Make sure that the personnel has read this manual and under-
stood all instructions relating to safety.
OK
92
96
92
91 96
96
PEM555_D00016_00_Q_XXEN/04.2014 1
Quick start: PEM555
Connection
1. Connect the device according the wiring diagram. The con- 2. Line protection: 6 A fuse recommended. If being supplied
nections are located on the rear of the device. Connect the from an IT system, both lines have to be protected by a fuse.
PEM555 to the supply voltage (terminals A1 and A2 3. Connection to the RS-485 bus is made via the terminals D+,
resp. +/-). Connect terminal " " to the protective conduc- D- and SH. Up to 32 devices can be connected to the bus.
tor. The maximum cable length for the bus connection of all
devices is 1200 m.
Connection diagram voltage inputs
AC 400 V / 230 V LV / MV / HV
AC 400 V
L1 L2 L3 N
L1 L2 L3 N L1 L2 L3 N
Ri
Ri Ri
PEM
PEM PEM
2 PEM555_D00016_00_Q_XXEN/04.2014
Quick start: PEM555
PEM555_D00016_00_Q_XXEN/04.2014 3
Quick start: PEM555
2
NET kvar TOT kvarh
Reactive energy Total reactive kVAh
5 net amount energy Apparent
energy
4 PEM555_D00016_00_Q_XXEN/04.2014