Generator set data sheet

Model: C28 D5T (X-series)


Frequency: 50 Hz
Fuel type: Diesel

Spec sheet: EMERS-5629-EN


Noise data sheet (enclosed): MSP-1144

Standby (3 phase) Prime (3 phase)


Fuel consumption kVA (kW) kVA (kW)
Ratings 28 (22) 25 (19.8)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
gph 0.74 1.00 1.37 1.72 0.71 0.85 1.08 1.59
L/hr 2.80 3.80 5.20 6.50 2.70 3.20 4.10 6.00

Engine Standby rating Prime rating


Engine manufacturer Cummins
Engine model X2.5G2
Configuration 4 cycle, in-line, 3 cylinder diesel
Aspiration Naturally aspirated
Gross engine power output, kWm 27 24.37
BMEP at set rated load, kPa 851 768.1
Bore, mm 91.7
Stroke, mm 127
Rated speed, rpm 1500
Piston speed, m/s 7.62
Compression ratio 18.5:1
Lube oil capacity, L 6.5
Overspeed limit, rpm 1650
Regenerative power, kW 2
Governor type Mechanical - Std
Starting voltage 12 Volts DC

Fuel flow
Maximum fuel flow, L/hr 40
Maximum fuel inlet restriction, mm Hg 258.58
Maximum fuel inlet temperature, °C 60

power.cummins.com
©2017 Cummins Inc. | EMERD-5640-EN (10/17)
Air Standby rating Prime rating
3
Combustion air, m /min 2.30 2.30
Maximum air cleaner restriction, kPa 6.23

Exhaust
3
Exhaust gas flow at set rated load, m /min
Exhaust gas temperature, °C 660 660
Maximum exhaust back pressure, kPa 3.38

Standard set-mounted radiator cooling


Ambient design, °C 50
Fan load, kWm 0.95
Coolant capacity (with radiator), L 15
3
Cooling system air flow, m /sec @ 12.7 mm H2O 0.95
Total heat rejection, Btu/min 1309
Maximum cooling air flow static restriction mm H2O

Weights* Enclosed
Unit dry weight kgs 1415
Unit wet weight kgs 1427
* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Dimensions Length Width Height


Standard enclosed set dimensions mm 2180 987 2006

Genset outline
Enclosed set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

power.cummins.com
©2017 Cummins Inc. | EMERD-5640-EN (10/17)
Alternator data
Connection Temp rise ºC Duty Alternator Voltage
3 phase 125 P PI144F 380-415 V
1 phase 105 P PI144G 220-240 V

Ratings definitions
Emergency Standby Limited-Time Running Prime Power (PRP): Base Load (Continuous)
Power (ESP): Power (LTP): Power (COP):
Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited Time Prime Power (PRP) is in unlimited hours. Continuous
reliable utility source. Running Power (LTP) is in accordance with ISO 8528. Power (COP) is in
Emergency Standby Power accordance with ISO 8528. Ten percent overload accordance with ISO 8528,
(ESP) is in accordance capability is available in ISO 3046, AS 2789,
with ISO 8528. Fuel Stop accordance with ISO 3046, DIN 6271 and BS 5514.
power in accordance with AS 2789, DIN 6271 and
ISO 3046, AS 2789, BS 5514.
DIN 6271 and BS 5514.

Formulas for calculating full load currents:

Three phase output Single phase output

kW x 1000 kW x Single Phase Factor x 1000


Voltage x 1.73 x 0.8 Voltage

For more information contact your local Cummins distributor


or visit power.cummins.com

©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
EMERD-5640-EN (10/17)