Professional Documents
Culture Documents
SIPROTEC-5-Motor-Protection-Application-Guide
SIPROTEC-5-Motor-Protection-Application-Guide
SIPROTEC-5-Motor-Protection-Application-Guide
SIPROTEC 5
Motor Protection
Application Guide • Edition 1
Content
Current-Transformer Requirements 5
Examples 5.3
8.3 Parameterizations
9 Appendix
[fo_Polzahl, 1, en_US]
arm creates a resulting torque. Figure 1.1/1 Main Components of the 3-Phase Asynchronous Machine
According to Lenz’s law, the force action between currents and (U, V, W: Line Terminal V A, V B, V C)
the rotating field is directed in such a way that it opposes the
(1) Stator core lamination
cause of the induction. If, with the machine still stopped, the
rotating field moves over the rotor, the rotor begins to turn in (2) Stator winding
the direction of the rotating field to reduce the relative speed (3) Rotor winding
between the rotating field and the rotor. The frequency of the
rotor (speed of rotation) can never reach the frequency of the (4) Rotor core
rotating field of the stator because, if it did, voltage would (5) Slip rings
no longer be induced in the rotor and the force action would
(6) Shaft
become zero. The deviation between the rotating field and rotor
frequencies is known as slip s. The slip adjusts so that the rotor (7) End shield
current created is just sufficient for the motor load. (8) Fan
(9) Housing
(10) Fan cover
[dw_stabformen_kurzschlusslaeufers, 1, --_--]
The air gap between the stator core lamination and the rotor
core lamination must be kept small to keep the magnetizing
current as small as possible. As all slot openings along the rotor
or stator circumference act like an enlarged air gap and result in
distortions to the field of the air gap (voltage distortions, addi-
tional losses), the slots are designed generally as semi-closed
or in part completely closed and are only open in the case of
high-voltage machines.
Equivalent Circuit of the Asynchronous Machine electrical active power PS,W minus the losses in the stator PVS and
Essential characteristic quantities will be derived from the in the rotor PVL of the machine.
example of an equivalent circuit. There are analogies to the
transformer so that the equivalent circuit of the asynchronous
motor (see Figure 1.2/2) can be developed from the equivalent [fo_Drehmoment, 1, en_US]
[fo_Luftspaltleistung, 1, en_US]
[fo_Realteil-Ständerstrom, 2, en_US]
[fo_Staenderstrom_Summe-Laeufer-Leerlaufstrom, 2, en_US]
The power factor results from the real portion of the rotor Substituting Equation 10 in Equation 9 leads to the final rela-
current of Figure 1.2/3 and leads to the relationship of Figure tionship for the torque of the machine.
1.2/4.
[fo_Realteil-Laeuferstrom, 2, en_US]
[fo_Drehmoment_maschine, 1, en_US]
Another characteristic key value is the torque of the machine.
This can be derived from the power balance. The mechanical Figure 1.2/10 Equation 11
power output Pmech results from the difference of the supplied
[fo_Drehmoment-Schlupf-charakter, 1, en_US]
(MS Starting torque, Mbreak Breakdown torque; Mrated Rated
torque, nbreak Breakdown speed, nsyn = nD Speed of the stator
Figure 1.2/13 Equation 14
rotating field, sbreak Breakdown slip, srated slip Rated slip)
This is how essential mathematical relationships are derived for Figure 1.2/3 shows that the starting current, among other
the operating quantities of the asynchronous motor. These help factors, is a function of the applied voltage and, in particular,
with the interpretation of the curves and data supplied by the of the rotor resistance. The rotor resistance is designed to be
motor manufacturer. Figure 1.2/14 shows the basic curve of low to keep the rotor losses low. This results in the relatively
the characteristic quantities. At the same time, the typical key large starting currents that may easily reach 5 to 8 times the
values are also entered. rated current. In addition, the low rotor resistance limits the
starting torque according to Figure 1.2/10. There are limits to
reducing the starting current by lowering the stator voltage.
The quadratic dependence of the torque on the applied stator
voltage (M ∼ V2) becomes clear in Figure 1.2/10 and leads
to a drastic reduction in the starting torque (half the terminal
voltage results in a quarter of the original torque).
Increasing the rotor resistance using starting resistors (wound-
rotor motor according to Figure 1.1/1) results in a reduction of
the starting current. This increases the cosφ and consequently
the starting torque. In normal operation, the resistors are short
circuited. The disadvantage of this solution is the higher effort.
It can also be derived from the quadratic voltage dependency
of the torque that, according to Figure 1.2/12, the breakdown
torque is also clearly reduced. As a result, there is the risk
that, when operating a motor with a reduced voltage, the
required mechanical torque exceeds the breakdown torque and
the motor may then literally stop.
circuit
Figure 1.3/3 Restart Factor kr as a Function of the Slip and for Different
• Stalling of motors in operation up to standstill Startup Factors ks
In extension to Figure 1.2/14, Figure 1.3/1 shows the envelope
of the starting current. When powering on the motor with a The startup or restart condition is satisfied for every drive when,
slip of s = 1, a transient inrush current occurs similar to when at every point in time, the motor torque M is greater than the
powering on an inductance. This transient inrush current then resistance torque MR (counter torque of the prime mover, sum
passes into the quasistationary starting current. At first, this of the frictional torques, miscellaneous losses). A safety factor
current decays very slowly and only drops quickly to the normal of 10 % is used. The required minimum voltage can be specified
operating current when it is near the rated slip. using Figure 1.3/4. This is in the range of Vmin = (0.55 to 0.7) VN,
M.
[fo_Mindestspannung_Umin, 1, en_US]
1.3
[dw_Netzersatzschaltung_Motors-ein, 1, en_US]
Figure 1.3/5 Equivalent Circuit for the Power System When Powering
on a Motor
[fo_Netzersatzimpedanz_ZN, 2, en_US]
Figure 1.4/1 Curve of the Losses PV, of the Speed n, and of the Overtemperature ϑ for the Operating Modes S1, S2, S3, S6 (TL Load Duration, TP Off Time,
Top Operating Duration, Tno-load No-Load Duration)
Out-of-Step Conditions of Synchronous Motors In the following variants, the behavior of the motors is discussed
for the 2 failure mechanisms, based on calculations with a
Figure 1.5/1 describes the power equation for stable operation
dynamic network calculation program:
of a 3-phase synchronous motor.
• Out-of-step condition due to underexcitation
• Out-of-step condition due to brief loss of the power-system
voltage
[fo_Synchrondrehstrommotors_Pmech, 1, en_US]
1.5
Figure 1.5/3 Admittance Curve during Excitation Failure (Motor of 9.88 Figure 1.5/4 Locus Diagram of the Admittance as a Result of a 3-Phase
MVA) Short Circuit of 0.15 s Duration (Motor 2.22 MVA)
angle in this case is to be understood as the angle between Figure 1.5/5 Locus Diagram Curve of the Admittance Resulting from a
the synchronous generated voltage and the fixed-frequency 3-Phase Short Circuit of 0.2 s Duration (Motor: 9.88 MVA)
power-system voltage. After the short circuit is disconnected
and the associated voltage recovery occurs, there may be either a) Power locus diagrams
a resynchronization or an out-of-step condition depending on b) Admittance locus diagrams
the motor constants, the mechanical load, and the duration of
(1) Starting value
the short circuit.
(2) Value at the start of the short circuit
Figure 1.5/4 shows a locus diagram curve where the motor
is close to but is not yet out-of-step. In the de-energized (3) Value at disconnection of the short circuit
time, the speed drops by up to 5 % and the rotor angle has (4) Value after disconnection of the short circuit
reached almost 180°, but the synchronizing torque after voltage
recovery is so large that the motor is pulled into synchronism
Conclusion
again.
The examples clearly show that you can handle the out-of-step
condition of synchronous motors very well by means of under-
excitation protection with the admittance characteristic (see the
7UM85 Manual). You only need a protection characteristic that
is to be set to 1/Xd. To give the motors the chance of resynch-
ronization, a sufficient time delay should be set. In the simula- a reactive power monitoring system can be used because the
tions, this resynchronization occurs for the worst case of motor motor terminal voltage changes only slightly due to the usually
load at rated load in a maximum of 0.5 s. A tripping delay of 1 s small source reactance.
is recommended for out-of-step protection. If several character-
istic curves are used, time grading is possible. As an alternative,
Literature
[1] Weßnigk, K.-D.: Kraftwerkselektrotechnik. Vde-verlag GmbH, Berlin, Offenbach, 1993
[2] Brendler, W.; Roseburg, D.: Elektrische Maschinen. 4th Lehrbrief fürs Hoch- schulfernstudium in der ehemaligen DDR, 1988
[3] Müller, G.: Grundlagen elektrischer Maschinen. VCH Verlagsgesellschaft mbH, Weinheim, 1994
[4] Clemens, H.; Rothe, K.: Schutztechnik in Elektroenergiesystemen. Verlag Technik GmbH, Berlin, 1991
1.5
[5] IEC 60034-1 - Rotating electrical machines. Part 1: Rating and performance, Release 2004
[6] Fischer, A.: Außertrittfall und Außertrittfallschutz von Synchronmotoren. Etz Vol. 111 (1990) Issue 6, pages 306 to 309
Overview of the Protection Functions and Protection Devices Defects and Protection Functions
for Motors
Different causes for defects in motors are possible. Table 2.1/1
In this chapter, the suitable protection functions are introduced shows an overview of the essential causes for defects and their
starting from possible errors in synchronous and asynchronous effects. In this, thermal overload plays a central role both for
motors. Further on, there is an overview of the distribution of stators and for rotors. The impermissible stress has a general
the protection functions to the individual protection devices. effect on the service life of the motor and leads to premature
Finally, the principal application of the protection equipment for aging. In turn, this impairs the insulation capability while, at the
the different types of motors and performance classes will be same time, increasing the probability of evolving faults that can
discussed. In general, it must be noted that the protection func- usually be ground faults and short circuits.
tions discussed are used mainly for motors connected directly
with the infeed (direct on line). If a motor is operated by way of
a frequency converter, the appropriate protection functions are
usually integrated into the frequency converter.
Table 2.1/1 Overview of the Causes for Defects and Defect Types in Asynchronous Motors
Causes for defects such as hidden manufacturer's defects and The task of the protection system is
assembly defects (for example, warping of the motor, one-sided
bearing pressure when connecting the prime mover) as well as
• To protect the motor against destruction, and thus against a
reduction of its service life, in case of a thermal overload.
deficient maintenance are not listed.
• To counteract propagation of damage on the motor (destruc-
tion of the core, motor fire) by sufficiently fast disconnection
in case of a short circuit, ground fault, or turn-to-turn fault
as well as to limit the effects to other connected consumers
(voltage balance, voltage collapse, current overload).
Table 2.1/2 shows the relationship between the possible defects and the protection function that detects these defects.
Distribution of the Protection Functions Across the activated depending on the application. In the compact devices
Protection Devices (7SX800, 7SK82, 7SX82), the hardware quantity structure is
limited. In the modular devices (7SK85, 7SX85, 7UM85), the
Digital protection is distinguished in particular by its multi-func-
hardware can be configured as desired depending on the appli-
tionality. Various protection functions can run on standard hard-
cation.
ware depending on the application. Regardless of whether you
are protecting a cable, an overhead line, a generator, or a Table 2.2/1 provides an overview of the functions and protocols
motor, you always work with the same device type. This simpli- contained in the protection devices for the motor protection
fies the engineering with an identical hardware quantity struc- applications and a listing of selected additional functions.
ture. You can standardize applications and even reduce spare
part expenses.
The concept was systematically implemented in SIPROTEC 5. The
protection functions are standardized in all devices and can be
Additional Ethernet protocols/services DHCP, DCP DHCP, DCP DHCP, DCP DHCP, DCP
2
Line mode Line mode Line mode Line mode
2.2 PRP PRP PRP HSR PRP HSR
HSR HSR RSTP SNTP RSTP
RSTP RSTP SNMP SNTP
SNTP SNTP IEEE1588V2 SNMP
SNMP V3 2 SNMP IEEE1588V2 IEEE802.1q (VLAN) IEEE1588V2
IEEE1588V2 2 IEEE802.1q (VLAN) IEEE802.1q (VLAN)
IEEE802.1q (VLAN)
2 in preparation
Application of the Protection Devices the protection devices are shown in the left column. If addi-
tional functionalities such as a larger number of binary inputs
The protection scope to be used acts in accordance with the
and outputs and other hardware properties are required, you
rated power of the motor, its operating mode, and its role and
can switch to the devices in the right column. As most of the
importance in the view of the technology process connected
protection devices are installed directly in the medium-voltage
to it. Of course, cost plays an appropriate role. You should
compartment, the control functionality sees greater use. Here,
consider the total cost because some of the costs for repairing
the devices or ordering options with a large display have bene-
a motor are relatively low in comparison to the repair costs for
fits in representing a feeder with the switching devices.
other electric equipment. However, the follow-up costs for the
production system cannot be neglected and are often a multiple Another selection criterion may be, for example, standardization
of the repair costs. of the hardware – for example, one device type in the company.
In this case, the 7SX85 universal device is available and can
The overview in Figure 2.3/1 shows a distribution of the protec-
protect, in addition to motors, cables (overhead lines) and trans-
tion devices according to performance classes of the motors
formers.
and applies to asynchronous motors. The preferred types of
2.3
Figure 2.3/1 Assignment of the Protection Devices to the Motor Performance Classes
The power of synchronous motors is usually significantly greater Additional hints for use, connection, and setting the protection
than 2 MW. For this reason, it is essential to provide a differ- devices are listed in the following articles.
ential-protection system. A 7UM85 (7SX85, 7SK85, 7SX85)
is recommended as the protection device. These variants
contain underexcitation protection to detect excitation prob-
lems (outage or control problems), an out-of-step condition,
and a rotor ground-fault protection.
Thermal Stressing of Motors and Protection Functions insulation system used by the stipulated maximum temperature
of the coolant (ambient temperature) that is specified at 40 °C.
This chapter covers the thermal stressing of motors. The
That is, the maximum overtemperature is the maximum allowed
different operating states are considered and the resulting
temperature of the insulation minus the ambient temperature.
thermal effect is derived. The 2nd part provides illustrations
Usually, a safety factor of 5 Kelvin to 15 Kelvin is added.
of suitable protection principles and the main explanation of
implementation using digital relays. Hints for setting the protec- 2 types of operation must be differentiated for the thermal
tion functions are provided, taken from the motor data sheets. consideration of a motor:
Heating Processes
• Normal operation under load
• Startup
In the energy transformation process from electrical to mechan-
ical energy, there are losses that lead to heating of the motor Normal Operation under Load
equipment. The structural variant allows for specific thermal
loads. Depending on the torque to be supplied, the appropriate current
is taken from the electrical power system. This causes the
As the thermal sources become active, a heating process starts. heating described above depending on the design. In this situa-
The supplied energy is first stored as heat in each volume tion, mainly the stator is concerned. The motor manufacturer
element. The starting curve of the temperature rise, ϑ= f(t), is designs the machine thermally for a permissible thermal class.
independent of the thermal resistances that dissipate the heat Operation under rated operating conditions causes an overtem-
later. In addition, the curve is not the same everywhere because perature that can generally be assigned to a lower thermal class.
different loss densities occur in the various windings as well If, for example, you see the specification F/B (design/operation)
as in the individual sections of the magnetic circuit. For this in the motor data, the motor is designed for thermal class F but
reason, the motor cannot be considered in general a single-body is used to full capacity according to thermal class B. This yields a
system. continuous overload capacity of about 10 % from these thermal
Temperature differences form between the parts of the motor reserves. A higher overload is possible for a brief time but the
and the surrounding coolant. In this situation, heat begins to manufacturer does not specify any data because of the diverse
flow in the direction of the coolant. The temperature difference influencing factors. You must orient yourself to the “thermal
3.1 between the coolant (this can also be air) and the machine part withstand curve" (see Figure 3.1/2).
is known as the overtemperature. After a sufficient amount of
time, a state of equilibrium for the heat flows is established. At
this point, there is no additional storage of heat. The tempera-
ture has reached its final overtemperature. Figure 3.1/1 shows
the curve of the overtemperature for characteristic points within
the stator of a motor.
[dw_Kennl-max-zulaess-therm-Ueberlast-Motor, 1, en_US]
worst case where the curve uses the copper time constant for If not specified otherwise, it can be assumed that about 2 %
short-time duty. The time constant for continuous duty is to be of the negative-sequence voltage does not result in additional
used for the protection setting. The continuously permissible heating of the motors. This corresponds to a continuously
current can also be read from the characteristic curve and is, permissible negative-sequence current of roughly 10 %. If the
according to Figure 3.1/2, about 1.15 I/INMotor. current increases beyond this value, a trip occurs after defined
times. In this case, the motor manufacturers seldom provide
In the American area (NEMA), the overload is described using
information.
the Service Factor (SF). It specifies the allowed overload
regarding rated power in S1 operation. This overload refers to
Startup
the entire system (both the electrical and mechanical parts). As
per NEMA MG 1, the permissible limit overtemperatures of the During startup, thermal stress is placed on the rotor because
corresponding thermal class may be 10 K higher. The values for of the starting currents. The typical startup processes were
the service factors are, for example, 1.1 or 1.15. If, say, SF = covered in the article entitled "Introduction to synchronous and
1 is specified, this means that the motor may only be operated asynchronous motors." Basically, the cases of a "locked rotor"
with the rated power. The thermal overload protection refers and an "accelerating" rotor are to be considered. In the case
only to the motor winding. When specifying SF = 1, a contin- of motors with critical rotors (most of them), the locked rotor
uous permissible winding overcurrent of 10 % can be assumed case constitutes the higher stress from the thermal point of
because the design of the insulation usually uses thermal class F view. This is why motor manufacturers frequently specify the
and the motor is predominantly operated according to thermal thermal limits of the locked motor/locked rotor in the thermal
class B. With an SF = 1.1, that can be greater than 10 % (for limit curve. These curves are shown on the right in Figure 3.1/2.
example, even 15 %). The exact value for the continuously If the motor accelerates, the thermal limits are usually above
allowed overload current can be read from the thermal charac- them.
teristic curve (see Figure 3.1/2). You can find the motor starting times, for both the rated voltage
Mostly, 2 temperature sensors (preferably PT100) are installed and for reduced voltage (for example, the 80 % case) in the
for each phase in the stator winding to detect overtempera- technical data. These times apply when connecting the prime
tures. The motor manufacturers have placed them at thermally mover or with the motor under the rated load conditions. For
critical points. The tripping temperature can be derived from the example, the motor starting time is 24.0 s with a starting
3.1
thermal class. F means a maximum permissible temperature of current of 5.6 I/IN under rated-voltage conditions (Vrated) and
155°C and, for B, the value is 130°C. The latter temperature has 52 s at 4.15 I/IN and 0.8 Vrated. In Figure 3.1/2, we read a time
to be reached approximately under load at the rated quantities. of about 40 s for the warm condition at 5.6 I/IN with the result
The trigger value results minus a safety margin of (10 to 15) K
that the characteristic curve of the starting time supervision can
to about (155 °C -10 K = 145 °C).
easily lie below the locked rotor characteristic curve. During
Operating the motor with an unbalanced voltage results in addi- startup with a larger load (the initial starting current is not
tional heating of the rotor. The most critical case is an open changed by this!), the reserve of between 24 s and 40 s is avail-
circuit in one phase. Voltage unbalance means that a voltage able. A speed check is not absolutely necessary here because the
negative-sequence system is present that drives the negative- starting time supervision trips before the maximum locked rotor
sequence current. This negative-sequence system rotating field time is reached.
causes an alternating current in the rotor (100 Hz/120 Hz rela-
A further thermal stress comes from the frequency of successive
tive speed in a 50-Hz/60-Hz electrical power system) in the
motor restarts. Here, the manufacturer differentiates between
opposite direction of rotation. As a result of the skin effect,
warm and cold. You frequently find these typical specifications:
there is a larger rotor resistance and this, in turn, leads to higher
3 startups from the cold state and 2 startups from the warm
warming. It can be assumed that 1 % of the negative-sequence
state. This statement also applies to startup with a reduced
voltage leads to about 5 % to 6 % negative-sequence current.
voltage (80 %).
The stator current can be estimated using the equivalent circuit.
Another important key value is the number of permissible
Here, this can be divided into the positive-sequence system
startups per year. This is 1000, for example, and must not be
and the negative-sequence system. As the negative-sequence
exceeded.
system rotating field moves in the negative direction at the
synchronous speed, the slip for the negative-sequence system
is 2 s. You can clearly see the influence of the different rotor
resistances in Figure 3.1/3.
[dw_motorersatzschalt_mit-und-gegensystem, 1, en_US]
As all values are scaled, the tripping time can be calculated from
Figure 3.2/4 when Θ(t) = 1. If we also use the scaling quanti-
ties of Figure 3.2/3 and assume a measured ambient tempera-
ture, the tripping time can be calculated using the following
equation. If the ambient temperature is not measured, ϑa, meas-
ured = 40°C should be used and this leads to further simplification
3.2
[dw_Ersatzschalt-therm-modell, 1, en_US]
of Figure 3.2/5.
[fo_therm-belast_bezugstemperatur_07, 2, en_US]
There are 2 possible strategies: accordance with the definition equation of the symmetrical
components, the negative-sequence current that is to be eval-
• Freezing the thermal memory during startup processes uated in protection terms. In the simplest case, thresholds are
This is intended to avoid overfunction of the overload protec-
polled and tripping is initiated after a set delay. To consider
tion during startup processes.
the heat development process, an I22t characteristic must be
• Internal limiting of the starting current simulated, which is a well-known characteristic (for example,
The current supplied to the thermal model is limited during
I22t = 10 s in synchronous machines). The characteristic curve
the startup process. This "slows down" the heat development.
Current limiting should be at about 2.5 I/IN, M (also see Figure is released when the permissible unbalanced load threshold (for
example, 10 %) is exceeded. Below this threshold, motor cooling
3.1/2). A reduction of limiting is recommended if starting
is necessary. An inverse curve results as the operate curve (also
times are long and successive warm startups are possible. In
see Figure 3.3/2).
the example, a value of 2 I/IN, M makes sense for a starting
time of 52 s (at 0.8 VN).
Starting Time Supervision
Different operating states were assumed to provide insight into If the startup process is too long, the rotor is thermally over-
the thermal behavior of the thermal model. Figure 3.2/6 encom- loaded. The thermal limit (seeFigure 3.1/2) is described by an I2t
passes the following sequence: Startup with rated voltage characteristic curve. The characteristic curve must be simulated.
(starting time = 24 s), continuous duty under rated conditions, The following equilibrium condition (see Figure 3.2/7) can be
powering off and immediate powering on again at a reduced set up and, using it, the permissible starting time or locked rotor
voltage (starting time = 52 s), brief operation with a reduced time can be determined.
load (0.9 I/IN, M) followed by stopping the motor. After stopping,
we recognize the effect of the longer cooling time constant very
well. During startup, the starting current for the thermal model
was limited to 2 I/IN, M. [fo_therm-Belast_anlaufueberwachung, 1, en_US]
Ist, tst is a value pair that can be found in the technical data of
the motor. t is the resulting tripping time at constant current I,
which can deviate from Ist, depending on the voltage present on
the motor.
If the actual starting time is longer than t, tripping occurs. The
operate curve has an inverse character and adjusts very well to
the startup conditions (with rated voltage and reduced voltage).
The calculation according to Figure 3.2/7 is not released until
the startup process is detected. For typical motors, the required
current threshold is about 2.5 I/IN, M. The threshold must be
[dw_therm-modell_unterschiedl-belastungsfaelle, 1, en_US]
lowered appropriately for motors with reduced starting currents.
[dw_therm-belast_anlaufstroeme, 1, en_US]
Restart Inhibit
When the motor is started too many times in succession, an
impermissible heating of the rotor occurs. In the simplest case,
the permissible limiting values can be monitored with counters
and the specified dead times met.
[dw_therm-modell_unterschiedl-belastungsfaelle_02, 2, en_US]
3.2 Another approach is to model heating of the rotor to determine
Figure 3.2/10 Behavior of the Thermal Rotor Model under Different
the thermal limit for the permissible restarts. In this way, we get Loads (tstart = 52 s; ISTART = 4.15 I/IN, M; nC = 3 and nW = 2)
closer to the physical conditions and can generally better load
the motor. A single-body model is also practical for modeling.
The 1st startup from the cold state leads to rotor heating,
The 2 values needed, the k factor for the rotor (kR) and the
which also happens during rated operation. From this warm
rotor time constant τR must be found. Both values are not state, 2 startups are allowed. When the warm motor restarts
usually given. However, they can be derived from data of the the 2nd time, the restart-inhibit threshold is exceeded and
manufacturer, such as the number of cold startups (nC) and the temperature approaches the limiting value 1. This value
warm startups nW), the starting time and the associated starting corresponds to the maximum permissible rotor temperature.
current. We create a system of equations describing the cold Subsequent continued operation under load conditions leads to
and warm states with the known quantities and we use that to corresponding cooling of the motor. If the motor was powered
determine the 2 unknown values (kR and τR). Figure 3.2/9 shows off now, it could be restarted immediately because there is a
sufficient thermal reserve. If, instead, it was powered off imme-
the approximated solution.
diately after the 2nd startup from the warm state, the restart
inhibit function would immediately take effect and prevent
restarting. From the thermal point of view, this is only permitted
when the temperature falls below the 67-% threshold.
[fo_therm-belast_bezugstemperatur_09, 1, en_US]
It should still be mentioned that, in addition to the introduced
Figure 3.2/9 Equation 6
thermal stage, the restart inhibit function provides 2 other
stages. On the one hand, there is a counter stage that can
These parameters, calculated internally in the function, are
monitor and ensure that no more than the specified number of
incorporated into the thermal model (similar to Figure 3.2/3).
restarts has occurred within a specific time. On the other hand,
If the thermal memory has reached an appropriate filling level,
a time stage was implemented to monitor compliance with a
the restart inhibit becomes active. This threshold is at about (nC
minimum time between 2 consecutive startups. Both stages
– 1)/nC. measure the thermal situation of the rotor not as precisely as
At standstill, the slower cooling is considered by extending the the thermal stage and are intended to be used, when additional
time constant. Before then, the thermal model is frozen for an appropriate motor data are available and are to be used in
adjustable time to consider internal transient phenomena. Only parallel with the thermal stage or when the user does not wish
then does exponential decay cooling occur. Another restart is to use the thermal stage.
prevented for this time to allow the motor to run down.
Protection Setting are shown in brackets. In SIPROTEC 5, the functions are standar-
dized across devices. All referenced protection parameters are
In the sense of a summary, the essential setting parameters for
exclusively primary values. For this reason, a protection setting
the thermal protection function are compiled into a table and
using primary values is recommended in DIGSI.
provided with brief comments. The SIPROTEC 5 function texts
3.3
Unbalanced-Load Protection
Thermal function
Table 3.3/3 Negative-Sequence Current Function (I2>, with, for Example, 2 Definite-Time Overcurrent Protection Stages)
Restart inhibit and the motor current. The function Motor restart inhibit
processes the input data of the function Th.repli.rotor and
In SIPROTEC 5, the function was divided into 2 function blocks.
blocks the restart. The longest time (minimum restart inhibit
In the function Th.repli.rotor, an equivalent rotor temperature
time or the restart inhibit time of the thermal model) deter-
and a restart time are calculated from the setting parameters
mines the duration of startup blocking.
[dw_Kennl-Einstell_schieflastschutz, 1, en_US]
3.3
[dw_Kennl-Einstell_Therm-belastung, 1, en_US]
Literature
[1] IEC 60034-1 – Rotating electrical machines. Part 1: Rating and performance, Release 2004
[2] IEC 62114 – Electrical insulation systems (ISM). Thermal classification, Release 2001
[3] SIPROTEC 5 motor protection 7SK82/85 C53000-G5040-C024-B (parameter reference)
[fo_Erdstromschutzfunktion, 2, en_US]
system determine the fault current in the faulty feeder. The both the position of the zero-sequence voltage and the zero-
capacitive currents of the faulty feeder A cancel out at the meas- sequence current. The primary-side phasor quantities for the
uring point (gray arrows in Figure 4.1/3). zero-sequence voltage and the zero-sequence current are
shown for the 2 measuring points (feeders A and B) for the
The phasor quantities resulting in the phasor diagram for
evaluation of the direction of the ground current.
the healthy feeder are shown at the bottom left. It depicts
4.1
[dw_Erdschluss_isoliertes-Netz, 1, en_US]
Figure 4.1/3 Measured Quantities during a Ground Fault in an Isolated Electrical Power System
[dw_Iso-Netz_Motorabgang, 1, en_US]
The ground-current protection does not pick up in the healthy
Figure 4.1/4 Isolated System with Several Outgoing Motor Circuits motor. In the faulty motor, a terminal-side ground fault is
detected but the 80-% protection range is not reached. If you
The current for a ground fault with full offset (see Figure 4.1/1, set the ground-current protection to be more sensitive, for
terminal-side ground fault) can be estimated for each outgoing example, to 10 mA, the pickup value of 0.6 A results.
motor circuit as follows. In the case of capacitive currents that are changed some-
what, the healthy feeder can also pick up now. The selec-
tivity is circumvented. Directional sensitive ground-fault protec-
tion provides the remedy. This protection evaluates the phase-
[fo_gnd-sc_01, 1, en_US] angle position of the phasors in addition to the zero-sequence
current and the zero-sequence voltage. The directional sensitive
The cable capacity C0, cable depends on the cable geometry, the ground-fault protection is the recommended protection function
conductor cross-section, and the voltage level. You can take the in an isolated electrical power system. The sinϕ circuit (SIPROTEC
values from the cable data. There are virtually no specifications stage type 3I0>cos/sinϕ) is used. Figure 4.1/3 shows the phasor
in the motor data for the stator ground capacitance C0, motor. You quantities at the secondary side for the example power system
must request this from the motor manufacturer. One feasible of Figure 4.1/5 (current-phasor rotation of 180° in input IN for
value is 0.12 μF. The outgoing motor circuits have lengths of the core balance current transformer).
100 m to 200 m on average.
Example:
[fo_Kabelkapazität, 1, en_US]
4.1
[fo_gnd-sc_02, 2, en_US]
Isolated Neutral Point and Grounding Transformer Load resistor and power of the grounding transformer:
The discussions in Isolated Neutral Point, Page 29 have shown
that the protection range is determined by the capacitances
in the electrical power system and that these can change [fo_gnd-sc_04, 1, en_US]
depending on the switching state. To ensure defined meas-
uring conditions, one grounding transformer is installed for
each busbar. If a ground fault occurs, a residual voltage at the
secondary side (zero-sequence voltage V0) occurs at the broken-
[fo_gnd-sc_05, 1, en_US]
delta winding. The residual voltage drives a current through the
connected load resistor RL. The current at the secondary side is The grounding transformer and the load resistor are designed
transferred to the primary side and feeds a resistive fault current for a short-term power or short-term current. For the applica-
(3I0). Figure 4.1/6 shows the grounding transformer, a faulty tion, 10 s are sufficient, assuming a protection delay of about
outgoing motor circuit, and the path of the ground current in 0.3 s to 0.5 s. If the ground fault is present for significantly
case of a ground fault. longer, for example, in cable networks where there is only one
ground-fault direction message, the load resistor RL must be
disconnected after ≤ 10 s.
For continuously damping the zero-sequence system and thus
avoiding relaxation oscillations, a resistor R is connected in
parallel to the grounding transformer. The grounding trans-
former can withstand the resistor thermally continuously. The
load resistor is disconnected by way of the zero-sequence
voltage and a timer Figure 4.1/7.
[dw_GndTr-error-Motor_01, 1, en_US]
[dw_abschalt_belastungswiderstand, 1, en_US]
The grounding transformer is dimensioned so that the resistive
4.1 zero-sequence current on the primary side 3I0 does not exceed Figure 4.1/7 Disconnection of the Load Resistor
10 A at the fault location.
The active current can be evaluated due to the resistive zero-
sequence current fed in. Now, the cosϕ stage (SIPROTEC stage
Rated voltage VN = 10 kV
type 3I0> cos/sinϕ) from the ground-fault direction protection
Protection range S = 85 % is used. Since the ground-fault current has a capacitive and a
Core balance current transformer knI = 60 (60 A/1 A) resistive component, as an alternative, the method of measure-
Secondary tripping current Ipickup, sec = 15 mA ment using inclined tripping characteristic (SIPROTEC stage type
Limb transformation ratio, RatioTr = (VN / √(3)) / (500 V/3)
3I0>ϕ (VI)) can be used. Figure 4.1/8 shows the phasors at the
grounding transformer secondary side for both variants.
Calculation steps:
[fo_gnd-sc_03_01, 1, en_US]
[fo_gnd-sc_03, 2, en_US]
4.1
4.1
[dw_Erdschluss_kompensiertes-Netz, 2, en_US]
Figure 4.1/9 Measured Quantities in an Arc-Suppression-Coil-Ground System (IN Active Residual Current with Arc-Suppression Coil)
In the example, the arc-suppression coil was configured with In this way, the ground current phasor 3I0,A skews with respect
an additional watt-metric residual current increase in the trans- to the representation in the isolated electrical power system.
former neutral point. The resistive-inductive current IY addition-
The cosϕ stage (SIPROTEC stage type 3I0> cos/sinϕ) is used
ally supplied in case of a ground fault is depicted in green. The
as the method of measurement. The active component is calcu-
active current (watt-metric residual current) IR is also supplied to
lated from the zero-sequence current phasor 3I0,A. This is in-
ensure a reliable detection of the direction.
phase with the zero-sequence voltage for the measured quanti-
Figure 4.1/9 shows that a purely capacitive current flows in the ties at the secondary side. Therefore, no active current occurs
healthy feeder. The conditions are identical to the isolated elec- in the healthy feeder 3I0,B. The ground-fault direction function
trical power system (see Figure 4.1/3). For the faulty outgoing does not pick up. Figure 4.1/10 shows the phasor quantities.
motor circuit, the inductive current IY is superimposed on the
With regard to the watt-metric residual current increase, the arc-
capacitive current of the healthy electrical power system (-3I0,B).
suppression coil must be designed in such a way that an appro-
priate current flows to ensure the protection range. A maximum current measurement (cosϕ circuit) is critical. As you can see in
primary current of < 10 A is sufficient. Figure 4.1/8 and Figure 4.1/10, the current in the healthy feeder
is a purely capacitive current. With longer cables and larger
stator ground capacitances of the motor, the tripping current
can be exceeded for this feeder. If the core balance current
transformer is not correctly installed (for example, the gap is
not properly closed), a larger angle error occurs (positive angle
error→ phasor rotation mathematically positive). The protection
function now calculates an active current leading to incorrect
direction determination.
Furthermore, wiring errors must be eliminated as they result
in an incorrect direction determination. It must be checked
whether the screen grounding is routed back through the core
balance current transformer. Figure 4.1/11 shows the correct
connection.
[dw_sek-Zeigergroeße_isoliertes-Netz_cos-method_02, 1, en_US]
4.1
[dw_secondary_test_SGFP_3W, 1, en_US]
[dw_pruefaufbau_mit_sek-pruefeinrichtung, 1, en_US]
Isolated Compensated
Forward Backward Forward Not Faulty
VA 0 0° 0 0° 0 0° 0 0°
VB 100 V -150° 100 V -150° 100 V -150° 100 V -150°
VC 100 V +150° 100 V +150° 100 V +150° 100 V +150°
Vdadn (V4) 100 V 180° 100 V 180° 100 V 180° 100 V 180°
IA (3I0) 2A +90° 2A -90° 1A 0° 2A -90°
4.1
Short-Circuit Protection Rough estimation of the short-circuit curve for the asynchronous
motor [1, section 15.5.6]: τ
Faults between the stator windings are short circuits. In the
isolated and arc-suppression-coil-ground system, 2-phase or
3-phase short circuits occur. These must be disconnected as
quickly as possible. The maximum short-circuit current ISC,3-pole [fo_gnd-sc_06, 1, en_US]
is essentially determined by the short-circuit impedance of the ISt Motor starting current
infeed transformer. In terms of power and short-circuit voltage, Motor time constant
the infeed transformer is to be designed in such a way that the
maximum number of motors or loads can be operated and a reli-
able motor startup (voltage dip according to the specification) is XM Motor reactance (stator + rotor)
ensured.
RS Stator resistance
Figure 4.2/1 shows a system configuration with several asyn-
chronous motors connected at the busbar. In case of a short
circuit, the transformer contributes the greatest amount to Figure 4.2/2 shows the current curve for an example motor (for
the stationary short-circuit current. The asynchronous motors the data, see the section on overcurrent protection).
remaining on the electrical power system supply a short-circuit
current at fault inception. However, this current decays quickly
with the motor time constant. The motors do not supply any of
the steady short-circuit current.
[dw_Kennl-Isc_asynchronmotor, 1, en_US]
[fo_gnd-sc_09, 1, en_US]
[fo_gnd-sc_09a, 1, en_US]
Parameters Value
[fo_Bsp Kurzschlussschutz, 1, en_US] Method of measurement RMS value
Threshold value 2283.0 A
Tripping delay 0s
[fo_gnd-sc_10, 1, en_US]
Table 4.2/1 Definite-Time Overcurrent Protection 1
Parameters Value
[fo_gnd-sc_11, 1, en_US] Method of measurement Fundamental component
Threshold value 1053.0 A
Tripping delay 0.1 s
The transformer rated current on the low-voltage side is 962 A The RMS-value measurement is recommended as the method
and the maximum 2-phase short-circuit current is 6.95 kA. of measurement for the definite-time overcurrent protection
1 stage because transformer saturation is possible due to the
Overcurrent Protection larger currents and the secondary current can be lower than
The startup process (see Figure 1.3/1) must be considered the actual current. The RMS-value measurement integrates the
when setting the protection function. After the transient current current-time integral and counteracts the effect of transformer
comes the starting current and then the load current. 2 definite- saturation.
time overcurrent protection stages are recommended. The definite-time overcurrent protection 2 stage is set to be
Instantaneous definite-time overcurrent protection stage 1: closer to the starting current. You can prevent overfunction
during startup by setting the parameter Method of meas-
The stage is set via the “transient” current: urement to Fundamental comp.. Filtering to the funda-
mental component attenuates direct-current components. The
tripping delay considers the decay of the transient current (typi-
cally, this is approx. 50 ms). A value of 0.1 s is selected. If a
shorter time is measured during commissioning, it is possible to
[fo_gnd-sc_12, 1, en_US] reduce this.
ISt Motor starting current as per the technical data at If you compare the threshold values to the short-circuit currents
rated voltage determined (8.02 kA or 6.95 kA), the protection is certain to
ISt, trans Transient current at the beginning of motor pick up. If the short circuit within the motor is near the neutral
startup point, the motor reactance takes effect (see Startup Processes of
Asynchronous Motors, Page 9). 4.2
Ithreshold, stage1 Primary threshold value to be set
Rough estimate for the motor above at the 80-% protection
Short-time delay definite-time overcurrent protection stage 2: range:
The stage is set via the starting current.
Ithreshold, stage 2= 1.2 ∙ ISt
The time delay is in accordance with the duration of the tran-
sient current. The transient process has decayed after approx.
50 ms. A time delay of 0.1 s is recommended.
Example:
VrM = 6 kV, IrM = 154 A, PrM = 1370 kW,
[fo_gnd-sc_13, 1, en_US]
ISt = 5.7 IrM (with V = VrM), ISt = 3.9 IrM (with V = 0.7 VrM)
Stage 1: In this “hypothetical” case, the short-circuit current is slightly
below the threshold value of the “definite-time overcurrent
ISt, trans ≈ 2 ⋅ ISt = 2⋅ 5.7 ⋅ IrM = 2 ⋅ 5.7⋅ 154 A = 1756 A protection 2” stage. The short circuit is disconnected with a
Ithreshold, stage 1 = 1.3 ⋅ ISt, trans = 1.3 ⋅ 1756 A = 2283 longer time delay via the function starting time supervision.
For this reason, as an alternative, another definite-time overcur-
Stage 2:
rent protection stage can be used. This is set to half the starting
Ithreshold, stage 2 = 1.2 ⋅ ISt = 1.2 ⋅ 5.7⋅ IrM = 1.2 ⋅ 5.7 ⋅ 154 A = current (in the example, 0.5 ⋅ 5.7 ⋅ 154 A ≈ 440 A) and is
1053 A thus insensitive to brief heavy-duty load cases. This definite-time
overcurrent protection stage must be blocked via the binary detection, and the detection of external errors are located in the
input during motor startup. This requires CFC logic that uses function group 87M diff. prot.. Almost all the default settings of
signals from the motor monitor and the close signal from the the functions can be used here.
circuit breaker. To preclude overfunctions, in particular when
feeding short circuits via the asynchronous motor, a time delay The following adaptations are necessary:
of about 0.5 s is recommended for this definite-time overcurrent
protection stage (see Figure 4.2/2). The logic is to be tested. Address Parameter Value Unit
Tripping during motor startup must be excluded. Idiff
_:109 Maximum starting t > t startup (with V = Vmin) s
As an alternative, the function load-jam protection can perform time
this task. It provides delayed tripping of occurring overcur-
Idiff fast
rents while the motor is running because of undesired loads.
_:3 Threshold value I = 1.1 ⋅ ISt/ IrM I/Irate-
Consequently, it simultaneously performs the disconnection of
dObj
internal short circuits with a small amplitude – faster than
Idiff unstabilized
the thermal overload functions. It has the advantage that it is
only released after the motor startup, thus when the motor is _:3 Threshold value I = 2 ⋅ ISt/ IrM I/Irate-
dObj
running. Separate CFC logic is not necessary here.
[dw_kennl_Motordifferentialschutzes-Idiff, 1, en_US]
4.2
Parameter Value to the direction of rotation at the shaft after a delay (Figure
Threshold value, tripping I = 2 ⋅ IrM 4.3/1). An uncontrolled startup results in impermissible stress. It
is necessary to wait for standstill.
Tripping delay 1.00 s
Release delay Release delay t = tAM
Undercurrent monitoring
The protection function is to identify and if necessary stop a
driven machine running at no-load. For example, it is possible
with pumps running in no-load for the pump to experience
thermal overload because of the compression. In the normal [dw_Pumpe, 1, en_US]
case, the medium to be pumped (water, oil, etc.) provides addi-
Figure 4.3/1 Change in the Direction of Rotation at the Shaft
tional cooling.
If the protection function is necessary, the undercurrent protec- The close command is blocked as long as the shaft is rotating.
tion function must be loaded from the library. A pragmatic approach is to measure the time until standstill
during commissioning after powering off the motor. Using a
Parameter Value logic in the CFC, the close command is interlocked for the time
Blocking, trip. & flt.rec. Yes (warning indication); No (tripping) determined.
Threshold value I ≤ = (0.1 – 0.2) IrM If speed monitoring using a tachometer generator is installed on
Tripping delay 10.00 s (depending on the application) the shaft as an alternative, a signal can be injected via a binary
input or an analog input (4 mA to 20 mA) and the signal can
Table 4.3/3 Protection Settings (Changes to the Default Setting) then be processed via CFC. In this way, the standstill can be
measured and the blocking time of the startup depends on the
Protection against rotation reversal (backspin) current process state.
If the motor drives, for example, an oil pump, after powering off
the motor, backflow of the oil into the pipes results in a change
Literature
[1] Oeding, D., Oswald, B: Elektrische Kraftwerke und Netze. [Electricity power plants and power systems] Springer-Verlag Berlin Heidelberg,
2011, ISBN 978-3-19245-6
4.3
Current-Transformer Requirements for Motor Protection formers and designing new ones are the 2 procedures
selected. The pertinent IEC standards (IEC 61869-2, IEC TR
This chapter covers the design of current transformers for
61869-100 and the German versions DIN IEC 61869-2, DIN
motor-protection applications. The different operating cases
IEC TR 61869-100) form the basis for the considerations.
and typical protection principles are considered. The design
is explained using examples. Checking existing current trans-
Parameter Description
Current transformer
ALF Accuracy limit factor
ALF' Operational accuracy limit factor
This comes from the connected burden Rbc:
5.1
Requirements from Motor Startup The following current-transformer requirements are specified in
the device manual for the overcurrent protection. In practice,
The starting current ISt ranges from 4 to 7 times the motor
current transformers of class 10P (5P) according to IEC and class
rated current IrM with a direct-current time constant TAM of about
C according to ANSI are commonly used.
40 ms (< 1 MW) to 70 ms (> 1 MW). An inrush current of the
same order of magnitude that decays in 2 to 3 periods with a
time constant of about 20 ms is superimposed on this.
[fo_maximale_Anlaufstrom_IAM_01, 1, en_US]
5PR, 10PR 20
ANSI class
Required transformer terminal voltage Vta
C (Isr = 5 A) 20 ⋅ Isr ⋅ Rbc
5.2
Example 1: Definite-Time Overcurrent Protection, Checking Hint: The specific electrical copper resistance at 75 °C is used for
the Existing Current Transformer calculation.
[fo_alf-alf_Rct-Rb_01, 1, --_--]
[fo_alf_I-Thresh-max_01, 1, en_US]
[dw_diff-schutz_ueberpruefung_I-Wdl_01, 1, en_US]
[fo_IrM_PrM_03, 1, en_US]
[fo_maximale_Anlaufstrom_IAM_02, 1, en_US]
[fo_I-threshold-max-1,3fach_01, 1, en_US]
[fo_Rbc_Rcable_Rdevice_01, 1, en_US]
Example 2: Differential Protection and Checking of the Rating of the current transformer -T2
Current Transformers
[fo_IrM_PrM_02, 1, en_US]
[fo_maximale_Anlaufstrom_IAM_03, 1, en_US]
[dw_diff-schutz_ueberpruefung_I-Wdl, 1, en_US]
5.3
Table 5.3/1 Requirements for Differential Protection from the Device Manual
The required operational accuracy limit factor ALF‘ is: The transformer class should be 5P and, because of the long
transformer supply line, a rated burden of 20 VA is selected. The
internal resistance is Rct ≤ 4 Ω (at 75 °C).
[fo_alf_IAMtrans, 1, en_US]
3 The angle error is not specified in IEC 61869-2, therefore, the classes 10P and 10PR are not recommended for differential protection.
[fo_rb-device_ct_02, 1, --_--]
[fo_Rbc_Rcable_Rdevice_02, 2, en_US]
[fo_alf-alf_Rct-Rb_02, 1, --_--]
[fo_rb-device_ct_01, 1, --_--]
[fo_Rbc_Rcable_Rdevice_01, 1, en_US]
[fo_alf-alf_Rct-Rb_03, 1, --_--]
5.3
Example 3: Differential Protection with Cable Type Current The required operational accuracy limit factor ALF‘ according to
Transformers the manual (see the table, example 1) is:
[fo_alf_I-Thresh-max_02, 1, en_US]
[fo_Nennbürde, 1, en_US]
[fo_Rbc_Rcable_Rdevice_01, 1, en_US]
The classic motor protection functions (overload, starting time An accuracy limit factor of ALF = 10 is selected.
supervision, unbalanced load, overcurrent, etc.) work with this
current transformer. This results in the following transformer data: 1000 A/1 A,
10P10, 5 VA, Rct ≤ 4 Ω
Checking the current cable type current transformer –T2
For machines connected via cables, a safe differential protection
[fo_IrM_PrM_01, 1, en_US] with high responsivity can be implemented with this method.
The condition is that the 3 phases of the neutral-point side
A transformer with a primary rated current of Ipr = 1000 A is are routed back separately and through the cable type current
selected. transformer in the opposite direction. With a healthy motor
winding, the currents in the transformer cancel each other
and no current flows into the (differential) current relay. The
[fo_maximale_Anlaufstrom_IAM_03, 1, en_US] current is compared with high precision and without saturation
problems as a magnetic self-balancing. No stabilization against
The threshold value of the instantaneous overcurrent-protection external errors is needed because these errors do not occur
stage is set to 1.3 times the maximum transient motor starting downstream of the motor and are also not relevant for the
current. selectivity. This means simple overcurrent-protection stages can
be used. The pickup value can be set to 5 % to 10 % of the 5.3
motor rated current. The overcurrent-protection stage must pick
[fo_I-threshold-max-1,3fach_02, 1, en_US]
up in the case of high-current internal errors.
If a time delay of > 50 ms is set, the threshold value can be As the setting value is low and, in the case of healthy
reduced (see chapter Ground-Fault Protection and Short-Circuit operation, the total current is zero, a transformer with
Protection and Additional Motor Protection Functions, Page 29). 500 A/1 A, 10P10, 5 VA, Rct = 2 Ω is used.
Although in this application, differential protection is involved,
the requirements for the overcurrent protection are used here
because, in the case of an internal error in the motor, an over-
current protection function is to pick up and trip. The value of
the overcurrent protection stage (see example 1) applies as the
required operational accuracy limit factor and ALF‘ is ≥ 20.
[fo_Nennbürde, 1, en_US]
[fo_Rbc_Rcable_Rdevice_02, 2, en_US]
[fo_alf-alf_Rct-Rb_05, 1, --_--]
Summary
The requirement on the current transformer is also determined
by the requirements of the protection principle in addition to
the startup process. Additional important quantities are the
burden due to the supply line and the internal burden of the
current transformer. The current-transformer types selected in
the examples can easily be used for orientation. However,
checking is generally recommended.
5.3
System Implementation and Protection Scope preceding chapters as a reference. Adaptations to any system
are possible by adding or omitting items. From the SIPROTEC 5
This chapter discusses an implementation example for motors of
family, the 7SX800, 7SK82, 7SK85, and 7SX85 can be used as
up to medium power. It covers the essential motor protection
protection devices.
functions and their setting in DIGSI 5. The variants use the
Figure 6.1/1 System Implementation and Protection Scope for an Outgoing Motor Circuit
CI Communication interface
RTD External temperature measurement
Using an infeed transformer, the 10-kV medium voltage motors spare-part strategy (as many identical devices as possible),
and connected consumers are supplied from the 110-kV high- the hardware scope (binary inputs and outputs, scope of the
voltage power system. The grounding transformer that supplies communication interfaces), and more.
a defined ground-fault current (active current) in the event of a
The protection device shown displays the internal structure with
ground fault is connected to the busbar. In the double-busbar
the measuring points and the connection to the transformers,
design, each busbar has its own grounding transformer. The
the required function groups (FG) as well as their connection
voltage is measured at the busbar and is looped through to addi-
and the protection functions (shown using ANSI numbers). The
tional feeders. The protection device is located in a medium-
temperature is measured by means of an external RTD unit
voltage switchgear compartment. Only the circuit breaker is
located directly on the motor. The measured temperatures are
shown in a simplified way. The possible local control by the
transmitted to the protection device using a serial or Ethernet
protection device including the integrated interlocking is not
interface. The benefit of having the RTD unit close to the motor 6.1
part of this example. It can be easily implemented with a
lies in the short connections to the temperature sensors on
SIPROTEC 5 device.
the motor. It should be mentioned that the 7SK82 device can
The motor is supplied using a 3-phase cable and the ground be equipped with an RTD input module as an option. In this
current is measured with a core balance current transformer. case, the temperature sensors must be connected directly to the
The SIPROTEC devices mentioned above can be used as the protection equipment.
motor protection device. Selection criteria are the price, the
6.1
[fo_Rbc_Rcable_Rdevice_03, 1, en_US]
[fo_alf-alf_Rct-Rb_06, 1, --_--]
[fo_alf_I-Thresh-max_03, 1, en_US]
[fo_max-Isc_knl, 1, en_US]
[fo_Isec-max, 2, en_US]
Configuration of the Device in DIGSI and Basic Settings The measuring-point configuration must be adjusted because
the residual voltage is measured directly according to Figure
The minimum hardware requirements are derived from Figure
6.1/1:
6.1/1. The device must have 4 voltage inputs and 4 current
inputs. One current input must be designed as a sensitive
measuring input. In addition, one serial or Ethernet interface
is required for communication with the RTD unit. The number
of binary inputs and outputs comes from the necessary input [sc_verlagerungsspannung-messstellenkonfig, 1, en_US]
If a device is specified, the product code (7SK82, 7SK85, In the next step, the motor data used for normalization/denorm-
7SX85) or an MLFB (7SX800) is available. Create a project alization are set in FG Motor 1 and Circuit breaker 1 under
using DIGSI 5 and configure the device. Select the application General.
template Current and voltage measurement (7SX800: Motor
current/voltage measurement). After this, delete unused func-
tions under Settings > Motor 1and add additional functions
from the library (Overvoltage, 3-phase). The FG Analog units
will be added once the SUP protocol is selected in the Editor
Hardware and protocols. This protocol is used especially for
connecting an RTD unit. These are available as devices with
serial or Ethernet interface.
Table 6.2/1 shows the selected functionality in comparison to [sc_einstell_fg-motor1, 1, en_US]
[sc_einstell_fg-leistungsschalter1-allgemein, 1, en_US]
[sc_einstellwert_ueberlastschutz_mittlerer-leistung, 1, en_US]
Unbalanced-Load Protection
No information is provided in the technical data regarding an
unbalanced load. For this reason, the setting recommendations
[dw_kennl_motortemperaturverlauf, 2, en_US]
of chapter Unbalanced-Load Protection, Page 26 are used.
Figure 6.2/1 Motor Temperature Curve (Sequence: Operation at Rated
Current; Overload at 1.17 I/IrM; Tripping of the Motor) Motors can easily be operated continuously with a negative-
sequence current of I2, perm = 10 % I2/IrM. A warning indica-
If after tripping of the overload protection with a pending trip tion (recommendation: 10 s) is issued after a delay when
a new start command related to the process is desired, the the threshold value is exceeded. The parameter Unbalanced
binary input signal >Emergency start is actuated. The binary load factor K is set to 2 s. This means that with a negative-
information blocks the trip signal and the motor can be started. sequence current of 100 %, the protection trips in 2 s.
The Emerg. start T overtravel maintains blocking of the
tripping for a certain amount of time. As the thermal replica is In general, the following value is best used for the parameter
active during the emergency start, it is assumed that the motor Cooling time therm. replic.:
is running at rated current. If the temperature is still above the
Dropout threshold, trip command when the emergency
start is terminated, the trip command of the overload protec-
tion continues to operate. Further cooling is made possible with
[fo_Abkühlzeit therm_01, 1, en_US]
the Emerg. start T overtravel. After this, the tempera-
ture must drop below the dropout threshold. As the stator time
The function Unbalanced-load protection1 has the following
constants are large, the default setting of 300 s is a feasible
setting values:
value.
The parameter Imax thermal limits the input current for the
thermal replica. It is set to the value for the startup detection of
2 ⋅ IrM = 2 ⋅ 47.5 A = 95 A.
A switch to the thermal time constant by cooling is made using
the parameter Imin cooling when the current drops below
the threshold. This applies to the standstill. For this reason, a
[sc_einstellwert_Schieflastschutz, 1, en_US]
setting to approx. 10 % of the motor rated current 0.1 IrM =
0.1 ⋅ 47.5 A = 4.7 A ≈5 A is used as the threshold. Figure 6.2/3 Setting Values of the Unbalanced-Load Protection
time belonging to the starting current and not the locked rotor Figure 6.2/4 Setting Values, Thermal Replica, Rotor
time (often also known as the maximum permissible starting
time and, in this case, 85 s for the cold state) is set. The thermal rotor model is simulated in a program and the
According to chapter Restart Inhibit, Page 24, the internally current specified as a sequence. The setting parameters are
used parameters of the thermal model (k factor (kR) and the calculated according to Figure 6.2/4.
time constant (τL)) are estimated as follows. The sequence is:
• 1st motor startup with 4.2 I/IrM&52s; standstill for 200 s
• 2nd motor startup with 4.2 I/IrM&52s; standstill for 200 s
• 3rd motor startup with 4.2 I/IrM&52s; continuous standstill
[fo_therm-model_k-faktor_Zeitkonstante, 1, en_US]
The thermal time constant for the rotor has the same order of
magnitude as for the stator because of the long starting time.
The parameter Factor T-const. at oper. acts on the
thermal time constant by cooling (extension factor) when the
motor is running. Normally, the value of 1 can be retained. If a
longer thermal time constant by cooling for a running machine
is desired by the customer, increase this value. With a value of 1,
the thermal time constant and the thermal time constant by
cooling are identical. If the motor is at a standstill, cooling takes
considerably longer. For this reason, the parameter Factor T-
const. standstill is selected to be a value of 7. In this
way, at motor standstill, the thermal time constant by cooling
of the rotor is virtually identical to the thermal time constant by
[dw_kennl_wiedereinschaltzyklus_min-Anlaufstrom_max-Anlaufzeit, 1, en_US]
cooling for the stator.
After every motor disconnection, an Equilibrium time Figure 6.2/5 Restart Cycle with Minimum Starting Current and
Maximum Starting Time
starts. The thermal replica is not updated (the state is retained)
during this time. Afterwards, the cooling action uses the
Figure 6.2/5 clearly shows that 3 restarts from a cold state
extended thermal time constant by cooling. The default setting
and 2 restarts from the warm state are permitted one after
for the equilibrium time of 1 min is a feasible value.
another. The restart threshold is exceeded internally during the
In case of a supply-voltage failure, the calculated temperature in last restart. Exceeding the restart threshold and a subsequent
percent must be saved. For this reason, the parameter Storage disconnection of the motor lead to blocking of the startup. Once
of thermal replica must be set to Yes. the restart threshold is not exceeded (line in pink), restarting
The parameter Tempr.thres. cold motor is evaluated is possible again. In the example, the blocking time is approx.
during starting time supervision. During the typical startups 2000 s (33.3 min).
(3 cold, 2 warm), the default setting of 25 % is feasible. If In Figure 6.2/6, for comparison purposes, the identical cycle
the motor is operated for a longer time at rated current, the is shown but now with maximum starting current (5.6 I/IrM)
percentage temperature of the rotor will reach about 35 %. This and minimum starting time (24 s). The restart threshold is also
6.2 exceeds the 25-% threshold and the motor state is warm. exceeded here with the last restart. The thermal replica does not
warm up as much due to the shorter starting time. After the
3rd disconnection, this leads to the fact that the blocking time is
shortened to approx. 1800 s.
As the locked rotor time (40 s) is far away from the starting time
under rated conditions (24 s), a value for the maximum starting
time of something less than the maximum blocked rotor time
was selected here (35 s).
The starting time supervision is implemented as an I2t char-
acteristic curve. The appropriate time can be determined for
each current according to chapter Starting Time Supervision,
Page 23. For the startup at reduced voltage, the following time
results.
[fo_anlaufzeitueberwachung_64s, 1, en_US]
IS, Set Setting value for the starting current (5.6 I/IrM)
tS, Set Setting value for the selected starting time (35 s)
[dw_kennl_wiedereinschaltzyklus_max-Anlaufstrom_min-Anlaufzeit, 1, en_US]
I Measured starting current referenced to IrM
Figure 6.2/6 Restart Cycle with Maximum Starting Current and
Minimum Starting Time
The determined time of 64 s for startup at a reduced voltage is
greater than the starting time (52 s) and less than the locked
The function Restart inhibit uses the calculation results from
rotor time, warm (70 s). Consequently, there is a reasonable
the described thermal replica of the rotor. Under General,
value even for startup with a reduced voltage.
retain the default setting for the parameter Autom. restart
inhibit. The setting no is used for special applications, The starting time supervision is started when a current threshold
for example, blocking another circuit breaker (see the Device is exceeded. As this threshold value is required for deter-
manual). mining possible operating states of the motor, the setting
is made in the function Motor monitor. The parameter
The parameter Min. restart inhibit time takes effect Curr.thres.starting is set to 2 ⋅ IrM = 2 ⋅ 47.5 A = 95 A.
with the lockout active and has an OR connection to the
blocking time of the thermal replica. It acts for the longer time.
If not specified otherwise, 30 min is set. The setting value is thus Motor monitor
in the same order of magnitude as the blocking time of the
thermal replica.
[sc_motor-monitor-zustandserkennung, 1, en_US]
[sc_einstellpara_fg-wiedereinschaltsperre_mittlere-leisung, 1, en_US]
6.2
Measuring Point Temperature, Time Delay, Warning Temperature, Trip- Time Delay, Tripping
Warning ping
Stator winding 135 °C 20 s 145 °C 5s
Journal bearing 90 °C 20 s 95 °C 5s
Rolling bearing 105 °C 20 s 115 °C 5s
Figure 6.2/10 shows an example of the setting for a sensor • The parameter Threshold value 3I0> is set to the same
(stator winding). value (0.6 A).
• Due to the protection range of 85 %, the parameter V0>
threshold value is 0.15 ⋅ 10 kV/√3 = 0.866 kV.
• Tripping of the ground-fault direction protection (parameter
Operate delay) is to be delayed. A feasible value is 0.5 s.
This results in the following settings:
[sc_einstell_Sensormesstelle-staenderwicklung, 1, en_US]
[fo_parametr-Erdschlussschutz_Ian-prim, 1, en_US]
[sc_einstell-Stufe-U0, 1, en_US]
phase-to-ground voltages increase as a maximum to the value Figure 6.2/15 Angle-Error Correction, Core Balance Current Transformer
of the phase-to-phase voltage. The parameter V> healthy
ph-to-gnd volt. must be greater than the operational Parameterization of the Short-Circuit Protection
phase-to-ground voltage and less than the maximum phase-to-
phase voltage. A threshold value of 70 % phase-to-phase voltage 2 overcurrent-protection stages are used as short-circuit protec-
is feasible (0.7 ⋅ 10 kV ≈ 7 kV). For the parameter V> healthy tion. These are set in the function OC-3phase B 1 function. The
ph-to-gnd volt., the settings are to be somewhat above
Definite-time overcurrent protection 1 stage trips
without delay and is set above the transient starting current.
50 % of the phase-to-ground voltage (0.5 ⋅ 10/√3 kV ≈ 3 kV).
The Definite-time overcurrent protection 2 stage
Depending on the system, it may occur that with ground faults
trips after a slight delay and is set above the starting current.
in the motor near the neutral point with correspondingly low
The following tripping currents result according to chapter Over-
zero-sequence voltage, the healthy phases are no longer reliably
current Protection, Page 39 from the data in Table 6.1/2:
detected.
[fo_parametr-SC-prot_stage1, 1, en_US]
[fo_parametr-SC-prot_stage2, 1, en_US]
6.2
The method of measurement recommended for the Defi-
nite-time overcurrent protection 1 stage is the
RMS value and the measurement of the fundamental compo-
nent is recommended for the Definite-time overcurrent
protection 2 stage. Their tripping delay considers the decay
of the transient current (typically, that is approx. 50 ms). A value Overvoltage Protection
of 0.1 s is selected. If a shorter time is measured during commis-
The function 59 Overvolt.-3ph uses the Definite-T 1 stage
sioning, it is possible to reduce this. More detailed information
as the warning indication. This results in the following settings.
has already been covered in chapter Overcurrent Protection,
Page 39.
Parameter Recommenda- Setting Value
This results in the following settings: tion
Operate & flt.rec. yes yes
blocked
Threshold value V ≥ 1.1 VrM V ≥ 1.1 * 10 kV = 11
Dropout ratio 0.98 0.98
Operate delay 10.00 s 10.00 s
[sc_einstell_ueberspannungsschutz_unabhaengig_synchronmotorschutz, 1, en_US]
[sc_einstell_ueberstromzeitschutz_mittlere-leistung, 1, en_US]
Figure 6.2/18 Setting the Overvoltage Protection
Figure 6.2/16 Setting the Overcurrent Protection
Undervoltage Protection
Parameterization of the Load-Jam Protection
The function 27 Undervolt.-V1 uses 2 stages. The protection
The load-jam protection is set according to the recommenda- function evaluates the positive-sequence voltage. Its value
tions in chapter Protection Functions for Special Applications, comes from the rated voltage by division by √3.
Page 42.
The stage 1 is parameterized as a warning stage. This results in
Using the data from Table 6.1/2 results in the following setting the following setting values.
values:
Parameter Recommenda- Setting Value
Parameter Recommenda- Setting Value tion
tion Operate & flt.rec. yes yes
Threshold for I = 1.5 * IrM I = 1.5 * 47.5 A = 71.25 A ≈ blocked
warning 70 A Threshold value V ≤ 0.9 VrM V ≤ 0.9 * 10 kV√3 ≈
Warning delay 2 s to 3 s 3.00 s 5.2 kV
Threshold for I = 2 * IrM I = 2 * 47.5 A = 95 A Dropout ratio 1.02 0.98
operate Operate delay 10.00 s 10.00 s
Operate delay 1.00 s 1.00 s
Release delay t = tAM t = 24 s A smaller dropout ratio allows a faster dropout if the value
drops below the threshold value for a short time. The Operate
The following setting values result for the function Load-jam delay expired indication is available as a delayed warning.
prot.: Make sure that a possible voltage dip during motor startup does
not lead to a warning indication of the 1st undervoltage protec-
tion stage.
To allow a reliable startup of the motors in case of an infeed
outage followed by restoration, selected motors are discon-
nected. These motors are powered on later. The motor is discon-
nected from the power line system by stage 2 in the application.
6.2
[dw_Kennl-Einstell_strombasierenden-Schutzfkt_mittlere-Leistung, 1, en_US]
Protection of High-Power Asynchronous Motors From the SIPROTEC 5 family, the modular protection devices
7SK85 and 7SX85 can be used.
To keep the loading effects on the power system as small as
possible when powering on motors, high-power motors are
frequently connected by means of a starting process. Various System Implementation and Protection Scope 7.1
methods have an influence on the design of the protection. This Figure 7.1/1 shows the system configuration and the motor
chapter introduces the protection setting while giving consider- protection including the functions used. The motor is connected
ation to partial voltage starting by way of a starting transformer. to an 11-kV busbar via a transformer. To decrease the starting
In addition to thermal protection functions, differential protec- current, the voltage is reduced using an auto transformer. This
tion is a main focus area. method is known as the Korndörfer starter [1].
The protection device shown displays the internal structure with ture is measured using an external RTD unit located directly on
the measuring points and the connection to the transformers, the motor. The measured temperatures are transmitted to the
the required function groups (FG), and their connection and the protection device using a serial interface. The benefit of having
protection functions (shown using ANSI numbers). The tempera-
the RTD unit close to the motor lies in the short connections to Protection Function ANSI Number
the temperature sensors on the motor. Unbalanced-load protection 46
Since all thermal motor protection functions run in the FG Motor Sensitive ground-fault protection (V0>) 59 N
7.1
(stator), this FG uses the current of the transformer CT1 on Differential protection 87 M
the neutral-point side of the motor. During motor startup at a Undervoltage protection (warning and tripping) 27
reduced voltage, the exact motor current is always measured. Overvoltage protection (warning) 59
The following protection functions are used (Table 7.1/1) Table 7.1/1 Overview of the Protection Functions
Protection Function ANSI Number
In addition to these functions, another overcurrent protection
Stator overload protection 49
can be provided as backup protection for the differential protec-
Starting time supervision 48
tion. On this topic, see chapter Thermal Stressing of Motors and
Restart inhibit (with thermal replica) 66 Protection Functions, Page 20 and chapter System Implementa-
Temperature supervision, stator and bearing 38 tion and Protection Scope, Page 51.
[fo_Motorspannung_UM, 1, en_US]
[fo_Stromaufnahme_aus_Inetz, 1, en_US]
The current from the power system Inet (current through CT2)
is, according to the turns ratio, lower than the motor current
(current through CT1) by a factor of 0.7158. In accordance
with Kirchhoff's current law, the remaining current (ISp = (1 -
0.7158) IM = 0.2842 IM) flows through the current transformer
CT3.
Figure 7.2/1 summarizes the distribution of the voltage and
current.
Configuration of the Device in DIGSI and Basic Settings ters/Device settings. This setting is to be kept for all
The minimum hardware requirements are derived from Figure the parameterization. This makes it easier for the setting action
7.1/1. The device must have 4 voltage inputs and 12 current because the setting value is calculated only on the primary. If
inputs. In addition, one interface (USART or Ethernet) is required you want to use the secondary setting values for test purposes,
for communication with the RTD unit. In the minimum case, this you can switch to secondary after completing parameterization
can also be the interface J (Ethernet). The number of binary in DIGSI 5. Percent or per-unit values always refer to the primary
inputs and outputs comes from the necessary input signals, trip- reference value (object) for all setting modes.
7.3 ping actions, and indications. These must be specified for each The following steps must be completed (for details, also see
application. Furthermore, communication with a control system chapter Configuration of the Device in DIGSI and Basic Settings,
(for example, using Ethernet) is to be provided. If local control is Page 54):
used, there are devices with a large display. 100 function points
are needed for the required functionality.
• Measuring-points routing: Addition of the 3rd current meas-
uring point (3-phase + IN) and modification of the voltage
If a device is specified, the product code (7SK85, 7SX85) is measuring point (3 phase-to-ground voltage + VN)
available. Create a project using DIGSI 5 and configure the
device. Select Differential protection and current • Function-group connections: Connect the 3rd current meas-
measurement, voltage measurement as the application uring point to the FG Motor side 2 and Motor side 2 to the FG
template. After this, delete unused functions under the param- Motor diff. 1
eter Motor (stator) and add additional functions from the • Parameters/System data: Enter the data for the voltage and
library (Overvoltage, 3-phase; Overvoltage V0>). As the differen- current transformers.
tial protection processes 3 sides, add the FG Motor side 2.
• Make the appropriate settings for all function groups in the
General setting sheet under Parameters. According to Figure
1, the neutral-point current transformer (CT1) is grounded
in the Motor direction (parameterNeutral point in
dir.of ref.obj = Yes). With the motor under load, the
active and reactive power consumed is shown as negative in
this FG. To obtain positive operational measured values, set
the parameter P, Q sign in the FG Motor (stator).
The current transformer of motor side 1 points in the motor
direction. For this reason, the power flowing in the motor
direction is counted as positive in this FG. If the parameter
P, Q sign = not inverted, the operational measured
values are displayed as positive. The parameter P, Q sign
only affects the sign of the operational measured values. It
does not generally interfere in the protection functions (for
example, power direction, underexcitation).
After this, you may start parameterization of the individual
protection functions.
[fo_parametrierung_Idiff, 1, en_US]
The RMS value of the maximum current from one side is used
as the restraint current. During startup, this is the motor current,
measured at the neutral point. The mismatch can be estimated
using the current distribution.
[sc_ausgewaehlte-fkt-gruppen, 1, en_US]
[fo_Fehlanpassung_Idiff-Istab, 1, en_US]
Before you start with parameterization, switch the param-
eter Mode from Secondary to Primary under Parame-
7.3
[dw_Kennl-anlaufstrom_phs-L2, 1, en_US]
[dw_Kennl-diff-stab_3-Beinausfuehrung, 1, en_US]
The parameters for the sides of the teed feeder design are all Parameterization of the Sensitive Ground-Fault Protection
the same and must be set as follows:
The motor is connected to the 11-kV busbar via a transformer.
Since the motor is galvanically isolated from the busbar via
the infeed transformer, it is sufficient to use only the residual
voltage for the sensitive ground-fault protection. To reliably
detect ground faults in the motor, a protection range of about
85 % is targeted (also see Figure 4.1/1). However, coupling
7.3 [sc_Nennscheinleistung_SN, 1, en_US] disturbance voltage from the 11-kV side influences the protec-
tion range. A ground fault on the 11-kV side causes a distur-
The rated apparent power consumed is calculated according to bance voltage on the 3.3-kV side of the transformer. The magni-
SrM = √3 * VrM * IrM tude of the disturbance voltage is determined by the capacitor
voltage divider: Coupling capacitance CC between the 11-kV and
As already discussed in chapter Differential Protection, Page 40,
the 3.3-kV windings and the ground capacitance Cgnd (domi-
you can keep the default settings. Switch on the startup detec-
nant: rotor ground capacitance of the motor). The disturbing
tion and adapt to the maximum starting time. With the voltage
influence is limited by a load resistor RL in the broken-delta
reduced to 57 % VrM, the starting time is 28 s. It is set to 30 s
winding of the voltage transformer (or of a grounding trans-
(Figure 7.3/5). former) and thus ensures the protection range. Figure 7.3/7
shows the simplified equivalent circuit referenced to the primary
voltage.
[dw_Ersatzschalt-bedaempfung-Stoerbeeinflussung, 1, en_US]
[sc_einstell-Anlauferkennung_Idiff, 1, en_US]
• Conversion of the ground current to the secondary circuit of
Figure 7.3/5 Stage Idiff, Setting of the Startup Detection the delta winding ICsec
The tripping stage Idiff fast is set above the maximum starting
current. As the motor startup uses a reduced voltage (VM =
0.7158 * Vnet), a starting current of IAM ≈ 5 IrM is assumed for the
setting. The setting value is 1.1 * IAM/IrM = 1.1 * 5 = 5.5 (Figure
7.3/6).
• Required load resistor for a protection range S = 85 %. A
safety margin SF = 1.5 is used in the calculation.
• Required power
[sc_einstell-schwellwert-Idiff, 1, en_US]
The load resistor on the broken-delta winding is approx. 26 Ω
Figure 7.3/6 Stage Idiff Fast, Setting of the Threshold
and the voltage transformer has a power of at least 380 VA.
The sensitive ground-fault protection V0> is set to 15 % of the
zero-sequence voltage and delayed by 0.3 s.
[sc_einstell-fkt-ueberspg-U0, 1, en_US]
The function Unbalanced-load protection 1 has the following
Figure 7.3/8 Setting Function Overvoltage -V0 1 setting values:
[sc_einstellwert-ueberlastschutz, 1, en_US]
Unbalanced-Load Protection
No information is provided in the technical data regarding an
unbalanced load. For this reason, the setting recommendations
of chapter Unbalanced-Load Protection, Page 26 are used.
7.3
[sc_einstellwert_therm_Abbild-laeufer, 1, en_US]
[sc_fkt_anlaufzeitueberwachung, 1, en_US]
Temperature Supervision
The winding and bearing temperatures are measured using an
RTD unit that is connected to the device via a serial interface
Figure 7.3/16 shows an example of the setting for a sensor Undervoltage Protection
(stator winding).
A stage is used as the warning stage in the function 27
Undervolt.-V1 . The protection function evaluates the positive-
sequence voltage.
As shown in Figure 7.3/11, the undervoltage on the transformer
dips to approx. 1.7 kV during startup. For this reason, the
threshold value is selected to be somewhat lower.
Overvoltage Protection
The function 59 Overvolt.-3ph uses the stage Independent 1
as the warning indication. This results in the following settings.
[sc_einstell_ueberspannungsschutz_unabhaengig, 1, en_US]
7.3
[dw_Kennl-Einstell_strombasierenden-Schutzfkt, 1, en_US]
Literature
[1] https://en.wikipedia.org/wiki/Kornd%C3%B6rfer_autotransformer_starter
Protection of Synchronous Motors other motor protection devices 7SK82/85 and 7SX800, the
7UM85/7SX85 have underexcitation protection and rotor
This chapter discusses the protection design for synchro-
ground-fault protection.
nous motors. The main point of focus is the underexcita-
tion protection and rotor ground fault. Setting recommenda-
tions are provided for the other protection functions. Synchro- System Implementation and Protection Scope
nous motors perform various tasks in the raw-materials and Figure 8.1/1 shows as an example the system configuration and
processing industries, in power-generation plants, and in infra- the protection design for a synchronous motor. The synchro-
structure. In the area of high performance requirements for the nous motor is connected to a 10-kV busbar. There are different
motor-drive mechanism, synchronous motors with a power of starting processes for starting the motor. These include direct
up to 50 MW are preferred for use. These motors have the starting, startup with a starting transformer (auto transformer),
benefit that they can easily be controlled regarding the voltage and startup using a starting-frequency converter. In the first
8.1 and have an active influence on the reactive-power balance. 2 methods, the machine starts as an asynchronous motor and,
From the SIPROTEC 5 family, the modular protection devices after reaching the rated speed, the excitation is connected.
7UM85 and 7SX85 can be used. In comparison to the Then, the motor pulls into synchronism.
The example shows startup with a reduced voltage using an tions for startup as an asynchronous motor. The typical protec-
auto transformer. The protection device shown displays the tion functions for synchronous motor operation run in the FG
internal structure with the measuring points and the connection Generator stator. The rotor ground-fault protection requires the
to the transformers, the required function groups (FG) and their FG V/I 1-ph.
connection, and the protection functions (shown using ANSI
numbers). The FG Motor (stator) contains the protection func-
Configuration of the Device in DIGSI and Basic Settings Protection Functions during Motor Startup (FG Motor
(Stator))
The minimum hardware requirements are derived from Figure
8.1/1. The device must have 4 voltage inputs and 8 current Restart Inhibit
inputs. The number of binary inputs and outputs comes from
The protection function is set in 2 functions in SIPROTEC 5. All
the necessary trip initiations, tripping actions, and indications.
the parameters relevant for the thermal rotor replica are entered
These must be specified for each application. Furthermore,
in the function Th.repli.rotor.
communication with a control system (for example, using
Ethernet) is to be provided. If local control is used, there are According to Table 8.1/2, 2 cold startups and 1 warm startup are
devices with a large display. 125 function points are needed for allowed. The motor starts up at the reduced voltage. With 69 %
the required functionality. voltage, the starting current is specified as 2.13 I/IrM (param-
eter Start.cur./mot.rated cur.) and the starting time is
If a device is specified, the product code (7UM85, 7SX85) is
available. Create a project using DIGSI 5 and configure the specified as 55 s. The number of possible startups is usually valid
also at reduced voltage (if necessary, clarify this with the motor
device. Select the application template Generator busbar
manufacturer). Normally, this puts a higher thermal load on the
8.2 connection 4 V 8I . After this, delete unused function
motor. To fully exploit the thermal reserve of the motor, the
groups and add the function groups specific to motor protection
values for reduced voltage are used in this case.
according to Figure 8.1/1. Then, update the protection func-
tionality, the measuring-point routing, and the function-group Leave the parameter Factor T-const. at oper. at the
connections in every FG. default setting of 2. If the motor is at a standstill, cooling takes
considerably longer. For this reason, the parameter Factor
T-const. standstill is set to the value of 15, which is
adapted to the ratio of the stator (300 min/20 min = 15).
The default setting applies for the rest of the parameters. With
2 permissible cold starts, the rotor temperature in the warm
state (after 1 start) is about 56 %. If you set the temperature
threshold for the cold motor to 35 %, there is sufficient reserve
to the 56 %.
[sc_einstellwert_therm_Abbild-laeufer_synchronmotorschutz, 1, en_US]
[sc_fkt_anlaufzeitueberwachung_synchronmotorschutz, 1, en_US]
[sc_einstellpara_fkt_anlaufzeitueberwachung_synchronmotorschutz, 1, en_US]
[sc_einstellwert_Schieflastschutz_syncrhonmotorschutz, 1, en_US]
8.3
[dw_Kennl_Synchronmotors in Per Unit, 1, en_US]
The underexcitation protection is designed such that the setting to slip. In this case, tripping occurs after a short delay (for
values can be read directly from the per-unit illustration of the example, 0.3 s).
capability diagram and a good adaptation to the stability limits is
Division by zero must be avoided by the conductance calculation
possible. How close you come to the limit depends on whether
(I/V). For this reason, the protection function is blocked if the
the motor is also being used for reactive-power compensation.
voltage drops below a minimum voltage. As the threshold value,
In this respect, the underexcitation limit of the voltage controller
25 % of the positive-sequence voltage has proven effective.
must have a minimum safety interval of 10 % to the character-
istic curve of the protection.
Figure 8.3/5 shows the characteristic curves entered into the
capability diagram. When taking over the values, keep in mind [fo_Leitwertberechnung_I-U, 1, en_US]
that the sign of the x-axis is inverted by the transformation
of the capability diagram into the admittance diagram. The The resulting setting values for the underexcitation protection
numerical values remain unchanged by the per-unit illustration. are summarized in Figure 8.3/5.
If the characteristic curves 1 or 2 are exceeded, the protection
is delayed (for example, 3 s) so that, in case of a slight exceed-
ance, the voltage controller can move the machine back into the
stable operating range. When exceeding characteristic curve 3,
the problems with excitation are greater and the motor begins
The stage I-DIFF fast is set above the maximum starting current
(>3.2 I/IrM). Values of 4 I/IrM were selected. The pickup margin is
high because a high short-circuit current (222 MVA/ (√3 10 kV)
≈ 12.8 kA ≈ 17.5 I/IrM) flows due to the large short-circuit power
of the infeed.
[sc_einstell-schwellwert-Idiff_synchronmotorschutz, 1, en_US]
8.3
[sc_einstell_gericht-Erdschlussschutz_Synchronmotorschutz, 1, en_US]
Figure 8.3/9 Current Transformer in Holmgreen Connection Parameterization of the Voltage Protection
Determination of the pickup values for a protection range of The following settings are based on the recommendations in
S = 80%. A safety margin SF = 1.5 is selected for the current chapter Voltage Protection, Page 42 and chapter Parameteriza-
pickup value. tion of Voltage Protection, Page 61.
Overvoltage Protection
The function 59 Overvolt.-3ph uses the Independent 1 stage
as the warning indication. For calculating the setting value, see
the preceding chapters
[fo_I-ansprechwerte-schutzsbereich, 1, en_US]
is used as the ground-fault indication and for disconnection of Figure 8.3/11 Setting the Overvoltage Protection
the load resistor. The load resistor is disconnected after 10 s.
Undervoltage Protection
The function 27 Undervolt.-V1 uses 2 stages. The protection
function evaluates the positive-sequence voltage.
Stage 1 is parameterized as a warning stage and set to approx.
85 % of the voltage (0.85 * 10 kV/√3 = 4.9 kV; the voltage
measured during the start is the voltage in the electrical power
system, not the reduced motor voltage) because, during motor
startup, the voltage on the busbars can dip by up to 10 %. The
2nd stage trips to disconnect the motor in case of an outage
of the electrical power system infeed. After restoration of the
electrical power system, there can be a restart as an asynchro-
nous motor. As the synchronous motor feeds in a short-circuit
current over a longer time in case of faults in the 10-kV electrical
power system, the stage must have sufficient delay. A value
of 3 s is selected. The coordination with the high-speed switch- This results in the following setting values:
over equipment must be kept in mind. Consider the descrip-
tions in chapter Undervoltage Protection, Page 61. A value of
0.6 VrM (0.6 * 10 kV/√3 = 3.46 kV) is selected for the pickup
value.
8.3
[sc_einstell_Lauefererdschlussschutz_synchronmotorschutz, 1, en_US]
Figure 8.3/12 Setting of the Undervoltage Protection Parameterization of the Overcurrent Protection
The overcurrent protection in the FG Motor side 1 is used as
Parameterization of the Rotor Ground-Fault Protection backup protection if the motor feeds back to a short circuit for
The synchronous motor can, in principle, be operated with a too long. The definite-time overcurrent protection stage acts in
ground fault in the rotor winding. However, the double ground parallel with the 2nd stage of the undervoltage protection. The
fault that results in impermissible stresses is critical. For this tripping current is set to 1.3 IrM (1.3 * 713 A ≈ 930 A). As the
reason, the rotor ground-fault protection is of two-stage design motor starting currents are greater than the threshold value, the
(warning and tripping). For detecting rotor ground faults, in the protection function must be blocked during motor startup. Like
example (Figure 8.1/1), a power-frequency voltage is injected for the undervoltage protection, a value of 3 s is selected as the
into the rotor circuit by means of a coupling unit (for example, tripping time.
7XR85). The protection function Rotor ground fault I1
monitors the ground current and reacts in accordance with the
setting. A small ground current flows due to the existing rotor
ground capacitances. If this current is dropped below, a fault
exists in the trip initiation (for example, broken wire or supply-
voltage failure) and a warning indication is issued. You make
this setting under General.
The current pickup values of the protection stages can be esti-
mated as follows.
[sc_einstell_ueberstromzeitschutz_synchronmotorschutz, 1, en_US]
[fo_I-ansprechwerte-schutzstufen, 1, en_US]
Figure 8.3/14 Setting of the Overcurrent Protection (Function
OC-3phase B 1)
The coupling impedance Zcoupling for the 7XR85 is approx. 400 Ω.
Indication of Conformity
OpenSSL 9.1
This product includes software developed by the OpenSSL
Project for use in OpenSSL Toolkit (http://www.openssl.org/).
This product includes software written by Tim Hudson
(tjh@cryptsoft.com).
This product includes cryptographic software written by Eric
Young (eay@cryptsoft.com).
Disclaimer of Liability
Subject to changes and errors. The information given in this
document only contains general descriptions and/or perform-
ance features which may not always specifically reflect those
described, or which may undergo modification in the course
of further development of the products. The requested perform-
ance features are binding only when they are expressly agreed
upon in the concluded contract.
Copyright
Copyright © Siemens AG 2022.
The disclosure, duplication, distribution and editing of this docu-
ment, or utilization and communication of the content are not
permitted, unless authorized in writing. All rights, including
rights created by patent grant or registration of a utility model
or a design, are reserved.
Trademarks
SIPROTEC, DIGSI, SIGRA, SIGUARD, SIMEAS SAFIR, SICAM, and
MindSphere are trademarks of Siemens. Any unauthorized use is
prohibited.