Quick start: PEM555

Quick start PEM555


kWh kvarh
LINETRAXX®

This short operating instruction does not replace the manual!

You will find the manual on the website


www.bender.de

Make sure that the personnel has read this manual and under-
stood all instructions relating to safety.

V/I POWER HARMONICS ENERGY

OK

Intended use Scope of delivery

The universal measuring device PEM555 is suitable for ● 1 PEM555


● the analysis of energy and power (Power Analyzer) ● Safety instructions
● monitoring of the power supply quality (Power Quality) ● This short operating instructions
● data recording for energy management (Energy Manage- ● 1 sealing frame "IP54"
ment).
Safety instruction
As a compact device for front panel mounting, it is suitable to re-
place analogue indicating instruments. The PEM555 is suitable for
3 and 4-wire systems and can be used in TN, TT and IT systems. Danger of electric shock!
The current measurement inputs of the PEM are connected via Follow the basic safety rules when working with electricity.
external ../1 A or ../5 A measuring current transformers. Consider the data on the rated voltage and supply voltage as
specified in the technical data!
Measurement in medium and high-voltage systems are principal-
ly carried out using measuring current and voltage transformers.
The accuracy of the active energy metering corresponds to class
0.2 S in compliance with the DIN EN 62053-22 (VDE 0418 Part 3-
22):2003-11.

Installing the device

Front-panel mounting (front view, side view, panel cutout)


106 18 88 18
91
88

92
96

92

91 96

96

A front-panel cutout of 92 mm x 92 mm is required for the device.


1. Insert the device into the installation opening of the front panel.
2. Insert the two installation clips into the equipment rail from behind.
3. Push the installation clips towards the front panel and tighten the screws by hand.
4. Check the device to ensure that it is firmly mounted in the front panel.

PEM555_D00016_00_Q_XXEN/04.2014 1
Quick start: PEM555

Connection of the device


Wiring diagram
Terminal Description
DIC DI1 DI2 DI3 DI4 DI5 DI6 Power
A1 A2
Connection to supply voltage, 6 A fuse (when sup-
US
A1, A2, plied by IT systems, both phase conductors have to
ETH RS-485 DO34 DO33 DO24 DO23 DO14 DO13
be protected).
D+ D- SH

DI1…DI6, DIC Digital inputs


DO13, DO14,
SH • l41 l42 L1 L2 L3 N
DO23, DO24 Digital outputs (N/O contacts)
DO33, DO34

• l11 l12 • l21 l22 • l31 l32


I11, I12,
I21, I22, Connection to the system to be monitored
DI1 DI2 DI3 DI4 DI5 DI6 DIC
I31, I32
D+, D-, SH Connection RS-485 bus
I12 I22 I32 I42
Measuring voltage inputs: The measuring leads
I11 I21 I31 I41 L1, L2, L3, N
should be protected with appropriate fuses.
L1
L2 DO13 DO14 Modbus TCP: Pin assignment
L3 1 Transmit Data +
DO23 DO24 12345678
N
2 Transmit Data –
DO33 DO34
3 Receive Data +
L1 L2 L3 N 4, 5, 7, 8 not used
6 Receive Data –

Connection
1. Connect the device according the wiring diagram. The con- 2. Line protection: 6 A fuse recommended. If being supplied
nections are located on the rear of the device. Connect the from an IT system, both lines have to be protected by a fuse.
PEM555 to the supply voltage (terminals A1 and A2 3. Connection to the RS-485 bus is made via the terminals D+,
resp. +/-). Connect terminal " " to the protective conduc- D- and SH. Up to 32 devices can be connected to the bus.
tor. The maximum cable length for the bus connection of all
devices is 1200 m.
Connection diagram voltage inputs

Three-phase 4-wire system (TN, TT, IT


Three-phase 3-wire system Connection via voltage transformers
systems)
The PEM can be used in three-phase 4-wire The PEM can be used in three-phase 3-wire The coupling via measuring current trans-
systems, independent of the type of distribu- systems. The line conductor voltage must not formers allows the use of the measuring de-
tion system (TN, TT, IT system). exceed AC 400 V. vice in medium and high voltage systems.
The transformation ratio can be adjusted in
When used in 3-wire systems, the con- the PEM555 (1…2200).
nection type (TYPE) has to be set to delta con-
nection (DELTA).
For this purpose, the measuring inputs L2 and
N are to be bridged.

AC 400 V / 230 V LV / MV / HV
AC 400 V

L1 L2 L3 N
L1 L2 L3 N L1 L2 L3 N
Ri
Ri Ri
PEM
PEM PEM

2 PEM555_D00016_00_Q_XXEN/04.2014
Quick start: PEM555

Commissioning of the device Start


Check proper connection Pressing the "ENERGY/OK" button enters the setup mode (> 3 s).
Observe the relevant standards and regulations that have to be ob- Pressing the "ENERGY/OK" again (> 3 s) returns to the display
served for installation and connection as well as the manual of the mode.
respective device.
Before switching on A correct password must be entered before changes are
Before switching on think carefully about these questions: allowed. (factory setting: 0)
1. Does the connected supply voltage US correspond to the
The following diagram will help you to familiarise yourself with the
nameplates information?
menu:
2. Is the nominal system voltage of the measuring current
transformer not exceeded?
Serial number
3. Does the measuring current transformer's maximum current Date update UPDAT
correspond to the nameplate information of the connected Protocol version PROVER
Info INFO OK OK Software version SW-VER
device?
Clear event memory CLR SOE
After switching on Set time CLK Clear pulse counter CLR DIC
Clear peak demand CLR PDMD
After switching on, proceed as follows: Set date DAT
Clear max/min values CLR MXMN
1. Connect the supply voltage. Clear memory CLR SET OK OK Clear energy values CLR ENGY
DO3 control DO3
2. Set the bus address/IP address. DO2 control DO2
Trigger mode
DO1 control DO1
3. Set the CT transformer ratio (for each channel). digit. output DO SET OK OK

Apparent energy S kVAh


4. Change the measuring current transformer's counting direc- Reactive energy export EXP kvarh

tion, if required. Reactive energy import IMP kvarh


Active energy export EXP kWh
Presetting
5. Set the nominal voltage (line-to-line voltage ULL). energy values ENGY SET OK OK Active energy import IMP kWh
Set pulse constant EN CONST
6. Select wye connection or delta connection. Presetting
OK OK
energy pulsing PULS SET Activate energy pulsing EN PULSE

Display and operating controls Presetting


demands DMD SET OK OK
Sliding Windows NUM
Measuring period PERIOD
PEM555 Gateway address (LoWord) GWL
kWh kvarh
LINETRAXX®
Gateway address (HiWord) GWH
Subnet mask (LoWord) SML
Subnet mask (HiWord) SMH
Set IP address (LoWord) IPL
Ethernet parameter ETH SET OK OK IP address (HiWord) IPH
Protocol PRO1
Parity bit CONFIG1
Set baud rate BAUD1
Communications
interface COM1 SET OK OK Set address ID1
V/I POWER HARMONICS ENERGY

OK Duration of display lighting BLTO SET


Change polarity I3 I3 REV

Key Change polarity I2 I2 REV


Change polarity I1 I1 REV
LED "kWh" and LED "kvarh": pulse outputs
Nominal frequency Hz NOM
"V/I" button: displays mean values and total values (current, Nominal system voltage V NOM
voltage); Calculation method THD HD SET
kVA calculation method KVA SET
In the menu:
Power factor rule PF SET
moves the cursor to the left if the parameter to be changed is Neutral conductor current I4
a numeric value CT transformation ratio CT

"POWER" button: displays energy-related parameters. OK OK


Voltage transformer transf. ratio PT
System settings SYS SET Select connection type TYPE
In the menu: to move up to the next entry;
Change password PAS SET OK OK Enter new password NEW PAS
in case of numeric values: increments the value.
Enter password PASWORD
"HARMONICS" button: displays harmonics.
PROGRAMMING OK Device button
In the menu: moves down to the next entry;
in case of numeric values: decrements the value ENERGY/OK >3s
"ENERGY button:
Press > 3 s:
toggles between the setup menu and the standard mode.
Displays measuring values: Active and reactive energy import/
active and reactive energy export (line 5).
In the menu: selects the parameters for modification;
confirms parameter change.
Data display via buttons Data display via communication interface
A large number of measuring values can be obtained from the All measuring values can be obtained via the communications
device via the buttons without having to use the communications interface. Details on the Modbus register assignment can be found
interface. Which button is to be activated to obtain the individual in the manual.
values is described in more detail in the manual.

PEM555_D00016_00_Q_XXEN/04.2014 3
Quick start: PEM555

Standard display indications (continuation of


Setup example
the left column)
Measuring current transformer setting Legend to the display areas
transformation ratio 1000:5 (= 200) 1. Shows the status of the digital inputs and outputs
(DI Status, DO Status)
2. Measured values
Indication 3. Harmonic Distortion HD,
Button Description voltage unbalance (unb), quadrant, measurement units
display
4. Shows energy information such as active energy (import, export, net
ENERGY/OK > 3 s PROGRAMMING energy and total energy in kWh), reactive energy (import, export,
energy net amount and total energy in kvar), apparent energy (Sges in
PASSWORD ****
kVAh)
OK PASSWORD 0 0 flashes 5. Shows parameters such as voltage, current, fundamental component,
OK PASSWORD 0 0 Factory setting power, total harmonic distortion THD, TOHD, TEHD (2nd…31st har-
monic), k-factor, unbalance (unb), phase angle for voltages and cur-
PAS SET NO
rents, demands.
SYS SET NO Description of standard display indications (areas 1, 3 and 4)
OK SYS SET NO NO flashes

or SYS SET YES YES flashes Area Segments Symbol description

OK SYS SET YES


DI open DI closed
TYPE WYE Factory setting 1

PT 1 Factory setting DO open DO closed


3 V, kV, A, %, Hz kW, MW, kvar, kVA,
CT 1 Factory setting Measurement units for U, MVA
I, THD, f Measurement units for P,
OK CT 1 1 flashes (units place) Q, S

CT 0 0 flashes (units place)


0 on the left flashes (tens Current value expressed inductive, capacitive
CT 00 as a percentage
place)
0 on the left flashes (hundreds Q2 Q1
CT 0 0 C1
place)
Status commu-
nications inter- Q3 Q4
CT 200 2 flashes
face
OK CT 200 CT ratio 200 adjusted Alarm symbol Quadrant
ENERGY/OK > 3 s Standard display 4 IMP kWh EXP kWh NET kWh
Active energy Active energy Active energy
import export net amount
Standard display indications TOT kWh
Total active
IMP kvarh
Reactive energy
EXP kvarh
Reactive energy
energy import export
1

2
NET kvar TOT kvarh
Reactive energy Total reactive kVAh
5 net amount energy Apparent
energy

All rights reserved.


Reprinting only with permission
of the publisher.
Subject to change! D0006900QXXEN
© Bender GmbH & Co. KG
Bender GmbH & Co. KG Tel.: +49 6401 807-0 E-Mail: info@bender.de
Londorfer Str. 65 • 35305 Gruenberg • Germany Fax: +49 6401 807-259 Web: http://www.bender.de
P. O. Box 1161 • 35301 Gruenberg • Germany

4 PEM555_D00016_00_Q_XXEN/04.2014