power Transformer
Section-Electrical
REVISION CHART
REVISION REVISION REVISION
PAGE PAGE ATTACH
A B C A B C MENTS A B C
1 X
2 X
3 X
4 X
5 X
6 X
7 X
8 X
Title:MEPL-PRC-OMD-MEL-008
MEENAKSHI ENERGY Page: Page 3 of 8
Date: 06/08/2016
PVT LTD Rev: A
Maintenance
Procedure Standard Procedure for Preventive
Maintenance maintenance of Power Transformer
Section-Electrical
Table of contents
1 Purpose.........................................................................................
2 Scope............................................................................................
3 Responsibility.................................................................................
4 Safety, Health and Environment Issues..............................................
5 Reference Documents & Protocols.....................................................
6 Special Tools, Spares & Consumables................................................
7 Precautions....................................................................................
8 Procedure......................................................................................
9 Testing procedure...........................................................................
9 Codes and Standards.....................................................................
9 Revision History............................................................................
Title:MEPL-PRC-OMD-MEL-008
MEENAKSHI ENERGY Page: Page 4 of 8
Date: 06/08/2016
PVT LTD Rev: A
Maintenance
Procedure Standard Procedure for Preventive
Maintenance maintenance of Power Transformer
Section-Electrical
1 Purpose:
Purpose of this document is to provide a detailed procedures for carrying
out the Preventive maintenance of Power Transformer in a safe and
effective manner to improve the reliability and to upkeep the long term
healthiness of the same.
2 Scope:
This document applicable for the preventive maintenance of all 2 No’s of
400/15.75 kV Generator Transformer, 4 No’s of 15.75/6.9kV Power
Transformer (ST, UAT) installed in the Transformer Yard.
3 Responsibility:
Maintenance Apply for PTW, receive PTW, Guide technicians in
Engineer carrying out the job and clear the PTW.
Area Operator/SCE: Issue of PTW.
Personal Supervisor Supervise the job continuously without leaving the work
area till the work is completed or suspended.
Maintenance Execute the job safely and efficiently as per the
Technician: Standard Maintenance Procedure and fill the protocols.
7 Precautions:
Wear all the required PPE’s
Ensure the Isolation of correct Breaker and Isolators.
Ensure the Transformer has been disconnected from both end. (GCB,
Switchyard, MV Switchgear)
Ensure that No live power in equipment with high voltage tester.
Follow standard EHS and engineering practices throughout the job.
8 Procedure:
8.1 Daily:
1. Check oil level of main transformer and OLTC
2. Check the temperature of winding temperature indicator and oil
temperature indicator
3. Check oil leakage
4. Check the silica gel color and oil in breather
11. The Record the results and compare results with previous results.
If any deviation observed with respect to previous results, the
results are not satisfactory, inform to higher authority for further
course of action.
12. Check the oil level in transformer bushing. Bushing gaskets if leaks
occur, tightening usally will help, if the gasket has lost its elasticity,
it must be replaced. The reason for loss of elasticity could be
excessive heating or aging.
13. OLTC functional checks
14. Check the tap changing counter
15. Check the tightness of the earthing of Core to Earth and core to
clamp external connections,
16. Check the IR of the Core to clamp and Core to Erath.
17. Inspection and maintenace on the active part should not be
performed unless there are unambiguous indication of defects.
18. Clear all the tools and tackles from the location and clean the area.
19. Clear the PTW
20. Fill up the protocol sheet with all relevant data. Record any
abnormalities in the remarks column of the protocol.
21. Submit all records to Electrical Maintenance Engineer for review.
22. Update the data in the computerized maintenance management
system.
23. Close the Work Order.
Title:MEPL-PRC-OMD-MEL-008
MEENAKSHI ENERGY Page: Page 8 of 8
Date: 06/08/2016
PVT LTD Rev: A
Maintenance
Procedure Standard Procedure for Preventive
Maintenance maintenance of Power Transformer
Section-Electrical
9 TESTING PROCEDURE:
9.2 General:
1. Reproduce the name plate details of the Power transformer in register.
2. Following tests are to be performed on Power transformer before arriving on
the decision for putting it in to service and deciding the connections for various
protective circuit.
3. All the safety precautions must be taken while carrying out each test.
measurement of bushing and winding. Refer procedure of tan delta for Current
Transformer.
11 Revision History:
Date Revision# Page # Purpose
06-08-2016 A All First issue