PVsyst_LOT 3_Batmete_ICOD-Report (1)
PVsyst_LOT 3_Batmete_ICOD-Report (1)
11
Project: Batmete
Variant: ICOD Jinko
Sheds, single array
System power: 220.0 MWp
Batmete - Algeria
POWERCHINA HUADONG
HDEC MIDDLE EAST CO DMCC (United arab emirates)
Project: Batmete
Variant: ICOD Jinko
Project summary
Geographical Site Situation Project settings
Batmete Latitude 35.20 °N Albedo 0.30
Algeria Longitude 3.73 °E
Altitude 783 m
Time zone UTC
Meteo data
Batmete
SolarGIS Monthly aver. , period not spec. - Synthetic
System summary
Grid-Connected System Sheds, single array
System information
PV Array Inverters
Nb. of modules 379344 units Nb. of units 200 units
Pnom total 220.0 MWp Pnom total 220.0 MWac
Pnom ratio 1.000
Results summary
Produced Energy 415146 MWh/year Specific production 1887 kWh/kWp/year Perf. Ratio PR 86.79 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Near shading definition - Iso-shadings diagram 6
Main results 7
Loss diagram 8
Special graphs 9
17/06/23 PVsyst Licensed to HDEC MIDDLE EAST CO DMCC (United arab emirates) Page 2/9
Project: Batmete
Variant: ICOD Jinko
General parameters
Grid-Connected System Sheds, single array
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane Nb. of sheds 168 units Transposition Perez
Tilt/Azimuth 29 / 0 ° Single array Diffuse Perez, Meteonorm
Sizes Circumsolar separate
Sheds spacing 8.50 m
Collector width 4.58 m
Ground Cov. Ratio (GCR) 53.8 %
Top inactive band 0.02 m
Bottom inactive band 0.02 m
Shading limit angle
Limit profile angle 26.4 °
Bifacial system
Model 2D Calculation
unlimited sheds
Bifacial model geometry Bifacial model definitions
Sheds spacing 8.50 m Ground albedo 0.30
Sheds width 4.62 m Bifaciality factor 77 %
Limit profile angle 26.4 ° Rear shading factor 5.0 %
GCR 54.3 % Rear mismatch loss 10.0 %
Height above ground 0.81 m Shed transparent fraction 0.0 %
PV Array Characteristics
PV module Inverter
Manufacturer Jinkosolar Manufacturer Sungrow
Model JKM580N-72HL4-BDV Model SG1100UD-20
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 580 Wp Unit Nom. Power 1100 kWac
Number of PV modules 379344 units Number of inverters 200 units
Nominal (STC) 220.0 MWp Total power 220000 kWac
Modules 13548 Strings x 28 In series Operating voltage 938-1500 V
At operating cond. (50°C) Max. power (=>12°C) 1320 kWac
Pmpp 204.1 MWp Pnom ratio (DC:AC) 1.00
U mpp 1096 V
I mpp 186248 A
17/06/23 PVsyst Licensed to HDEC MIDDLE EAST CO DMCC (United arab emirates) Page 3/9
Project: Batmete
Variant: ICOD Jinko
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 2.0 % Module temperature according to irradiance Global array res. 0.13 mΩ
Uc (const) 29.0 W/m²K Loss Fraction 2.0 % at STC
Uv (wind) 0.0 W/m²K/m/s
LID - Light Induced Degradation Module Quality Loss Module mismatch losses
Loss Fraction 0.8 % Loss Fraction -0.2 % Loss Fraction 1.0 % at MPP
System losses
Auxiliaries loss
Proportionnal to Power 4.0 W/kW
0.0 kW from Power thresh.
AC wiring losses
Inv. output line up to MV transfo
Inverter voltage 660 Vac tri
Loss Fraction 0.00 % at STC
Inverter: SG1100UD-20
Wire section (200 Inv.) Copper 200 x 3 x 700 mm²
Average wires length 0m
MV line up to HV Transfo
MV Voltage 30 kV
Average each inverter
Wires Copper 3 x 500 mm²
Length 13800 m
Loss Fraction 0.50 % at STC
AC losses in transformers
MV transfo
Medium voltage 30 kV
Operating losses at STC
Nominal power at STC 216300 kVA
Iron loss (24/24 Connexion) 8.65 kW/Inv.
Loss Fraction 0.10 % at STC
Coils equivalent resistance 3 x 0.50 mΩ/inv.
Loss Fraction 1.00 % at STC
17/06/23 PVsyst Licensed to HDEC MIDDLE EAST CO DMCC (United arab emirates) Page 4/9
Project: Batmete
Variant: ICOD Jinko
AC losses in transformers
HV transfo
Grid voltage 220 kV
Transformer from Datasheets Operating losses at STC
Nominal power 330000 kVA Nominal power at STC 216300 kVA
Iron loss 600.00 kVA Iron loss (24/24 Connexion) 600.00 kW
Loss Fraction 0.18 % of PNom Loss Fraction 0.28 % at STC
Copper loss 900.00 kVA Coils equivalent resistance 3 x 7.44 mΩ
Loss Fraction 0.27 % of PNom Loss Fraction 0.18 % at STC
17/06/23 PVsyst Licensed to HDEC MIDDLE EAST CO DMCC (United arab emirates) Page 5/9
Project: Batmete
Variant: ICOD Jinko
Iso-shadings diagram
Orientation #1
17/06/23 PVsyst Licensed to HDEC MIDDLE EAST CO DMCC (United arab emirates) Page 6/9
Project: Batmete
Variant: ICOD Jinko
Main results
System Production
Produced Energy 415146 MWh/year Specific production 1887 kWh/kWp/year
Performance Ratio PR 86.79 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
17/06/23 PVsyst Licensed to HDEC MIDDLE EAST CO DMCC (United arab emirates) Page 7/9
Project: Batmete
Variant: ICOD Jinko
Loss diagram
1886 kWh/m² Global horizontal irradiation
+15.3% Global incident in coll. plane
Bifacial
17/06/23 PVsyst Licensed to HDEC MIDDLE EAST CO DMCC (United arab emirates) Page 8/9