Professional Documents
Culture Documents
ET200X EM148 FC Frequency Converter - Manual [A5E00065321-02]
ET200X EM148 FC Frequency Converter - Manual [A5E00065321-02]
ET200X EM148 FC Frequency Converter - Manual [A5E00065321-02]
1
Product Overview
SIMATIC
Wiring
2
EM 148-FC 3
Commissioning and Diagnostics
Frequency Converter
Functions and Technical
Specifications
4
Manual 5
Mode of Functioning
Order Numbers
A
Dimensioned Drawings
B
Index
08/2000
A5E00065321-02
Safety Guidelines
This manual contains notices which you should observe to ensure your own personal safety, as well as
to protect the product and connected equipment. These notices are highlighted in the manual by a
warning triangle and are marked as follows according to the level of danger:
Danger
! indicates that death, severe personal injury or substantial property damage will result if proper precau-
tions are not taken.
Warning
! indicates that death, severe personal injury or substantial property damage can result if proper precau-
tions are not taken.
Caution
! indicates that minor personal injury or property damage can result if proper precautions are not taken.
Note
draws your attention to particularly important information on the product, handling the product, or to a
particular part of the documentation.
Qualified Personnel
Only qualified personnel should be allowed to install and work on this equipment. Qualified persons
are defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and
systems in accordance with established safety practices and standards.
Correct Usage
Note the following:
Warning
! This device and its components may only be used for the applications described in the catalog or the
technical descriptions, and only in connection with devices or components from other manufacturers
which have been approved or recommended by Siemens.
This product can only function correctly and safely if it is transported, stored, set up, and installed cor-
rectly, and operated and maintained as recommended.
Trademarks
SIMATIC, SIMATIC HMI and SIMATIC NET are registered trademarks of SIEMENS AG.
Some of other designations used in these documents are also registered trademarks; the owner’s rights
may be violated if they are used by third parties for their own purposes.
Siemens AG
Bereich Automatisierungs- und Antriebstechnik (A&D)
Geschäftsgebiet Industrie-Automatisierung Siemens AG 2000
Postfach 4848, D- 90327 Nürnberg Technical data subject to change.
EM 148-FC Frequency Converter
Index-2 A5E00065321-02
Siemens Aktiengesellschaft Drawing No. A5E00065321-02
Important Information
Target Group
This manual describes the hardware and the firmware of the EM 148-FC frequency
converter. It is aimed at configuration engineers, commissioning engineers and
maintenance personnel who use the ET 200X with PLC functionality.
Delivery Package
The delivery package (order number 6ES7 198-8FA01-8BA0) consists of several
manuals with the following contents:
Applicability
This manual is valid for the EM 148-FC frequency converter. It contains a
description of the components that were valid at the time the manual was
published. We reserve the right to enclose a product information document
containing up-to-date information about new components and new versions of
components.
Note
You can find an exact list of the contents of the ET 200X manuals in Section 1.3 of
this manual.
We recommend that you begin by reading this section so as to find out which parts
of which manuals are most relevant to you in helping you to do what you want to
do.
Important Information
1 Product Overview
1.1 What is the EM 148-FC Frequency Converter? . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2 Conditions for Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.3 Guide to the ET 200X Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
2 Wiring
2.1 Wiring Rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.2 Wiring the EM 148-FC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.2.1 Preparing the Connecting Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.2.2 Wiring the Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.2.3 Electrical Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
3 Commissioning and Diagnostics
3.1 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.2 Parameter Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.3 Commissioning After a Lengthy Storage Period . . . . . . . . . . . . . . . . . . . . . . 3-4
3.4 Unusual operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3.5 Status Indication by Means of LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
3.6 EM 148-FC Diagnosis with STEP 5 or STEP 7 . . . . . . . . . . . . . . . . . . . . . . 3-7
4 Functions and Technical Specifications
4.1 Cyclic Data Traffic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4.1.1 Output Data Object (Control Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4.1.2 Input Data Object (Feedback Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4.1.3 Error Acknowledgment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.2 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4.2.1 Parameters of the EM 148-FC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4.2.2 Meaning of the Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
4.3 Inching Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
4.3.1 Inching Mode from the Programmable Controller . . . . . . . . . . . . . . . . . . . . 4-16
4.3.2 Inching Mode Using the Hand-Held Controller . . . . . . . . . . . . . . . . . . . . . . . 4-17
4.4 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
5 Mode of Functioning
5.1 Operating Procedure Following Voltage Recovery . . . . . . . . . . . . . . . . . . . 5-2
5.2 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
A Order Numbers
B Dimensioned Drawing
Index
Figures
1-1 Connectors and Indicators of the EM 148-FC Frequency Converter . . . . 1-3
2-1 Power Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
3-1 Structure of the Station Diagnosis (Header), Bytes 9 to 12 . . . . . . . . . . . . 3-8
3-2 Structure of the Station Diagnosis (Record 0, also Included
in Record 1), Bytes 13 to 16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
3-3 Structure of the Station Diagnosis (Record 1), Bytes 17 to 28 . . . . . . . . . 3-9
4-1 Linear and Quadratic Voltage/Frequency Characteristic . . . . . . . . . . . . . . . 4-10
4-2 Frequency Curve with Release Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
4-3 Frequency Curve with External Brake Stopping Time . . . . . . . . . . . . . . . . . 4-13
4-4 Voltage/Frequency Characteristic With and Without Starting Boost . . . . . 4-14
4-5 Voltage/Frequency Characteristic With and Without Continuous Boost . . 4-14
4-6 Frequency Curve With and Without Rounding . . . . . . . . . . . . . . . . . . . . . . . 4-15
5-1 Operating Procedure Following Voltage Recovery . . . . . . . . . . . . . . . . . . . 5-2
5-2 Stopping the Motor by Normal Ramping Down, Renewed Ramping Up . 5-3
5-3 Abrupt Braking of the Motor, Renewed Ramping Up . . . . . . . . . . . . . . . . . . 5-4
5-4 Disabling and Re-Enabling Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
5-5 Rapid Stop, Ramp-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
5-6 Disabling and Re-Enabling the Ramp Generator . . . . . . . . . . . . . . . . . . . . . 5-7
5-7 Interrupting and Continuing Ramp-Up or Ramp-Down . . . . . . . . . . . . . . . . 5-7
5-8 Disabling and Re-Enabling the Setpoint Value . . . . . . . . . . . . . . . . . . . . . . . 5-8
5-9 Change of Direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
B-1 Dimensioned Drawing of the EM 148-FC . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Tables
1-1 Topics of the Manuals in the ET 200X Manual Package . . . . . . . . . . . . . . 1-4
1-2 Separate Manuals for the ET 200X Components . . . . . . . . . . . . . . . . . . . . 1-5
2-1 Accessories Required to Prepare Connecting Cables . . . . . . . . . . . . . . . . 2-4
2-2 Assignment of the Power Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
3-1 Forming Procedure After a Lengthy Storage Period . . . . . . . . . . . . . . . . . 3-4
3-2 Meaning of the LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
3-3 Status Indication by means of LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
3-4 Error Messages in Accordance with the PROFIBUS Standard . . . . . . . . 3-10
3-5 Vendor-Specific Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
4-1 Structure of the Output Data Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4-2 Structure of the Control Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4-3 Structure of the Input Data Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4-4 Structure of the Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4-5 Parameters of the EM 148-FC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4-6 Procedure for Inching Mode from the Programmable Controller . . . . . . . . 4-16
4-7 Procedure for Inching Mode Using the Hand-Held Controller . . . . . . . . . . 4-17
5-1 Effect of the External Brake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
A-1 Frequency Converter – Order Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
A-2 Accessories – Order Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
In This Chapter
View
The figure below shows you the connectors and indicators of the EM 148-FC
frequency converter.
Earthing screw
LEDs
To indicate:
SF: Fault status
STAT: Status
PWR: Power supply
(400 V)
Manual
ET 200X BM 147/C EM 300 EM 148-FC
Contents Distributed PU Basic Motor Frequency Chapter/
I/O Device Module Starter Converter Appendix
Table 1-1 Topics of the Manuals in the ET 200X Manual Package, continued
Manual
ET 200X BM 147/C EM 300 EM 148-FC
Contents Distributed PU Basic Motor Frequency Chapter/
I/O Device Module Starter Converter Appendix
Contents Manual
Using a CP 142-2 (ASI master) CP 142-2
Manual
Order no. 6GK7 142-2AH00-8AA0
In This Chapter
Warning
! This device generates dangerous electrical voltages and controls dangerous
rotating mechanical parts. Correct handling, installation, operation and
maintenance of the device are vital to ensure effective and safe operation.
For safety reasons you must connect all screw-type connectors with the ground
symbol to protective ground.
The EM 148-FC works with voltages of up to 800 V and may still be live for a
short period even after the power supply has been switched off.
The EM 148-FC can in certain circumstances be connected to the power
supply via a residual current-operated circuit breaker (see DIN VDE 0160).
Pins in the power connectors can carry dangerous voltages even when the
motor is at a standstill.
The EM 148-FC ensures internal motor overload protection that complies with
UL508C, Section 42. Alternatively, you can use an external thermistor.
The EM 148-FC must not be used as an emergency stop mechanism (see
EN 60204, 9.2.5.4).
The EM 148-FC must not be used in systems where safety is an issue (e.g.
passenger transport).
There must be a break of at least a minute between the repeated,
simultaneous connection of the supply voltage and the motor (e.g. after the
residual current-operated circuit breaker has switched off).
You must find out whether or not a residual current-operated circuit breaker can
be used depending on the type of network/relevant standards. If you can use a
residual current-operated circuit breaker, the following conditions apply:
– A residual current-operated circuit breaker of type B must be used.
– The fault current of the residual current-operated circuit breaker must be
300 mA.
– The neutral conductor of the supply system must be grounded.
– Only an EM 148-FC can be connected to a residual current-operated circuit
breaker.
Cross- TU = 30 C TU = 40 C TU = 45 C TU = 50 C TU = 55 C
Section
2.5 mm2 19 A 16.5 A 15.0 A 13.5 A 11.6 A
4.0 mm2 26 A 22.6 A 20.5 A 18.5 A 15.9 A
Unused connectors
Seal off unused connectors with screw caps (3RK1 902-0AL00). Only in this way
can the IP 65 degree of protection be complied with.
Accessories
To prepare the connecting cables for the frequency converter, you will need a
crimping tool as well as the accessories listed in the table below. Alternatively, you
can obtain ready-prepared motor connecting cables and power connecting cables
(see Appendix A). The assignment of the power connecting cables does not
comply, however, with the DESINA specification.
Requirements
For X1: Infeed for the Load For X2: Connection of the Load For X3: Loop Through of the
Supply Voltage to the Brake and Thermistor Load Supply Voltage
A flexible 4- or 7-core1) Cu cable A flexible 8-core shielded Cu A flexible 4- or 7-core1) Cu cable
2.5 mm2 or 4.0 mm2 (3 or 6 cable 2.5 / 0.75 mm2 2.5 mm2 or 4.0 mm2 (3 or 6
conductors + protective ground) (3 conductors + protective conductors + protective ground)
ground + 4 conductors)
A connector set A shielded connector set A connector set
2.5 mm2:
3RK1 902-0CA00 2.5 /0.75 mm2: 2.5 mm2: 3RK1 902-0CC00
4.0 mm2: 3RK1 902-0CB00 6ES7 194-1AB00-0XA0 4.0 mm2: 3RK1 902-0CD00
1) 7-core cables are only required if all the power supplies are looped through in accordance with the DESINA
specification.
Pin Assignment
The figure below shows the power connectors of the EM 148-FC. The pin
assignment can be found in the table below.
6 7 8
1 2 3 3 2 1
4 5
4 5 5 4
1 2 3
6 7 8 8 7 6
* These signals are required only for the DESINA specification. They are looped through but
not used by the frequency converter.
Power Supply
To ensure the supply of the EM 148-FC both the supply voltage for the electronic
components and sensors and the load voltage (possibly using a power module)
must be connected to the basic module.
Galvanic Isolation
Warning
! Even when the motor is not being driven, it remains galvanically connected to the
power supply (400 V AC).
EMC Measures/Grounding
The whole of the EM 148-FC must be installed on a metal base.
The screw-type terminal marked with ground symbol on the front of the heat sink
must be connected with a short ground cable to the protective ground of the
system (refer to the corresponding standard).
To avoid EMC problems, particular care must be exercised when shielding the
motor connecting cable. The shields of the motor connecting cable must be
connected:
To the metallic DESINA connector (see Appendix A) on the EM 148-FC in such
a way as to ensure electromagnetic compatibility
To the metal connection housing of the motor via an EMC-compatible, metal
heavy-gauge threaded joint.
The motor housing must be grounded.
Caution
! Short circuits can damage the converter.
3.1 Configuration
You can configure the frequency converter in the following ways:
With STEP 7 using the hardware configuration application
To do this, you will need STEP 7 V5.1.
With PROFIBUS DP standard tools (e.g. COM PROFIBUS)
To do this, you will need the device database (DDB) files of the ET 200X basic
modules BM 141, BM 142 (as of version 4) or BM 143 (as of version 2).
You can download the DDB file:
– On the Internet at http://www.ad.siemens.de/csi_e/gsd
– Using a modem on +49 (911) 737972
Note
If you reparameterize the EM 148-FC during operation, the motor is switched off.
This also means that Reaction to CPU-/Master-STOP is changed.
Result: After you have parameterized Ramp down, Keep last value, or Rapid
stop, the motor is still switched off. A connected motor with a brake will stop
abruptly!
What to do: To prevent this happening, make sure that you only transfer
parameters that have been changed to the module once the motor has been
switched off.
Caution
! If the EM 148-FC is not used for some time, the capacitors in the intermediate
circuit can become conductive. At the rated voltage this can cause irreparable
damage to the EM 148-FC. To avoid this happening, the capacitors must be
reformed. The procedure required to do this depends on the length of the storage
period.
Warning
! The LEDs are electronically controlled. If there is no voltage supplied to the
electronic components and sensors, the LEDs do not light up. However, the power
unit might still be receiving power.
This means the following status indications to the DESINA specification are
possible:
Slave Diagnosis
The slave diagnosis complies with EN 50170, Volume 2, PROFIBUS. Depending
on the DP master, the diagnosis can be read for all DP slaves that comply with the
standard using STEP 5 or STEP 7.
You can find out how to read out the slave diagnosis and learn about its structure
in the chapter on commissioning and diagnostics in the ET 200X Distributed I/O
Device manual.
The structure of the station diagnosis of the EM 148-FC is indicated in the figures
below.
S7 Diagnosis
The S7 diagnostic data of a module is in data records 0 and 1 of the system data
area of the module.
Data record 0 contains 4 bytes of diagnostic data describing the current state of a
module. The data record 1 also contains module-specific diagnostic data. It has 16
bytes in the case of the EM 148-FC.
The records of the S7 diagnosis are included in the station slave diagnosis.
Bytes 13 to 16 of the station diagnosis correspond to record 0 of the S7 diagnosis.
Bytes 13 to 28 correspond to record 1 of the S7 diagnosis. Record 1 contains
record 0 in the first 4 bytes.
Diagnostic Interrupt
If a fault in the frequency converter is supposed to trigger a diagnostic interrupt,
this must be specified during parameter assignment of the EM 148-FC (see
Section 4.2) and the basic module (by enabling the diagnostic interrupt).
7 0 Bit no.
Byte 9 0 0 0 1 0 1 0 0
7 0
Byte 10 01H: Code for S7 diagnostic interrupt
7 0
Byte 11 “Slot” of the module that provides the diagnostic
interrupt (5 to 11)
7 0
Byte 12 00H: Reserved
7 6 4 3 2 1 0 Bit no.
Byte 13
Module malfunct., i.e. a problem has been detected
Internal fault in the module
External fault: module no longer addressable
Channel fault in the module
No load voltage (see note below)
Module is not parameterized.
Parameter assignment error
7 0
Byte 14 1FH: Module class: digital module
7 3 0
Byte 15
Time monitoring (watchdog) triggered
7 3 2 0
Byte 16
ROM error
RAM error
Figure 3-2 Structure of the Station Diagnosis (Record 0, also Included in Record 1), Bytes
13 to 16
7 0 Bit no.
Byte 17 7DH: Channel type: frequency converter
7 0
Byte 18 20H: Length of the channel-specific diagnosis
7 0
Byte 19 01H: Number of channels
7 0
Byte 20
Diagnostic event on channel 0 of the module
7 4 3 2 0
Byte 21
Undervoltage (see note below)
Overvoltage
Overload
Bytes 22 Unassigned
and 23
7 0
Byte 24
Actuator shut down
Bytes Unassigned
25 to 28
Note
If the station diagnosis, Undervoltage (byte 21/bit 2) exists, the diagnosis
Missing load voltage (byte 13/bit 4) is not reported.
If the load voltage is switched on and off, the errors Undervoltage, Overvoltage
and Actuator shut down can occur briefly.
Address Description
Word 0 (bytes 0 and 1) Control word (see below)
Word 1 (bytes 2 and 3) Main setpoint value = setpoint value for motor frequency
(resolution = 0.01 Hz)
The EM 148-FC is controlled in accordance with the PROFIDRIVE profile using the
bits in the control word. The control word is divided up into bytes and bits as
follows:
Address Description
Word 0 (bytes 0 and 1) Status word (see below)
Word 1 (bytes 2 and 3) Actual value of the motor frequency (resolution 0.01 Hz)
The bits in the status word return the status of the EM 148-FC. The status word is
divided up into bytes and bits as follows:
4.2 Parameters
The parameter names listed in bold in the tables are explained in further detail in
Section 4.2.2.
Reaction to CPU-/Master-STOP
This parameter controls the behavior of the frequency converter if the controlling
CPU goes into STOP or if DP communication fails.
Rapid stop:
Standstill in half the ramp-down time
Ramp down:
Ramp down to standstill in ramp-down time
Coast to a standstill:
Voltage disconnection (if the External brake control parameter is set to
Enable, the external brake is also activated).
Keep last value:
Motor continues to run with the last valid setpoint value.
Behavior after CPU/Master restart:
After the CPU is restarted, the frequency converter can continue to run without
interruption when the last valid control word is sent again in the startup OB of the
CPU. For this to happen, the control word must be stored in a retentive memory
area.
After the DP master restarts, the frequency converter carries out an emergency
stop by means of voltage disconnection and the external brake and must then be
reparameterized.
Operation in Europe/USA
This parameter defines the unit for the Rated power of motor parameter:
EUR: Rated power of motor in kW (1 kW = 1.341 hp)
USA: Rated power of motor in hp (1 hp = 0.746 kW)
Note
If the thermistor is not being used by the motor, you can use it to monitor the
motor line:
1. In the motor terminal box, bridge the thermistor cables of the supply line.
2. Enable the Thermistor monitoring of the motor parameter.
3. Evaluate the diagnosis (Actuator error).
Pulse Frequency
If low-noise operation is not necessarily required, the losses in the frequency
converter and radio interference emissions can be reduced by means of a lower
pulse frequency of the output voltage.
Frequency Suppression
Mechanical resonances can be avoided with this parameter. Setpoint values within
the range of the frequency specified here ±2 Hz are not tolerated. The following
are used instead as the substitute setpoint value:
If fsuppress – 2 Hz ≤ fsetpoint < fsuppress:
fsubstitute = fsuppress – 2 Hz
Inching Frequency
Inching Mode (see Section 4.3) turns the motor in small increments at the motor
frequency set here.
Control Mode
This parameter determines the relationship between the frequency output by the
frequency converter and the voltage.
Linear voltage/frequency characteristic:
Linear voltage rise from the minimum voltage when f = 0 to the rated voltage at
the rated frequency of the motor.
This adjustment ensures an almost constant torque until the rated operating
speed is reached.
Quadratic voltage/frequency characteristic:
A slow increase in voltage at the start and therefore reduced torque.
This adjustment is particularly suitable for machines such as rotary pumps or
fans, since these have a perfect squared torque/frequency curve.
A
UN
0 fN f
Ramp-Up Time
This parameter controls the acceleration of the motor. The motor accelerates from
the minimum to the maximum parameterized motor frequency in the time specified.
Note
If the ramp-up time set is too short, this can result in the converter switching off
due to excess current.
255
Parameter value = 30 s * = 15
510 s * 1
This formula only applies when fmax = fsetpoint
Ramp-Down Time
This parameter controls the deceleration of the motor. The motor brakes from the
maximum to the minimum parameterized motor frequency in the time specified.
Note
If the ramp-down time set is too short, this can result in the converter switching off
due to overvoltage.
f Switch on
fmax
fsetpoint
fmin
0 t
Release delay
Brake 1
0
Note
The value for the External brake release delay parameter should be slightly
greater than the time actually required to release the external brake.
f Switch off
fmax
fsetpoint
fmin
0 t
External brake stopping time
Brake 1
0
Note
The value for the External brake stopping time parameter should be slightly
greater than the time actually required to apply the external brake.
Starting Boost
This parameter controls the voltage/frequency characteristic of the frequency
converter. When the motor starts, the motor voltage is increased until the motor
current exceeds the motor’s rated current by the value specified here.
Consequently, a higher ramp-up torque can be achieved.
A
UN
Starting boost
0 fN f
Continuous Boost
This parameter controls the voltage/frequency characteristic of the frequency
converter. Until the motor’s rated voltage is reached, the motor voltage is
increased until the motor current exceeds the motor’s rated current by the value
specified here. Consequently, a high acceleration torque can be achieved up to the
rated frequency.
A
UN
Continuous
boost
0 fN f
Smoothing
This parameter controls the frequency curve when the motor ramps up and down.
This ensures a smooth run, which is important for textile processing or conveyor
systems, for example. The ramp-up and ramp-down times increase by the time
specified here.
0 t
Smoothing
Counterclockwise Rotation
This parameter allows you to prevent the motor running counterclockwise.
Enable:
The motor can run in both directions.
Disable:
The motor cannot run counterclockwise. All the switch-on commands start
clockwise rotation.
Prerequisites
The following prerequisites must be met to execute inching mode from the
programmable controller:
Control bits 0 to 2 must be set
Control bit 3 must be reset
Setpoint value = 0
Control bit 10 must be set
Procedure
Table 4-6 Procedure for Inching Mode from the Programmable Controller
Step Effect
Control bit 8 or 9 is set Ramp-up to the parameterized motor
frequency required for inching mode
(Inching frequency parameter)
Control bit is reset again Ramp-down to standstill
If control bits 8 and 9 are set at the same time, the motor stops.
Prerequisites
The “local” operating mode (manual operation) must be set for inching mode using
the hand-held controller. To do this, proceed as follows:
1. In case you haven’t already done it, connect the hand-held controller to the
“local” subminiature D female connector of the EM 148-FC.
2. Press the “local” key on the hand-held controller.
If the motor is running at this point, it will be stopped by means of the normal
ramp-down.
Procedure
Table 4-7 Procedure for Inching Mode Using the Hand-Held Controller
Step Effect
The “right” or “left” key is pressed and held Ramp-up to the parameterized motor
down frequency required for inching mode
(Inching frequency parameter)
The key is released again Ramp-down to standstill
During manual operation the feedback interface (see Section 4.1.2) continues to
be updated. The active operating mode is displayed in bit 9 of the status word.
Faults indicated by bit 3 in the status word are acknowledged automatically.
Warning
! If the connecting cable for the hand-held controller is disconnected from the EM
148-FC during manual operation, the frequency converter will remain in this
operating mode. It can then no longer be addressed by the programmable
controller.
Warning
! If control bits 0 to 6 and 10 are set (e. g. control word 047FH) when you terminate
manual operation, the motor will automatically ramp up to the setpoint frequency.
This happens, for example, if the motor was running when you switched to manual
operation.
You can avoid this potentially dangerous situation if the programmable controller
detects manual mode by evaluating status bit 9 and resets one of the control bits
0 to 3.
Module-Specific Data
At 16 kHz Max. 1.05 A
Output overload current
Cable length Max. 10 m
At 55 °C 3.1 A
Voltages, Currents, Potentials
Stored energy time in 20 ms at the following
Power input for the the event of a power maximum currents:
electronic components failure
(from backplane bus)
For Ue < 380 V 1.85 A
From supply voltage Max. 50 mA For Ue ≥ 380 V 2.1 A
for electronic
components and Continuous input Max. 16 A
sensors current when the load
supply voltage is looped
From load voltage Max. 150 mA
through
Galvanic isolation
Efficacy of the Typically 97 %
Between load Yes converter
voltages
Power loss of the Typically 30 W
Between load Yes module
voltage and all other
circuit components Status, Interrupts, Diagnostics
Permissible potential Status indication with To DESINA
difference LEDs specification
Between different 1500 V AC Group error Red LED (”SF”)
circuits indication
Insulation tested at 2830 V DC Status indication Yellow LED (“STAT”)
Input voltage Monitoring of the Green LED (“PWR”)
Power unit power supply
In accordance with 340 V to 500 V AC (power unit)
VDE 340 V to 480 V AC Interrupts Diagnostic interrupt
In accordance with Diagnosis Yes
UL
System frequency 47 Hz to 63 Hz 1 Continuous currents > 1.9 A are only permissible
if at least one of the following conditions are met:
Network filter Integrated, type A
– Ambient temperature < 50 °C
Overload capacity 150 % for 60 s in – Continuous input current when the load supply
relation to the rated voltage is looped through < 8 A
current
In This Chapter
Set permissives:
Ctrl. word = 0000 1100 0111 0110
Specify setpoint value for motor
frequency
No Acknowledge fault
Ctrl. bit 7 = 1
Set operating condition
Ctrl. bit 0 = 1
Enable operation
Ctrl. bit 3 = 1
St. bit 2 = 1? No
Yes
Ramp up
5.2 Applications
The sequences required in different applications are explained in the status
diagrams below.
In these diagrams the effect of the external brake is represented by the statuses
“0” and “1”.
0 t
Brake 1
0
Figure 5-2 Stopping the Motor by Normal Ramping Down, Renewed Ramping Up
0 t
Brake 1
0
The frequency converter is switched off immediately. The motor is stopped by the
external brake. If there isn’t an external brake, the motor will stop of its own
accord.
The AUS2 command has a higher priority than AUS1 and AUS3. In other words, a
normal ramp down or an abrupt stop is canceled by AUS2.
Control bits
Disable operation Enable operation
Bit 3 1
0
t
f
fmax
fsetpoint
Brake 1
0
t
The frequency converter is switched off immediately. The motor is stopped by the
external brake. If there isn’t an external brake, the motor will stop of its own
accord.
In contrast to the AUS2 command (see above), the frequency converter does not
enter the starting lockout state. It is therefore not necessary to switch on control
bit 0 again.
“Disable operation” does not have a higher priority than AUS1 and AUS3. In other
words, it will not affect a ramp down or rapid stop that has already started.
0 t
Parameterized ramp-down time
Brake 1
0
Caution
! Frequent braking operations with high power consumption can heat up the motor
significantly, possibly resulting in excess temperature.
0 t
Brake 1
0
Bit x 1
0
Bit 5 1
0
t
f
fmax
fsetpoint
0 t
Brake 1
0
Control bits
Disable setpoint value Enable setpoint value
Bit 6 1
0
t
f
fmax
fsetpoint
fmin
0 t
Brake 1
0
Change of Direction
Control bits
Clockwise rotation
Bit 11 1
0
Counterclockwise rotation No counterclockwise rotation
Bit 12 1
0
t
f
fmax
fsetpoint
Clockwise
rotation
0 t
Counter-
clock-
wise
rotation
fsetpoint
Frequency Converter
Accessories
120 28.25
53.5 181
265
270
160.5
147
B
Braking, the motor, 5-4 G
Galvanic isolation, 2-7
Grounding, 2-7
C Guide, 1-4
Certificates and approvals, iv
Change, 5-8
Commissioning, 3-4 I
Conditions for use, 1-3 Inching frequency, 4-9
Configuration, 3-2 Inching mode, 4-16
Continuous boost, 4-14 Input data object, structure, 4-4
Control interface, 4-2
Control mode, 4-10
Control word, structure, 4-2 L
Counterclockwise rotation, 4-15
LED, 3-6
D M
Data traffic, cyclic, 4-2
Mode of functioning, 5-1
DDB (device database) file, 3-2
Diagnosis with
STEP 5, 3-7
STEP 7, 3-7 O
Dimensioned drawing, B-1 Operation, disabling/enabling, 5-5
Operation in Europe/USA, 4-8
Order numbers, A-1
E Output data object, structure, 4-2
Electrical configuration, 2-7
EM 148-FC frequency converter
connectors, 1-3 P
features, 1-2 Parameter assignment, 3-2
indicators, 1-3 Parameters, EM 148-FC frequency converter,
parameters, 4-6 4-6
view of, 1-3 Pin assignment, 2-5
wiring, 2-1, 2-4 Power connections, wiring, 2-5
EMC measures, 2-7 Power connectors, wiring, 2-3
Error acknowledgment, 4-5 Power supply, 2-7
External brake control, 4-12 Pulse frequency, 4-9
R T
Ramp generator, disabling/enabling, 5-7 Thermistor monitoring of motor, 4-9
Ramp-down time, 4-11
Ramp-up time, 4-11
Rapid stop, 5-6 V
Release delay, external brake, 4-12
Voltage recovery, 5-2
Reparameterization, during operation, 3-3
Rules, wiring, 2-2
W
S Wiring
EM 148-FC frequency converter, 2-1, 2-4
Smoothing, 4-15
power connections, 2-5
Standards, iv
power connectors, 2-3
Starting boost, 4-14
rules, 2-2
Status word, structure, 4-4
Stopping, the motor, 5-3
Stopping time, external brake, 4-13
From:
Your Name: . .................................................................
Your Title: . ............................................................
Company Name: . ............................................................
Street: .............................................................
City, Zip Code: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Country: .............................................................
Phone: .............................................................
Automotive Pharmaceutical
Chemical Plastic
Electrical Machinery Pulp and Paper
Food Textiles
Instrument and Control Transportation
Nonelectrical Machinery Other . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Petrochemical
Please give each of the following questions your own personal mark within the range
from 1 (very good) to 5 (poor).
Additional comments:
. ..................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .EM
. . 148-FC
. . . . . .Frequency
. . . . . . . .Converter
......
2 A5E00065321-02
Siemens AG
A&D AS E82
Postfach 1963
D–92209 Amberg
Federal Republic of Germany
From:
Your Name: . .................................................................
Your Title: . ............................................................
Company Name: . ............................................................
Street: .............................................................
City, Zip Code: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Country: .............................................................
Phone: .............................................................
Automotive Pharmaceutical
Chemical Plastic
Electrical Machinery Pulp and Paper
Food Textiles
Instrument and Control Transportation
Nonelectrical Machinery Other . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Petrochemical
Please give each of the following questions your own personal mark within the range
from 1 (very good) to 5 (poor).
Additional comments:
. ..................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
...................................................................................
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .EM
. . 148-FC
. . . . . .Frequency
. . . . . . . .Converter
......
2 A5E00065321-02