GPMC Field Property Visit Findings Learnings and Operational Requirements
GPMC Field Property Visit Findings Learnings and Operational Requirements
Propert
Location Particulars
Booster Pumps
Roof Manifold
Hose Bib With Isolation Valve
Lightning Arrester Access
Emergency Light
Heat Detector
Fire Extinguisher
Meter Center Gutters
Floor Finish
Location
Liquid Carrying Pipes
Emergency Light
Convenience Outlet
Smoke Detector
Hose Bib With Isolation Valve
Floor Drain
Sprinkler
Fire Extinguisher
Fire Pump and Jockey Pump
Fire Pump and Jockey Pump Sensing Line
Pump Room
Fire Protection Pressure Gauge and Isolation Valve
Transfer Pumps
Water System Pressure Gauge and Isolation Valve
Cistern Tank Cover
Cistern Tank Accessories
Cistern Tank Vent
Cistern Tank Equalization Valve
Floor Finish
Ventilation
Smoke Detector
Emergency Light
Convenience Outlet
MDF Room
Fire Extinguisher
Floor Finish
Ventilation
Floor Finish
Liquid Carrying Pipes
Emergency Light
Convenience Outlet
Heat Detector
Generator Room Nearby Hose Bib
Floor Drain
Fire Extinguisher
Radiator Cover
Exhaust Muffler
Ventilation
Parking Emergency Light
Heat Detector
Sprinkler
Fire Hose Cabinet
Fireman's Cabinet
Steel Bollard Barriers
Ramp Trench Drain
Parking Signages and Directional Arrows
Tower 1 Tower 2
Not Provided
Not Provided
Provided
Not Provided
Not Provided
Located at Reception Counter
Provided
Provided
Provided
Provided
Provided
Provided
Provided
Not Provided
Provided
Provided (PWD)
Provided
Mitsubishi / Machine Roomless
1050 kg
Not Provided
Provided
Provided (all sides)
Provided
Not Provided
Provided
Sidewall (located at wall facing elevators)
Not Provided
Provided (Photoluminiscent)
Provided
Provided
Provided
Provided
Provided
Not Provided
Awning
Provided
Alternate / Fluorescent
Provided
Provided
Provided
Provided
Provided
ABC
Sliding
Without Glass and Lockset
Not Provided
Without Pressure Gauge
Without Pressure Gauge and Sight Glass
Not Provided
Provided
Provided (135 °F)
Provided
Provided
Not Provided
Tiles
Provided
Without Undercut Ventilation
Provided (135 °F)
Not Provided
Provided
ABC
Smooth Finish
With Louver
Provided
Provided
Provided
With Nosing
Tiles
Smooth Finish
Without Hand Rails on Walls
With Restriction
Tiles
With Nosing
Storm Louvered Window
Not Provided
Provided
Not Provided
Provided
Not Provided
Provided
Not Provided
Not Provided
Glass Windows
Smooth Finish
Provided
Not Provided
Provided
Provided
Not Provided
ABC
Provided (2 Units)
Not Provided
Duplex
Provided
Not Provided
Not Provided
Not Provided
Not Provided
Not Provided
With Grounding
Smooth Finish
Outdoor
N/A since located Outdoors
Not Provided
Not Provided
Provided
Not Provided
Not Provided
Not Provided
Provided
Provided
Black Iron Pipe
Provided
Duplex
Provided
Stainless Steel
Stainless Steel
Provided
Provided
Smooth Finish
Louvered Door
Provided
Not Provided
Provided
Not Provided
Smooth Finish
Glass Windows
Smooth Finish
Not Present
Not Provided
Provided
Provided
Provided
Provided
Provided
Storm Louver
Connected to Sewer System
Wiremesh Door
Provided
Not Provided
Provided
Provided
Provided
Provided
Provided
Provided
POST CONSTRUCTION FINDINGS : LEARNINGS
Item no. Location Particulars/Specific Findings Description Reference Photos Recommendation Project Remarks
CODE REQUIREMENT
Shell - Raise it to
engineering
PECSection 6.95.1.6( b)
Fire pump supply conductors on
the load side of the final
disconnecting means and
overcurrent device(s) permitted
by 6.95.1.4(b) shall be kept
entirely independent of all other
Non fire rated cables used for wiring. They shall supply only
loads that are directly associated
fire pump controllers
Non-compliant of code with the fire pump system, and If the material doesn’t comply, it Raised it to the
17 Pump Room Shell
requirements they shall be protected to resist should be replaced as required. Engineering
Not reflected on approved potential damage by fire,
design. structural failure, or operational
accident
PEC 6.20.3.4
A separate branch circuit shall
supply the hoistway pit lighting
and receptacles. Required
Non provision of lighting and In case of trouble lighting shall not be connected
Shell
convenience outlet at elevator inside the pit there will to the load side of a ground- As per Codal requirement Elevator
Grace Punchlisted. To be
20 Elevator Pit pit. be a light and power fault circuit interrupter Pit shall have socket outlet for
Green provided.
outlet for maintenance OSHAS 12.23.6(f.) maintenance purposes.
Based on approved design. purposes A permanent lighting fixture
shall be provided in all pits,
which shall provide an
illumination of not less than 54
lux at the pit floor
NSCP,2010,6th Edition
Section 105.2
National Building Code of the
Philippines Section 102 To be provided (1
Memorandum dated July 15, unit for whole
2013 complex).
Grace
Requirement of DPWH for Basis for
Non provision of accelerograph Green
Building Permit accelerograph:
No accelerograph Shell
22 Complex N/A Provide accelerograph. 1. Building height
Not reflected on approved provided. Shine
Every building in Seismic Zone is greater than 50
design. Trees
4 over 50meters in height shall mts.
be provided with not less than 3 2. Property radius
approved recording is greater than 50
accelerograph. mts.
Seismic Zone 4 covers entire
Philippines except Palawan and
Tawi Tawi
PEC 4.30.7.11
Table 4.30.7.11 provides the
basis for selecting enclosures
for use in specific locations
other than hazardous
Use of NEMA 1 controllers and
(classified) locations. The
ECBs on outdoor areas instead Aircon Controllers and
enclosures are not intended to Contractor will give
of NEMA 3R ECB uses NEMA 1 but
protect against conditions such Use NEMA 3R Enclosure for all Shell certification that
24 Outdoor Area it should be NEMA 3R
as condensation, icing, exposed ECB's Trees the installed ECB
Reflected on material specs that as per code
corrosion, or contamination that is NEMA3R
outdoor enclosure should be requirement.
may occur within the enclosure
use.
or enter via the conduit or
unsealed openings. These
internal conditions shall require
special consideration by the
installer and user
As per consultant,
this is requested
by SMDC to
Take into consideration during
Difficulty of access Difficulty of access change the
design stage of the next project. All
33 15th floor Pump Room going to Pump Rooms Operational Requirement Shell location of pumps
utility room should be accesible for
Base on approved plans at 15th floor including access to
maintenance personnel
Pump Room due
to operational
noise issues.
Inconvenience to the
Exhaust of ACCU facing parking ACCU exhaust air throw must be
unit owner everytime
slot considered during design stage of
35 Parking Space/Area they use their parking Operational Requirement Grace Done
the next project. Provide air deflector
slot due to heat
Base on approved layout plan. for ACCU
provided by ACCU.
AFTER
BEFORE
Grace- For
approval of PD
These pipes are prone
Non provision of protection for asya agreed to put
to physical Provide protection from physical
PVC pipes beside parking slot. Grace plunger
36 Parking Space/Area damage(might get Operational Requirement damage. Project team may use
Green Green- Consultant
bumped by cars when plunger for pipe protection
Base on approved layout plan. advice that there
parking).
must be a plunger
as per plan.
Electricity
No dedicated MERALCO
consumption is hooked On going
electric meters for commercial Isolate commercial electric meter to
44 LVSG Room in the electric meter of Operational Requirement Shell coordination with
tenants. common area
residential common the project team
area.
On going
Unsafe installation of fire hose
45 Parking Area Bump hazard. Safety Requirement Relocate to strategic location Shine coordination with
cabinet
the project team
Manholes should be
provided on strategic
locations to address On going
No provision of service manhole
46 Land Dev leak incidents and for Operational Requirement Provide service manhole. Trees coordination with
on fire protection piping flanges.
maintenace purposes the project team
also during operation.
Item no. Location
CODE REQUIREMENT
1 Storage Room
OPERATIONAL REQUIREMENT
4 Cistern Tank
5 Lightning Arrester
6 Genset Room
14 Air-con Drain
15 Main Power Meters
17 Mailboxes
19 Multi-Level Parking
20 Parking
MENT
REQUIREMENT
Fire exit pressurization fan not be able to maintain or There is no industrial catwalk to
repair because the opening of the door is on the access the maintenance door of
other side. Access of the door is very risky. the pressurization fan.
Mailbox is too high that needs a step ladder to Mailbox height should not exceed
access the mailboxes on the top row. 6 feet.
Multi-level parking should have a
floor indicator/signage to identify
Multi-level parking that does not have floor indicator
and direct all drivers to their
for better navigation in parking area.
desired
destination.
Operational Requirement
Pressurization
Fan Diffuser
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Operational Requirement
Value Engineering
Value Engineering
D AND LEARNINGS
Photos Recommendation
Berkeley
Chateau
Field
Grass
Light
Learnings
Mezza 1
Sea
Sun
Wind
Trees
Berkeley Residences
Chateau Elysee Punchlisted
Mezza 1
Sea Residences Punchlisted
Sea
Field Punchlisted
Trees
Berkeley
Chateau
Field
Grass
Light
Punchlisted
Mezza 1
Sea
Sun
Wind
Trees
Berkeley
Chateau
Field
Grass
Light
Punchlisted
Mezza 1
Sea
Sun
Wind
Trees
Grass Residences
Sun Residences Learnings
Berkeley Residences
Learnings
Chateau Residences
Field Residences
MPST Learnings
Grass
Learnings
Mezza 1
Jazz
MPST Learnings
Wind Resdiences Tower 5
Mezza 1
Learnings
Sea
Sea Learnings
Field Punchlisted
Trees
Field Punchlisted
Sea
Mezza 1 Punchlisted
Sea Punchlisted
Mezza 1
Punchlisted
Sea
Mezza 1
Berkeley Punchlisted
Field
Grass
Mezza 1
Grass
Mezza 1
Grass
Mezza 1
Mezza 2
Shell Residences
Shell Residences