Professional Documents
Culture Documents
Advanced Temperature measurement & Control Valves Volume -4
Advanced Temperature measurement & Control Valves Volume -4
Volume : 4
Kingdom of Saudi Arabia
Saline Water Conversion Corporation
General Directory Of Training Programs
Training Center – JUBAIL
ADVANCED TEMPERATURE
MEASUREMENT
Module: 72206
Module No.: 72206
Version 1.1
Prepared by: Selvaraj Vignesh
Date: 2010
Table Of Contents
Lesson Subject
1 Temperature Measurement
LESSON
1 TEMPERATURE MEASUREMENT
LECTURE
Objectives
At the end of the lesson the Trainee will be able to:
1 THERMOCOUPLES
When two wires composed of dissimilar metals are joined at both ends and
one of the ends is heated, a continuous current flows in the "thermoelectric"
circuit. Thomas See beck made this discovery in 1821. This circuit is shown is
Fig. 1-1 (a). If this circuit is broken at the center, as shown in Fig. 1-1 (b), the
net open circuit voltage (the See beck voltage) is a function of the junction
temperature and the composition of the two metals.
Current Flow
Metal 1
Heat
Metal 2
(a) The See beck Effect
+ Metal 1
Heat
_V ab Metal 2
(b)The See beck Voltage (V ab)
All dissimilar metals exhibit this effect, and this configuration of two dissimilar
metals joined together is called a thermocouple or TC. The most common
TC's and their normal temperature ranges are listed in Table 1-1. For small
changes in temperature, where: the See beck coefficient is the constant of
proportionality. the See beck voltage is linearly proportional to temperature:
Lesson 1 Page 1
Instrument Maintenance Temperature Measurement
EXAMPLE 6-1-1.
Problem: Find the See beck voltage for a thermocouple with = 40 V/
C if the junction temperatures are 40°C and 80°C.
Lesson 1 Page 2
Instrument Maintenance Temperature Measurement
Cu Cu
+
+
V V1 J1
__ Cu Cu C
V2 __
Digital Voltmeter (DVM) J2
(a) ICE Bath Circuit
Cu Cu
+
V1 J1
__ Cu C
V2
o
J2
T=0 C
(b) Equivalent Circuit
Since both voltmeter terminal junctions are now copper, they create no
thermal voltage, and the reading "V" on the voltmeter is proportional to the
temperature difference between J1 and J2.
This involved discussion has been used to emphasize that the ice bath
junction output, V2, is not zero volts but it is a function of absolute
temperature.
By adding the voltage of the ice point reference junction the TC voltage
reading (V) to 0°C has been referenced. This method is very accurate
because the ice point temperature can be precisely controlled.
Lesson 1 Page 3
Instrument Maintenance Temperature Measurement
Cu J3 Fe
+
V J4 V1 J1
__ Cu Fe V2 C
ICE Bath
Digital Voltmeter (DVM) J2
This circuit will still provide moderately accurate measurements as long as the
voltmeter (+) and ( - ) terminals (J3 and J4) are at the same temperature,
because the thermoelectric effects of J3 and J4 act in opposition :
V1 = V
if V3 = V4
i.e., if TJ3 = TJ4
If both front panel terminals are not at the same temperature, there will be an
error. For a more precise measurement, the copper voltmeter leads should be
extended so the copper to iron junctions are made on an "isothermal” (same
temperature) block as shown in Fig. 1-5.
Isothermal
Block
Cu J3 Fe
+
V J4 V1 J1
__ Cu Fe V2 C
ICE Bath
Digital Voltmeter (DVM) J2
The isothermal block is not only a good electrical insulator but a good heat
conductor, and this helps hold J3 and J4 at the same temperature. The
absolute block temperature is unimportant because the two Cu-Fe junctions
act in opposition. We still have
V= (T1 -Tref)
The circuit in Fig. 1-5 will give us accurate readings, but it would be nice to
eliminate the ice bath, if possible. One way to do this is to replace the ice bath
with another isothermal block, as shown in Fig. 1-6.
Isothermal
Block
Cu Cu J3 Fe
+
V J4 V1 J1
__ Cu Cu Fe V2 C
Isothermal
Digital Voltmeter (DVM) J2 Block
T ref
Lesson 1 Page 4
Instrument Maintenance Temperature Measurement
The new block is at reference temperature Tref. and because J3 and J4 are
still at the same temperature and again it is shown that:-
V = (TJ1 Tref)
V = (TJ1 Tjref)
Isothermal
Block
Cu J3 Fe
+
V J4 V1 J1
__ Cu Fe V2 C
Digital Voltmeter J2
(DVM) T ref
Now we call upon the law of intermediate metals to eliminate the extra
junction. This empirical law states that a third metal (in this case, iron)
inserted between the two dissimilar metals of a thermocouple junction will
have no effect upon the output voltage as long as the two junctions formed by
the additional metal are at the same temperature see Fig. 1-8.
This is a useful conclusion, as it completely eliminates the need for the iron
(Fe) wire in the negative lead. This can be seen in Fig. 1-9, where again, V =
(TJ1 - Tref), where is the See beck coefficient for an Fe-C thermocouple.
Cu J3 Fe
+
V V1 J1
__ Cu C
J4
Isothermal
Lesson 1 Page 5
Instrument Maintenance Temperature Measurement
Junctions J3 and J4 take the place of the ice bath. These two junctions now
become the "reference junction". Now we can proceed to the next logical
step: Directly measure the temperature of the isothermal block (the reference
junction) and use that information to compute the unknown temperature, TJ1.
Cu J3 Fe
+
V J4 V1 J1
__ Cu C
Digital Voltmeter Rt
(DVM)
The single most important answer to this question is that the thermistor, the
RTD, and the integrated circuit transducer are useful only over a limited
temperature range. Thermocouples, on the other hand, can be used over a
wide range of temperatures and are much more rugged than thermistors, as
evidenced by the fact that thermocouples are often welded to metal process
equipment or clamped under a screw. They can be manufactured easily,
either by soldering or welding.
Lesson 1 Page 6
Instrument Maintenance Temperature Measurement
reference junction temperature, and this introduces dead time into a control
loop.
The thermocouple in the mineral insulated metal sheath form used in the
power industry, is protected from the environment, so in theory there is no
need for further protection. In practice, numerous points of temperature
measurement on the plant have to be provided with protective pockets:
The following factors should be taken into account when designing a pocket:
Commercially designed pockets usually have the tip positioned at the center
of the pipe, or have an immersion length, typically, of at least ten times the
outside diameter of the pocket.A thermocouple located in a pocket obviously
responds more slowly to changes in fluid temperature so the pocket should be
designed to minimize this response lag, particularly for dynamic applications.
Lesson 1 Page 7
Instrument Maintenance Temperature Measurement
There are two totally different duties for metal surface thermocouples:
1. Permanently installed thermocouples for continuous monitoring of
plant.
2. Temporary installations for spot readings, used during commissioning
tests, validating mathematical models, etc.
The Chordal hole attachment comes nearest to meeting the objective and is
the preferred design. Where its use is not possible, alternative attachments
are available. Boiler thermocouples for metal temperature measurement are
fitted on the gas side and in the dead space. There are three main methods of
thermocouple attachment for gas side temperature measurement:
1. Chordal hole
2. Longitudinal groove
3. Circumferential groove
The Chordal hole design is shown in Figs. 1-12 and 1-13. A hole is drilled at
an angle into the wall of the tube, in which the hot junction is located. Two
different forms of protection of the interface with the carrier tubes are shown;
the choice depends on the locations.
Lesson 1 Page 8
Instrument Maintenance Temperature Measurement
1. Attachment directly to the tube. This can only be used on tubes having
a wall thickness 24.5 mm.
2. Attachment to a pad of weld deposit, built up on the outside diameter of
the tube. This is used on tubes having a wall thickness <4.5 mm.
Lesson 1 Page 9
Instrument Maintenance Temperature Measurement
Three methods are commonly used for making electric connections from the
resistance thermometer assembly to the measuring instrument, namely, the
use of two-, three-, or four-lead circuits.
Lesson 1 Page 10
Instrument Maintenance Temperature Measurement
The shown in Fig. 1-16 is the simplest, consisting of two relatively low-
resistance leads a and b connecting the resistance thermometer with the
measuring apparatus. For this example, the thermometer lead wires are
copper and a whetstone bridge is shown. Note that the leg RX comprises the
resistance of the element plus the resistance of the leads a and b.
Circuit equations:
R1 + R3 = R2 + a + b + X
R1 = R2
R3 = a + b + X
Therefore, leads a and b, unless of very low resistance, can add appreciably
to the resistance of the element. Even though the resistances of the leads
may be known and allowed for in the measurement, they are subject to
ambient temperature changes and do not, of course, follow a precise
resistance-temperature function.
Therefore, the two-lead measuring method should be used only where lead
wire resistance can be kept to a minimum and only where a moderate degree
of accuracy is required. The extent of lead wire error is related to the
resistance of the element and obviously will be proportionately greater with
windings of low resistance than with windings having a higher resistance.
The three-lead circuit shown in Fig. 1-17 is the most widely used method in
industrial resistance thermometry. In this circuit leads a and c are connected
in close proximity to the resistance thermometer element at a common node.
The third lead, b, is connected to the opposite resistance leg of the element.
The resistance of lead a is now added to bridge arm R3, while the resistance
of lead b remains on bridge arm RX, thereby dividing the lead resistance and
retaining a balance in the bridge circuit.
Lesson 1 Page 11
Instrument Maintenance Temperature Measurement
Circuit equations:
R1 + R3+ a + c = R2 + b + X + c
R1 = R2
Lead resistance c is common to both the left and right loops of the bridge
circuit. Although this method compensates for the effect of lead resistance,
the ultimate accuracy of the circuit depends on leads a and b being of equal
resistance. Special matching techniques are used on leads a and b,
particularly when distances between the sensor and measuring equipment are
relatively great.
Lesson 1 Page 12
Instrument Maintenance Advanced Temperature Measurement
LESSON
CALIBRATION OF A
2 THERMOCOUPLE TRANSMITTER
LECTURE
Objectives
At the end of the lesson the Trainee will be able to:
Thermocouple materials are available for use within the approximate limits of -
300 to +3200°F (-185 to +1760°C). No single thermocouple meets all
application requirements, but each possesses characteristics desirable for
selected applications and portions of this range. Depending on the type of
thermocouple selected, the Thermocouple Transmitter can be used in a wide
variety of temperature measurement applications.
Lesson 2 Page 1
Instrument Maintenance Advanced Temperature Measurement
The span or range adjustment is used to set the transmitter to its upper range
output value when the measured temperature is at its maximum or upper
range value. Calibration of a transmitter is the process of matching the lower
and upper output values of the transmitter to the minimum and maximum
temperatures to be measured. The temperatures that are to be measured by
the a pump, it is called a heart of a process plants and a large varieties of
pump are being used to meet the all requirement of a plant.
Lesson 2 Page 2
Instrument Maintenance Advanced Temperature Measurement
Lesson 2 Page 3
Instrument Maintenance Advanced Temperature Measurement
LESSON
CALIBRATION OF AN RTD
3 TRANSMITTER
LECTURE
Objectives
At the end of the lesson the Trainee will be able to:
An RTD Transmitter is used to sense this change in the resistance of the RTD
and produce an electrical output proportional to the temperature of the RTD.
Care should always be taken to select the proper RTD Transmitter for the
temperature range to be measured.
Lesson 3 Page 1
Instrument Maintenance Advanced Temperature Measurement
Lesson 3 Page 2
Instrument Maintenance Advanced Temperature Measurement
Lesson 3 Page 3
Kingdom of Saudi Arabia
Saline Water Conversion Corporation
General Directory Of Training Programs
Training Center – JUBAIL
CONTROL VALVES
Module: 72207
Module No.: 72207
Version 1.1
Prepared by: Selvaraj Vignesh
Date: NOV. 2010
Table Of Contents
Lesson Subject
LESSON
1 FINAL CONTROL ELEMENTS
LECTURE
Objectives
At the end of the lesson the Trainee will be able to:
In order to get warmer water, he should open the valve on the steam line to
some extent and give more steam to the heat exchanger. In order to get
cooler water, he should close the valve to some extent and give less steam.
Lesson 1 Page 1
Final Control Elements Final Control Elements
Controller
Heated
Water
Heat
Cold Exchanger
Water
Feed
Pump
Drain
Lesson 1 Page 2
Final Control Elements Final Control Elements
Fig. 1-3 shows a generalization of the signal flow in the above control loop.
Manipulated Controlled
Variable Variable
Process
Comparison
Control +
Algorithm _
Controller Set-point
Seen from the process, the manipulated variable is the cause and the
controlled variable is the result.
Lesson 1 Page 3
Final Control Elements Final Control Elements
Lesson 1 Page 4
Final Control Elements Final Control Elements
Lesson 1 Page 5
Final Control Elements Final Control Elements
Lesson 1 Page 6
Final Control Elements Final Control Elements
Lesson 1 Page 7
Final Control Elements Fundamentals of Control Valve Characterization
LESSON
FUNDAMENTALS OF CONTROL VALVE
2 CHARACTERIZATION
LECTURE
Objectives
At the end of the lesson the Trainee will be able to: Understand the
Fundamentals of Control Valve Characterization.
1 INTRODUCTION
In any type of control application where control valves are used, the topic of
valve characterization inevitably arises. Individuals who design control
systems, or who select, operate, and maintain control equipment need to
understand the fundamentals of valve characterization. The proper
application of some basic principles will assure the best possible system
performance
There is a tremendous variety in the types of control loops that exist. It would
be a mistake to assume that they are all alike, yet there are some similarities
that can be taken advantage of. The gas pressure control loop, Fig. 2-1,
shows a typical system that will serve to illustrate the general principles.
Every control loop has something that can be defined as the process to be
controlled. A description of the process would have to include information
about the geometry of the containing vessel, the fluid properties, the
dynamics of the fluid action, and the interface between the containing vessel
and the outside world. In the case of Fig. 2-1, the process is represented by
the pressure of the gas contained in the pipe between the control valve and
the load valve. Some of the important descriptive parameters for this process
are the size and length of the connecting pipe, the type of gas contained the
temperature and specific heat ratio of gas, flow rate, and the valve
characteristics of both the control valve and the load valve. Another element
in the loop measures the controlled variable, compares it to a set point, and
then provides some type of predetermined control action to correct for any
deviations. Frequently one device, called a controller, will perform all three of
these functions. Occasionally these functions are performed by several
separate pieces of hardware such as a sensor, transmitter, and a receiver-
controller. It serves the purpose of this discussion to simply lump them
together under the signal heading of controller.
Lesson 2 Page 1
Final Control Elements Fundamentals of Control Valve Characterization
Positioner
Controller
Control Load
Valve Process
The output of the controller goes to an actuator that provides the necessary
mechanical power to operate the control valve. Sometimes there may be an
auxiliary device, such as a booster or a positioner that is used in conjunction
with the actuator. The booster is a special purpose, impedance matching
device which is used infrequently and has little bearing upon the subject of
valve characterization. Positioners are much more commonly used, and their
dynamic characteristics are intimately connected with those of the actuator.
For that reason, they are considered in this discussion as a single unit called
a positioner actuator. The final control element in the loop is the control
valve. The actuator adjusts the restricting element in the control valve to
provide whatever flow has been dictated by the controller. There are a
multitude of valve styles on the market today, each with its own special
features, but the characteristic of most interest in this study is the relationship
between the motion, or travel, of the restricting element and the resulting flow.
This relationship is called the valve characteristic. Any element in the loop
can be characterized by proper selection or design. Characterization simply
refers to the establishment of a particular relationship between the output and
the input of any element. Valve characterization in particular refers to the
establishment of a relationship between the valve flow and the valve travel.
The four basic elements that have just been defined in the control loop are
shown schematically in the block diagram of Fig. 2-2.
3 LOOP GAIN
Every element in the control loop receivers some kind of input and provides
some type of output as represented by the connecting arrows in Fig. 2-2. The
ratio of a change in output magnitude to the change in input magnitude is
known as gain. The higher the gain the greater the output changes for a
given input. Gain is simply a way to express the sensitivity of a device to
changes in its input. A device with high gain will be very sensitive to input
changes.
The purpose of the control loop in Fig. 2-2 is to maintain the controlled
variable at its described value at all times despite changes in the load. If a
deviation of the controlled variable should occur, the controller will sense it
Lesson 2 Page 2
Final Control Elements Fundamentals of Control Valve Characterization
and provide corrective feedback action around the loop, i.e. from the
controlled variable through the controller, positioner actuator, valve, and
process back again to the controlled variable. Obviously, the more sensitive
this control loop is, the sooner the correction will occur and the better the
performance will be. This is just another way of saying that high loop gain is
needed for good loop performance. If the loop gains changes, the loop
performance changes also. The sensitivity of the loop is determined by the
sensitivity of each element in the loop. If the sensitivity of any element is
changed the loop sensitivity changes by the same factor. The loop gain is
determined by multiplying together the gains of all the elements in the loop.
4 PROCESS GAIN
There are many different types of industrial processes, and each has its
unique characteristics. The gain of the process is of particular concern in this
study. Many processes are such that the gain varies with the load condition.
This can be best illustrated with an example. Imagine a gas pressure process
with a mean flow rate of 1000 scfh. A 500 scfh increase in flow rate would
represent a significant change and would undoubtedly cause a large change
in the process pressure. Now consider the same process with a mean flow
rate of 100,000 scfh. In this case, the same 500 scfh change in flow rate will
cause only a minor change in the process pressure.
Controlled
Load Variable
Process
Set Point
As system flow increases, the system pressure becomes less sensitive to the
same change in flow, i.e. the process gain decreases with load flow. Without
resorting to a rigorous mathematical proof, this example gives an intuitive feel
for why the gain of a process can vary with the load on the system.
Depending upon the type of process, the gain may decrease, increase, or
even remain constant with respect to the load.
If the process gain changes with load, then the loop gain will also change by
the same factor, causing a change in the system performance. Depending
upon how the system is turned initially, it may become unstable if the gain
increases too much, or it may become unduly sluggish if the gain becomes
too low.
Lesson 2 Page 3
Final Control Elements Fundamentals of Control Valve Characterization
5 COMPENSATION
When the loop gain changes due to the process gain changing with load, it is
desirable to compensate for this change so that the loop performance remains
constant with load. Fig. 2-2 shows that the only place where this
compensation can be accomplished is in the controller, positioner actuator, or
the valve. The controller requires a great deal of flexibility in its design. Any
attempt to build a characterizing feature into the controller may not only
conflict with its primary function, but may also be economically prohibitive.
6 VALVE CHARACTERIZATION
Lesson 2 Page 4
Final Control Elements Fundamentals of Control Valve Characterization
The linear flow characteristic curve shows that the flow rate is directly
proportional to the valve travel. This proportional relationship produces a
characteristic with a constant slope, so that with constant pressure drop, the
valve gain is the same at all flow rates. The linear valve plug is commonly
specified for liquid level control and for certain flow control applications
requiring constant gain. As previously noted, in situations where a linear
characteristic is recommended, a quick opening valve characteristic can be
used. While the controller will have to operate on a wider proportional band
setting, the same degree of control accuracy may be expected, assuming no
significant dead band in the actuator. With the equal percentage flow
characteristic, equal increments of valve travel produce flow changes which
are equal percentages of the existing flow. The change in flow rate is always
proportional to the flow rate that exists just before.
Lesson 2 Page 5
Final Control Elements Fundamentals of Control Valve Characterization
Fig. 2-4. Valve Gain Variation With∆P. Point (a) Is Flow Condition For Low ∆P ;
Point (b), For Higher ∆P
Q S
=
Q max S max
Lesson 2 Page 6
Final Control Elements Fundamentals of Control Valve Characterization
3. Equal Percentage
This is a very important type of valve employed in flow control. This type
depends on a term called RANGEABILITY (R).
Q max
R =
Q min
8 SUMMARY
Lesson 2 Page 7
Final Control Elements Control Valve Sizing
LESSON
3 CONTROL VALVE SIZING
LECTURE
Objectives
At the end of the lesson the Trainee will be able to: Understand how the
Control Valves are sized in liquid, gas and steam lines.
1 INTRODUCTION
The selection of proper port and body size for a control valve is based on
calculation of the correct valve flow coefficient Cv and consideration of a
number of secondary factors discussed in the article. An accurate prediction
of actual valve capacity for most services is now possible as a result of the
efforts of the instrument Society of America (ISA), culminating in ANSI/ISA
S75.01. This standard sets forth basic equations with which control valve flow
determinations can be made for a wide range of operating conditions. Since
the equations in the standard are not n a convenient form for everyday use, a
proprietary set, easier to use, is outlined here.
The results do not differ materially from those obtained when using the
aforementioned standard. The actual sizing process is still largely dependent
on good analysis of the data available as a basis for computation. Usually
one or more of the flowing conditions is an approximation. The engineering
evaluation of these data is the most important single factor in determining the
final valve size. For this reason, an explanation of the relative importance of
the data used in sizing is prescribed before outlining a detailed procedure.
Pressure drop is perhaps the most arbitrary factor in valve sizing. For a
simple back-pressure or reducing application, the drop across the valve may
be known quite accurately. This is also true for a liquid-level control
installation where the liquid passes from one vessel to another at constant
pressure. If the valve is installed in a long piping system or a system
including heat exchange equipment, the pressure drop across the valve
should be estimated at the maximum flow condition with reasonable
allowance for the pressure losses in series with the valve. Pressure drop
across a control valve is often expressed as a percentage of the total friction
drop in the system.
A good working rule is that at least one-third of the total system drop should
be absorbed by the control valve at maximum flow. This rule may, of
necessity, will be relaxed for extremely long or high-pressure-drop systems,
particularly when the actual desired flow is known reasonably accurately and
does not vary substantially. Reasonably good control can then be attained
with as little as 15% of the total system drop across the valve. An interesting
Lesson 3 Page 1
Final Control Elements Control Valve Sizing
The three figures to be considered are the normal, maximum, and minimum
flow. The maximum figure for valve sizing should be chosen realistically and
must be carefully related to the available pressure drop. It should be the
required maximum flow, not the full capacity of the valve. The valve capacity
is then generally set 25 to 60% above the required or normal maximum flow.
An alternative approach may be to double the expected normal flow.
Unrealistic combinations of flow and pressure drop should be avoided.
The number of gallons per minute of water which will pass through any flow
restriction with a pressure drop of 1 psi.
Example
In view of the enormous range of flowing conditions and the variety of valve
styles, it is not surprising to find that there is still much to be done toward
improving the accuracy of the sizing formulas. A more rigorous approach for
compressible fluid service is set forth in ANSI/ISA S75.01, but the equations
in this article give comparable results. The first control valve sizing standards
based on the flow coefficient Cv such as the Fluid Controls Institute Voluntary
Lesson 3 Page 2
Final Control Elements Control Valve Sizing
standards 58-1 (1958) and 61-1 (1962) did not take into account the variation
in predicted capacity caused by pressure recovery effects. A substantial
variation in flow prediction occurs because of differences in the contouring of
the valve flow passages. The current ANSI/ISA standard and the equations
discussed in this article take this important factor into account.
For liquids
G f
C = q
V
P
For Gas and Vapor Service
Q GT
CV = P(
963 P1 + P 2)
2.1 FOR LIQUID SERVICE
ENGLISH FORMULAS
A. Subcritical Flow
_P<Cf2(_Ps)
Volumetric Flow
G f
C V = q
P
Flow by Weight
W
CV =
500 G f P
Lesson 3 Page 3
Final Control Elements Control Valve Sizing
ENGLISH FORMULAS:
A. Sub critical Flow
_P < 0.5Cf2P1
Volumetric Flow
Q GT
CV =
963 P( P1 + P 2)
Flow by Weight
W
CV =
3.22 P( P1 + P 2)G f
For Saturated Steam
W
CV =
2.1 P( P1 + P2)
For Superheated Steam
(1 + 0.0007 Tsh )
CV =
2.1 P( P1 + P 2)
B. Critical Flow
_P > 0.5 Cf2P1
Q GT
C V =
834 C f P 1
W
CV =
2.8 C f P 1 G f
W
C V =
1.83 C f P 1
W
CV =
1.83 C f P 1
Where:
Lesson 3 Page 4
Final Control Elements Control Valve Noise
LESSON
4 CONTROL VALVE NOISE
LECTURE
Objectives
At the end of the lesson the Trainee will be able to: Understand the types of
Control Valve Noise.
1 INTRODUCTION
2 NOISE TERMINOLOGY
Lesson 4 Page 1
Final Control Elements Control Valve Noise
Sound intensity (I) is defined as the acoustic sound power transmitted per unit
area, perpendicular to a specified direction. the common unit of measurement
for sound intensity is watts per square centimeter W/cm². Sound intensity for
a plane wave is given by the relation.
Ps ²
I= (1)
C
where the product of the density (p) and sonic velocity (c) of the transmitting
medium represents the characteristic impedance.
I
Sound intensity level = 10 log10
-16
dB (2)
10
The reference sound intensity is selected as 10-16 W/cm2. This is
approximately the minimum intensity audible to the average human ear at
1000 Hz/s for standard air
Lesson 4 Page 2
Final Control Elements Control Valve Noise
Noise control employs either one or both of the following basic approaches.
1. Source Treatment.
Prevention or attenuation of the acoustic power at the source (quiet valves)
2. Path Treatment.
Reduction of noise transmitted from a source to a receiver.
Lesson 4 Page 3
Final Control Elements Main Valve Body & Major Structures
LESSON
MAIN VALVE BODY AND MAJOR
5 STRUCTURES
LECTURE
Objectives
At the end of the lesson the Trainee will be able to: Understand the Main Valve
Body and Major Structures of control valve.
1.1 GENERAL
A control valve is a final control element whose purpose is to vary the cross-
sectional area through which a fluid has to pass in a conduit as a result of a
signal from a manual loading station or an automatic controller. This variation
of the cross-sectional area can be from the fully open to fully closed.
The control valve consists of two main parts, the valve body assembly and the
actuator, as shown in Fig.5-1.
The body, bonnet, bottom flange and trim elements constitute the valve body
assembly. The trim includes the valve plug which opens, closes or partially
obstructs one or more ports.
The function of a control valve body is to regulate the rate of flow of a fluid as
the position of the valve plug is changed by a force from the actuator. To fulfill
this function, the valve body must contain the fluid without leaking, must have
adequate capacity, must resist erosion and corrosion, and must be equipped
with a movable valve plug that can be positioned properly by the actuator to
control the flow. There are many various types of valve bodies available with
the single or double port reversible globe bodies considered standard. Valves
for special applications and for specific services have been developed through
the years, giving the widest possible selection to meet any need. The
following outlines shows some of the most common types of control valve
bodies in use today.
Lesson 5 Page 1
Final Control Elements Main Valve Body & Major Structures
Lesson 5 Page 2
Final Control Elements Main Valve Body & Major Structures
Fig. 5-2. shows the most popular type of single port body. It is versatile and
reversible since it can be constructed to have the valve plug move into or out
of the port with increasing loading pressure on the actuator. It is widely used
in process control applications, particularly in sizes less than 2".
Angle valves are nearly always single ported. Some types have very large
capacities when installed so that flow tends to open valve. Angle valves are
most commonly used as boiler feedwater and heater drain valves and in
piping systems where space is at a premium and the valve can also serve as
an elbow. They are self draining valves and are often used to handle slurries
see Fig. 5-3.
Lesson 5 Page 3
Final Control Elements Main Valve Body & Major Structures
Lesson 5 Page 4
Final Control Elements Main Valve Body & Major Structures
Fig. 5-4. shows a typical reversible double port control valve body. Valve plug
can be installed to "push down to open" or "push down to close". Double port
bodies are used on high pressure drop applications since the valve plugs is
essentially balanced and a relatively small amount of force is required from
the actuator. Metal-to-metal seating cannot give tight shut-off.
Lesson 5 Page 5
Final Control Elements Main Valve Body & Major Structures
The three-way body Fig. 5-5. is an adaptation of a single port globe body. It is
used for mixing or blending service with two inlets and one outlet. The three-
way body Fig. 5-6. is an adaptation of a double port globe body. It is used for
diverting or flow splitting service with one inlet and two outlets.
Lesson 5 Page 6
Final Control Elements Main Valve Body & Major Structures
Lesson 5 Page 7
Final Control Elements Main Valve Body & Major Structures
Butterfly valves are available in sizes through 100". They exhibit an equal
percentage flow characteristic. Used for throttling and on-off applications.
Can be fitted with composition seating either by lining the valve or by inserting
a rubber ring in the body.
Lesson 5 Page 8
Final Control Elements Main Valve Body & Major Structures
There are three types of control valves in use in SWCC plants which are
classified with regard to the actuators. They are:
2.1 ACTUATORS
Lesson 5 Page 9
Final Control Elements Main Valve Body & Major Structures
The most commonly used actuators for control valves are operated by
instrument air. Two types are available: diaphragm actuator and piston
actuator.
Instead of compressed air, some kind of oil (mostly machine oil) is utilized for
the piston actuator. This actuator is used for high power elements. It needs
special equipment to maintain the pressure and cleanliness of the oil.
2.1.3 MOTORS
Motors are used as actuators of valves, which, in this case, are called motor
operated valves (MOV). However motors are most commonly used as
actuators of rotating machines such as pumps, fans, mixers and so on. In our
plant motors are also used as actuators for pumps, vane controllers, bar
screens, traveling band screens and loading arms.
2.1.4 OTHERS
Lesson 5 Page 10
Final Control Elements Main Valve Body & Major Structures
3.2 POSITIONERS
This section describes some of the most common types of pneumatic control
valve accessories. Since the positioner is often considered to be the most
important of them, it is covered first. A pneumatic valve positioner is a device
which precisely positions, by the use of air, the moving part (or parts) of a
pneumatically operated valve in accordance with a pneumatic signal. A
typical positioner is shown in Fig. 5-11.
Lesson 5 Page 11
Final Control Elements Main Valve Body & Major Structures
Fig. 5-13. shows a valve with a positioner, in addition to the controller. The
signal from the controller in this case goes to the positioner instead of directly
to the control valve. The positioner compares the signal with the valve stem
position. If the stem is incorrectly positioned, the positioner either adds or
exhausts air from the valve actuator until the correct valve stem position is
obtained.
The positioners illustrated in Fig. 5-15 employs the principle of force balance
operation by spring loading the bellows unit (from the actual motion of the
valve stem) to the same force as that exerted by the control-instrument air
pressure. Either a rise or a fall of the control instrument air pressure will move
the bellows and operate the air pilot. Supply air is either admitted to the
Lesson 5 Page 12
Final Control Elements Main Valve Body & Major Structures
diaphragm actuator chamber or exhausted past the upper pilot stem, to the
atmosphere. As the valve moves, the balance-spring load is changed. This
action brings the bellows and pilot back to their original positions thus
restoring the balance between the spring loading and the control-instrument
pressure.
Pressure boosters are generally also volume boosters; however, their main
function is to increase the pressure the pressure from the controller to above
20 psig in certain valve application. Fig. shows a single-seated, air-to-open
valve with a 6-30 psi spring. The heavy spring may be used to close the valve
against a high upstream pressure; however, the normal controller output (20
psi maximum) cannot open the valve. A 2:1 booster makes the system
operational. The booster may be preferred over a positioner because of its
lower cost. Also, the booster does not close a loop around the valve, a fact
which may enhance stability in fast-response systems.
Lesson 5 Page 13
Final Control Elements Main Valve Body & Major Structures
An on-off air relay may be used in some applications where the maximum
output (20 psi) of the controller is insufficient to operate a diaphragm control
valve. Fig. shows an on-off pneumatic controller operating an air relay. The
relay in turn applies 35 psig or O psig to the diaphragm control valve to open
or close the valve. The 35 psi pressure allows the single-seated diaphragm
control valve to close against higher line pressure than would be possible with
the 20 psig output from the controller.
The pneumatic relay may be used with a throttling controller where the relay is
used in emergency service, as shown in Fig. In this application the relay is
normally positioned so that the exhaust port is closed and the path through
the relay from controller to the diaphragm control valve is kept open. With
proper piping, an emergency signal (0 to 20 psi) can be applied to the relay to
Lesson 5 Page 14
Final Control Elements Main Valve Body & Major Structures
close off the controller signal and to open the exhaust port. With the relay
exhaust port connected to the control valve, the air-to-open valve is rapidly
closed by the valve spring.
5 SOLENOID VALVES
Lesson 5 Page 15
Final Control Elements Main Valve Body & Major Structures
7 AIR LOCKS
This device is used for applications that require a control valve to hold its
position in the event that the plant air supply pressure falls below a given
level. One type is shown in Fig. The plant air supply is fed into a chamber
sealed by a spring-opposed diaphragm. In the event that the plant air
decreases to a predetermined lower limit,the spring closes the connection to
the actuator and locks the existing controller-signal pressure in the line
connecting the valve operator.
Lesson 5 Page 16
Final Control Elements Main Valve Body & Major Structures
8 ELECTROPNEUMATIC TRANSDUCERS
Lesson 5 Page 17
Final Control Elements Main Valve Body & Major Structures
Lesson 5 Page 18
Final Control Elements Control Valve Maintenance &Application
LESSON
CONTROL VALVE MAINTENANCE &
6 APPLICATION
LECTURE
Objectives
At the end of the lesson the Trainee will be able to: Understand the
Control Valve Maintenance.
Control valve maintenance is generally divided into two categories. The first
is preventive maintenance, which involves the installation precautions taken
and the in line follow-up of the valve's performance and environmental
deterioration while in service. The second is the overhaul of a control valve
when it is no longer able to perform satisfactorily.
Periodic Inspection
1. Check that there is no air leakage from the pipeline or the diaphragm
actuator.
2. Check that there is no air leakage from the packing.
3. Check that there are no flaws or scratches on the plug stem.
4. Check that the valve operates smoothly under air pressure. Perform
the above mentioned inspections periodically.
Lesson 6 Page 1
Final Control Elements Control Valve Maintenance &Application
Lesson 6 Page 2
Final Control Elements Control Valve Maintenance &Application
2 CURRENT-TO-PNEUMATIC CONVERTER
Lesson 6 Page 3
Final Control Elements Control Valve Maintenance &Application
2.2 GENERAL
Fig. 6-3. Typical Connection Diagram for General Use Type and Flameproof
Type Instruments.
Lesson 6 Page 4
Final Control Elements Control Valve Maintenance &Application
When current input signal is sent to torque motor of the instrument from
controller, current flows in force coil and generates a torque to move moving
bar. At equilibrium, the moving bar and the bellows balance with each other.
When the current in the force coil increases, the moving bar moves down
wards and closes an air nozzle. Then the nozzle back-pressure increases
and pushes control relay diaphragm downwards which closes relay valve and
increases output air pressure. This output air pressure is supplied to external
instruments and at the same time it enters the feedback bellows to balance
again with the moving bar. As such, output air pressure is always proportional
to current input signal received from controller.
Lesson 6 Page 5
Final Control Elements Control Valve Maintenance &Application
INSTALLATION
1. Before installing the valve on the pipeline, remove dust, oil, grease,
welding chips and any other foreign matter from the interior of the
pipeline and clean inside the pipeline thoroughly. Such foreign matter
may cause leakage - due to poor contact between the plug and the
seat ring - and affect normal operation of the valve.
2. When servicing or repairing the valve, it may be necessary to remove
the valve from the body. Therefore, at installation time, allow sufficient
space above the actuator.
3. Install the valve so that the actuator is vertical. It makes maintenance
work easier. Avoid installing it horizontally or upside down: you may
have to remove the whole valve from the pipeline for maintenance.
3/4, 1 100
1-1/2, 2 150
2-1/2, 3 200
Lesson 6 Page 6
Final Control Elements Control Valve Maintenance &Application
Lesson 6 Page 7
Final Control Elements Control Valve Maintenance &Application
Lesson 6 Page 8
Final Control Elements Control Valve Maintenance &Application
2.4.1 DISASSEMBLY
1. Loosen the lock nut. In case diaphragm rod clamp is attached, loosen
the hexagonal bolt locking the clamp. Remove the plug from the
diaphragm rod by turning the plug (03). If the valve is a direct acting
type (valve opens with a decrease in air pressure), stop the supply of
air pressure to the actuator and if it is a reverse acting type (valve
closes with a decrease in air pressure), supply about half of the
operating air pressure to the actuator so that the plug (03) is separated
from the seat ring (04) and then turn the plug (03). Avoid turning the
plug with the plug and seat ring in contact: this may damage the seat
surface and cause leakage.
Fig. 6-8.
2. Lift off the actuator by removing the yoke nut and separating the
actuator from the body.
3. To disassemble the body, take off the nut (20) locking the body (01)
and the bonnet (02).
4. Take the bonnet (02) from the body. For an unbalanced type valve, the
seat retainer (05) may be removed along with the plug (03), then drop
off the plug.
For a balanced type valve, the P/B sleeve (06) may be removed with
the plug then drop off the plug back into the valve. This may injure the
Lesson 6 Page 9
Final Control Elements Control Valve Maintenance &Application
Notes:
Lesson 6 Page 10
Final Control Elements Control Valve Maintenance &Application
(Take care not to reduce its outside diameter too much). When this
adjustment has been made, fix it on the vide and after cutting, mount it
on the plug, setting the section to the plug.
Fig. -6-9.
a. In charging the gland packing, tighten them after adding each ring.
b. Insert the gland packing so that their joints may be deviated by 120
respectively.
c. Tighten the gland packing evenly.
d. The upper guide (09) has V grooves. Tighten so that the upper surface
of the bonnet comes at the same position as the V grooves.
Fig. 6-10.
Lesson 6 Page 11
Final Control Elements Control Valve Maintenance &Application
Stop the supply of air pressure to the actuator, thrust the plug (03) into the
diaphragm rod and tighten with yoke nut. Next, supply air pressure to the
actuator to bring the plug into contact with the seat ring. Turn the nut (20)
about 1/6 turn with air pressure applied to the actuator. Fully tighten all outs
after purging the air pressure in the actuator. Next, supply air pressure
gradually, holding the indicator at such a position as to indicate "OPEN" and
thrust in the plug (03) so that the indicator stops at the position "SHUT".
When this adjustment has been made, tighten the locking nut. If a diaphragm
rod clamp is attached, tighten the clamp locking bolt, too.
Supply air pressure to the actuator, thrust the plug (03) into the diaphragm rod
and tighten with yoke nut. Next, purge the air pressure in the actuator to bring
the plug into contact with the seat ring. Then, tighten the nut (20) about 1/6
turn. Fully tighten all nuts evenly after supplying air pressure to the actuator.
Hold the indicator at such a position as to indicate "OPEN" with air pressure
applied, and then, purge air pressure gradually and thrust in the plug so that
the indicator stops at the position "SHUT". When this adjustment has been
made, tighten the locking nut. If the diaphragm rod clamp is attached, tighten
the clamp locking bolt, too.
Note: In adjusting the "SHUT" position by thrusting in the plug, keep the plug
off the seat when turning the plug. This also applies when fixing with locking
nut after adjustment.
3.1 GENERAL
Lesson 6 Page 12
Final Control Elements Control Valve Maintenance &Application
3.2 SPECIFICATIONS
Stroke:
Stroke (mm)
6 12 16 20 25 30 40 50 60 70 80 110 130
Nominal
Diameter
(mm)
270 o o o o
320 o o o o
400 o o o o o o o
500 o o o o o o o o o o
600 o o o o o o o
Type of action
and handle Direct-acting type Reverse acting
type
Nominal Top (side)
diameter (mm) Top handle handle type Side hand type Side handle
type type
270 o o
320 o o
400 o o
500 o o
650 o o
Lesson 6 Page 13
Final Control Elements Control Valve Maintenance &Application
Effective area:
Lesson 6 Page 14
Final Control Elements Control Valve Maintenance &Application
When signal pressure is applied through air supply port A, this pressure acts
on diaphragm .08, lowering diaphragm plate .04 and diaphragm rod .05 to the
position where the force produced by signal pressure balances the reaction
force of the spring .12. When signal pressure is reduced, diaphragm plate .04
is moved upwards by the force of spring .12 and stops at the position where
the spring force balances the force produced by signal pressure.
When signal pressure is applied through air supply port B, this Pressure acts
on diaphragm .08, lifting diaphragm plate .04 and diaphragm rod .05 to the
position where the force produced by signal pressure balances the reaction
force of the spring .12. When the signal pressure is reduced, diaphragm plate
.04 is lowered by the force of spring .12 and stops at the position where the
spring force balances the force produced by signal pressure.
3.3.3. ADJUSTMENT
Apply 50% signal pressure to the actuator after connecting it to the control
valve, and adjust the adjust screw so that the stroke of the actuator becomes
50% of full stroke. Change the signal pressure to 25%, 75% and 100% and
confirm that the stroke correctly corresponds to the respective pressure level.
Lesson 6 Page 15
Kingdom of Saudi Arabia
Saline Water Conversion Corporation
General Directory Of Training Programs
Training Center – JUBAIL