# BLOQUEO 87L

#PLT12S := (PB8_PUL) AND NOT PLT12 # BLOQUEO 87T


#PLT12R := (PB8_PUL) AND PLT12 # DESBLOQUEAR 87T
# ALARMAS
PCT01IN := (87R OR 87U) AND NOT PLT12 # OPERO 87T
PCT01PU := 0.000000
PCT01DO := 60.000000
PCT02IN := 24D1T OR 24D2T # OPERO V/HZ
PCT02PU := 0.000000
PCT02DO := 60.000000
PCT03IN := 591P1T OR 591P2 # OPERO 3V0
PCT03PU := 0.000000
PCT03DO := 60.000000
PCT04IN := PCT17Q OR PCT18Q # OPERO PROTECCIONES MECANICAS SPRESION Y BZ
PCT04PU := 0.000000
PCT04DO := 60.000000
PCT05IN := PCT19Q OR PCT20Q # OPERO PROTECCIONES TEMPERATURA 49T Y 26Q
PCT05PU := 0.000000
PCT05DO := 60.000000
#PLT01S := IN321 AND NOT PLT01 # EDO CUCHILLA 1 CERRADO
#PLT01R := IN322 AND PLT01 # EDO CUCHILLA 1 ABIERTO
#PLT02S := IN323 AND NOT PLT02 # EDO CUCHILLA 2 CERRADO
#PLT02R := IN324 AND PLT02 # EDO CUCHILLA 2 ABIERTO
#PLT03S := # EDO CUCHILLA 9 CERRADO
#PLT03R := # EDO CUCHILLA 9 ABIERTO
PSV01 := NOT IN317 AND NOT IN319 AND NOT IN320 # PERMISIVO CIERRE INT
PSV02 := PCT17Q OR PCT18Q # OPERO PROTECCIONES MECANICAS SPRESION Y BZ
PSV03 := PCT19Q OR PCT20Q # OPERO PROTECCIONES TEMPERATURA 49T Y 26Q
PSV04 := PCT07Q # EDO INDETERMINADO INT 85 KV
PCT06IN := NOT IN102 AND NOT IN201 # MONITOR 86TG
PCT06PU := 20.000000
PCT06DO := 60.000000
PCT07IN := IN205 AND IN104 OR NOT IN205 AND NOT IN104 # EDO INDET INT 85 KV
PCT07PU := 9.000000
PCT07DO := 0.000000
##PCT08IN := IN321 AND IN322 OR NOT IN321 AND NOT IN322 # EDO INDET CU 1 85 KV
##PCT08PU := 300.000000
##PCT08DO := 0.000000
##PCT09IN := IN323 AND IN324 OR NOT IN323 AND NOT IN324 # EDO INDET CU 2 85 KV
##PCT09PU := 300.000000
##PCT09DO := 0.000000
#PCT10IN := IN318 AND IN319 OR NOT IN318 AND NOT IN319 # EDO INDET CU 9 85 KV
#PCT10PU := 300.000000
#PCT10DO := 0.000000
PCT11IN := (87R OR 87U) # OP 87
PCT11PU := 0.000000
PCT11DO := 1.000000
PCT12IN := 24D2T # OP V/HERTZ
PCT12PU := 0.000000
PCT12DO := 1.000000
PCT13IN := NOT IN301 AND NOT IN302 # SBD1
PCT13PU := 20.000000
PCT13DO := 1.000000
PCT14IN := NOT IN313 AND NOT IN314 # SBD2
PCT14PU := 20.000000
PCT14DO := 1.000000
PSV10 := PCT11Q #OP 87
PMV01 := FREQ # FREQ 85 KV
PMV02 := (3PUF * CTRU * PTRV) * 0.100000 # POT ACT 85 KV
PMV03 := (3QUF * CTRU * PTRV) * 0.100000 # POT REACT 85 KV
PMV04 := (3SUF * CTRU * PTRV) * 0.100000 # POT APARENTE 85 KV
PMV05 := IAURMS # I FASE A 85 KV
PMV06 := IBURMS # I FASE B 85 KV
PMV07 := ICURMS # I FASE C 85 KV
PMV08 := VAVRMS # V FASE A 85 KV
PMV09 := VBVRMS # V FASE B 85 KV
PMV10 := VCVRMS # V FASE C 85 KV
PCT17IN := IN219 AND NOT IN220 # DISPARO SEGURO VSP
PCT17PU := 4.000000
PCT17DO := 0.000000
PCT18IN := IN221 AND NOT IN208 AND NOT IN222 # DISPARO SEGURO BUCCHHOLZ
PCT18PU := 4.000000
PCT18DO := 0.000000
PCT19IN := IN223 AND IN206 AND NOT IN224 #DISPARO SEGURO ALTA TEMP DEVANADOS T1
PCT19PU := 4.000000
PCT19DO := 0.000000
PCT20IN := IN224 AND IN207 # DISPARO SEGURO ALTA TEMP ACEITE T1
PCT20PU := 4.000000
PCT20DO := 0.000000
PSV18 := 592P1T OR 592P2 # DISPARO ALTO VOLTAJE BUS 13.8 KV
PSV19 := 593P1T OR 593P2 # DISPARO ALTO VOLTAJE BUS85 KV
PSV20 := 594P1T #ALARMA ALTO VOLTAJE BUS 13.8 KV
PSV21 := 595P1T # ALARMA ALTO VOLTAJE BUS 85 KV
PSV22 := 273P1T # ALARMA BAJO VOLTAJE BUS 13.8 KV
PSV23 := 274P1T # ALARMA BAJO VOLTAJE BUS85 KV
PSV24 := 271P1T # DETECCION DE BUS MUERTO 13.8 KV
PSV25 := 272P1T # DETECCION DE BUS MUERTO 85 KV
PSV26 := 81D1T #ALARMA BAJA FRECUENCIA 85 KV
PSV27 := 81D2T #ALARMA ALTA FRECUENCIA 85 KV
PSV28 := PSV24 AND PSV25 # AND CLU # TRANSF MUERTO, HABILITA ARR NEGRO
PCT21IN := IN219 AND IN220 OR NOT IN219 AND NOT IN220 # FALLA ALAMBRADO VSP
PCT21PU := 6.000000
PCT21DO := 0.000000
PCT22IN := IN221 AND IN222 OR NOT IN221 AND NOT IN222 # FALLA ALAMBRADO BUCCHHOLZ
PCT22PU := 6.000000
PCT22DO := 0.000000
PCT23IN := IN223 AND NOT IN206 # FALLA ALAMBRADO ALTA TEMP DEVANADOS T1
PCT23PU := 6.000000
PCT23DO := 0.000000
PCT24IN := IN224 AND NOT IN207 # FALLA ALAMBRADO ALTA TEMP ACEITE T1
PCT24PU := 6.000000
PCT24DO := 0.000000
#####SENALES DE CUCHILLAS B1 Y B2 QUEDAN COMO DISPONIBLES#####
##PLT04S := IN322 AND PLT01 # EDO CUCHILLA 1 ABIERTO
##PLT04R := IN321 AND NOT PLT01 # EDO CUCHILLA 1 CERRADO
##PLT05S := IN324 AND PLT02 # EDO CUCHILLA 2 ABIERTO
##PLT05R := IN323 AND NOT PLT02 # EDO CUCHILLA 2 CERRADO
PLT06S := IN205 AND NOT PLT06 # EDO CERRADO INT 85KV
PLT06R := IN104 AND PLT06 # EDO ABIERTO INT 85KV
PLT08S := (PCT13Q OR PCT14Q) AND NOT PLT08 #FALLA BD
PLT08R := NOT PCT13Q AND NOT PCT14Q AND PLT08
PSV29 := NOT IN203 AND NOT IN317 AND NOT IN319 AND NOT IN320 # CONDS CIERRE 71010
PSV30 := PLT01 OR PLT02 # GOOSE EDO CUCHILLAS PERMISIVO CIERRE 52BT-TA
PCT25IN := (TRW OR IN213 OR TRXFMR) AND 50WP2 AND IN106 AND NOT IN107 # 50FI 52BT01
PCT25PU := 18.000000
PCT25DO := 0.000000
PCT26IN := NOT IN105 AND NOT IN315 # MONITOR 86FI 52BT01
PCT26PU := 20.000000
PCT26DO := 60.000000
PCT27IN := IN106 AND IN107 OR NOT IN106 AND NOT IN107 # EDO INDET INT 52BT01
PCT27PU := 9.000000
PCT27DO := 0.000000
PSV17 := PCT17Q # GOOSERD
PSV31 := PCT18Q # GOOSERD
PCT28IN := NOT IN105 AND NOT IN315 # FALLA BOBINA 86BT01
PCT28PU := 20.000000
PCT28DO := 60.000000
PCT30IN := (TRW OR IN213 OR TRXFMR) AND 50WP2 AND IN106 AND NOT IN107 # REDISPARO
52BT01
PCT30PU := 3.000000
PCT30DO := 0.000000
PSV32 := NOT IN205 #CONDICION MODO ISLA
PSV33 := NOT IN208 #ALARMA BHZ