PROJECT: IJT Ac Addax Bioenergy Ltd – 1x32MW


CUSTOMER: M/s ISGEC John Thompson End Customer: M/s Addax Bioenergy, Sierra Leone (SL) Ltd., Africa ALTERNATOR DATA SHEET
R D H Issued: RVP Page Doc No : 1CYJ476632A712D
e C G Checked SD
v B F Released BD
n A Customer Comments E Date 01.07.2011 REV-0
Rev Sl No. Description Technical Detail Vender Data Quantity Make Remarks
1 Rated Apparent Output 40000 kVA 1 TDPS
2 Rated Active out put 32000 kW
3 Rated current 2099 A
4 Synchronous speed 1500 rpm
5 Power factor 0.8 lag
6 Duty - Continuous OK
7 Voltage 11kV + 10%
8 Frequency 50Hz + 5%
9 Combine Variation Voltage & Freq. - + 10%
10 Excitation type - Brushless OK
11 Excitation system response time <25 ms
12 Excitation system with PMG. OK
13 Type of rotor - Cylindrical OK
14 Type of coupling - Flanged End OK
Rotor -F OK
Stator -F OK
15 Class of insulation Exciter armature -F OK
Exciter field -F OK
PMG stator -F OK Alternator with PMG
Rotor -B OK
Stator -B OK
16 Temperature rise Exciter armature -B OK
Exciter field -B OK
PMG stator -B OK
Star point design
17 NGR Earthing
(RESISTIVELY EARTHED) -
Direction of rotation
18 CW from DE
(Looking from Drive END) :
19 Type of driving machinery - Steam turbine OK
Generator - IP 54 OK
20 Degree of protection Exciter - IP 54 OK
PMG stator - IP54 NA
21 Colour shade - RAL 7032 OK
22 Coat thickness - 125 microns OK
23 Installation - Indoor OK
24 Design Ambient Temp. - 50 DegC OK
26 Altitude Above sea level - 1000MSL OK
Air inlet temperature - 42 degC
27
Air outlet temperature 56 degC
28 Method of cooling - CACW OK

29 Atmosphere - Non Hazardous OK


Page 2 of 3

PROJECT: IJT Ac Addax Bioenergy Ltd – 1x32MW


CUSTOMER: M/s ISGEC John Thompson End Customer: M/s Addax Bioenergy, Sierra Leone (SL) Ltd., Africa ALTERNATOR DATA SHEET
R D H Issued: RVP Page Doc No : 1CYJ476632A712D
e C G Checked SD
v B F Released BD
n A Customer Comments E Date 01.07.2011 REV-0
Rev Sl No. Description Technical Detail Vender Data Quantity Make Remarks
30 Cooling System Cooling water Inlet Temperature: 32 Deg C
31 Cooler Location : TOP
No. of Coolers - 4 x 33% cooler sections
32
Required cooling water flow - 3500 LPM
33 Temperature rise of cooling water (Max. temp rise) 6 degC
Cooling water recommended Pr. At the inlet 1 to 2 kg/cm2
34
Pressure Drop cooling water - 1 kg/cm2
35 Fouling factor (Cleanliness Factor 85% req.) - 0.0002 m2/kcal/hr/deg.C
Cooling water type - Clear untreated water
36
Type of bearing: Sleeve
37 Required Oil Flow to Bearing (LPM) - 60 LPM
Required Oil Pressure - 1 to 2 kg/cm2
38
Type of Oil- ISO VG 46 OK
Generator - 400V, 3-ph, 50/60Hz, 4Nos.x1kW OK
39 Space heater
Exciter - 220V, 1-ph, 50/60Hz, 1No.x200W OK
For winding temperature 5 per phase - 15 nos duplex OK
Core teeth temperature - 6 nos. duplex OK
For bearing temperature(for each bearing) - 01 No(Duplex) OK
40 RTD (Pt100/6Wire/Duplex)
Hot air Temperature - 02 Nos(Duplex) OK
Cold AirTemperature - 02 Nos (Duplex) OK
Exciter Field RTD - 02 Nos OK
For hot air outlet temperature - 2 Nos OK
41 Local Temperature gauges without contacts For cold air temperature - 2Nos OK
For Each Bearing - 1 No. OK
42 Leak/moisture detector Leakage Detector device - 1 No per tray OK (Total 2 no.s of WLD provided)
Moisture detector - 2 nos. OK
43 Short circuit ratio 0.61
Effective winding capacitance to earth
44 (a) Per Phase (Micro Farad) 0.258 Micro Farad
(b) All phase connected together (Micro Farad) 0.774 Micro Farad
45 Surge Impedance - Ohm /Phase 46.9 ohm
46 Synchronous impedance - Ohm 4.92 ohm
47 Maximum permissible cap. Loading (MVAR) 20.6 MVAR
48 Maximum permissible ind. Loading (MVAR) 30.9 MVAR
49 Stator Wdg. Test voltage - kV / Min 23 kV for 1 min
50 Field Wdg. Test voltage - kV / Min 1.5 kV for 1 min
51 Maximum Over speed - 1800 rpm for 2 min
52 Critical speed First Lateral Critical speed > 2160 RPM
53 Rotor Inertia GD2 - kg-m2 12,216
54 Rotor Inertia WK2 - 3,054
55 Minimum Barring speed 15 RPM
Total weight of rotor - - 20,500
Total weight of stator - - 42,000
56 Total weight of generator -
Total weight of Alternator - 78,000
Heaviest lift - Complete Generator (Without Cooler)
Page 3 of 3

PROJECT: IJT Ac Addax Bioenergy Ltd – 1x32MW


CUSTOMER: M/s ISGEC John Thompson End Customer: M/s Addax Bioenergy, Sierra Leone (SL) Ltd., Africa ALTERNATOR DATA SHEET
R D H Issued: RVP Page Doc No : 1CYJ476632A712D
e C G Checked SD
v B F Released BD
n A Customer Comments E Date 01.07.2011 REV-0
Rev Sl No. Description Technical Detail Vender Data Quantity Make Remarks
BASE MVA / Base kV 40 MVA / 11 kV
Xd unsat/sat ( P.U.) 1.849 / 1.627
Xd' unsat/sat ( P.U.) 0.304 / 0.268
Xd" unsat/sat ( P.U.) 0.18
Reactance - 1.814 / 1.597
Xq unsat/sat ( P.U.)
57 ( IS / IEC tolerence is applicable for all
reactance & resistance value ) Xq' unsat/sat ( P.U.) 1.814 / 1.597
Xq" unsat/sat ( P.U.) 0.374
X0 unsat/sat ( P.U.) 0.157 / 0.138
X2 ( P.U.) 0.28
Armature Leakage Reactance (unsat/sat) ( P.U.) 0.178 / 0.157
Td' (s) 0.789
Time Constant - Td" (s) 0.035
A 58 ( IS / IEC tolerence is applicable for all time Tdo' (s) 4.795
constant value ) 1.011
Tdo" (s)
Ta (s) 0.526
59 Armature Resistance (25Deg.C) - ohm/phase 0.0060
60 Armature Resistance (100Deg.C) - ohm/phase 0.0077
61 Field Resistance (25Deg.C) - ohm/phase 0.5656
62 Field Resistance (100Deg.C) - ohm/phase 0.7287
63 Effective Neg. seq. Resistance ohm/phase 0.0142
64 Stator insulation treatment VPI
65 Rotor insulation treatment VPI
110% overload for one hour
66 Overload capability of generator
in every 12 hour
67 Nagative sequence capabilities I2 = 15%.I2²t = 20 sec
68 Temp rise in stator ( ETD method) 83 Degree C
69 Temp rise in rotor ( Resistance method ) 88 Degree C
70 Cooler tube material SS 304
100% of rated output with one cooler
71 Redundancy in case of one cooler out of service
out of service.
Generator withstand capability for three phase line to line , 3 sec
72
line to earth or two line to earth short circuit
Excitation (Main Machine) - Excitation System Type - brushless Brushless
PMG rating and Voltage - kVA / V 10 / 200
PMG full load current - A 28.8
Exciter Rating - kW 250
Maxi. Field Voltage(EXCITER) - V 147
Min. Field Voltage(EXCITER) - V 12
73
Maxi. Field current(EXCITER) - A 26
Min. field current(EXCITER) - A 2
Voltage at no load (Main Field) - V 144
Voltage at full load (Main Field) - V 399
Current at no load (Main Field) - A 197
Current at full load (Main Field) - A 548
At full load - 97.9
At 3/4 load - 97.8
74 Efficiency at rated PF (%)
At 1/2 load - 97.4
At 1/4 load - 95.8