IEEE Std 2800™-2022
New IEEE Interconnection Standard
for Large-Scale Solar, Wind,
and Energy Storage
IEEE-ESIG-PSERC-CURENT JOINT WEBINAR
The views presented in this presentation are the personal views of the individuals presenting it and shall not be
considered the official position of the IEEE Standards Association or any of its committees and shall not be considered to
be, nor be relied upon as, a formal position of IEEE, in accordance with IEEE Standards Association Standards Board
Bylaws 5.2.1.6.
Today:
Joint IEEE–ESIG–PSERC–CURENT Webinar for Subject Matter Experts & Academia
Tomorrow:
Joint NERC–NATF–NAGF–EPRI Webinar for Transmission Planners
May 3, 2022 @ 12:00pm-1:30pm ET | 9:00am-10:30pm PT | 6:00pm-7:30pm CET); no registration
required, join the webinar here
TBD:
Joint SEIA–ACP (formerly AWEA) Webinar for OEMs & Developers
Resources and Media
https://www.irena.org/publications/2022/Apr/Grid-codes-for-
renewable-powered-systems
https://beyondstandards.ieee.org/addressing-grid-reliability-as-renewable-energy-integration-speeds-up/ https://www.esig.energy/ieee-p2800-enhancing-the-dynamic-performance-of-high-ibr-grids/
Outline – Joint IEEE-ESIG-PSERC-CURENT Webinar – May 2, 2022
For those working group members whose effort on the standard was partially or fully supported by the U.S.
DOE’s National Renewable Energy Laboratory, the following statement applies:
This work was supported in part by the National Renewable Energy Laboratory, operated by Alliance for
Sustainable Energy, LLC, for the U.S. Department of Energy (DOE) under Contract No. DE-AC36-08GO28308.
Funding provided by U.S. Department of Energy Office of Energy Efficiency and Renewable Energy Solar Energy
Technologies Office and Wind Energy Technologies Office. The views expressed in the article do not necessarily
represent the views of the DOE or the U.S. Government.
IRENA Report: Key Messages
“Power system transformation towards decentralisation,
digitalisation and electrification calls for evolving grid codes”
• [Inverter-based resources, IBR] impact the way power systems are operated
• The role of grid codes in building trust between different actors
• An imperfect grid code is, in many cases, better than no grid code at all
• Grid codes should be technology-neutral and should evolve to meet system
needs
• Grid codes should enable innovations to connect safely to the grid
• Ensuring compliance with the code is key
• International standardisation and regional grid codes facilitate sharing of
flexibility and increased economy of scale for equipment manufacturers
new capability
Recurring Reliability Issues with IBRs
§ Unexpected tripping, cessation of active
power, oscillations, etc.
NERC Recommendations
Ø Significant Updates and Improvements Needed to the
FERC Large Generator Interconnection Agreements
(LGIA)
• Insufficient, diverse, or Limited screening for: • System impact studies • No common assessment • What is built in the field • Only a (limited) set of field • Limited collection of field
vague RTO/ISO/TP’s • Grid strength metrics often use insufficient of IBR plant-level does often not match tests are performed to data to validate/verify IBR
technical interconnection (neither conventional nor models that may not be conformity with regard to what had been previously validate/verify IBR plant plant model.
requirements (TIRs) advanced) site-specific and may be RTO/ISO/TP’s technical studied/modeled model. • Often not for large-
configured with generic interconnection • No “as-built” plant-level • Limited to small-signal signal disturbances.
that could help determine parameters requirements (TIRs)
what type of models and evaluation disturbances.
system impact studies • May not represent IBR • Detailed IBR plant design • Often no verification
• Submission of any units, supplemental IBR may change after
available models, often would be needed to reliably of large-signal
connect the IBR. devices, and the IBR plant Interconnection disturbances such as
inappropriately design ultimately Agreement (IA) is
configured ride-through
commissioned in the field executed
Source: EPRI, 2021-2022
• Vague model ‘acceptance
criteria’
• IEEE 1547.1-2020
Distribution
(for DER)
• IEEE Std 1547-2018
• IEEE Std 1547a-2020 ü • Ul 1741 (SB)
• IEEE ICAP
ü DER: Distributed
Energy Resources
Only when adopted by the appropriate authorities, IEEE standards become mandatory
IEEE Standards Classification and Consensus Building
IEEE
Standards IEEE
IEEE 1547 documents
1547.1 2800
specifying mandatory
requirements (shall)
• Specifies
– performance and functional capabilities and not utilization & services
– functional default settings and ranges of available settings
– performance monitoring and model validation
– type of tests, plant-level evaluations, and other verifications means, but not detailed procedures (è
IEEE P2800.2)
• Scope
– Limited to all transmission and sub-transmission connected, large-scale wind, solar, energy storage and
HVDC-VSC
What not to expect from IEEE 2800?
• No exhaustive requirements for evolving IBR technology solutions
– IEEE 2800 applies to all IBRs (including grid-forming ones), but was designed with conventional grid-
following IBRs in mind
– Considers synchronous condensers as ”supplemental IBR devices” but allows for exceptions when used
in IBR plants
POC (EITHER)
Default RPA: point of interconnection
measurement (POM) system
IBR unit,
IBR unit,
e.g., string-
inverter
e.g., inverter transmission
system (TS)
IBR unit,
e.g., string- POC
IBR
inverter main IBR
tie line
transformer(s)
IBR unit, supplemental supplemental
e.g., string- IBR device, IBR device, Legend
inverter e.g., compensation e.g., compensation
1: inverter-based resource (IBR):
collector system
supplemental any parts that are within the scope of
IBR device, this standard, including IBR plant, IBR
e.g., string units, supplemental IBR devices,
controller IBR plant 1 feeders, collector bus, main IBR
transformer, etc.
+ wind, solar, and/or energy storage systems
2: hybrid IBR plant: IBR with various
hybrid IBR plant2 resources like wind, solar, and/or
energy storage systems
+ other electric generating units and equipment,
e.g., synchronous condensers, synchronous generators, compensation 3: hybrid plant: only the IBR are within
the scope of this standard
hybrid plant3 © IEEE 2022
Reference Point of Applicability – Example 2
© IEEE 2022
IEEE 2800-2022 Technical Minimum Capability Requirements
Modeling &
TS owner Reactive Ride-Through Validation,
Tests and
can require General Frequency Power Power Capability and Measurement
Data, and verification
additional Requirements Response – Voltage Quality Performance,
Control Protection Performance requirements
capability TS owner
“shall have” “should” specify Monitoring
Q for voltage
Harmonic
Fast Voltage Unbalanced
Raising Frequency control at zero Process and
Post-
Measurement Limitations Current
the Response active power commissioning
accuracy Injection criteria for Monitoring
for under- AC-connected model
minimum frequency Prevent
offshore wind: validation
bar conditions “should have” Transient Balanced
Overvoltage Current
“may” for Injection Plant-level
Controls
over-frequency Harmonic Evaluation &
Prioritization Modeling
conditions Automatic Current Voltage
Limitations High Fidelity
Required in 2800
Voltage Ride-through
Regulation Performance
including TrOV Monitoring
Capability
R=0
Rg Lg
Q*
Qref
Timed
1.0e6 [ohm]
Fault
Logic BC
Fault location
© IEEE 2022
Voltage and Reactive Power Control Modes
The IBR plant shall provide the following mutually exclusive modes of reactive power
control functions:
¾ RPA voltage control mode Performanc
Parameter Notes
e target
¾ Power factor control mode
Reaction < 200 ms
¾ Reactive power set point control mode time
Max. step As required Typical step response
RPA voltage control response by the TS time ranges between 1 s
Closed-loop automatic control to regulate the time operator and 30 s.
voltage at the RPA Damping Damping Damping ratio, indicative
ratio of 0.3 of control stability,
Capable of reactive power droop to ensure a stable or higher depends on grid
and coordinated response strength.
Any switched shunts or LTC transformer tap change
operation needed to restore the dynamic reactive
© IEEE 2022
power capability shall respond within 60 s.
Plant level voltage control
rise time = 1.0 sec vs 30.0 seconds
Red trace is the plant controller voltage setpoint (pu)
Blue trace is the measured 34.5 kV voltage (pu)
: Graphs : Graphs
vd_mv Vref vd_mv Vref
1.050 1.050
1.040 1.040
1.030 1.030
1.020 1.020
1.010 1.010
1.000 1.000
0.990 0.990
0.980 0.980
sec 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 ... sec 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 ...
... ...
... ...
© IEEE 2022
Exception
• Within V/Hz capability of IBR units,
transformers & supplemental IBR devices.
Primary Frequency Response (PFR) Capability
PFR capability for both Continuous and Mandatory Operation Regions
Pre-disturbance
Active Power
© IEEE 2022
© IEEE 2022
Definition of FFR
FFR1: FFR proportional to frequency deviation Other variants of FFR (Informative Annex K)
§ FFR2: FFR proportional to df/dt
§ FFR3: Fixed magnitude FFR with frequency trigger
§ FFR4: Fixed magnitude FFR with df/dt trigger
200 MVA
• Each 200 MVA PV plant is a full switching model1 Source: EPRI, 2021
80%
70%
Mandatory Operation
60%
50%
30%
Permissive
20%
Operation
10%
0.16
5.0
4.0
6.0
2.0
3.0
1.0
2.5
1.2
© IEEE 2022
Cumulative Time (Seconds)
Voltage Ride-Through Capability – Plants without
Aux. Load limitations, i.e., Solar Plant
120%
Mandatory may ride-through or may trip Default RPA: Point of Measurement
Operation
110%
Continuous Operation - 30 minutes
100%
Continuous Operation – Infinite time
90%
Voltage (Percentage)
80%
60%
50%
30%
Permissive
20% Operation
10%
5.0
4.0
6.0
2.0
3.0
1.0
1.2
0.32
© IEEE 2022
Cumulative Time (Seconds)
Clarification of Voltage Ride-Through Capability Req.
Three possible understanding:
§ Voltage versus Time curve: For a given voltage, IBR plant shall not trip
until the duration at this voltage exceeds ride-through curve capability.
üCorrect understanding
The IBR plant may trip if V2 of the applicable voltages in % of nominal voltage is
> 3% for greater than 10 s, OR
> 2% for greater than 300 s OR
> 6.7% for a duration specified by the TS owner,
provided that the voltage unbalance is neither caused nor aggravated by the IBR plant.
For a voltage disturbance that reduces the applicable voltage at the RPA to < 50% of nominal, the IBR plant shall be considered
compliant with this standard if the post-disturbance apparent current of the IBR plant is not less than 90% of the pre-
disturbance apparent current.
When Tripping of the IBR plant is required to clear faults either internal to the IBR plant, on the interconnection system (IBR tie
line) or any portion of the TS which may provide sole connectivity between the IBR plant and the TS
© IEEE 2022
Voltage Ride-Through Performance
No specification of The 1-cycle time required for DFT (to derive phasor quantities) is
current magnitude included in specified response/settling time.
300
Three phase fault such that POM voltage drops 50%
200
100
-100
-200
-300
-400
2.9 2.92 2.94 2.96 2.98 3 3.02 3.04 3.06 3.08 3.1 3.12 3.14 3.16 3.18 3.2
© IEEE 2022
Seconds
Illustration of VRT Performance Requirements
2.9 2.92 2.94 2.96 2.98 3 3.02 3.04 3.06 3.08 3.1 3.12 3.14 3.16 3.18 3.2
Phase shift
2.9 2.92 2.94 2.96 2.98 3 3.02 3.04 3.06 3.08 3.1 3.12 3.14 3.16 3.18 3.2 Seconds
Iwtg_PhaseA Iwtg_PhaseB Iwtg_PhaseC
© IEEE 2022
Illustration of VRT Performance Requirements
WTG Terminal RMS current
Active current
Total current
Reactive current
2.9 2.92 2.94 2.96 2.98 3 3.02 3.04 3.06 3.08 3.1 3.12 3.14 3.16 3.18 3.2 Seconds
The IBR unit’s TOV ride-through capability may differ from the IBR plant’s TOV ride-through requirement specified in
this subclause. The IBR plant design should coordinate an IBR unit’s TOV ride-through capability with surge protection
implemented within the IBR plant to allow the IBR plant to meet specified TOV ride-through requirements. © IEEE 2022
Nomenclature of fundamental frequency signals
1
*
i1 i1R i1R
1
vt2
i2p vt1
i1p Based on this nomenclature, during unbalanced
faults, we expect:
positive sequence current lags positive sequence voltage
𝑖1𝑅 > 0
i2r
negative sequence current leads negative sequence voltage
i1r 𝑖2𝑅 < 0 Source: EPRI, 2022
Inverter response to B-C fault at the 34.5 kV bus
Negative sequence current injection enabled
: Graphs : Graphs
vt1 i1 vt2 i2
1.2 0.70
0.60
1.0
0.50
0.8
0.40
0.6 0.30
0.20
0.4
0.10
0.2
0.00
0.0 -0.10
vt1PH i1PH vt2PH i2PH
200.000 200.000
100.000 100.000
0.000 0.000
-100.000 -100.000
-200.000 -200.000
1.0
0.2
0.8
0.6 0.0
0.4
-0.2
0.2
0.0 -0.4
-0.2
-0.6
-0.4
-0.8
sec 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 ... sec 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 ...
... ...
... ...
0.60
1.0
0.50
0.8
0.40
0.6 0.30
0.4
0.20 Δ𝑣𝑡2
0.10
0.2
0.00
0.0 -0.10
vt1PH i1PH vt2PH i2PH
200.000 200.000
100.000 100.000
0.000 0.000
-100.000 -100.000
-200.000 -200.000
0.6 0.0
0.4
-0.2
0.2
Δ𝑖1𝑅 Δ𝑖2𝑅
0.0 -0.4
-0.2
-0.6
-0.4
-0.8
sec 4.6 4.8 5.0 5.2 5.4 5.6 5.8 6.0 ... sec 4.6 4.8 5.0 5.2 5.4 5.6 5.8 6.0 ...
... ...
... ...
0.60
1.0
0.50
0.8
0.40
V2 higher
0.6 0.30
0.20
0.4
V1 higher
0.10
0.2
0.00
0.0 -0.10
vt1PH i1PH vt2PH i2PH
200.000 200.000
100.000 100.000
0.000 0.000
-100.000 -100.000
-200.000 -200.000
0.6
Active current
0.0
0.4
-0.2
0.2
0.0 -0.4
-0.2
-0.6
-0.4
-0.8
sec 4.6 4.8 5.0 5.2 5.4 5.6 5.8 6.0 ... sec 4.6 4.8 5.0 5.2 5.4 5.6 5.8 6.0 ...
... ...
... ...
1.0 0.60
0.50
0.8
0.40
0.6 0.30
0.4 0.20
V1 higher
0.10
0.2
0.00
0.0 -0.10
vt1PH i1PH vt2PH i2PH
200.000 200.000
100.000 100.000
0.000 0.000
-100.000 -100.000
-200.000 -200.000
0.6 0.0
0.4
-0.2
0.2
0.0 -0.4
-0.2
-0.8
sec 4.6 4.8 5.0 5.2 5.4 5.6 5.8 6.0 ... sec ...
4.6 4.8 5.0 5.2 5.4 5.6 5.8 6.0
... ...
... ...
© IEEE 2022
65
Protection Requirements
■ Standard does not require specific type of protection to be applied within IBR Plant.
■ If protection is applied (including on auxiliary load), shall allow IBR plant to meets its ride-
through requirements
■ Some requirements for frequency, ROCOF, overvoltage, overcurrent protection.
■ Unintentional Islanding protection
if not permitted by TS owner, protection shall be implemented in accordance with
requirements of TS owner
■ Interconnection System protection
shall be in accordance with requirements of TS owner
© IEEE 2022
66
Modeling Data
■ Some specified requirements cannot be verified based on tests (type, commissioning etc.)
■ Development of verified models is outside the scope of this standard; however, some
guidance is provided.
© IEEE 2022
Test and Verification Framework
Where’s the Category of test and
What’s the Required path to
reference point of verification verification needed
requirement?
applicability (RPA)?
Plant-Level Testing
69
P2800.2 WG Drafting
Kick-Off
individual in Parallel Balloting Publication
Jan 18, 2022
project* SubGroups
Potential Potential
Related IEEE 1547.1 NERC IRPWG
… IEEE P2882 2800 è P2800.2
activities is published Guidelines
Adoption Adoption
*Project authorization request (PAR) approved by NesCom on May 21, 2021 (https://development.standards.ieee.org/myproject-web/app#viewpar/12623/9133); contact andy.hoke@nrel.gov and sign
up for P2800.2 Working Group and Task/Project on IEEE SA myProject at https://development.standards.ieee.org/myproject-web/app#interests
Now that IEEE 2800 has been published, the drafting of conformance
procedures has commenced under IEEE P2800.2
Summary & Conclusion
q IEEE Std 2800™ harmonizes minimum Interconnection
Requirements for Large Solar, Wind and Storage Plants
q Expected to mitigate most reliability issues identified by NERC
vector/143421095?prev_url=detail
q Get involved:
P2800 WG P2800.2 WG
• Jens C Boemer, • Andy Hoke,
j.c.boemer@ieee.org Andy.Hoke@nrel.gov
• Manish Patel, • Manish Patel,
mpatel@southernco.com mpatel@southernco.com
https://sagroups.ieee.org/2800/ https://sagroups.ieee.org/2800-2/
IEEE 2800-2022
Available from IEEE at https://standards.ieee.org/project/2800.html
and via IEEExplore: https://ieeexplore.ieee.org/document/9762253/
Outline – Joint IEEE-ESIG-PSERC-CURENT Webinar – May 2, 2022
Today:
Joint IEEE–ESIG–PSERC–CURENT Webinar for Subject Matter Experts & Academia
Tomorrow:
Joint NERC–NATF–NAGF–EPRI Webinar for Transmission Planners
May 3, 2022 @ 12:00pm-1:30pm ET | 9:00am-10:30pm PT | 6:00pm-7:30pm CET); no registration
required, join the webinar here
TBD:
Joint SEIA–ACP (formerly AWEA) Webinar for OEMs & Developers