Professional Documents
Culture Documents
Bulk MTO Spec
Bulk MTO Spec
Bulk MTO Spec
251034DIST50888
ZMDE-I-ST-50888
CPCPECC – PEG Consortium
Vendor logo and business name Vendor Document ID
na
Facility Name Location Scale Sheet of Sheets
ZUBAIR MISHRIF DGS ONSHORE n.a. 1 of 31
REVISION HISTORY
Re
Date Nr. of Sheets Description
v.
00 17/01/2022 31 For Comments
HOLD SUMMARY
INDEX
1 INTRODUCTION .......................................................................................................................................... 6
15 SPARES ..................................................................................................................................................... 30
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 5 / 31
ENI Iraq b.v. EX-DE 00
16 DOCUMENTATION .................................................................................................................................... 30
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 6 / 31
ENI Iraq b.v. EX-DE 00
1 INTRODUCTION
ENI has been awarded the Zubair project for the development of an oil field (ZUBAIR FIELD) in
joint venture with, Korea Gas and Missan Oil COMPANY (as state partner), with Eni as operator.
The Zubair Field is in the southern area of Iraq, 20 km from Basra city. The structure of the Zubair
Field is a relatively gentle anticline-oriented NNW - SSE, approximately 60 km long and 10-15
km wide.
The Zubair project is a “brown field project”, with existing facilities and infrastructure. The field is
currently in production.
The Zubair Field Development Plan foresees the introduction of new facilities required for the
ramp-up of the field and partial integration with the existing facilities. New facilities include also
water injection capacity to meet the reservoir injection water requirements.
Zubair field is currently in production through 5 de-gassing stations (DGS) (one of them being
Zubair Mishrif) plus Safwan flow station.
In order to achieve the 700 kBOPD the required overall revised ERP (Enhanced Re-development
Plan) plateau of 700 kBOPD additional 4 process oil trains (50 kBOPD each) and related facilities
along with supporting utilities and Water Injection Plant to be installed.
2 SCOPE OF DOCUMENT
This specification covers the minimum technical requirements for instrument bulk materials -
Junction Box, Cable Tray, Tube, Fittings, Earthing, etc. for the Zubair Mishrif DGS Expansion
Project.
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 7 / 31
ENI Iraq b.v. EX-DE 00
3.2 Abbreviation
AI Analogue Input.
AO Analogue Output.
DI Digital Input.
DO Digital Output.
HDG Hot Dipped Galvanized.
SH Individual Shield / Screen.
OSH Overall Shield / Screen.
4 MEASUREMENT UNITS
For measurement units, refer to project Instrumentation & Control Basis of Design, Doc. No.
251034DIRB50863.
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 8 / 31
ENI Iraq b.v. EX-DE 00
5 REFERENCE DOCUMENTS
The selection of material and equipment, and the design, construction, maintenance, and repair
of equipment and facilities shall comply with the COMPANY Standard and project documents
listed below:
6 ORDER OF PRECEDENCE
The order of precedence, in case of conflict between applicable documents, shall be as follows:
7 GENERAL REQUIREMENT
7.1 Electrical Connections
In general, electrical cable entries shall be M20 x 1,5.
• In hazardous area where concentrations mixture of flammable gases (or vapour) and
air are presents frequently for operational or maintenance activity.
7.4 Painting
The paint system that is supplied on all instrumentation must be able to meet the harsh
environmental conditions experience at the plant site.
Refer to Site & Climatic Conditions – as specified in project Basic Engineering Design Data Doc.
No. 251034DPRB03047.
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 11 / 31
ENI Iraq b.v. EX-DE 00
Manufacturers standard finish that meets or exceed these requirements shall be followed.
Stainless steel instruments shall not be painted.
For additional information, refer to the Specification for Painting, Coating, Lining and Fireproofing
- 251034DXSF50646.
• Working pressure shall be calculated in accordance with ASME code for pressure piping
B 31.1 and B 31.3.
• Impulse line for gas applications should slope upwards, to facilitate self-drainage of liquid.
In case of liquid applications impulse line should slope downwards, to facilitate self-vent of
non-condensing gases. The slope of the impulse lines, connecting the instruments to the
process take-off points, shall be 15% as a minimum.
• For general applications the impulse line shall be realized with component suitable for use
at pressure rating of 414 bar (6000 Psi) as a minimum.
better keep 316 L,
• For applications with pressure rating up to 690 Bar what (10000is reason
Psi) the to
above components
PEG: As part of TQ, we are
shall be suitable forproposing
the pressure change.
and temperature ratings applied.
to use 316 for
Non-Sour service. For sour
service 316L or higher
8.1.1 Tubing material shall be used. It is
already identified as TQ
• For general applications the impulse line shall be made at least of type 316 stainless steel
tubing (HOLD-1).
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 12 / 31
ENI Iraq b.v. EX-DE 00
• For application where SS316 (HOLD-1) is not suitable with respect to general corrosion,
other material SS316L or Inconel 625 can be applied for the components of the impulse
line selected to suit the application in the same way as the process piping using the piping
classes.
• Process signal tubing shall be 1/2” OD. x 0.05” wall thickness as minimum; for vent/drain
tubing shall be 1/4” OD. x 0.03” wall thickness as minimum (HOLD-1). Tubing shall be
seamless type.
• Instrument impulse line shall be as short as possible. For straight lengths up to a maximum
of 1 m the tubing is self-supporting, for larger lengths the tubing shall be supported by trays.
• The standard tubes are available in nominal 6m straight lengths (bar stock). End caps are
suggested as protection for instrumentation tubes to avoid potential contamination during
storage or transportation.
• Condensate & seal pots shall be properly supported to prevent stresses on compression
fittings and damage to the tubing.
• Tube clamp assembly shall be one-piece, snap closing design with point fixing to minimize
effects of crevice corrosion. Tube clamp assemblies suitable for single and multi-level tube
installations, shall be PVC based with metallic clamps & SS316 top plate and shall be
supplied complete with mounting brackets and assembly key.
• In order to guarantee the operation at minimum temperature the impulse line where
required shall be insulated. The insulation should normally consist of mineral wool or similar
wrapped around and covered with weatherproof material.
• It may be necessary to heat the tubing; this shall be provided by means of pre-insulated
tubing bundle with self-regulating electric tracing composed by:
- Single or double process tubing.
- Self-regulating heating cable.
- Insulation made by fibrous glass or similar.
- Jacket made of a material hydrolytically stabilized, halogen free, abrasion resistant,
UV resistant.
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 13 / 31
ENI Iraq b.v. EX-DE 00
• Loose ends shall be sealed off with self-vulcanising tape in accordance to VENDOR’s
instructions.
• The heating equipment shall satisfy the requirements for electrical safety in accordance
with the area classification. The arrangement of the electrical tracing shall be such that
transmitters can be removed without disconnecting the electrical heating block. Electrical
tracing shall not be applied for processes where the maximum working temperature
exceeds the guaranteed temperature limitation of the select heating tape.
• The tube mechanical seal shall be assured by means of two compressing ferrules with
hardness suitable to the pipe and resistant to corrosion (particularly to the saline fogs).
• The fittings shall have a residual elasticity able to bear thermal ranges without seal
damages.
• The nut and the ferrules must be auto-aligning for a fast insertion of the pipe and shall be
interchangeable with the respective spare parts.
• The fitting must lock the tube at least in three points in order to allow the maximum seal,
also in presence of vibration and must satisfy the dimensional tolerance considered into
relevant standards, for a good coupling with the pipe; besides, the fittings shall assure a
perfect seal also after at least 10 disassembling and reassembling, without parts replacing.
• All parts constituting the assembled component (fitting) shall be manufactured with the
same material.
• The fittings must neither transmit to the pipe any torsional couple during the tightening, nor
leave residual torsion. They shall not considerably reduce the pipe cross section nor
weaken the pipe wall.
8.1.3 Nipples
• The nipples shall be manufactured according to ASTM A733 Standard (Standard
Specification for Welded and Seamless Carbon Steel and Austenitic Stainless Steel Pipe
Nipples). Stainless steel nipples shall be manufactured from welded or seamless pipes in
accordance to ASTM A312/312M Standard (Standard specification for Seamless, Welded,
and Heavily Cold Worked Austenitic Stainless Steel Pipes).
• Unless different project requirements, the relevant main features are the following:
- 316 SS material as minimum for body, trim and stem. Superior grade material shall
be considered in-line with instrument manifold trim material.
- End connections: ½ NPT
- FIRESAFE execution (if requested).
- Anti-static design as standard.
- Pressure rating according to project requirements (6000/10000 psig).
- Temperature rating: Suitable for the process conditions.
8.1.5 Manifolds
• The instrument manifolds must be made of 316 stainless steel as minimum from bar stock
or from forged block, according to the individual Technical Data Sheet. Superior material
shall be used based on process fluid and process condition requirements.
• The construction shall be as compact as possible, in order to reduce either the volume or
the weight, but the manifolds must be arranged for the clamping, or direct mounted to
instruments.
• The manifolds shall be equipped with needle valves and the relevant orifice size.
• The valves threads shall be coated with anti-seizing material to limit the screwing-up stress.
• The different components must be singly replaceable without the necessity of special tools.
• The functions and open/closed positions of the valves must be clearly and permanently
identified. Sticky labels or other not permanent systems are not allowed.
• The outgoing stems of the valves must be sheltered against the dust.
• The packing must be placed in a position that shall prevent the contact between the
process fluid and the stem, avoiding corrosion phenomena.
• When required, they shall have soft seat for use with low density fluid and gases.
• Each manifold shall have indelible marking with the following information:
- Manufacturer' s name.
- Model number.
- Type of construction material.
- Code for the traceability of the material characteristics and of the production lot.
- Valve line diagram.
- Exercise maximum pressure.
8.1.6 Pots
All types of pots must be made from drawn seamless pipe of carbon steel or stainless steel, hot
formed caps, forged coupling and taps, manufactured according to ASME ''Boiler & pressure
vessel code sect. VIII”.
The types of pots used on instrument primary connections are the following:
• Seal pots
They are used as part of instrumentation piping in all applications where a direct contact
of the sensing elements with the process media is not acceptable.
They collect deposits, dirt, moisture and other elements that might damage the instruments
or compromise their operation and contain sealing liquids for the measurement of high
density or corrosive fluids.
• Condensing pots
They are used in humidity gas metering lines to cool, condense and to maintain a constant
liquid leg above the instruments.
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 16 / 31
ENI Iraq b.v. EX-DE 00
• Alternatively, air distribution header (by piping) with branch connection for each user shall
be considered. The air distribution material with branch connection shall be as per the
relevant pipe class suitable for the service.
• A pressure filter regulator shall be provided for each instrument / equipment air supply near
to the instrument by the instrument VENDOR.
• Diameter and thickness of air supply tubing between valves take off and filter regulators,
between filter regulator and air user, and for instrument signal shall be indicated on the
project data sheet. All instrument air tubing shall be seamless type in 316 stainless steel
as a minimum (HOLD-1). Instrument pneumatic tubing & fittings up to
VENDOR/CONTRACTOR interface point shall be 1/2"OD x 0.065” wall thickness (HOLD-
1) and connection at VENDOR interface component (e.g. AFR) shall be 1/2" NPTF for air
supply. Instrument pneumatic tubing & fittings which are in VENDOR scope for actuator
assembly shall be 1/4" OD as minimum.
• Same consideration applicable for pneumatic hook ups are valid also for hydraulic hook
ups.
• The air manifold must be made in stainless steel from drawn seamless pipe, hot formed
caps and forged coupling and taps, and manufactured according to ASME ''Boiler &
pressure vessel code sect. VIII”.
• The standard type for air distribution manifold shall be 5 or 10 connections; designed for
the simultaneous operation of all instruments with minimum 20% spare take off which shall
be plugged. The air distribution manifold shall be provided with isolating Ball Valves ½”
NPT-F fitted with hexagonal male plugs, and 1 no. of drainage Ball Valve ½” NPT-F fitted
with hexagonal male plug. The air distribution manifold shall be threaded to the shut-off
valve.
• Same considerations are applicable in case the fluid used is not air but another utility (for
example nitrogen).
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
PEG reply: this is a general
requirement
Status inRev.
case air
251034DIST50888 ZMDE-I-ST-50888 manifold is used, details 17 / 31
ENI Iraq b.v. EX-DE 00 spec.
already in the FEED
• Unless different project requirements, the relevant main features are the following:
- 316 SS material for body, ball and stem or as per the relevant pipe class.
- End connections: ½ NPT
- Ball seats materials: soft seats (i.e.: PTFE).
- Spindle locknut is vibration resistant to avoid working loose.
- Full bore or reduced bore execution.
- FIRESAFE execution (if requested).
- Anti-static design as standard.
- Pressure rating according to project requirements (6000/10000 psig).
- Temperature rating: -50°C to +150°C.
• In concrete ducts
Mixed solutions are possible.
ESD and F&G instruments wiring shall include separate junction boxes and cables. However,
cables shall share the common routes and cable trays.
Whenever possible, signal cables shall not be laid close to equipment (transformers, motors,
power change-over switches, etc.), that could interfere with measurement signals.
Since both instrument signal and electric power cable may coexist in some of underground cable
banks, suitable design shall be provided to ensure that proper separation exists between the
power wiring and instrument wiring to avoid any induced voltage or electrical interference.
The cabling system between buildings (e.g., Control Room, RR, LER, MCC Room, etc.) shall
preferably be routed direct buried trenches where necessary structure is not available for trays.
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 18 / 31
ENI Iraq b.v. EX-DE 00
Inside the buildings, the field cables, prefab & system cables shall be orderly laid underneath the
floating floor in cable trays having sufficient spare capacity to permit addition of future cabling
without the need to rearrange existing cabling.
Separate tray system shall be provided for power (110/230 Vac) and instrumentation signal/power
cables. Multiple tray levels are recommended for cable segregation.
The following wiring classifications shall run in separate trays or conduits, as a minimum:
• 24 Vdc circuits (Analog-Digital Signal Cables, Communication, Telecom and 24Vdc Power
Cables)
≤400 300
In case of electrical and instrument cable crossing at 90° (right angle), minimum distances shall
be 300 mm.
For above ground and underground cable routing requirement, refer to the project Typical
Installation Drawing Doc. No. - 251034DIDQ02253, 251034DIDQ02254, 251034DIDQ50795 &
251034DIDQ50796.
• Tubing/pipes and cables need a system for clamping on the relevant trays about every
meter or according to project requirements. The system to be used has to be simple,
quickly opened to allow dismounting for repairs and service.
• To prevent corrosion of tubing, the tubing clamps have to properly designed (i.e.: with an
insulating gasket of rubber or Teflon type) that shall be placed every 2-3 meters between
tubing and tray. Tube clamp assemblies, suitable for single and multi-level tube
installations, shall be PVC based with metallic clamps & SS316 top plate and shall be
supplied complete with mounting brackets and assembly key.
• Any cable/tubing trays shall be complete of all grounding equipment that assures an
electric continuity for all the elements.
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 19 / 31
ENI Iraq b.v. EX-DE 00
• Cable trays shall be ladder type for main cables with cover (junction box to marshalling
cabinet) and perforated type for secondary cables (instrument to junction box). It shall be
heavy duty, return flanged cable trays with accessories, Hot Dipped Galvanised Steel to
provide an average thickness of 100 microns. Sheet thickness shall be >=1 mm, dependent
on the tray’s width and on the loading requirement.
• Typical perforated tray widths shall be 50mm, 100mm, 150 mm, 300 mm and ladder tray
widths shall be 450 mm, 600 mm, or 750 mm. Other tray widths can be used based on
cable loading requirement.
• All accessories, internal couplings and continuity straps shall be fully compatible with cable
tray, or cut lengths of tray, irrespective of where cut has been made.
• Dimension shall be suitable for the required number and types of cables contained,
including 20% of the room to accommodate future spare cables.
• Angles in cable trays, conduit or trenches shall be based on the minimum-bending radius
of the thickest cable.
• The electric continuity of a system of cable trays shall be obtained by sections of earth
wires, fixed by bolts through the tray. Each system of cable trays shall be connected to the
protection earthing system.
• Support Systems:
- Metal channel cable support system shall comprise channels, channels combinations,
cantilever arms, brackets, fittings, nuts, bolts and washer, all in accordance with EN
ISO 1461:2009.
- Channel, channel combinations cantilever arms and support brackets shall be
fabricated from a minimum 2.5 mm thick Grade 430 A steel according to EN 10025,
hot dipped galvanised to an average thickness of 140 microns according to EN ISO
1461 or painted as per the project Specification for Painting, Coating, Lining and
Fireproofing - 251034DXSF50646 suitable for structural requirement (HOLD-3).
- Fittings shall be flat plates, angles, V and Z shape and beam clamps fabricated from
a minimum 6 mm thick Grade 430A steel to EN 10025, hot dipped galvanised to an
average thickness of 80 microns to EN ISO 1461 or painted as per the project
Specification for Painting, Coating, Lining and Fireproofing - 251034DXSF50646
suitable for structural requirement (HOLD-3).
- Trays routed outside shall be supported on the structural steel racks, sometimes
common with piping, if required.
• Refer to the project specific Typical Electrical and Instrument Installation Drawings for
additional information.
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 20 / 31
ENI Iraq b.v. EX-DE 00
• Cable Transit shall be also capable to protect sensitive electric/electronic equipment from
electromagnetic disturbances. It shall be achieved with cable transit for EMC
(Electromagnetic Compatibility) application that reduces Electromagnetic Interference
(EMI) level.
• Refer to the project specific Typical Electrical and Instrument Installation Drawings for
additional information.
• Cable glands shall be dimensionally compatible with the specified cable on which they are
to be used. The overall seal provided by the cable gland shall comply with IP65 minimum
as protection degree according to IEC 60529. Cable glands shall have ISO threading
(usually M20, M25, M32, M40 and M50).
• Earth tags are required for guaranteed ground continuity between cable glands and
equipment.
• For anti-loosening protection each cable gland must be provided with relevant locknut.
• Cable gland shall be complete of seals suitable for cables which could have 'cold flow'
characteristics as requested in the IEC 60079-14, clause 9.1.3. “Cold flow” is a term used
for materials that flow when subjected to pressure at ambient temperature.
• The threads of cable glands shall be protected during installation with silicone grease.
• Cable glands shall have metric threads according to ISO 7-1 (ex UNI 6125).
• Refer to the project specific Typical Electrical and Instrument Installation Drawings for
additional information.
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 23 / 31
ENI Iraq b.v. EX-DE 00
• All marking shall be clear, permanent, and resistant to UV light, smudging, solvents, water,
oil and dirt.
• Refer to the project specific Typical Electrical and Instrument Installation Drawings for
additional information.
8.3.7 Earthing
• The earthing system shall be executed according to electrical codes and taking into
consideration the constraints for cathodic protection of pipeline.
• The "Functional Earthing network" shall gather all earth connections of all
electric/electronic “zero volt” reference signal, intrinsic safety barriers and shields of cables.
• The “Protection Earthing network " shall gather all earth connections of all structures and
metallic casings of instrument or equipment (e.g., supports, cable tray, cable armours,
casing or housing, junction boxes, cabinet, etc.).
• A ground wire for each instrument case to the ground bus shall be provided.
• For shielded cables, the shield (and drain wire) shall be carried as an additional insulated
conductor. Instrument cable shield wire shall be tied back at the instrument side and
terminated at the marshalling panel on isolated earth bar
(instrument signal earth bar).
• The cable armour shall be connected to safety earth at both sides of the cable via the cable
gland.
• For the earthing of Ex-i instruments and relevant cable screens special requirements shall
be applicable according to IEC 60079-14 and COMPANY standard 20532.ENG.STA.STD.
• Instrument and JB earthing connections on the enclosure are suitable for 6mm2 earthing
cable & 16mm2 earthing cable is applicable for Panels.
define coductor
matereial solid /• For more details, refer to the COMPANY standard Earthing Systems for Instrumentation
stranded copper ? Plants Doc. No. - 20532.ENG.STA.STD. Also, refer to the project specific Typical Earthing
outer pvc color ? Scheme - Doc. No. 251034DIDQ02255 and 251034DIDQ50797.
• Instrument location shall ensure sufficient free space around for ease of installation,
removal and maintenance.
• Instrument mounting supports shall not be fixed to grating, as this does not provide
sufficient stiffness and does not allow the grating to be removed.
• Instrument stands shall be fabricated from 2” NB or 4” NB pipe and be of welded and bolted
construction. Instrument stands pipe shall be hot dipped galvanized or painted as per the
project Specification for Painting, Coating, Lining and Fireproofing - 251034DXSF50646
suitable for structural requirement (HOLD-3).
• To avoid corrosion, insulation pads shall be installed wherever dissimilar metal come into
contact.
8.5.1 General
• The junction boxes shall be suitable for outdoor operation and under the environmental
conditions as specified in project Basic Engineering Design Data Doc. No.
251034DPRB03047.
Account shall be taken of all the environmental factors that may affect materials life and
safety, such as:
- Minimum and maximum temperatures.
- Combined effects of temperature and humidity.
- Solids, sand, dust.
- Corrosive and polluting substances.
- Mechanical stress and vibrations.
• Junction boxes shall receive signals of the same type and shall be segregated by
destination of cable in Control Room.
Junction boxes shall be provided separately for:
- Analogue and digital signals
- Digital signals (E.g., Solenoid valves, lamps with high power consumption, etc.)
- Fire & Gas detection
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 25 / 31
ENI Iraq b.v. EX-DE 00
- Vibration monitoring
- Low voltage cables
- Communications
- 24 Vdc power supply.
• The junction boxes shall be made of stainless steel AISI 316 or copper free aluminium
alloy
• Screws, mounting accessories, hinges shall be of AISI 316. Seal gasket for cover shall be
made of Neoprene.
• Junction boxes shall be complete with terminals and accessories such as mounting rails,
end plates, mounting lugs, seal gasket for cover, breathing device and earthing bolt.
• Non hygroscopic and non-loosening composable terminals shall be installed on rail DIN
type. For I.S. circuits, terminals shall be Blue. Terminals for Non-I.S. circuits shall be
Grey/Biege. Terminals shall be minimum section of 2.5 mm2, built with modular type
terminals complete with terminal blocks platelets and label holders. Terminals shall be
isolated from the junction box body.
• Junction boxes shall have adequate space between terminals and sides of the box to
facilitate easy cabling.
• All gaskets utilised for box/accessories assembly shall be suitable for the environmental
conditions specified on the technical data sheet.
• The multicore cable shall enter in the boxes generally from the bottom plate, and the
individual cables from bottom/side plates according to cable quantities/sizes.
• The junction boxes must be supplied with gland plates for cable entry. Unused entries shall
be sealed to maintain equipment certification, with nickel-plated brass, Ex-d and Ex-e dual
certified plug.
• Breathing devices shall be mounted on boxes installed in hazardous area for providing a
suitable ventilation and minimize condensation phenomena inside the box.
• The breather shall contain a flame-trap; holes, placed under the head of the body, allow
breathing without affecting the protection degree of the enclosure.
• Breather shall be tightly engaged in either a horizontal or vertical bottom position into a
threaded hole of the box.
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 26 / 31
ENI Iraq b.v. EX-DE 00
• The identification Tag of each junction box shall be clearly indicated on the front of junction
box.
• The tag number label may be integrated with the “Nameplate”. The provided tag number
shall be large, clear and easy to read in the final installed position.
• All junction boxes shall have highly durable and corrosion resistant stainless steel
certification label, giving the following information:
- Manufacturer’s name, model and serial number.
- Junction box tag.
- Certification type and degree of protection (electrical and mechanical).
- Certification No.
- Year of manufacture.
- CONTRACTORs name
- Order item No.
• Cable entries’ quantity and dimensions shall be confirmed in accordance with the cable
selection and wiring drawings.
No. of Terminal Numbering
Type of Junction Boxes Type of Cables (Note-1)
Terminals (Note-2)
6 Pair – Individual & 1,2,SH / 3,4,SH…/
19 Nos.
Overall Shield 11,12,SH,OSH
Analog Signals (AI / AO)
12 Pair – Individual & 1,2,SH / 3,4,SH…/
37 Nos.
Overall Shield 23,24,SH,OSH
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 27 / 31
ENI Iraq b.v. EX-DE 00
Notes:
1. Cable conductor size shall be 1 sqmm for multipair / triad cables and 2.5 sqmm for
multicore cables as minimum. However, the same shall be decided based on voltage drop
calculation for long run cables.
2. Individual shield (SH) and Overall shield (OSH) of cable shall be terminated at dedicated
terminals in terminal strip at junction box side.
Most of the components described in this specification can be considered suitable for unattended
tests.
Attended tests
Unless otherwise required, the attended tests are required when one of the following conditions
applies:
- complexity of the equipment
- importance of the service for which the equipment is provided
- safety requirements
An attended test is a test carried out in front of COMPANY's personnel or personnel of an external
Body nominated by the COMPANY.
The tests specified for each type shall be carried out on the percentage of specimens defined. in
accordance with the applicable Specifications, Inspection Data Sheets (I.D.S.) and code
requirements as appropriate.
The VENDOR shall provide a complete report of all tests undertaken.
12 PERFORMANCE GUARANTEE
The VENDOR shall guarantee the mechanical design, material of construction, workmanship and
performance of the equipment for the specified application as per the data sheet and material
requisition.
VENDOR shall provide weights and dimensions of all equipment and items during transport,
installation, operation and maintenance activities.
15 SPARES
The VENDOR shall provide itemized and priced recommended spare parts and consumable lists
as follows for:
- Installation and commissioning
- First two years of operation
- Insurance / Capital spares
- Parts to be replaced because of their operating life limitations.
After the award of Purchase Order, the VENDOR shall complete and submit the Spare Parts
Interchangeability List (SPIL) provided by the COMPANY/CONTRACTOR.
16 DOCUMENTATION
VENDOR shall submit all documentation related to each equipment / system for CONTRACTOR’s
authorization or information, as required by COMPANY’s standard procedure. Mutual agreement
on scheduled submittal of drawings and engineering data shall be an integral part of any formal
Purchase Order. Comments made by CONTRACTOR on drawing submittal shall not relieve
VENDOR or Sub VENDOR of any responsibility in meeting the requirements of the specifications.
Such comments shall not be construed as permission to deviate from requirements of the
Purchase Order unless specific and mutual agreement is reached and confirmed in writing.
Logo and business name COMPANY Document CONTRACTOR Revision Index Sheet of
of Document Company Identification Document Identification Sheets
Validity
Rev.
Status
251034DIST50888 ZMDE-I-ST-50888 31 / 31
ENI Iraq b.v. EX-DE 00
Such comments shall not be construed as permission to deviate from requirements of the
specification/purchase order unless specific and mutual agreement is reached and confirmed in
writing by CONTRACTOR/COMPANY.
Each drawing shall be provided with a title block in the bottom right-hand corner incorporating the
following information: