Project: ETAP Page: 1

11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

IEC 60909 Standard


3-Phase Fault Currents

Swing V-Control Load Total


Number of Buses: 1 0 34 35

XFMR2 XFMR3 Reactor Line/Cable Impedance Tie PD Total


Number of Branches: 3 0 0 31 0 0 34

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total
Number of Machines: 0 1 0 0 0 1

System Frequency: 50.00 Hz

Unit System: Metric

Project Filename: Aykan 2 GES

Output Filename: C:\ETAP 1100\aykan 2 ges\Untitled.SI1


Project: ETAP Page: 2
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent

Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C

Transmission Line Resistance: Yes Individual

Cable Resistance: Yes Individual


Project: ETAP Page: 3
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Aykan 2 GES Ölçü Load 31.500 31.500 1 100.00 0.00

Bus3 Load 31.500 31.500 1 100.00 0.00

Bus7 Load 0.400 0.400 1 100.00 0.00

Bus8 Load 0.400 0.400 1 100.00 0.00

Bus9 Load 0.400 0.400 1 100.00 0.00

Bus10 Load 0.400 0.400 1 100.00 0.00

Bus11 Load 0.400 0.400 1 100.00 0.00

Bus12 Load 0.400 0.400 1 100.00 0.00

Bus13 Load 0.400 0.400 1 100.00 0.00

Bus17 Load 31.500 31.500 1 100.00 0.00

Bus18 Load 0.400 0.400 1 100.00 0.00

Bus19 Load 0.400 0.400 1 100.00 0.00

Bus21 Load 31.500 31.500 1 100.00 0.00

Bus22 Load 0.400 0.400 1 100.00 0.00

Bus23 SWNG 154.000 154.000 1 100.00 0.00

Bus27 Load 31.500 31.500 1 100.00 0.00

Bus29 Load 0.400 0.400 1 100.00 0.00

Bus30 Load 0.400 0.400 1 100.00 0.00

Bus32 Load 0.400 0.400 1 100.00 0.00

Bus33 Load 0.400 0.400 1 100.00 0.00

Bus34 Load 0.400 0.400 1 100.00 0.00

Bus35 Load 0.400 0.400 1 100.00 0.00

Bus42 Load 0.400 0.400 1 100.00 0.00

Bus43 Load 0.400 0.400 1 100.00 0.00

Bus44 Load 0.400 0.400 1 100.00 0.00

Bus46 Load 0.400 0.400 1 100.00 0.00

Bus47 Load 0.400 0.400 1 100.00 0.00

Bus66 Load 0.400 0.400 1 100.00 0.00

Bus67 Load 0.400 0.400 1 100.00 0.00

Bus68 Load 0.400 0.400 1 100.00 0.00

Bus70 Load 0.400 0.400 1 100.00 0.00

Bus71 Load 0.400 0.400 1 100.00 0.00

EMİRGAZİ DM Load 31.500 31.500 1 100.00 0.00

EMİRGAZİ KÖK Load 31.500 31.500 1 100.00 0.00


Project: ETAP Page: 4
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

MEDAŞ DAĞITIM MERKEZİ Load 31.500 31.500 1 100.00 0.00

35 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP .
Project: ETAP Page: 5
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

Line/Cable Input Data

Ohms or Siemens/1000 m per Conductor (Cable) or per Phase (Line)


Line/Cable Length

ID Library Size Adj. (m) % Tol. #/Phase T (°C) R X Y

Cable2 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable4 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable5 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable6 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable7 33NCUS1 95 10.0 0 1 75 0.23654 0.14300 0.0000531

Cable9 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable11 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable13 1,0NCUN4 16 225.0 0 1 75 1.39251 0.08000 0.0000971

Cable14 33NCUS1 95 10.0 0 1 75 0.23654 0.14300 0.0000531

Cable15 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable16 33NCUS1 240 10.0 0 2 75 0.09347 0.12500 0.0000719

Cable17 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable18 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable19 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable20 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable22 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable24 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable41 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable42 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable43 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable44 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable46 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable54 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable55 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable56 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable58 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable59 1,0NCUN4 16 16.0 0 1 75 1.39251 0.08000 0.0000971

Cable61 33NCUS1 240 10.0 0 2 75 0.09347 0.12500 0.0000719

Line1 168 35700.0 0 1 75 0.47088 0.38387 0.0000031

Line3 168 1000.0 0 1 75 0.47088 0.38387 0.0000031

Line5 168 2250.0 0 1 75 0.47088 0.38387 0.0000031

Line / Cable resistances are listed at the specified temperatures.


Project: ETAP Page: 6
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted


ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z

T2 0.630 31.500 0.400 4.00 1.50 0 0 0 0 0 4.0000

T8 0.630 31.500 0.400 4.00 1.50 0 0 0 0 0 4.0000

T9 50.000 154.000 31.500 12.50 45.00 0 0 0 0 0 12.5000


Project: ETAP Page: 7
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb


ID Type From Bus To Bus R X Z Y

T2 2W XFMR Bus17 Bus19 344.43 516.65 620.93

T8 2W XFMR Bus27 Bus13 344.43 516.65 620.93

T9 2W XFMR Bus23 Bus21 0.54 24.30 24.30

Cable2 Cable Bus29 Bus30 1392.51 80.00 1394.81

Cable4 Cable Bus29 Bus32 1392.51 80.00 1394.81

Cable5 Cable Bus29 Bus33 1392.51 80.00 1394.81

Cable6 Cable Bus29 Bus34 1392.51 80.00 1394.81

Cable7 Cable Bus27 Aykan 2 GES Ölçü 0.02 0.01 0.03

Cable9 Cable Bus29 Bus35 1392.51 80.00 1394.81

Cable11 Cable Bus12 Bus29 1392.51 80.00 1394.81

Cable13 Cable Aykan 2 GES Ölçü MEDAŞ DAĞITIM MERKEZİ 3.16 0.18 3.16

Cable14 Cable Bus17 MEDAŞ DAĞITIM MERKEZİ 0.02 0.01 0.03

Cable15 Cable Bus3 MEDAŞ DAĞITIM MERKEZİ 0.22 0.01 0.22

Cable16 Cable Bus18 Bus19 29.21 39.06 48.78

Cable17 Cable Bus12 Bus46 1392.51 80.00 1394.81

Cable18 Cable Bus46 Bus42 1392.51 80.00 1394.81

Cable19 Cable Bus46 Bus43 1392.51 80.00 1394.81

Cable20 Cable Bus46 Bus44 1392.51 80.00 1394.81

Cable22 Cable Bus46 Bus47 1392.51 80.00 1394.81

Cable24 Cable Bus46 Bus22 1392.51 80.00 1394.81

Cable41 Cable Bus12 Bus70 1392.51 80.00 1394.81

Cable42 Cable Bus70 Bus66 1392.51 80.00 1394.81

Cable43 Cable Bus70 Bus67 1392.51 80.00 1394.81

Cable44 Cable Bus70 Bus68 1392.51 80.00 1394.81

Cable46 Cable Bus70 Bus71 1392.51 80.00 1394.81

Cable54 Cable Bus12 Bus10 1392.51 80.00 1394.81

Cable55 Cable Bus10 Bus7 1392.51 80.00 1394.81

Cable56 Cable Bus10 Bus8 1392.51 80.00 1394.81

Cable58 Cable Bus10 Bus9 1392.51 80.00 1394.81

Cable59 Cable Bus10 Bus11 1392.51 80.00 1394.81

Cable61 Cable Bus12 Bus13 29.21 39.06 48.78

Line1 Line Bus21 EMİRGAZİ DM 169.42 138.11 218.58

Line3 Line EMİRGAZİ KÖK EMİRGAZİ DM 4.75 3.87 6.12

Line5 Line Bus3 EMİRGAZİ KÖK 10.68 8.70 13.78


Project: ETAP Page: 8
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

Power Grid Input Data

% Impedance
Power Grid Connected Bus Rating 100 MVA Base
ID ID MVASC kV R X" R/X

KARAPINAR 154 kV TM Bus23 2667.358 154.000 0.37304 3.73042 0.10

Total Connected Power Grids ( = 1 ): 2667.358 MVA


Project: ETAP Page: 9
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

SHORT-CIRCUIT REPORT

3-Phase fault at bus: Aykan 2 GES Ölçü

Nominal kV = 31.500
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 1.171 kA Method C
Steady State = 0.781 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Aykan 2 GES Ölçü Total 0.00 0.572 -0.532 0.9 0.781

Bus27 Aykan 2 GES Ölçü 0.00 0.010 0.000 0.0 0.010

MEDAŞ DAĞITIM MERKEZİ Aykan 2 GES Ölçü 1.21 0.562 -0.532 0.9 0.774

Bus13 Bus27 3.05 0.010 0.000 0.0 0.010

Bus17 MEDAŞ DAĞITIM MERKEZİ 1.21 0.001 0.000 0.0 0.001

Bus3 MEDAŞ DAĞITIM MERKEZİ 1.30 0.561 -0.532 0.9 0.774

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 0.781 0.782 0.039

0.02 0.781 0.781 0.001

0.03 0.781 0.781 0.000

0.04 0.781 0.781 0.000

0.05 0.781 0.781 0.000

0.06 0.781 0.781 0.000

0.07 0.781 0.781 0.000

0.08 0.781 0.781 0.000

0.09 0.781 0.781 0.000

0.10 0.781 0.781 0.000

0.15 0.781 0.781 0.000

0.20 0.781 0.781 0.000

0.25 0.781 0.781 0.000

0.30 0.781 0.781 0.000


Project: ETAP Page: 10
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus3

Nominal kV = 31.500
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 1.185 kA Method C
Steady State = 0.789 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus3 Total 0.00 0.573 -0.543 0.9 0.789

MEDAŞ DAĞITIM MERKEZİ Bus3 0.00 0.010 0.000 0.0 0.010

EMİRGAZİ KÖK Bus3 5.34 0.563 -0.542 1.0 0.781

Aykan 2 GES Ölçü MEDAŞ DAĞITIM MERKEZİ 0.02 0.010 0.000 0.0 0.010

Bus17 MEDAŞ DAĞITIM MERKEZİ 0.00 0.001 0.000 0.0 0.001

EMİRGAZİ DM EMİRGAZİ KÖK 7.71 0.563 -0.542 1.0 0.781

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 0.789 0.790 0.041

0.02 0.789 0.789 0.002

0.03 0.789 0.789 0.000

0.04 0.789 0.789 0.000

0.05 0.789 0.789 0.000

0.06 0.789 0.789 0.000

0.07 0.789 0.789 0.000

0.08 0.789 0.789 0.000

0.09 0.789 0.789 0.000

0.10 0.789 0.789 0.000

0.15 0.789 0.789 0.000

0.20 0.789 0.789 0.000

0.25 0.789 0.789 0.000

0.30 0.789 0.789 0.000


Project: ETAP Page: 11
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus7

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.427 kA Method C
Steady State = 4.455 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus7 Total 0.00 4.323 -1.078 0.2 4.455

Bus10 Bus7 40.63 4.281 -1.078 0.3 4.415

PVA16 Bus7 100.00 0.042 0.000 0.0 0.042

Bus12 Bus10 80.61 4.206 -1.087 0.3 4.344

Bus8 Bus10 40.85 0.025 0.003 0.1 0.025

Bus9 Bus10 40.85 0.025 0.003 0.1 0.025

Bus11 Bus10 40.85 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.455 4.455 0.000

0.02 4.455 4.455 0.000

0.03 4.455 4.455 0.000

0.04 4.455 4.455 0.000

0.05 4.455 4.455 0.000

0.06 4.455 4.455 0.000

0.07 4.455 4.455 0.000

0.08 4.455 4.455 0.000

0.09 4.455 4.455 0.000

0.10 4.455 4.455 0.000

0.15 4.455 4.455 0.000

0.20 4.455 4.455 0.000

0.25 4.455 4.455 0.000

0.30 4.455 4.455 0.000


Project: ETAP Page: 12
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus8

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.427 kA Method C
Steady State = 4.455 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus8 Total 0.00 4.323 -1.078 0.2 4.455

Bus10 Bus8 40.63 4.281 -1.078 0.3 4.415

PVA17 Bus8 100.00 0.042 0.000 0.0 0.042

Bus12 Bus10 80.61 4.206 -1.087 0.3 4.344

Bus7 Bus10 40.85 0.025 0.003 0.1 0.025

Bus9 Bus10 40.85 0.025 0.003 0.1 0.025

Bus11 Bus10 40.85 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.455 4.455 0.000

0.02 4.455 4.455 0.000

0.03 4.455 4.455 0.000

0.04 4.455 4.455 0.000

0.05 4.455 4.455 0.000

0.06 4.455 4.455 0.000

0.07 4.455 4.455 0.000

0.08 4.455 4.455 0.000

0.09 4.455 4.455 0.000

0.10 4.455 4.455 0.000

0.15 4.455 4.455 0.000

0.20 4.455 4.455 0.000

0.25 4.455 4.455 0.000

0.30 4.455 4.455 0.000


Project: ETAP Page: 13
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus9

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.427 kA Method C
Steady State = 4.455 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus9 Total 0.00 4.323 -1.078 0.2 4.455

Bus10 Bus9 40.63 4.281 -1.078 0.3 4.415

PVA18 Bus9 100.00 0.042 0.000 0.0 0.042

Bus12 Bus10 80.61 4.206 -1.087 0.3 4.344

Bus7 Bus10 40.85 0.025 0.003 0.1 0.025

Bus8 Bus10 40.85 0.025 0.003 0.1 0.025

Bus11 Bus10 40.85 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.455 4.455 0.000

0.02 4.455 4.455 0.000

0.03 4.455 4.455 0.000

0.04 4.455 4.455 0.000

0.05 4.455 4.455 0.000

0.06 4.455 4.455 0.000

0.07 4.455 4.455 0.000

0.08 4.455 4.455 0.000

0.09 4.455 4.455 0.000

0.10 4.455 4.455 0.000

0.15 4.455 4.455 0.000

0.20 4.455 4.455 0.000

0.25 4.455 4.455 0.000

0.30 4.455 4.455 0.000


Project: ETAP Page: 14
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus10

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 10.573 kA Method C
Steady State = 7.327 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus10 Total 0.00 6.828 -2.656 0.4 7.327

Bus12 Bus10 66.00 6.661 -2.656 0.4 7.171

Bus7 Bus10 0.38 0.042 0.000 0.0 0.042

Bus8 Bus10 0.38 0.042 0.000 0.0 0.042

Bus9 Bus10 0.38 0.042 0.000 0.0 0.042

Bus11 Bus10 0.38 0.042 0.000 0.0 0.042

Bus29 Bus12 66.57 0.085 0.047 0.6 0.097

Bus46 Bus12 66.51 0.076 0.043 0.6 0.088

Bus70 Bus12 66.41 0.061 0.034 0.6 0.070

Bus13 Bus12 67.52 6.439 -2.781 0.4 7.013

PVA16 Bus7 100.00 0.042 0.000 0.0 0.042

PVA17 Bus8 100.00 0.042 0.000 0.0 0.042

PVA18 Bus9 100.00 0.042 0.000 0.0 0.042

PVA10 Bus11 100.00 0.042 0.000 0.0 0.042

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 7.327 7.327 0.004

0.02 7.327 7.327 0.000

0.03 7.327 7.327 0.000

0.04 7.327 7.327 0.000

0.05 7.327 7.327 0.000

0.06 7.327 7.327 0.000

0.07 7.327 7.327 0.000

0.08 7.327 7.327 0.000

0.09 7.327 7.327 0.000

0.10 7.327 7.327 0.000

0.15 7.327 7.327 0.000

0.20 7.327 7.327 0.000


Project: ETAP Page: 15
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

(Cont.)

3-Phase fault at bus: Bus10

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 10.573 kA Method C
Steady State = 7.327 kA rms

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.25 7.327 7.327 0.000

0.30 7.327 7.327 0.000


Project: ETAP Page: 16
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus11

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.427 kA Method C
Steady State = 4.455 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus11 Total 0.00 4.323 -1.078 0.2 4.455

Bus10 Bus11 40.63 4.281 -1.078 0.3 4.415

PVA10 Bus11 100.00 0.042 0.000 0.0 0.042

Bus12 Bus10 80.61 4.206 -1.087 0.3 4.344

Bus7 Bus10 40.85 0.025 0.003 0.1 0.025

Bus8 Bus10 40.85 0.025 0.003 0.1 0.025

Bus9 Bus10 40.85 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.455 4.455 0.000

0.02 4.455 4.455 0.000

0.03 4.455 4.455 0.000

0.04 4.455 4.455 0.000

0.05 4.455 4.455 0.000

0.06 4.455 4.455 0.000

0.07 4.455 4.455 0.000

0.08 4.455 4.455 0.000

0.09 4.455 4.455 0.000

0.10 4.455 4.455 0.000

0.15 4.455 4.455 0.000

0.20 4.455 4.455 0.000

0.25 4.455 4.455 0.000

0.30 4.455 4.455 0.000


Project: ETAP Page: 17
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus12

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 26.463 kA Method C
Steady State = 16.847 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus12 Total 0.00 10.716 -13.000 1.2 16.847

Bus29 Bus12 2.09 0.227 0.000 0.0 0.227

Bus46 Bus12 1.88 0.204 0.000 0.0 0.204

Bus70 Bus12 1.51 0.164 0.000 0.0 0.164

Bus10 Bus12 1.51 0.164 0.000 0.0 0.164

Bus13 Bus12 5.27 9.956 -12.999 1.3 16.374

Bus30 Bus29 2.67 0.064 0.000 0.0 0.064

Bus32 Bus29 2.46 0.041 0.000 0.0 0.041

Bus33 Bus29 2.46 0.041 0.000 0.0 0.041

Bus34 Bus29 2.46 0.041 0.000 0.0 0.041

Bus35 Bus29 2.46 0.041 0.000 0.0 0.041

Bus42 Bus46 2.26 0.041 0.000 0.0 0.041

Bus43 Bus46 2.26 0.041 0.000 0.0 0.041

Bus44 Bus46 2.26 0.041 0.000 0.0 0.041

Bus47 Bus46 2.26 0.041 0.000 0.0 0.041

Bus22 Bus46 2.26 0.041 0.000 0.0 0.041

Bus66 Bus70 1.89 0.041 0.000 0.0 0.041

Bus67 Bus70 1.89 0.041 0.000 0.0 0.041

Bus68 Bus70 1.89 0.041 0.000 0.0 0.041

Bus71 Bus70 1.89 0.041 0.000 0.0 0.041

Bus7 Bus10 1.89 0.041 0.000 0.0 0.041

Bus8 Bus10 1.89 0.041 0.000 0.0 0.041

Bus9 Bus10 1.89 0.041 0.000 0.0 0.041

Bus11 Bus10 1.89 0.041 0.000 0.0 0.041

Bus27 Bus13 72.35 9.956 -12.999 1.3 16.374

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 16.847 16.964 1.991


Project: ETAP Page: 18
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

(Cont.)

3-Phase fault at bus: Bus12

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 26.463 kA Method C
Steady State = 16.847 kA rms

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.02 16.847 16.848 0.168

0.03 16.847 16.847 0.014

0.04 16.847 16.847 0.001

0.05 16.847 16.847 0.000

0.06 16.847 16.847 0.000

0.07 16.847 16.847 0.000

0.08 16.847 16.847 0.000

0.09 16.847 16.847 0.000

0.10 16.847 16.847 0.000

0.15 16.847 16.847 0.000

0.20 16.847 16.847 0.000

0.25 16.847 16.847 0.000

0.30 16.847 16.847 0.000


Project: ETAP Page: 19
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus13

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 27.897 kA Method C
Steady State = 17.758 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus13 Total 0.00 11.277 -13.717 1.2 17.758

Bus12 Bus13 0.24 0.758 -0.002 0.0 0.758

Bus27 Bus13 70.82 10.519 -13.715 1.3 17.284

Bus29 Bus12 2.25 0.227 -0.001 0.0 0.227

Bus46 Bus12 2.04 0.204 -0.001 0.0 0.204

Bus70 Bus12 1.68 0.164 0.000 0.0 0.164

Bus10 Bus12 1.68 0.164 0.000 0.0 0.164

Aykan 2 GES Ölçü Bus27 70.82 0.134 -0.174 1.3 0.219

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 17.758 17.882 2.101

0.02 17.758 17.759 0.178

0.03 17.758 17.758 0.015

0.04 17.758 17.758 0.001

0.05 17.758 17.758 0.000

0.06 17.758 17.758 0.000

0.07 17.758 17.758 0.000

0.08 17.758 17.758 0.000

0.09 17.758 17.758 0.000

0.10 17.758 17.758 0.000

0.15 17.758 17.758 0.000

0.20 17.758 17.758 0.000

0.25 17.758 17.758 0.000

0.30 17.758 17.758 0.000


Project: ETAP Page: 20
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus17

Nominal kV = 31.500
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 1.184 kA Method C
Steady State = 0.788 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus17 Total 0.00 0.573 -0.542 0.9 0.788

MEDAŞ DAĞITIM MERKEZİ Bus17 0.01 0.572 -0.542 0.9 0.788

Bus19 Bus17 0.17 0.001 0.000 0.0 0.001

Aykan 2 GES Ölçü MEDAŞ DAĞITIM MERKEZİ 0.03 0.010 0.000 0.0 0.010

Bus3 MEDAŞ DAĞITIM MERKEZİ 0.10 0.562 -0.541 1.0 0.781

Bus18 Bus19 0.18 0.044 0.000 0.0 0.044

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 0.788 0.790 0.041

0.02 0.788 0.788 0.002

0.03 0.788 0.788 0.000

0.04 0.788 0.788 0.000

0.05 0.788 0.788 0.000

0.06 0.788 0.788 0.000

0.07 0.788 0.788 0.000

0.08 0.788 0.788 0.000

0.09 0.788 0.788 0.000

0.10 0.788 0.788 0.000

0.15 0.788 0.788 0.000

0.20 0.788 0.788 0.000

0.25 0.788 0.788 0.000

0.30 0.788 0.788 0.000


Project: ETAP Page: 21
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus18

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 26.080 kA Method C
Steady State = 16.481 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus18 Total 0.00 10.038 -13.072 1.3 16.481

Bus19 Bus18 5.30 9.996 -13.072 1.3 16.456

PVA20 Bus18 100.00 0.042 0.000 0.0 0.042

Bus17 Bus19 72.71 9.996 -13.072 1.3 16.456

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 16.481 16.616 2.113

0.02 16.481 16.483 0.192

0.03 16.481 16.481 0.017

0.04 16.481 16.481 0.002

0.05 16.481 16.481 0.000

0.06 16.481 16.481 0.000

0.07 16.481 16.481 0.000

0.08 16.481 16.481 0.000

0.09 16.481 16.481 0.000

0.10 16.481 16.481 0.000

0.15 16.481 16.481 0.000

0.20 16.481 16.481 0.000

0.25 16.481 16.481 0.000

0.30 16.481 16.481 0.000


Project: ETAP Page: 22
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus19

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 27.530 kA Method C
Steady State = 17.402 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus19 Total 0.00 10.605 -13.797 1.3 17.402

Bus18 Bus19 0.01 0.042 0.000 0.0 0.042

Bus17 Bus19 71.19 10.563 -13.797 1.3 17.376

PVA20 Bus18 100.00 0.042 0.000 0.0 0.042

MEDAŞ DAĞITIM MERKEZİ Bus17 71.19 0.134 -0.175 1.3 0.221

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 17.402 17.543 2.226

0.02 17.402 17.403 0.202

0.03 17.402 17.402 0.018

0.04 17.402 17.402 0.002

0.05 17.402 17.402 0.000

0.06 17.402 17.402 0.000

0.07 17.402 17.402 0.000

0.08 17.402 17.402 0.000

0.09 17.402 17.402 0.000

0.10 17.402 17.402 0.000

0.15 17.402 17.402 0.000

0.20 17.402 17.402 0.000

0.25 17.402 17.402 0.000

0.30 17.402 17.402 0.000


Project: ETAP Page: 23
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus21

Nominal kV = 31.500
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 19.124 kA Method C
Steady State = 7.096 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus21 Total 0.00 0.248 -7.091 28.6 7.096

EMİRGAZİ DM Bus21 1.12 0.010 0.000 0.0 0.010

Bus23 Bus21 85.52 0.237 -7.091 29.9 7.095

EMİRGAZİ KÖK EMİRGAZİ DM 1.16 0.010 0.000 0.0 0.010

KARAPINAR 154 kV TM Bus23 100.00 0.049 -1.450 29.9 1.451

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 7.096 11.485 9.031

0.02 7.096 10.791 8.130

0.03 7.096 10.194 7.318

0.04 7.096 9.682 6.587

0.05 7.096 9.248 5.931

0.06 7.096 8.880 5.339

0.07 7.096 8.570 4.806

0.08 7.096 8.311 4.327

0.09 7.096 8.094 3.895

0.10 7.096 7.915 3.507

0.15 7.096 7.392 2.073

0.20 7.096 7.201 1.225

0.25 7.096 7.133 0.724

0.30 7.096 7.109 0.428


Project: ETAP Page: 24
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus22

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.446 kA Method C
Steady State = 4.469 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus22 Total 0.00 4.337 -1.077 0.2 4.469

Bus46 Bus22 40.75 4.295 -1.077 0.3 4.428

PVA27 Bus22 100.00 0.042 0.000 0.0 0.042

Bus12 Bus46 80.64 4.195 -1.089 0.3 4.334

Bus42 Bus46 40.97 0.025 0.003 0.1 0.025

Bus43 Bus46 40.97 0.025 0.003 0.1 0.025

Bus44 Bus46 40.97 0.025 0.003 0.1 0.025

Bus47 Bus46 40.97 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.469 4.469 0.000

0.02 4.469 4.469 0.000

0.03 4.469 4.469 0.000

0.04 4.469 4.469 0.000

0.05 4.469 4.469 0.000

0.06 4.469 4.469 0.000

0.07 4.469 4.469 0.000

0.08 4.469 4.469 0.000

0.09 4.469 4.469 0.000

0.10 4.469 4.469 0.000

0.15 4.469 4.469 0.000

0.20 4.469 4.469 0.000

0.25 4.469 4.469 0.000

0.30 4.469 4.469 0.000


Project: ETAP Page: 25
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus23

Nominal kV = 154.000
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 24.692 kA Method C
Steady State = 10.000 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus23 Total 0.00 0.997 -9.950 10.0 10.000

Bus21 Bus23 0.12 0.002 0.000 0.0 0.002

KARAPINAR 154 kV TM Bus23 100.00 0.995 -9.950 10.0 10.000

EMİRGAZİ DM Bus21 1.21 0.010 0.000 0.0 0.010

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 10.000 14.377 10.329

0.02 10.000 12.527 7.545

0.03 10.000 11.418 5.510

0.04 10.000 10.780 4.025

0.05 10.000 10.423 2.940

0.06 10.000 10.228 2.147

0.07 10.000 10.123 1.568

0.08 10.000 10.066 1.145

0.09 10.000 10.035 0.837

0.10 10.000 10.019 0.611

0.15 10.000 10.001 0.127

0.20 10.000 10.000 0.026

0.25 10.000 10.000 0.005

0.30 10.000 10.000 0.001


Project: ETAP Page: 26
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus27

Nominal kV = 31.500
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 1.171 kA Method C
Steady State = 0.781 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus27 Total 0.00 0.572 -0.532 0.9 0.781

Aykan 2 GES Ölçü Bus27 0.01 0.562 -0.532 0.9 0.774

Bus13 Bus27 3.05 0.010 0.000 0.0 0.010

MEDAŞ DAĞITIM MERKEZİ Aykan 2 GES Ölçü 1.22 0.562 -0.532 0.9 0.774

Bus12 Bus13 3.29 0.780 -0.022 0.0 0.781

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 0.781 0.782 0.039

0.02 0.781 0.781 0.001

0.03 0.781 0.781 0.000

0.04 0.781 0.781 0.000

0.05 0.781 0.781 0.000

0.06 0.781 0.781 0.000

0.07 0.781 0.781 0.000

0.08 0.781 0.781 0.000

0.09 0.781 0.781 0.000

0.10 0.781 0.781 0.000

0.15 0.781 0.781 0.000

0.20 0.781 0.781 0.000

0.25 0.781 0.781 0.000

0.30 0.781 0.781 0.000


Project: ETAP Page: 27
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus29

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 10.658 kA Method C
Steady State = 7.385 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus29 Total 0.00 6.887 -2.666 0.4 7.385

Bus30 Bus29 0.60 0.065 0.000 0.0 0.065

Bus32 Bus29 0.38 0.042 0.000 0.0 0.042

Bus33 Bus29 0.38 0.042 0.000 0.0 0.042

Bus34 Bus29 0.38 0.042 0.000 0.0 0.042

Bus35 Bus29 0.38 0.042 0.000 0.0 0.042

Bus12 Bus29 65.98 6.655 -2.666 0.4 7.169

PVA1 Bus30 100.00 0.065 0.000 0.0 0.065

PVA3 Bus32 100.00 0.042 0.000 0.0 0.042

PVA4 Bus33 100.00 0.042 0.000 0.0 0.042

PVA5 Bus34 100.00 0.042 0.000 0.0 0.042

PVA2 Bus35 100.00 0.042 0.000 0.0 0.042

Bus46 Bus12 66.49 0.077 0.043 0.6 0.088

Bus70 Bus12 66.39 0.061 0.034 0.6 0.070

Bus10 Bus12 66.39 0.061 0.034 0.6 0.070

Bus13 Bus12 67.50 6.456 -2.778 0.4 7.028

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 7.385 7.385 0.003

0.02 7.385 7.385 0.000

0.03 7.385 7.385 0.000

0.04 7.385 7.385 0.000

0.05 7.385 7.385 0.000

0.06 7.385 7.385 0.000

0.07 7.385 7.385 0.000

0.08 7.385 7.385 0.000

0.09 7.385 7.385 0.000

0.10 7.385 7.385 0.000


Project: ETAP Page: 28
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

(Cont.)

3-Phase fault at bus: Bus29

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 10.658 kA Method C
Steady State = 7.385 kA rms

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.15 7.385 7.385 0.000

0.20 7.385 7.385 0.000

0.25 7.385 7.385 0.000

0.30 7.385 7.385 0.000


Project: ETAP Page: 29
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus30

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.479 kA Method C
Steady State = 4.491 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus30 Total 0.00 4.360 -1.078 0.2 4.491

Bus29 Bus30 40.75 4.295 -1.078 0.3 4.428

PVA1 Bus30 100.00 0.065 0.000 0.0 0.065

Bus32 Bus29 40.97 0.025 0.003 0.1 0.025

Bus33 Bus29 40.97 0.025 0.003 0.1 0.025

Bus34 Bus29 40.97 0.025 0.003 0.1 0.025

Bus35 Bus29 40.97 0.025 0.003 0.1 0.025

Bus12 Bus29 80.64 4.195 -1.091 0.3 4.334

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.491 4.491 0.000

0.02 4.491 4.491 0.000

0.03 4.491 4.491 0.000

0.04 4.491 4.491 0.000

0.05 4.491 4.491 0.000

0.06 4.491 4.491 0.000

0.07 4.491 4.491 0.000

0.08 4.491 4.491 0.000

0.09 4.491 4.491 0.000

0.10 4.491 4.491 0.000

0.15 4.491 4.491 0.000

0.20 4.491 4.491 0.000

0.25 4.491 4.491 0.000

0.30 4.491 4.491 0.000


Project: ETAP Page: 30
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus32

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.457 kA Method C
Steady State = 4.476 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus32 Total 0.00 4.345 -1.076 0.2 4.476

Bus29 Bus32 40.82 4.303 -1.076 0.3 4.435

PVA3 Bus32 100.00 0.042 0.000 0.0 0.042

Bus30 Bus29 41.16 0.039 0.005 0.1 0.039

Bus33 Bus29 41.04 0.025 0.003 0.1 0.025

Bus34 Bus29 41.04 0.025 0.003 0.1 0.025

Bus35 Bus29 41.04 0.025 0.003 0.1 0.025

Bus12 Bus29 80.66 4.189 -1.090 0.3 4.329

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.476 4.476 0.000

0.02 4.476 4.476 0.000

0.03 4.476 4.476 0.000

0.04 4.476 4.476 0.000

0.05 4.476 4.476 0.000

0.06 4.476 4.476 0.000

0.07 4.476 4.476 0.000

0.08 4.476 4.476 0.000

0.09 4.476 4.476 0.000

0.10 4.476 4.476 0.000

0.15 4.476 4.476 0.000

0.20 4.476 4.476 0.000

0.25 4.476 4.476 0.000

0.30 4.476 4.476 0.000


Project: ETAP Page: 31
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus33

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.457 kA Method C
Steady State = 4.476 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus33 Total 0.00 4.345 -1.076 0.2 4.476

Bus29 Bus33 40.82 4.303 -1.076 0.3 4.435

PVA4 Bus33 100.00 0.042 0.000 0.0 0.042

Bus30 Bus29 41.16 0.039 0.005 0.1 0.039

Bus32 Bus29 41.04 0.025 0.003 0.1 0.025

Bus34 Bus29 41.04 0.025 0.003 0.1 0.025

Bus35 Bus29 41.04 0.025 0.003 0.1 0.025

Bus12 Bus29 80.66 4.189 -1.090 0.3 4.329

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.476 4.476 0.000

0.02 4.476 4.476 0.000

0.03 4.476 4.476 0.000

0.04 4.476 4.476 0.000

0.05 4.476 4.476 0.000

0.06 4.476 4.476 0.000

0.07 4.476 4.476 0.000

0.08 4.476 4.476 0.000

0.09 4.476 4.476 0.000

0.10 4.476 4.476 0.000

0.15 4.476 4.476 0.000

0.20 4.476 4.476 0.000

0.25 4.476 4.476 0.000

0.30 4.476 4.476 0.000


Project: ETAP Page: 32
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus34

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.457 kA Method C
Steady State = 4.476 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus34 Total 0.00 4.345 -1.076 0.2 4.476

Bus29 Bus34 40.82 4.303 -1.076 0.3 4.435

PVA5 Bus34 100.00 0.042 0.000 0.0 0.042

Bus30 Bus29 41.16 0.039 0.005 0.1 0.039

Bus32 Bus29 41.04 0.025 0.003 0.1 0.025

Bus33 Bus29 41.04 0.025 0.003 0.1 0.025

Bus35 Bus29 41.04 0.025 0.003 0.1 0.025

Bus12 Bus29 80.66 4.189 -1.090 0.3 4.329

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.476 4.476 0.000

0.02 4.476 4.476 0.000

0.03 4.476 4.476 0.000

0.04 4.476 4.476 0.000

0.05 4.476 4.476 0.000

0.06 4.476 4.476 0.000

0.07 4.476 4.476 0.000

0.08 4.476 4.476 0.000

0.09 4.476 4.476 0.000

0.10 4.476 4.476 0.000

0.15 4.476 4.476 0.000

0.20 4.476 4.476 0.000

0.25 4.476 4.476 0.000

0.30 4.476 4.476 0.000


Project: ETAP Page: 33
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus35

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.457 kA Method C
Steady State = 4.476 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus35 Total 0.00 4.345 -1.076 0.2 4.476

Bus29 Bus35 40.82 4.303 -1.076 0.3 4.435

PVA2 Bus35 100.00 0.042 0.000 0.0 0.042

Bus30 Bus29 41.16 0.039 0.005 0.1 0.039

Bus32 Bus29 41.04 0.025 0.003 0.1 0.025

Bus33 Bus29 41.04 0.025 0.003 0.1 0.025

Bus34 Bus29 41.04 0.025 0.003 0.1 0.025

Bus12 Bus29 80.66 4.189 -1.090 0.3 4.329

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.476 4.476 0.000

0.02 4.476 4.476 0.000

0.03 4.476 4.476 0.000

0.04 4.476 4.476 0.000

0.05 4.476 4.476 0.000

0.06 4.476 4.476 0.000

0.07 4.476 4.476 0.000

0.08 4.476 4.476 0.000

0.09 4.476 4.476 0.000

0.10 4.476 4.476 0.000

0.15 4.476 4.476 0.000

0.20 4.476 4.476 0.000

0.25 4.476 4.476 0.000

0.30 4.476 4.476 0.000


Project: ETAP Page: 34
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus42

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.446 kA Method C
Steady State = 4.469 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus42 Total 0.00 4.337 -1.077 0.2 4.469

Bus46 Bus42 40.75 4.295 -1.077 0.3 4.428

PVA12 Bus42 100.00 0.042 0.000 0.0 0.042

Bus12 Bus46 80.64 4.195 -1.089 0.3 4.334

Bus43 Bus46 40.97 0.025 0.003 0.1 0.025

Bus44 Bus46 40.97 0.025 0.003 0.1 0.025

Bus47 Bus46 40.97 0.025 0.003 0.1 0.025

Bus22 Bus46 40.97 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.469 4.469 0.000

0.02 4.469 4.469 0.000

0.03 4.469 4.469 0.000

0.04 4.469 4.469 0.000

0.05 4.469 4.469 0.000

0.06 4.469 4.469 0.000

0.07 4.469 4.469 0.000

0.08 4.469 4.469 0.000

0.09 4.469 4.469 0.000

0.10 4.469 4.469 0.000

0.15 4.469 4.469 0.000

0.20 4.469 4.469 0.000

0.25 4.469 4.469 0.000

0.30 4.469 4.469 0.000


Project: ETAP Page: 35
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus43

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.446 kA Method C
Steady State = 4.469 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus43 Total 0.00 4.337 -1.077 0.2 4.469

Bus46 Bus43 40.75 4.295 -1.077 0.3 4.428

PVA13 Bus43 100.00 0.042 0.000 0.0 0.042

Bus12 Bus46 80.64 4.195 -1.089 0.3 4.334

Bus42 Bus46 40.97 0.025 0.003 0.1 0.025

Bus44 Bus46 40.97 0.025 0.003 0.1 0.025

Bus47 Bus46 40.97 0.025 0.003 0.1 0.025

Bus22 Bus46 40.97 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.469 4.469 0.000

0.02 4.469 4.469 0.000

0.03 4.469 4.469 0.000

0.04 4.469 4.469 0.000

0.05 4.469 4.469 0.000

0.06 4.469 4.469 0.000

0.07 4.469 4.469 0.000

0.08 4.469 4.469 0.000

0.09 4.469 4.469 0.000

0.10 4.469 4.469 0.000

0.15 4.469 4.469 0.000

0.20 4.469 4.469 0.000

0.25 4.469 4.469 0.000

0.30 4.469 4.469 0.000


Project: ETAP Page: 36
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus44

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.446 kA Method C
Steady State = 4.469 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus44 Total 0.00 4.337 -1.077 0.2 4.469

Bus46 Bus44 40.75 4.295 -1.077 0.3 4.428

PVA14 Bus44 100.00 0.042 0.000 0.0 0.042

Bus12 Bus46 80.64 4.195 -1.089 0.3 4.334

Bus42 Bus46 40.97 0.025 0.003 0.1 0.025

Bus43 Bus46 40.97 0.025 0.003 0.1 0.025

Bus47 Bus46 40.97 0.025 0.003 0.1 0.025

Bus22 Bus46 40.97 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.469 4.469 0.000

0.02 4.469 4.469 0.000

0.03 4.469 4.469 0.000

0.04 4.469 4.469 0.000

0.05 4.469 4.469 0.000

0.06 4.469 4.469 0.000

0.07 4.469 4.469 0.000

0.08 4.469 4.469 0.000

0.09 4.469 4.469 0.000

0.10 4.469 4.469 0.000

0.15 4.469 4.469 0.000

0.20 4.469 4.469 0.000

0.25 4.469 4.469 0.000

0.30 4.469 4.469 0.000


Project: ETAP Page: 37
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus46

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 10.627 kA Method C
Steady State = 7.364 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus46 Total 0.00 6.866 -2.663 0.4 7.364

Bus12 Bus46 65.99 6.657 -2.663 0.4 7.170

Bus42 Bus46 0.38 0.042 0.000 0.0 0.042

Bus43 Bus46 0.38 0.042 0.000 0.0 0.042

Bus44 Bus46 0.38 0.042 0.000 0.0 0.042

Bus47 Bus46 0.38 0.042 0.000 0.0 0.042

Bus22 Bus46 0.38 0.042 0.000 0.0 0.042

Bus29 Bus12 66.56 0.085 0.047 0.6 0.097

Bus70 Bus12 66.40 0.061 0.034 0.6 0.070

Bus10 Bus12 66.40 0.061 0.034 0.6 0.070

Bus13 Bus12 67.51 6.450 -2.779 0.4 7.023

PVA12 Bus42 100.00 0.042 0.000 0.0 0.042

PVA13 Bus43 100.00 0.042 0.000 0.0 0.042

PVA14 Bus44 100.00 0.042 0.000 0.0 0.042

PVA11 Bus47 100.00 0.042 0.000 0.0 0.042

PVA27 Bus22 100.00 0.042 0.000 0.0 0.042

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 7.364 7.364 0.004

0.02 7.364 7.364 0.000

0.03 7.364 7.364 0.000

0.04 7.364 7.364 0.000

0.05 7.364 7.364 0.000

0.06 7.364 7.364 0.000

0.07 7.364 7.364 0.000

0.08 7.364 7.364 0.000

0.09 7.364 7.364 0.000

0.10 7.364 7.364 0.000


Project: ETAP Page: 38
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

(Cont.)

3-Phase fault at bus: Bus46

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 10.627 kA Method C
Steady State = 7.364 kA rms

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.15 7.364 7.364 0.000

0.20 7.364 7.364 0.000

0.25 7.364 7.364 0.000

0.30 7.364 7.364 0.000


Project: ETAP Page: 39
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus47

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.446 kA Method C
Steady State = 4.469 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus47 Total 0.00 4.337 -1.077 0.2 4.469

Bus46 Bus47 40.75 4.295 -1.077 0.3 4.428

PVA11 Bus47 100.00 0.042 0.000 0.0 0.042

Bus12 Bus46 80.64 4.195 -1.089 0.3 4.334

Bus42 Bus46 40.97 0.025 0.003 0.1 0.025

Bus43 Bus46 40.97 0.025 0.003 0.1 0.025

Bus44 Bus46 40.97 0.025 0.003 0.1 0.025

Bus22 Bus46 40.97 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.469 4.469 0.000

0.02 4.469 4.469 0.000

0.03 4.469 4.469 0.000

0.04 4.469 4.469 0.000

0.05 4.469 4.469 0.000

0.06 4.469 4.469 0.000

0.07 4.469 4.469 0.000

0.08 4.469 4.469 0.000

0.09 4.469 4.469 0.000

0.10 4.469 4.469 0.000

0.15 4.469 4.469 0.000

0.20 4.469 4.469 0.000

0.25 4.469 4.469 0.000

0.30 4.469 4.469 0.000


Project: ETAP Page: 40
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus66

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.427 kA Method C
Steady State = 4.455 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus66 Total 0.00 4.323 -1.078 0.2 4.455

Bus70 Bus66 40.63 4.281 -1.078 0.3 4.415

PVA32 Bus66 100.00 0.042 0.000 0.0 0.042

Bus12 Bus70 80.61 4.206 -1.087 0.3 4.344

Bus67 Bus70 40.85 0.025 0.003 0.1 0.025

Bus68 Bus70 40.85 0.025 0.003 0.1 0.025

Bus71 Bus70 40.85 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.455 4.455 0.000

0.02 4.455 4.455 0.000

0.03 4.455 4.455 0.000

0.04 4.455 4.455 0.000

0.05 4.455 4.455 0.000

0.06 4.455 4.455 0.000

0.07 4.455 4.455 0.000

0.08 4.455 4.455 0.000

0.09 4.455 4.455 0.000

0.10 4.455 4.455 0.000

0.15 4.455 4.455 0.000

0.20 4.455 4.455 0.000

0.25 4.455 4.455 0.000

0.30 4.455 4.455 0.000


Project: ETAP Page: 41
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus67

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.427 kA Method C
Steady State = 4.455 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus67 Total 0.00 4.323 -1.078 0.2 4.455

Bus70 Bus67 40.63 4.281 -1.078 0.3 4.415

PVA33 Bus67 100.00 0.042 0.000 0.0 0.042

Bus12 Bus70 80.61 4.206 -1.087 0.3 4.344

Bus66 Bus70 40.85 0.025 0.003 0.1 0.025

Bus68 Bus70 40.85 0.025 0.003 0.1 0.025

Bus71 Bus70 40.85 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.455 4.455 0.000

0.02 4.455 4.455 0.000

0.03 4.455 4.455 0.000

0.04 4.455 4.455 0.000

0.05 4.455 4.455 0.000

0.06 4.455 4.455 0.000

0.07 4.455 4.455 0.000

0.08 4.455 4.455 0.000

0.09 4.455 4.455 0.000

0.10 4.455 4.455 0.000

0.15 4.455 4.455 0.000

0.20 4.455 4.455 0.000

0.25 4.455 4.455 0.000

0.30 4.455 4.455 0.000


Project: ETAP Page: 42
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus68

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.427 kA Method C
Steady State = 4.455 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus68 Total 0.00 4.323 -1.078 0.2 4.455

Bus70 Bus68 40.63 4.281 -1.078 0.3 4.415

PVA34 Bus68 100.00 0.042 0.000 0.0 0.042

Bus12 Bus70 80.61 4.206 -1.087 0.3 4.344

Bus66 Bus70 40.85 0.025 0.003 0.1 0.025

Bus67 Bus70 40.85 0.025 0.003 0.1 0.025

Bus71 Bus70 40.85 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.455 4.455 0.000

0.02 4.455 4.455 0.000

0.03 4.455 4.455 0.000

0.04 4.455 4.455 0.000

0.05 4.455 4.455 0.000

0.06 4.455 4.455 0.000

0.07 4.455 4.455 0.000

0.08 4.455 4.455 0.000

0.09 4.455 4.455 0.000

0.10 4.455 4.455 0.000

0.15 4.455 4.455 0.000

0.20 4.455 4.455 0.000

0.25 4.455 4.455 0.000

0.30 4.455 4.455 0.000


Project: ETAP Page: 43
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus70

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 10.573 kA Method C
Steady State = 7.327 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus70 Total 0.00 6.828 -2.656 0.4 7.327

Bus12 Bus70 66.00 6.661 -2.656 0.4 7.171

Bus66 Bus70 0.38 0.042 0.000 0.0 0.042

Bus67 Bus70 0.38 0.042 0.000 0.0 0.042

Bus68 Bus70 0.38 0.042 0.000 0.0 0.042

Bus71 Bus70 0.38 0.042 0.000 0.0 0.042

Bus29 Bus12 66.57 0.085 0.047 0.6 0.097

Bus46 Bus12 66.51 0.076 0.043 0.6 0.088

Bus10 Bus12 66.41 0.061 0.034 0.6 0.070

Bus13 Bus12 67.52 6.439 -2.781 0.4 7.013

PVA32 Bus66 100.00 0.042 0.000 0.0 0.042

PVA33 Bus67 100.00 0.042 0.000 0.0 0.042

PVA34 Bus68 100.00 0.042 0.000 0.0 0.042

PVA31 Bus71 100.00 0.042 0.000 0.0 0.042

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 7.327 7.327 0.004

0.02 7.327 7.327 0.000

0.03 7.327 7.327 0.000

0.04 7.327 7.327 0.000

0.05 7.327 7.327 0.000

0.06 7.327 7.327 0.000

0.07 7.327 7.327 0.000

0.08 7.327 7.327 0.000

0.09 7.327 7.327 0.000

0.10 7.327 7.327 0.000

0.15 7.327 7.327 0.000

0.20 7.327 7.327 0.000


Project: ETAP Page: 44
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

(Cont.)

3-Phase fault at bus: Bus70

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 10.573 kA Method C
Steady State = 7.327 kA rms

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.25 7.327 7.327 0.000

0.30 7.327 7.327 0.000


Project: ETAP Page: 45
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: Bus71

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 6.427 kA Method C
Steady State = 4.455 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

Bus71 Total 0.00 4.323 -1.078 0.2 4.455

Bus70 Bus71 40.63 4.281 -1.078 0.3 4.415

PVA31 Bus71 100.00 0.042 0.000 0.0 0.042

Bus12 Bus70 80.61 4.206 -1.087 0.3 4.344

Bus66 Bus70 40.85 0.025 0.003 0.1 0.025

Bus67 Bus70 40.85 0.025 0.003 0.1 0.025

Bus68 Bus70 40.85 0.025 0.003 0.1 0.025

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 4.455 4.455 0.000

0.02 4.455 4.455 0.000

0.03 4.455 4.455 0.000

0.04 4.455 4.455 0.000

0.05 4.455 4.455 0.000

0.06 4.455 4.455 0.000

0.07 4.455 4.455 0.000

0.08 4.455 4.455 0.000

0.09 4.455 4.455 0.000

0.10 4.455 4.455 0.000

0.15 4.455 4.455 0.000

0.20 4.455 4.455 0.000

0.25 4.455 4.455 0.000

0.30 4.455 4.455 0.000


Project: ETAP Page: 46
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: EMİRGAZİ DM

Nominal kV = 31.500
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 1.285 kA Method C
Steady State = 0.854 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

EMİRGAZİ DM Total 0.00 0.616 -0.592 1.0 0.854

Bus21 EMİRGAZİ DM 91.75 0.605 -0.592 1.0 0.846

EMİRGAZİ KÖK EMİRGAZİ DM 0.03 0.010 0.000 0.0 0.010

Bus23 Bus21 98.68 0.605 -0.592 1.0 0.846

Bus3 EMİRGAZİ KÖK 0.10 0.010 0.000 0.0 0.010

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 0.854 0.855 0.047

0.02 0.854 0.854 0.002

0.03 0.854 0.854 0.000

0.04 0.854 0.854 0.000

0.05 0.854 0.854 0.000

0.06 0.854 0.854 0.000

0.07 0.854 0.854 0.000

0.08 0.854 0.854 0.000

0.09 0.854 0.854 0.000

0.10 0.854 0.854 0.000

0.15 0.854 0.854 0.000

0.20 0.854 0.854 0.000

0.25 0.854 0.854 0.000

0.30 0.854 0.854 0.000


Project: ETAP Page: 47
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: EMİRGAZİ KÖK

Nominal kV = 31.500
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 1.253 kA Method C
Steady State = 0.833 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

EMİRGAZİ KÖK Total 0.00 0.602 -0.576 1.0 0.833

EMİRGAZİ DM EMİRGAZİ KÖK 2.51 0.591 -0.575 1.0 0.825

Bus3 EMİRGAZİ KÖK 0.07 0.010 0.000 0.0 0.010

Bus21 EMİRGAZİ DM 91.97 0.591 -0.575 1.0 0.825

MEDAŞ DAĞITIM MERKEZİ Bus3 0.07 0.010 0.000 0.0 0.010

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 0.833 0.834 0.045

0.02 0.833 0.833 0.002

0.03 0.833 0.833 0.000

0.04 0.833 0.833 0.000

0.05 0.833 0.833 0.000

0.06 0.833 0.833 0.000

0.07 0.833 0.833 0.000

0.08 0.833 0.833 0.000

0.09 0.833 0.833 0.000

0.10 0.833 0.833 0.000

0.15 0.833 0.833 0.000

0.20 0.833 0.833 0.000

0.25 0.833 0.833 0.000

0.30 0.833 0.833 0.000


Project: ETAP Page: 48
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase fault at bus: MEDAŞ DAĞITIM MERKEZİ

Nominal kV = 31.500
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 1.184 kA Method C
Steady State = 0.789 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

MEDAŞ DAĞITIM MERKEZİ Total 0.00 0.573 -0.542 0.9 0.789

Aykan 2 GES Ölçü MEDAŞ DAĞITIM MERKEZİ 0.02 0.010 0.000 0.0 0.010

Bus17 MEDAŞ DAĞITIM MERKEZİ 0.00 0.001 0.000 0.0 0.001

Bus3 MEDAŞ DAĞITIM MERKEZİ 0.09 0.562 -0.542 1.0 0.781

Bus27 Aykan 2 GES Ölçü 0.02 0.010 0.000 0.0 0.010

Bus19 Bus17 0.17 0.001 0.000 0.0 0.001

EMİRGAZİ KÖK Bus3 5.41 0.562 -0.542 1.0 0.781

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 0.789 0.790 0.041

0.02 0.789 0.789 0.002

0.03 0.789 0.789 0.000

0.04 0.789 0.789 0.000

0.05 0.789 0.789 0.000

0.06 0.789 0.789 0.000

0.07 0.789 0.789 0.000

0.08 0.789 0.789 0.000

0.09 0.789 0.789 0.000

0.10 0.789 0.789 0.000

0.15 0.789 0.789 0.000

0.20 0.789 0.789 0.000

0.25 0.789 0.789 0.000

0.30 0.789 0.789 0.000


Project: ETAP Page: 49
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

Short-Circuit Summary Report

3-Phase Fault Currents

Device Capacity (kA)


Bus Device Short-Circuit Current (kA)
Making
ID kV ID Type Peak Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik

Aykan 2 GES Ölçü 31.500 Aykan 2 GES Ölçü Bus 0.781 1.171 0.781

31.500 CB9 CB 63.000 20.000 21.083 6.672 0.781 1.171 0.781 0.781 0.000

31.500 CB25 CB 63.000 20.000 21.083 6.672 0.781 1.171 0.781 0.781 0.000

Bus3 31.500 Bus3 Bus 0.789 1.185 0.789

Bus7 0.400 Bus7 Bus 4.455 6.427 4.455

Bus8 0.400 Bus8 Bus 4.455 6.427 4.455

Bus9 0.400 Bus9 Bus 4.455 6.427 4.455

Bus10 0.400 Bus10 Bus 7.327 10.573 7.327

0.400 CB 14 CB 17.000 7.500 9.703 7.327 10.573 7.327 7.388 0.949

0.400 CB 4 CB 17.000 7.500 9.703 7.327 10.573 7.327 7.388 0.949

0.400 CB20 CB 17.000 7.500 9.703 7.327 10.573 7.327 7.388 0.949

0.400 CB 10 CB 17.000 7.500 9.703 7.327 10.573 7.327 7.388 0.949

Bus11 0.400 Bus11 Bus 4.455 6.427 4.455

Bus12 0.400 Bus12 Bus 16.847 26.463 16.847

0.400 CB1 CB 105.000 50.000 59.053 16.847 26.463 16.847 16.964 1.991

0.400 CB2 CB 105.000 50.000 59.053 16.847 26.463 16.847 16.964 1.991

0.400 CB8 CB 105.000 50.000 59.053 16.847 26.463 16.847 16.964 1.991

0.400 CB30 CB 17.000 7.500 9.703 16.847 26.463 * 16.847 * 20.294 * 11.315

0.400 CB19 CB 17.000 7.500 9.703 16.847 26.463 * 16.847 * 20.294 * 11.315

Bus13 0.400 Bus13 Bus 17.758 27.897 17.758

Bus17 31.500 Bus17 Bus 0.788 1.184 0.788

Bus18 0.400 Bus18 Bus 16.481 26.080 16.481

0.400 CB32 CB 105.000 50.000 59.053 16.481 26.080 16.481 16.616 2.113

0.400 CB31 CB 105.000 50.000 59.053 16.481 26.080 16.481 16.616 2.113

Bus19 0.400 Bus19 Bus 17.402 27.530 17.402

Bus21 31.500 Bus21 Bus 7.096 19.124 7.096

31.500 CB13 CB 63.000 25.000 26.354 8.340 7.096 19.124 7.096 8.719 5.066

31.500 CB14 CB 80.000 31.500 33.206 10.508 7.096 19.124 7.096 8.719 5.066

Bus22 0.400 Bus22 Bus 4.469 6.446 4.469

Bus23 154.000 Bus23 Bus 10.000 24.692 10.000

154.000 CB16 CB 160.000 63.000 83.396 54.643 10.000 24.692 10.000 12.256 7.085

Bus27 31.500 Bus27 Bus 0.781 1.171 0.781

Bus29 0.400 Bus29 Bus 7.385 10.658 7.385

0.400 CB3 CB 17.000 7.500 9.703 7.385 10.658 7.385 7.445 0.946

0.400 CB5 CB 17.000 7.500 9.703 7.385 10.658 7.385 7.445 0.946
Project: ETAP Page: 50
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

3-Phase Fault Currents

Device Capacity (kA)


Bus Device Short-Circuit Current (kA)
Making
ID kV ID Type Peak Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik

Bus29 0.400 CB4 CB 17.000 7.500 9.703 7.385 10.658 7.385 7.445 0.946

0.400 CB6 CB 17.000 7.500 9.703 7.385 10.658 7.385 7.445 0.946

0.400 CB7 CB 17.000 7.500 9.703 7.385 10.658 7.385 7.445 0.946

Bus30 0.400 Bus30 Bus 4.491 6.479 4.491

Bus32 0.400 Bus32 Bus 4.476 6.457 4.476

Bus33 0.400 Bus33 Bus 4.476 6.457 4.476

Bus34 0.400 Bus34 Bus 4.476 6.457 4.476

Bus35 0.400 Bus35 Bus 4.476 6.457 4.476

Bus42 0.400 Bus42 Bus 4.469 6.446 4.469

Bus43 0.400 Bus43 Bus 4.469 6.446 4.469

Bus44 0.400 Bus44 Bus 4.469 6.446 4.469

Bus46 0.400 Bus46 Bus 7.364 10.627 7.364

0.400 CB 9 CB 17.000 7.500 9.703 7.364 10.627 7.364 7.425 0.947

0.400 CB 11 CB 17.000 7.500 9.703 7.364 10.627 7.364 7.425 0.947

0.400 CB10 CB 17.000 7.500 9.703 7.364 10.627 7.364 7.425 0.947

0.400 CB 12 CB 17.000 7.500 9.703 7.364 10.627 7.364 7.425 0.947

0.400 CB36 CB 17.000 7.500 9.703 7.364 10.627 7.364 7.425 0.947

Bus47 0.400 Bus47 Bus 4.469 6.446 4.469

Bus66 0.400 Bus66 Bus 4.455 6.427 4.455

Bus67 0.400 Bus67 Bus 4.455 6.427 4.455

Bus68 0.400 Bus68 Bus 4.455 6.427 4.455

Bus70 0.400 Bus70 Bus 7.327 10.573 7.327

0.400 CB 20 CB 17.000 7.500 9.703 7.327 10.573 7.327 7.388 0.949

0.400 CB 17 CB 17.000 7.500 9.703 7.327 10.573 7.327 7.388 0.949

0.400 CB29 CB 17.000 7.500 9.703 7.327 10.573 7.327 7.388 0.949

0.400 CB 18 CB 17.000 7.500 9.703 7.327 10.573 7.327 7.388 0.949

Bus71 0.400 Bus71 Bus 4.455 6.427 4.455

EMİRGAZİ DM 31.500 EMİRGAZİ DM Bus 0.854 1.285 0.854

31.500 CB11 CB 63.000 25.000 26.354 8.340 0.854 1.285 0.854 0.854 0.000

31.500 CB12 CB 63.000 25.000 26.354 8.340 0.854 1.285 0.854 0.854 0.000

EMİRGAZİ KÖK 31.500 EMİRGAZİ KÖK Bus 0.833 1.253 0.833

31.500 CB18 CB 63.000 25.000 26.354 8.340 0.833 1.253 0.833 0.833 0.000

31.500 CB21 CB 63.000 25.000 26.354 8.340 0.833 1.253 0.833 0.833 0.000

MEDAŞ DAĞITIM 31.500 MEDAŞ DAĞITIM Bus 0.789 1.184 0.789


MERKEZİ MERKEZİ
31.500 CB24 CB 63.000 20.000 21.083 6.672 0.789 1.184 0.789 0.789 0.000

31.500 CB26 CB 63.000 20.000 21.083 6.672 0.789 1.184 0.789 0.789 0.000

31.500 CB28 CB 63.000 20.000 21.083 6.672 0.789 1.184 0.789 0.789 0.000
Project: ETAP Page: 51
11.0.0
Location: Date: 01-04-2014
Contract: SN: 08a423fb
Engineer: Revision: Base
Study Case: SC
Filename: Aykan 2 GES Config.: Normal

ip is calculated using method C


Ib does not include decay of non-terminal faulted indunction motors
Ik is the maximum steady state fault current
Idc is based on X/R from Method C and Ib as specified above

LV CB duty determined based on service rating.


Total through current is used for device duty.
* Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit . ( 95 % times device capability)

Short-Circuit Summary Report

3-Phase
Short-Circuit
Device Capacity
Current
Bus ID Device ID Ithr (kA) Tkr (sec.) Ith (kA)

Bus12 CB1 9.600 1.00 16.885 *

Bus12 CB2 9.600 1.00 16.885 *

Bus12 CB8 9.600 1.00 16.885 *

Bus18 CB32 9.600 1.00 16.520 *

Bus18 CB31 9.600 1.00 16.520 *

Ithr = Rated short-circuit withstand current


Tkr = Rated short-time
Ith = Thermal equivalent short-time current
* Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit . ( 95 % times device capability)