VRV SERVICE HANDOVER CHECKLIST FOR COMMISSIONIN

Project Title:

Country/ State New Delhi Inspection Date


Project Location Plot No- 118, Raisina Road, Sansad Marg, Inspected By
Address
New Delhi Handed Over to
Clinet Name Tata Project Limited Contact Person
Dealer Name Advertent Building Technologies Pvt Ltd Contact Person
1)
2)
Remarks
3)
4)

DAIKIN's Information

Total Number of Outdoor Units RXYMQ8ARY16 Installation Date

Total Number Of Indoor Units 2


1)
Remarks
2)

Sl No. CHECK LIST Yes


1 Copy of unpriced Purchase Order Yes
2 Equipment Configuration with Sl No. as Annexure I Yes
Warranty Details and scope (Copy of document from Contract and
3 intimation letter to customer) Yes
4 Drawing of Piping layout Attached
5 All ODU and IDU are placed and fixation is done Yes
6 Service space provided for access to IDU and ODU Yes
Flushing of Copper tubes and Pressure test with Nitrogen at 580 PSI
7 (40 kg/sqcm) for 24 hrs Yes
8 Vacuum Test for 2 hrs report Yes
9 Extra Gas Calculation as Annexure II Attached
Checking of Control Wires (F1F2, P1P2 & Q1Q2) with wiring check
10 kit Yes
Dedicated Power supply at IDU (220±10%) and ODU
11 (380~415±10%) unbalance ≥ 2% Yes
12 Protection against neutral failure Yes
13 Drain pipe tested for Slope and Leaks Yes
14 Cleaning of Indoor and Outdoor Units Yes
15 Is the place clean and ready for commissioning Yes
LEGENDS:
COMPLECTED ACTIVITY

REMAINING ACTIVITY

REMAINING ACTIVITY
FOR COMMISSIONING

Reference No:

n Date
d By
Over to
Person TEL.
Person TEL.

stallation Date

Yes No REMARKS
Yes
Yes

Std. Warranty
Yes
Attached
Yes
Yes

Yes
Yes
Attached

Yes

Yes
Yes
Yes
Yes
Yes
EQUIPMENT CONFIGURATION DETAIL FOR COMMISSIONING
Daikin Airconditioning India Pvt Ltd.
Advertent Building Technologies Pvt Ltd
52-G, Beside Ryan Internation School, Sector-40, Gurgaon
Telephone: 9810706018 E mail: info.advertent@gmail.com
Date of Commissioning - 1/22/2024
Customer Name Tata Project Limited

Address Plot No- 118, Raisina Road, Sansad Marg, New Delhi

Contact Person:
Unit Model SERIAL No.
FXAR50ARVE16 46930
CKT NO-1 -
RQYMQ8ARY16 (2523)
1 FXAR50ARVE16 46923
ONING

aon
nt@gmail.com

System Name (Room Name)

Hansdwar Zone-2
Project Name / Location JUNEJA FARM HOUSE
of circuit
Circuit - C-1 12_HP
Pipe Sizes Length Mtr. Multiply Gas (Kg) Outdoor Model
Factor
Ø22.2 0.00 0.36 0.00
Ø19.1 0.00 0.26 0.00
Ø15.9 0.00 0.17 0.00
Ø12.7 0.00 0.11 0.00
RXYQ
Ø9.5 0.00 0.057 0.00
Ø6.4 0.00 0.022 0.00
Additional Charge As per Diversity 0.00 Note: This 30m condition is only for header pipe
Diversity Total Kg 0.00

Table A Part I> From Table A 12 HP Out Door Units System, amount of refrigerant =-- Kg.
3.30 KG
Since piping length is above 30m (Max Length=56m)
Table A Part II> Connectivity of the System
( Indoor Capacity) / (Outdoor Capacity X 25 ) X 100

Connectivity = #DIV/0! %

Total Refrigerant Charge ::