Professional Documents
Culture Documents
HV Side 7.5MVA Transformer (Star TCC)
HV Side 7.5MVA Transformer (Star TCC)
kV=161)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
100 100
Relay261 - P
50 OC1 50
ALSTOM
30 P127 30
CT Ratio 100:5
IEC - Standard Inverse
Pickup = 0.2 (0.1 - 25 xCT Sec)
Time Dial = 0.1
10 3x = 0.63 s, 5x = 0.428 s, 8x = 0.33 s 10
Inst = 1 (0.5 - 40 xCT Sec)
Time Delay = 0.2 s
5 5
Seconds
Seconds
3 3
Newton PV Farm2 T1
1 1
.5 .5
.3 .3
.1 Newton PV Farm2 T1 .1
Inrush
Newton PV Farm2 T1
.05 7.5 MVA .05
161/11 kV
.03 12 %Z .03
YNyn0
Relay261 Relay261 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Star1