Package Unit Specification

& Selection Sheets


Units Specification

1. MODEL: APMRH

SKM Packaged Units complete with the following:

 Hermetic scroll compressors.


 R-410A refrigerant.
 Condenser coils are copper tubes Aluminum fins.
 Copper tubes Aluminum fins cooling coil.
 Propeller type condenser fan direct driven by TEAO Class "F" insulation, IP-55 protection
motor.
 DIDW Forward curved Centrifugal Supply fan belt driven.
 Refrigerant piping includes filter drier and & thermostatic expansion valve.
 One inch thick fiber glass insulation in evaporator section.
 Electrostatic Polyester Powder coated casing.
 Thermostat.
 Power Supply 380V/3Ph/60Hz.
PAC/2023/R0
PACKAGED AIR CONDITIONERS
March, 2023
APMR62015H Bulletin # 147/2022

Unit Tag Prepared By MUHAMMEDROUSHAN


Customer Reference

Project Print Date Wednesday, 5 June, 2024

INPUT DATA

Required Capacity - Leaving Wet Bulb Temperature - Altitude 0 ft

Return Air Flow Rate 5000 cfm Return Air DBT / WBT / RH 80 °F / 67 °F / 51% Ambient Temperature 115 °F

Fresh Air Flow Rate - Fresh Air DBT / WBT / RH - Quantity 1

PERFORMANCE DATA

Calculated Capacity * 12.05 TR Compressor Power Input 14.26 kW


Sensible Capacity * 9.29 TR Sensible Heat Ratio 0.77
Entering Air Flow Rate 5000 cfm Air Face Velocity 375 fpm

Entering Air DBT / WBT / RH 80 °F / 67 °F / 51%


Leaving Air DBT / WBT / RH 59.5 °F / 58.1 °F / 92%

Air Pressure drop through Evap. Coil 0.3 in.wg

* Capacity given is gross capacity which does not include the effect of evaporator fan motor heat .

PHYSICAL DATA

CONDENSER

Compressor Type Scroll Refrigerant R-410A Fan Code / Quantity D-630 / 2

Compressor Model ZP76 + ZP067 Quantity 1+1 Motor Size / Quantity 0.35 kW / 2

Rows / Fins 3 / 16 fpi Coil Face Area 37.3 ft² Fin Material Aluminum fins

EVAPORATOR
Coil Size (H x L) 32 inch x 60 inch Rows / Fins 4 / 14 fpi Fin Material Aluminum fins

External Static Pressure 1.2 in.wg Total Static Pressure 1.66 in.wg Motor Size 2.2 kW

Fan Model SYT 12-12 / 2

Rotational Speed 1081 rpm

OCTAVE BAND IN-DUCT SOUND POWER LEVEL - SUPPLY FAN

Frequency Hz 63 125 250 500 1000 2000 4000 8000 Total

Lw dB 81.6 84.4 78.0 77.0 76.6 74.8 70.9 66.7 88.0

LwA dB(A) 55.6 68.4 69.4 73.8 76.6 76.0 72.0 65.6 81.6

ELECTRICAL DATA

Power Supply 380-400V/3Ph/60Hz Cond. Fan Motor(each) FLA 1.3


Compressor Qty RLA LRA
Cond. Fan Motor(each) LRA 3.9
MCA 37 ZP76 1 14 94
Evap. Fan Motor FLA 4.85
MFA 63 ZP067 1 12 88 Evap. Fan Motor LRA 42.2

Note :- • Power input mentioned here is at rated condition only, and should not be used for cable/fuse selection.
• MCA/MFA values given in the catalogue electrical data page should be refered for the same .
• For non standard units MCA/MFA values, please consult SKM engineering department.
• Evaporator motor electrical data is based on 4 poles, single speed.

SKM Air Conditioning LLC Email : sales.skm@skmaircon.com


P.O. Box: 6004, Sharjah, UAE Tel: +971 6 5143333 1 Visit us at: www.skmaircon.com
Fax: +971 6 5143300
PAC/2023/R0
PACKAGED AIR CONDITIONERS
March, 2023
APMR62015H Bulletin # 147/2022

Unit Tag Prepared By MUHAMMEDROUSHAN


Customer Reference

Project Print Date Wednesday, 5 June, 2024

Drawings

Loading Points

Unit A1 A2 A3 A4 Total
lbs 364 364 443 443 1614

Sound Data
SOUND PRESSURE LEVEL in dBA ref 2x10-5 Pa in free field
SPECTRUM PER OCTAVE BAND dB(A)

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Total

@ 1 meter 55.2 53.4 45.9 66.5 69.5 68.6 60.7 52.3 73.5

Note: Sound Pressure Level according to ISO 3744, full load operation at 95ºF (35ºC) ambient and 44ºF (6.7ºC) / 54ºF (12.2ºC) evaporator leaving and
entering water temperatures.

Options : -

SKM Air Conditioning LLC Email : sales.skm@skmaircon.com


P.O. Box: 6004, Sharjah, UAE Tel: +971 6 5143333 2 Visit us at: www.skmaircon.com
Fax: +971 6 5143300
PAC/2023/R0
PACKAGED AIR CONDITIONERS
March, 2023
APMR62018H Bulletin # 147/2022

Unit Tag Prepared By MUHAMMEDROUSHAN


Customer Reference

Project Print Date Sunday, 2 June, 2024

INPUT DATA

Required Capacity - Leaving Wet Bulb Temperature - Altitude 2008 ft

Return Air Flow Rate 5800 cfm Return Air DBT / WBT / RH 80 °F / 67 °F / 52% Ambient Temperature 115 °F

Fresh Air Flow Rate - Fresh Air DBT / WBT / RH - Quantity 1

PERFORMANCE DATA

Calculated Capacity * 15.12 TR Compressor Power Input 17.41 kW


Sensible Capacity * 11.34 TR Sensible Heat Ratio 0.75
Entering Air Flow Rate 6500 cfm Air Face Velocity 300 fpm

Entering Air DBT / WBT / RH 80 °F / 67 °F / 52%


Leaving Air DBT / WBT / RH 59.2 °F / 58.3 °F / 95%

Air Pressure drop through Evap. Coil 0.16 in.wg

* Capacity given is gross capacity which does not include the effect of evaporator fan motor heat .

PHYSICAL DATA

CONDENSER

Compressor Type Scroll Refrigerant R-410A Fan Code / Quantity K-710 / 2

Compressor Model ZP090 + ZP083 Quantity 1+1 Motor Size / Quantity 0.95 kW / 2

Rows / Fins 2 / 16 fpi Coil Face Area 52 ft² Fin Material Aluminum fins

EVAPORATOR
Coil Size (H x L) 40 inch x 78 inch Rows / Fins 4 / 14 fpi Fin Material Aluminum fins

External Static Pressure 1.5 in.wg Total Static Pressure 1.76 in.wg Motor Size 2.2 kW

Fan Model SYT 15-15 / 2 (Non Standard motor size, please consult SKM)

Rotational Speed 971 rpm (RPM out of range, please consult SKM)

OCTAVE BAND IN-DUCT SOUND POWER LEVEL - SUPPLY FAN

Frequency Hz 63 125 250 500 1000 2000 4000 8000 Total

Lw dB 82.4 87.3 77.6 80.4 78.6 77.0 74.7 69.4 90.2

LwA dB(A) 56.4 71.3 69.0 77.2 78.6 78.2 75.8 68.3 84.1

ELECTRICAL DATA

Power Supply 380-400V/3Ph/60Hz Cond. Fan Motor(each) FLA 2.4


Compressor Qty RLA LRA
Cond. Fan Motor(each) LRA 7.8
MCA 51 ZP090 1 19 123
Evap. Fan Motor FLA 5.8
MFA 80 ZP083 1 16 94 Evap. Fan Motor LRA 41.8

Note :- • Power input mentioned here is at rated condition only, and should not be used for cable/fuse selection.
• MCA/MFA values given in the catalogue electrical data page should be refered for the same .
• For non standard units MCA/MFA values, please consult SKM engineering department.
• Evaporator motor electrical data is based on 4 poles, single speed.

SKM Air Conditioning LLC Email : sales.skm@skmaircon.com


P.O. Box: 6004, Sharjah, UAE Tel: +971 6 5143333 1 Visit us at: www.skmaircon.com
Fax: +971 6 5143300
PAC/2023/R0
PACKAGED AIR CONDITIONERS
March, 2023
APMR62018H Bulletin # 147/2022

Unit Tag Prepared By MUHAMMEDROUSHAN


Customer Reference

Project Print Date Sunday, 2 June, 2024

Drawings

Loading Points

Unit A1 A2 A3 A4 Total
lbs 498 495 656 643 2292

Sound Data
SOUND PRESSURE LEVEL in dBA ref 2x10-5 Pa in free field
SPECTRUM PER OCTAVE BAND dB(A)

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Total

@ 1 meter 44.9 50.8 52.3 53.4 56.0 53.6 51.8 43.3 61.3

Note: Sound Pressure Level according to ISO 3744, full load operation at 95ºF (35ºC) ambient and 44ºF (6.7ºC) / 54ºF (12.2ºC) evaporator leaving and
entering water temperatures.

Options : -

SKM Air Conditioning LLC Email : sales.skm@skmaircon.com


P.O. Box: 6004, Sharjah, UAE Tel: +971 6 5143333 2 Visit us at: www.skmaircon.com
Fax: +971 6 5143300
PAC/2023/R0
PACKAGED AIR CONDITIONERS
March, 2023
APMR62025H Bulletin # 147/2022

Unit Tag Prepared By MUHAMMEDROUSHAN


Customer Reference

Project Print Date Sunday, 2 June, 2024

INPUT DATA

Required Capacity - Leaving Wet Bulb Temperature - Altitude 2008 ft

Return Air Flow Rate 7400 cfm Return Air DBT / WBT / RH 80 °F / 67 °F / 52% Ambient Temperature 115 °F

Fresh Air Flow Rate - Fresh Air DBT / WBT / RH - Quantity 1

PERFORMANCE DATA

Calculated Capacity * 20.66 TR Compressor Power Input 26.4 kW


Sensible Capacity * 14.05 TR Sensible Heat Ratio 0.68
Entering Air Flow Rate 7400 cfm Air Face Velocity 341.5 fpm

Entering Air DBT / WBT / RH 80 °F / 67 °F / 52%


Leaving Air DBT / WBT / RH 57.4 °F / 56.3 °F / 94%

Air Pressure drop through Evap. Coil 0.21 in.wg

* Capacity given is gross capacity which does not include the effect of evaporator fan motor heat .

PHYSICAL DATA

CONDENSER

Compressor Type Scroll Refrigerant R-410A Fan Code / Quantity K-710 / 2

Compressor Model ZP137 + ZP120 Quantity 1+1 Motor Size / Quantity 0.95 kW / 2

Rows / Fins 3 / 16 fpi Coil Face Area 52 ft² Fin Material Aluminum fins

EVAPORATOR
Coil Size (H x L) 40 inch x 78 inch Rows / Fins 4 / 14 fpi Fin Material Aluminum fins

External Static Pressure 1.5 in.wg Total Static Pressure 1.83 in.wg Motor Size 4 kW

Fan Model SYT 15-15 / 2

Rotational Speed 980 rpm (RPM out of range, please consult SKM)

OCTAVE BAND IN-DUCT SOUND POWER LEVEL - SUPPLY FAN

Frequency Hz 63 125 250 500 1000 2000 4000 8000 Total

Lw dB 81.5 86.9 77.8 81.2 79.3 78.1 75.9 70.6 90.1

LwA dB(A) 55.5 70.9 69.2 78.0 79.3 79.3 77.0 69.5 85.0

ELECTRICAL DATA

Power Supply 380-400V/3Ph/60Hz Cond. Fan Motor(each) FLA 2.4


Compressor Qty RLA LRA
Cond. Fan Motor(each) LRA 7.8
MCA 72 ZP137 1 26 145
Evap. Fan Motor FLA 8.6
MFA 100 ZP120 1 26 145 Evap. Fan Motor LRA 55

Note :- • Power input mentioned here is at rated condition only, and should not be used for cable/fuse selection.
• MCA/MFA values given in the catalogue electrical data page should be refered for the same .
• For non standard units MCA/MFA values, please consult SKM engineering department.
• Evaporator motor electrical data is based on 4 poles, single speed.

SKM Air Conditioning LLC Email : sales.skm@skmaircon.com


P.O. Box: 6004, Sharjah, UAE Tel: +971 6 5143333 1 Visit us at: www.skmaircon.com
Fax: +971 6 5143300
PAC/2023/R0
PACKAGED AIR CONDITIONERS
March, 2023
APMR62025H Bulletin # 147/2022

Unit Tag Prepared By MUHAMMEDROUSHAN


Customer Reference

Project Print Date Sunday, 2 June, 2024

Drawings

Loading Points

Unit A1 A2 A3 A4 Total
lbs 547 543 665 652 2407

Sound Data
SOUND PRESSURE LEVEL in dBA ref 2x10-5 Pa in free field
SPECTRUM PER OCTAVE BAND dB(A)

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Total

@ 1 meter 44.9 50.8 52.3 54.3 57.0 57.3 53.5 45.9 62.8

Note: Sound Pressure Level according to ISO 3744, full load operation at 95ºF (35ºC) ambient and 44ºF (6.7ºC) / 54ºF (12.2ºC) evaporator leaving and
entering water temperatures.

Options : -

SKM Air Conditioning LLC Email : sales.skm@skmaircon.com


P.O. Box: 6004, Sharjah, UAE Tel: +971 6 5143333 2 Visit us at: www.skmaircon.com
Fax: +971 6 5143300
Hi-Wall Unit Specification
& Selection Sheets
Units Specification

1. MODEL: MSKMP 410A

SKM Split Units – Wall Mounted Type complete with following

 Self-Diagnosis and Auto-Protection.


 Auto Restart Function.
 Modern Design Remote Control.
 Low Noise Level.
 Power supply of 220V/1Ph/60Hz.
 Louver Position Memory.
 3 Speed Fan and Turbo Mode.
 2-Way Freon Pipe connection.
 Evaporator coils of copper tubes aluminum fins.
 Condenser coils of copper tubes pre coated aluminum fins.
 Plastic casing of indoor unit.
 Evaporator and Condenser fan of hard plastic.
 The housing of outdoor unit is made of galvanized metal with powder coating.
 External control wires, power wires and Copper refrigerant piping excluded.
 Cool only units.
Hi Wall Mounted MSKMP - CWMSD0

Unit Specifications - Cooling Only


Model MSKMP 12CWMSD0 18CWMSD0 24CWMSD0 30CWMSD0 36CWMSD0
Power supply V-Hz-Ph 220-230V~ 60Hz, 1Ph
Capacity Btu/h 12000 18000 22000 28000 31400
Input W 968 1469 1781 2230 2614
Cooling (T1)
Rated current A 4.33 6.50 7.9 9.70 11.6
EER (Btu/h)/W 12.40 12.25 12.35 12.55 12.00
Capacity Btu/h 10400 15200 18200 24000 26800
Input W 1195 1747 2128 2652 3135
Cooling (T3)
Rated current A 5.28 7.75 9.42 11.75 13.85
EER (Btu/h)/W 8.70 8.70 8.55 9.05 8.55
Max. input consumption W 1490 2120 2570 3380 4100
Max. current A 7.6 10.7 13 17.5 20.5
Compressor Type ROTARY
Input W 58.5 89 60
Indoor Fan Motor Capacitor uF 1.5 3 /
Speed(Hi/Mi/Lo) r/min 1050/950/800 1200/1020/950 1200/1120/1050 1230/1150/1050 1200/1100/1000
Fin type (code) Golden Hydrophilic aluminium
Indoor Coil Tube outside dia.and type mm Φ7,innergroove tube
Coil length x height x width mm 750x336x26.74 820x336x26.74 965x378x40.11 1040x399x40.11
Indoor air flow (Hi/Mi/Lo) m3/h 690/610/490 1160/960/880 1200/1100/1010 1410/1310/1175 1620/1440/1280
Indoor noise level (Hi/Mi/Lo) dB(A) 41/37/32 48/43/40 47/44/42 51/49/45 51/48/45
Dimension(W*D*H) mm 965x215x319 1080x226x335 1259x282x362 1350x272x365
Indoor unit Packing (W*D*H) mm 1045x305x405 1155x415x315 1155x415x320 1340x450x385 1475x460x380
Net/Gross weight kg 11.5/15 14.9/18.7 14.1/17.8 19.9/25.6 21.3/27.3
Input W 77.5 136 150
Outdoor Fan Motor Capacitor uF 2.5 3 4 /
Speed r/min 860 830 910 910 940
Fin type (code) Golden Hydrophilic Aluminium Silver Aluminium
Outdoor Coil Tube outside dia.and type mm Φ5.innergroove tube Φ7,Inner groove tube
Coil length x height x width mm 760x507x23.2 778x663x34.8 1010x756x26.74+598x756x13.37 1000x756x40.11
Outdoor noise level dB(A) 54 57 56 58.5 61
Dimension(W*D*H) mm 770x300x555 845x363x702 946x410x810
Outdoor unit Packing (W*D*H) mm 900x345x585 965x395x765 1090x500x885
Net/Gross weight kg 30.1/33 47.1/51 60.9/65.5 64.2/68.5 68.4/73
Type R410A
Refrigerant
Charge g 850 1300 2200 2500 2600
Design pressure MPa 4.8/1.5 6.0/1.5 4.8/1.5
Liquid side/ Gas side mm(inch) Φ6.35/Φ12.7(1/4"/1/2") Φ6.35/Φ15.9(1/4"/5/8") Φ9.52/Φ15.9(3/8"/5/8") Φ9.52/Φ19(3/8"/3/4")
Refrigerant piping Max. refrigerant pipe length m 20 25
Max. difference in level m 8 10
Connection wiring 3x1.5(Optional) 3x2.5(Optional) 2.5x4(Optional) 4x2.5(Optional) 1.0x4(Optional)
Plug type 3x1.5/(no-plug) 3x2.5/(no-plug) 2.5x3/no-plug 3x2.5/(no-plug) //no-plug
Operation temperature °C 17-30
Indoor(cooling/ heating) °C 17-32/----
Room temperature
Outdoor(cooling/heating) °C 18-52/----
Thermostat type Remote Control (RG57A2/BGEF)
Power Supply Connection IDU ODU
Table 1
Note:
1. The above design and specifications are subject to change without prior notice for product improvement.
2. The values given in the table for the noise level reflect the levels in anechoic chamber.
3. The design conditions comply with SASO-2663-2018 regulation and based on SASO GSO ISO 5151 testing standard:
a) Evaporator entering air conditions of 80.6/66.2ºF (27/19ºC) dry bulb/wet bulb and condenser entering air temperature of 95ºF
(35ºC) dry bulb for T1.
b) Evaporator entering air conditions of 84.2°F/66.2°F (29°C/19°C) dry bulb/wet bulb and condenser entering air temperature of
114.8°F(46°C) dry bulb for T3. (Net Capacity)