It is important to read, understand and follow all instructions shipped with this
product. In addition, listed below are some other important safety instructions and
precautions you should follow.
PLANNING
• If suitable warning equipment is not selected, the installation site for the siren is
not selected properly or the siren is not installed properly, it may not produce the
intended optimum audible warning. Follow Federal Emergency Management
Agency (FEMA) recommendations.
• If sirens are not activated in a timely manner when an emergency condition exists,
they cannot provide the intended audible warning. It is imperative that
knowledgeable people, who are provided with the necessary information, are
available at all times to authorize the activation of the sirens.
• When sirens are used out of doors, people indoors may not be able to hear the
warning signals. Separate warning devices or procedures may be needed to
effectively warn people indoors.
• Activating the sirens may not result in people taking the desired actions if those to
be warned are not properly trained about the meaning of siren sounds. Siren users
should follow FEMA recommendations and instruct those to be warned of correct
actions to be taken.
• A siren that does not work will not provide any warning. After installation,
service, or maintenance, test the siren system to confirm that it is operating
properly. Test the system regularly to confirm that it will be operational in an
emergency.
• If future service and operating personnel do not have these instructions to refer to,
the siren system may not provide the intended audible warning and service
personnel may be exposed to permanent hearing loss, bodily injury, or death. File
these instructions in a safe place and refer to them periodically. Give a copy of
these instructions to new recruits and trainees. Also give a copy to anyone who is
going to service or repair the siren.
i
SAFETY NOTICES
People’s lives depend on your safe installation, service and operation of our products.
It is important to read, understand and follow all instructions shipped with this
product. In addition, listed below are some other important safety instructions and
precautions you should follow:
• After installation or service, test the siren system to confirm that it is operating
properly. Test the system regularly to confirm that it will be operational in an
emergency.
• If future service personnel do not have these warnings and all other instructions
shipped with the equipment to refer to, the siren system may not provide the
intended audible warning and service personnel may be exposed to death,
permanent hearing loss, or other bodily injury. File these instructions in a safe
place and refer to them periodically. Give a copy of these instructions to new
recruits and trainees. Also, give a copy to anyone who is going to service or
repair the sirens. For additional copies, call the Federal Warning Systems
Customer Care Center at 800-524-3021 or write to them at 2645 Federal Signal
Drive, University Park, IL 60466.
OPERATION
Failure to understand the capabilities and limitations of your siren system could result
in permanent hearing loss, other serious injuries or death to persons too close to the
sirens when you activate them or to those you need to warn. Carefully read and
thoroughly understand all safety notices in this manual and all operations-related-
items in all instruction manuals shipped with equipment. Thoroughly discuss all
contingency plans with those responsible for warning people in your community,
company, or jurisdiction.
ii
WARNING
iii
Limited Warranty
The Signal Division, Federal Signal Corporation, warrants each new product to be
free from defects in material and workmanship, under normal use and service, for a
period of two years on parts replacement and bench labor (one year for Informer,
EAS, and Federal software products) from the date of delivery to the first user-
purchaser. Federal Warning Systems warrants every 2001 Siren (Top of pole only)
to be free from defects in material, per our standard warranty, under normal use and
service for a period of five years on parts replacement.
Federal will provide warranty for any unit which is delivered, transported prepaid, to
the Federal factory or designated authorized warranty service center for
examination and such examination reveals a defect in material and/or workmanship.
This warranty does not cover travel expenses, the cost of specialized equipment for
gaining access to the product, or labor changes for removal and re-installation of the
product. The Federal Signal Corporation warranty shall not apply to components or
accessories that have a separate warranty by the original manufacturer, such as,
but not limited to, batteries.
This warranty does not extend to any unit which has been subjected to abuse,
misuse, improper installation or which has been inadequately maintained, nor to
units which have problems related to service or modification at any facility other than
Federal factory or authorized warranty service centers. Moreover, Federal shall
have no liability with respect to defects arising in Products through any cause other
than ordinary use (such as, for example, accident, fire, lightning, water damage, or
other remaining acts of god).
iv
TABLE OF CONTENTS
Paragraph Page
SECTION I - CHARACTERISTICS
SECTION II - SPECIFICATIONS
LIST OF ILLUSTRATIONS
Figure Page
iv
SECTION I
CHARACTERISTICS
1-1. GENERAL.
1-1
SECTION II
SPECIFICATIONS
2-1. CONTROLLER SPECIFICATIONS
Electrical
AC Power Inputs .............. ............. 120 or 208 - 240 VAC +/- 10%, 50-60 Hz
12VDC Battery Input........ ............. 11 - 15 VDC @ JP5-2
48VDC Battery Input........ ............. 14 - 60 VDC @ JP5-4
Input Current @120 VAC......... ............ 180 mA AC (maximum)
Input Current @12 VDC ...................... 460 mA DC (maximum)
Relay Outputs .... ............................ SPST (2 relays standard, 4 relays maximum)
5 A @ 30 VDC
5 A @ 240 VAC
Relay Output Timings .................... 0.5 seconds to 999 seconds
6 user programmable functions are available in addition to the 5 preset functions: ARM, DISARM, REPORT, GROWL TEST,
and MASTER RESET. Wildcard options can be used for each of the DTMF strings.
Two-Tone Sequential
Single Tone
Tone Accuracy +
/- 1.5%
Minimum Tone Spacing 5.0%
FSK
Baud rate 1200 bps
Modem type MSK (minimal shift key)
Mark frequency 1200 Hz
Space frequency 1800 Hz
Error checking 16 bit CRC
Relay Outputs
4 relay outputs SPST (2 relays standard, 4 relays max.)
Contact Rating 5 A @ 28 VDC
5 A @ 240 VAC
2-1
Audio Output (Optional)
Output Voltage >2 V peak to peak
Maximum Load 8 Ohms
Total Harmonic Distortion < 10% @ 1 kHz Sinewave
Serial Communications
Environmental
Operating Temperature -30 to +60° C
Dimensions (H x W x D)
Height 13.50 ”
Width 9.84 ”
Depth 6.00 ”
Frequency Spread +
/- 4.9 MHz for 30 - 50 MHz,
+
/- 1.5 MHz for 150 - 174 MHz,
+
/- 8.0 MHz for 450 - 470 MHz
Freq stability over temp range =/< 2.5ppm from -30°C to +60°C
Sensitivity - 12dB SINAD =/< 0.35 uV for 12 dB SINAD per EIA-603, Part 4.1.4
2-2
Audio Output with
1KHz tone at 3KHz deviation 0.8 Vp-p +/- 0.20 Vp-p
Audio frequency response 300 Hz – 3000 Hz, +/- 1 dB, w/ 6 dB per octave de-emphasis
Hum and Noise -35 dB relative to full quieting signal w/1 kHz tone @ 3 kHz
deviation
Audio distortion with
1Kc tone at 3Kc deviation < 10%
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
CAUTION
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference
by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
2-3
SECTION III
INSTALLATION
DANGER
If the controller is to be used in extremely hot climates, the
Electrocution or severe personal injury can controller should always be located out of the direct path
occur when making electrical connections, of the sun.
drilling holes, or lifting equipment. Therefore,
installation should be performed by If the antenna is to be mounted directly to the
experienced electricians in accordance with control cabinet, make sure the cabinet is mounted on the
national and local electrical codes acting under side of the pole facing the base station antenna. The FC
the direction of the installation crew safety unit has three 5/16" mounting holes located on both the top
foreman. and bottom mounting flanges. 1/2" conduit fitting
knockouts are provided in the bottom of the FC cabinet for
AC power and siren control conduit connections. A ground
3-1. SIREN CONTROLLER INSTALLATION stud is provided in the bottom of the FC cabinet, which
must be connected to earth ground.
The information in this section provides guidelines to
aid the user. The FC series controllers are factory installed
in 2001DC siren control cabinets. Therefore, parts A – C
of this section are not applicable to 2001DC controllers.
WARNING
A. Preliminary
B. Controller Mounting
3-1
C. Electrical Connections
3. Follow the instructions included with the
WARNING lightning protector (supplied with controller) and install in
the AC service disconnect.
Install the siren electrical system in compliance with
local electrical codes and NEC recommendations. 4. Set the AC input voltage selector switch
Federal Signal also recommends that all user- located near the bottom right of the controller for either
installed conduit connections enter from bottom of 110 or 220 VAC input voltage. Push the switch up for 110
cabinet. VAC or down for 220 VAC. Route two 12AWG wires
between the fused disconnect and the AC input at JP19(see
Figure 3-2).
CAUTION
SIREN UNITS AND CONTROL UNITS MUST 5. Route a 6AWG ground wire from the earth
BE SOLIDLY CONNECTED TO AN EARTH grounding rod to the FC cabinet ground stud.
GROUND. If the siren is installed on a building,
ground the system to a metallic object known to be 6. Route ½” conduit between the conduit
grounded. For pole mounted installations, drive a fittings on the bottom of the FC control cabinet and the
metal rod or bar at least eight feet into the ground, siren motor starter cabinet.
as close as practical to the base of the pole. FOR
MAXIMUM PROTECTION, USE A SEPARATE, 7. Route two 12AWG wires between JP18 on
CONTINUOUS 6AWG OR LARGER WIRE the FC circuit board and the siren motor contactor as
FROM THE SIREN FRAME TO GROUND AND follows. Connect one wire between JP18-8 of the FC
FROM THE CABINET OF EACH SIREN UNIT control and 3 of the contactor. Connect one wire between
TO GROUND. JP18-7 and L1 of the contactor (see figure 3-2). Make
other connections to the relay outputs at JP18 as necessary.
1. Install two ½” user supplied conduit fittings 8. If the siren is to be controlled remotely via a
bottom of the FC cabinet. momentary contact closure, apply the contact closure to
the appropriate input on JP12 (see Figure 5-1 for pin-outs
2. Route ½” conduit (steel preferred) between a of connectors). The wire run from the contact to JP12
user supplied fused disconnect switch, and the conduit must not exceed 50’. A model TRC1020 can be purchased
fittings in the bottom of the FC cabinet. Fuse the for each function if longer wire runs are required. The
disconnect switch with a 1 Amp fast acting fuse. inputs on JP12 require 1-second contact closures.
3-2
D. Optional DC Power Connections
The FC can also operate from a 12 VDC battery or a filtered power supply between 11 to 15 VDC or 14 to 60 VDC. The
DC power connections are made at JP5.
The FC provides an adjustable audio output at JP6. R32 adjusts the audio output level at JP6-1 between 0 and 2 Vp-p.
LED Indicators
3-3
JP6 Test Speaker
1 – 0 to 2 V p-p, Audio Source: Receiver Audio during P.A. functions,
Siren Audio during Electronic Siren functions.
2 – Ground.
JP12 Remote Activation and Sensor Inputs (#1 @ right edge of connector)
1 – Ground.
2 – Remote Activation Input #1, Activates Functions under code 1,
dry Contact closure < 1 k ohms.
3 – Ground.
4 – Remote Activation Input #2, Activates Functions under code 2,
dry Contact closure < 1 k ohms.
5 – Ground.
6 – Remote Activation Input #3, Activates Functions under code 3,
dry Contact closure < 1 k ohms.
7 – Ground.
8 – Remote Activation Input #4, Activates Functions under code 4,
dry Contact closure < 1 k ohms.
9 – Ground.
10 – Rotation Sensor Input (Current Sensor), dry Contact closure < 1 k ohms.
11 – Ground.
12 – Remote AC Sensor Input, dry Contact closure < 1 k ohms.
3-4
JP14 Short to Test Relay Output #1
1 – Short to pin 2, to engage Relay output #1.
JP18 Relay Outputs, 3 Amps, up to 240 VAC, (#1 @ right edge of connector)
1 – Relay 4, N.O. or N.C., depending on jumper JU2
2 – Relay 4, Common
3 – Relay 3, N.O. or N.C., depending on jumper JU1
4 – Relay 3, Common
5 – Relay 2, N.O.
6 – Relay 2, Common
7 – Relay 1, N.O.
8 – Relay 1, Common
JP20 Spare
1 – Directly to processor pin #54 (ADC7).
2 – Ground.
P1 Transceiver Interface
1 – Transmit audio, DC isolated, 0 to 1 Vp-p
2 – Receive audio, DC isolated, 350 mVp-p to 3 Vp-p
3 – PTT not, goes low during transmit
4 – Ground
5 – +12 Volts DC, 1 Amp max. current.
6 – Carrier Detect not, set low during receive
7 – No connection
8 – Ground
9 – Ground
TP1 RX Data
Receive data from digital modem IC, 0 to 5 Volts.
TP3 Receive audio level set - Receive audio set to 1 Vp-p using R58
TP6 DTMF Decoder STD - Goes low whenever a DTMF digit is being decoded.
3-5
TP9 8 Volt Regulated power supply
TP10 Ground
S2 Local Activation #1
Press and hold for ½ second, Activates Functions under code 1.
S3 Local Activation #2
Press and hold for ½ second, Activates Functions under code 2.
S4 Local Activation #3
Press and hold for ½ second, Activates Functions under code 3.
S5 Local Activation #4
Press and hold for ½ second, Activates Functions under code 4.
S6 Processor Reset
3-6
3-2. FACTORS AFFECTING RADIO RECEPTION 2. It is important to arrange the base station
AND ANTENNA CONNECTION keying circuitry so that the microphone is
disconnected when the tones are transmitted to
WARNING prevent microphone noise from distorting the signal.
If the Radio system is not installed and calibrated 3. To ensure good frequency response, the
properly, the controller may not receive the activation output of the tone encoder must be properly matched
signals. This may cause the siren to fail and not to the transmitter. Adjust the transmitter according to
operate in an emergency resulting in extensive the manufacturer's instructions to provide the proper
property damage or death. level of deviation. For best results, the transmitter
deviation for a single or two-tone system should be
3.3 kHz, a DTMF system's deviation should be set at
The radio network (transmitter, receiver and decoder) 3.0 kHz and a digital system should be set to 4 kHz.
is the vital link to proper controller operation. As such it is Key the transmitter, and set PL/DPL to 750 Hz, then
imperative that the factors shown below, which could strip PL/DPL and set DTMF/Tone deviation to
affect radio reception, be considered during installation. 3.0/3.3 kHz.
F. The following paragraphs pertain to the Other local siren sites may have the same activation
operation of the transmitter, tone-generating equipment, code. Take appropriate precautionary measures.
and other equipment used at the base station.
3-7
SECTION IV
RF RECEIVER DESCRIPTION, ALIGNMENT AND TESTING
The Receiver Module is a fully shielded receiver • Excellent selectivity, able to receive its signal
that plugs into the FC controller. It is available in Low, while rejecting others.
High and UHF bands. Narrow band models are also
available. • Clean, low distortion recovered audio.
The FC control board provided power and adjusts the RX • Noise based squelch circuit, doesn’t open receiver
frequency of the receiver. in high radio noise environments i.e., near
computers etc.
4-2. FEATURES
4-3. TERMINAL STRIPS & JACKS, CONTROLS
• Small size.
Connectors and Jacks:
• Rugged construction utilizing surface mount
components. J3
Shield Ground
• Shielded receiver assembly to prevent Center Antenna RF Input
interference.
J4
• Available in 3 frequency bands from 30 MHZ to Pin 1 Ground
450 MHz. Pin 2 +8 VDC input
Pin 3 Clock line to synthesizer
• Low current draw, excellent for battery powered Pin 4 Data line to synthesizer
operation. Pin 5 Latch Enable line to synthesizer
Pin 6 Carrier Detect (goes low with carrier)
• Synthesized frequency selection. Pin 7 De-emphasized receive audio
Pin 8 Flat receive audio
• Wide temperature operating range.
Controls:
• Excellent sensitivity. Squelch control = R1
4-1
4-4. THEORY OF OPERATION
4-2
CAUTION Setting the Synthesizer on frequency;
Remove power and use appropriate ESD Using a service monitor set in receive mode,
protection before removing or installing the monitor the frequency of the VCO by placing a pickup
receiver on the control board to avoid damage loop on top of the synthesizer, U8.
to components.
The VCO frequency should be the receive
NOTICE frequency - 21.4mHz, unless the unit is a Lowband VHF
unit, in which case the frequency will be 21.4 MHz + the
All receivers have been carefully tested and receive frequency.
aligned at the factory prior to shipment and,
under normal operating conditions and use, Adjust the frequency of the VCO using the
should not require attention beyond that trimmer cap in TCXO U3 until the frequency is within +/-
normally given to electronic equipment. 300Hz.
Replacement of a critical or major component
may require subsequent realignment of the
receiver. Receiver alignment should be
performed only by persons experienced in
this work using the proper test equipment.
4-3
Aligning the receiver; reduce the level of the RF signal from the service monitor
until the SINAD meter reads 12dB. This should be less
Using a service monitor set in generate mode, than 0.35uV for all bands.
inject an unmodulated RF carrier signal into the receiver.
With the RF level at 12dB SINAD, monitor Carrier
Connect an Oscilloscope to TP1. Set the Detect LED on the FCM board and adjust the squelch pot
Oscilloscope for 20mV per Division, Bandwidth limiting (R1) until the LED just comes on.
On, and a DC offset of 0.60 to 1.0Volts, whatever is
required to see the trace on the scope.
4-6. TCS/DCS PROGRAMMING
Turn up the signal level into the receiver until the
voltage on TP1 begins to rise.
The optional TCS/DCS decoder will normally come
Adjust the coils in FL1 and then FL2 for the most preprogrammed from the factory. If field reprogramming
voltage on TP1. TP1 will only rise to about 2 volts so it is desired, set switches 1 thru 12 as per the table in figure
will be necessary to turn down the level from the service 4-2.
monitor during the tuning process.
With the unit oriented with JP1 at the bottom,
Re-tune the coils in FL1 and FL2 after the first switch 1 is the left most switch and a “0” from the
pass through, as tuning the stages ahead of a coil can programming table would be with the switch in the up or
change it’s tuning. on position.
Inject a 100uV signal into the receiver and In Tone coded squelch mode, switches 7 thru 12
modulate the signal with a 1kHz tone at 3kHz deviation. must be in the up or “1” down or off position.
Monitor the receive audio at JP9 pin 7, or an In Digital coded squelch mode switches 1 thru 7
equivalent point, on the FCM board. With an Oscilloscope, set the digital code, switch 10 sets the polarity of the
carefully adjust coil L1 for the most level. transmit data, switch 11 sets the polarity of the receive data
and switch 12 must be in the up or “0” position, indicating
The level at JP9 pin 7 should be 800mVp-p +/- that the unit is set for digital coded squelch.
200mv.
The transmit data polarity can only be set with the
Using R58 on the FCM board, adjust the level at unit plugged into a controller which is connected to a
TP3 to 1Vpp. transmitter of the same type that will be used in the final
installation. The polarity switch should be set to
Connect a Distortion meter to TP3 on the FCM whichever position causes other units of the same type to
board and slowly adjust variable cap C46 for lowest decode or, if a service monitor is available that decodes
distortion. Should be less than 3.0%. digital codes, which ever switch position causes the
monitor to decode.
Connect a SINAD meter to TP3 of the FCM board and
4-4
Figure 4-1. PL Programming Chart
4-5
SECTION V
MAINTENANCE, SERVICE AND SPARE PARTS
5-1. PREVENTIVE MAINTENANCE
2. Re-connect power.
Test the Siren Controller for proper operation at least
once a month. A daily test at noon, curfew, or other 3. Check the voltage at test point TP10 for 13 to
selected time is preferred. This not only enhances the 17 VDC. The “POWER” LED, D32, should be on.
usefulness of the siren, but also instills public confidence
in the reliability of the warning system. 4. Check the voltage at test point TP9 for 8.0
VDC +/- 0.25 VDC.
In order to minimize the possibility of Siren
Controller failure, annual inspection and maintenance is 5. Check the voltage at test point TP8 for 5.0VDC
desirable. This schedule is only a suggested guideline. It /- 0.25 VDC.
+
3. Check contacts of the control relay(s). Replace FWS Customer Care Center
relay(s) if contacts are excessively worn. Signal Division
Federal Signal Corporation
4. Test the controller for proper operation. All 2645 Federal Signal Drive
functions of the controller should be tested locally and via University Park, Illinois 60466
radio when applicable. 800-524-3021
Refer to figure 5-1 at the end of this section for F1 ............................. 148A142A-01
component locations. F2 ............................. 148A135
RLY1-RLY4 ............ 131195
1. Remove AC power from the service disconnect CTCSS ..................... 2001107
and check F1 and F2 on the control board. ANT. CABLE .......... 175902A-07
BULKHEAD ........... 124A056
CAUTION MAIN PC BOARD.. 2005023
5-1
Figure 5-1. FC Assembly Drawing
5-2
FEDERAL SIGNAL CORPORATION
FC SERIES
SIREN CONTROLLER
255294H
11/05 Copyright 2005 Federal Signal Corporation
Printed in U.S.A. Price $15