Professional Documents
Culture Documents
MV Switchgear
MV Switchgear
CONTENTS
THEORY AND APPLICATIONS
DESIGN FEATURES
CONSTRUCTIONAL FEATURES
INSTALLATION REQUIREMENTS
TESTS
EXHIBITS
MV SWITCHGEAR
a) In India the utilization system voltage is at 415 Volts, 3phase. Hence switchgear (SG) for this
system is designated as MV switchgear.
b) Switchgear (SG) is a generic term which is used in this document to include:
i) Load centre / Power Control Centre (PCC) - Receive bulk power from transformer and
distribute the same to motor control centers, distribution boards etc.
ii) Motor Control Centre (MCC) - receive power from load centre / PCC and supply to
various motors in a plant section through motor starter modules.
iii) Power and Motor Control Centre (PMCC) – This is a combination of (i) and (ii).
iv) Distribution board – Receive power from load centre / PCC / MCC and supply to smaller
loads such as lighting panels, heating, etc.,
Page 1 of 21
MV SWITCHGEAR
b) SCPD unit in addition to tripping under short circuit condition does the following duties:-
i) Make, break and continuously carry the maximum load current of the circuit.
ii) Withstand starting currents during switching on the load particularly Squirrel cage
induction Motors.
MOTOR STARTER
a) Motor starter for three phase motor comprise:-
i) MCCB or HRC fuses with load break isolating switch.
ii) Contactor(s). Number of contactors to be provided as per mode of starting.
iii) Thermal overload relay (49OL)
iv) CTs, instruments, Protection relays, auxiliary relays, push buttons, indicating lamps etc as
required.
b) Motor starters are arranged as modules in MCC.
c) Separate motor starters comprising contactor and 49OL are also available in dust and vermin
proof enclosure made of sheet steel or cast iron for individual motor application. These are to be
supplied through SCPD unit. Motor starter up to certain size is also available with built in switch
and fuses.
CIRCUIT BREAKERS
MV circuit breakers are generally air break type. Hence, these are called Air Circuit Breaker (ACB)
Page 2 of 21
MV SWITCHGEAR
Category B Specifically intended for selectivity as above and has a short time withstand current rating.
ACB is generally manufactured as category B with short time withstand current assigned.
Page 3 of 21
MV SWITCHGEAR
Page 4 of 21
MV SWITCHGEAR
Page 5 of 21
MV SWITCHGEAR
CONTACTOR :
OPERATIONAL DUTIES OF CONTACTOR
Switch ON and OFF the motor.
Make & break the starting current of the motor.
Withstand thermal stresses due to the starting current flowing for the acceleration time of the motor.
Trip on over load.
Page 6 of 21
MV SWITCHGEAR
DOL STARTING
a) Motor is directly switched on to the power supply by the contactor (starting at full voltage).
b) The starting current is very high and also highly inductive. Starting current is 6-7 times full load
current + 20% tolerance at 0.25 power factor
c) Voltage at the motor terminals will considerably drop during starting due to additional regulations in
the transformer and voltage drop in the cables particularly for long lengths.
Motors are designed to start and accelerate satisfactorily at 85% of rated voltage. Hence voltage drops
must be limited to less than 15%
DOL starting is permissible for power plants and for industrial plants where power supply is obtained
from captive power plant or at EHV from State Electricity Board (SEB).
Where power is obtained at HV or MV from SEB, DOL starting is not permissible beyond certain rating
of motor. Check restrictions put by concerned SEB.
DOL is cheapest and most reliable mode of starting.
Page 7 of 21
MV SWITCHGEAR
STAR-DELTA STARTING
Both the ends of the winding of three phases are brought to motor terminal box i.e. 6 terminals.
Motor windings are connected in star during starting and reconnected in delta during running condition.
Motor is started at √ 3 times voltage. Hence line current is also √ 3 times less than DOL starting.
Voltage drop during starting is correspondingly less.
Starting torque is 1\3 of DOL starting. Hence requirement of driven equipment to be checked.
Three contactors are required :-
One for line connection
One to connect windings in star during starting
One to connect windings in Delta during running.
Only one over load relay provided with line contactor.
Fully automatic starter
Change over from star to delta is automatic (controlled by a timer).
Semi-automatic starter - Change over is controlled by start push button. When start push button is
pressed star connection is made and when released delta connection is made through respective contactor.
REVERSING STARTER
Certain applications such as valves need bidirectional rotation of motor to close and open.
Needs two contactors, one for forward run and other for reverse run.
The two contactors are electrically interlocked to permit operation of one contactor at a time.
Page 8 of 21
MV SWITCHGEAR
DESIGN FEATURES
SWITCHGEAR
a Rated voltage, phases and frequency 415 volts, 3 phases and neutral, 50 HZ
b Max.system voltage 457 volts
c Max.system fault current As per system detail in KA (rms)
d Short circuit withstand current for 1 Same as item (c)
sec (or 3 sec if required)
e One minute power frequency
withstand voltage
Main circuit 2500 volts
Control circuits. 1500 volts
Page 9 of 21
MV SWITCHGEAR
BUS BARS
a Material Electrical grade Aluminium E91E grade
as per IS5082 (copper optional)
b No of Busbars 3 phases and neutral
c Max. permissible 90˚c for non silver plated joints.
Temperature 105˚c for silver plated joints.
d Rated continuous current As per total load current
e Short time current withstand for 1 As per system fault current.
second (or 3 second if required)
f Bus bar insulation i) Air insulated or
ii) Fully insulated
Page 10 of 21
MV SWITCHGEAR
Page 11 of 21
MV SWITCHGEAR
Page 12 of 21
MV SWITCHGEAR
Page 13 of 21
MV SWITCHGEAR
HRC FUSES
a Rated voltage 500 volts
b Rated current As per circuit requirement. Available up
to 1000 Amps
c Rupturing capacity ( Prospective As per system fault level.
current ) Available up to 80 kA
d Applicable standard IS 9224
CONTACTORS
a Type Electro-magnetic, double air break, non
gravity type
b Rated voltage 415 volts
c Rated current To suit motor current, ratings up to 300
Amp available
d No of poles 3
e Rated duty Uninterrupted duty. Other duty category
may be specified if required.
f Utilisation category for squirrel cage
induction motor:
i) DOL/star-Delta/Auto transformer AC3
starter
ii) Reversing starter AC4
iii) Starter for inching operation AC4
g Insulation class of coil Class E or better
h Preferred control (coil) voltage 110 or 240 volts, single phase AC
i Limits of operation of control supply
voltage
i) Voltage variation for closing 85% to 110%
ii) Coil drop out voltage 75%
j Auxiliary contacts to be provided 2 NO and 2 NC
Page 14 of 21
MV SWITCHGEAR
Page 15 of 21
MV SWITCHGEAR
METERING
a Metering schemes
PROTECTION
Protection schemes and relay particulars are discussed in a separate lecture.
CONTROL SCHEMES
Control Schemes shall be according to the various module types mentioned below :-
i) Incoming circuit with ACB/ MCCB/ Switch fuse.
ii) Outgoing feeder with ACB/MCCB/ Switch fuse.
iii) Bus coupler with ACB/ MCCB/Switch fuse.
iv) Motor Control with DOL starting.
v) Motor Control with Star Delta Staring.
vi) Motor Control with Auto-transformer starting.
vii) Motor Control with reversing starter.
Page 16 of 21
MV SWITCHGEAR
Module type are further sub classified on the basis of control locations :-
Controlled from SG / MCC only.
Controlled remote from SG / MCC also.
CONTROL WIRING
a) Wires 660V grade, single core, stranded & tinned copper conductor, PVC
insulated colour coded as per standard
b) Size of the conductor Minimum 1.5sq.mm for general wiring 2.5 sq.mm for CT circuits.
TERMINAL BLOCKS
Type and Rating: 10Amp, 660V grade, one piece Moulded with insulated barriers.
Wire termination: i. Tinned copper
ii. Solder less crimping type
ACCESSORIES
240 V, single phase cubicle heater with thermostat, switch and fuse to prevent moisture condensation in
each vertical module.
CONSTRUCTIONAL FEATURES
SWITCHGEAR ARRANGEMENT
Switchgear should comprise several distinct vertical section comprising:
a) Busbar Compartment
Metal Enclosed main bus bar compartment with busbars running horizontally at the top or bottom.
b) Feeder Modules
i) Individual feeder modules are arranged in multi -tier formation.
ii) All equipment associated with a single circuit are housed in the respective feeder module
compartment.
iii) Sheet steel enclosures on all sides except on the cable alley side.
iv) On the Cable alley side a plate cover with slots is provided for cable connections.
v) Hinged door for each compartment.
vi) Control and selector switches, Push buttons, Relays, Meters etc., are mounted on the front
door of the compartment.
Page 17 of 21
MV SWITCHGEAR
c) Vertical Busbars:
One set of vertical Busbars from the main horizontal Busbars is provided in each vertical section
to serve all the feeder modules in that section.
d) Vertical cable alley:
i) Vertical cable alley covering full height of the SG is provided adjacent to the multitier
feeders to lead power and control cables to the Individual modules.
ii) The cable alley is provided with separate hinged door.
iii) Minimum width of cable alley:
- 500mm for Circuit Breaker modules.
- 200mm for all other modules.
e) Cable Entry facility:
i) Cable entry can be form top or bottom.
ii) Removable gland plates to be provided.
f) One Metal Sheet to be provided between two adjacent vertical sections running to the full length
of SG except for the bus bar chamber.
Page 18 of 21
MV SWITCHGEAR
SWITCHGEAR HEIGHT
Should be limited to 2450MM for the convenience of operation and maintenance
Degree of protection- IP-52
FEEDER MODULE
a) All the feeder modules including motor starter modules not incorporating Circuit Breaker should
have the following mounting arrangement.
b) All the equipment associated with a single circuit is mounted on a withdrawable chassis.
c) The withdrawable chassis have alternative arrangements as follows :-
i) Fully Drawout type.
ii) Semi Drawout type.
iii) Fixed type
Page 19 of 21
MV SWITCHGEAR
SAFETY EARTHING
a) Earth busbar runs along entire length of SG.
b) Material of Earth Bus - Galvanized Steel (GS) (copper optional).
c) Positive connection to be made between all equipment mounted in the SG and the earth bus.
INSTALLATION REQUIREMENTS
Preferred dimension for locating SG.
a SG front space :
i) Front to front distance between two rows of SG 2000 MM
ii) Front of SG to nearest obstruction (wall, column etc.,)
In single row arrangement. 1500 MM
b SG back space from deepest part of SG to nearest 1000 MM
obstruction (min. 800 MM as
per code)
c Sides and Top of SG 800 MM
Page 20 of 21
MV SWITCHGEAR
TESTS
Test for Switchgear
Switchgear shall be subjected to the following tests :-
a) Temperature rise test on power circuits.
b) Short time current withstand test on power circuits.
c) Mechanical operation test.
d) Insulation resistance of power & control circuits.
e) Electrical control, Interlock & sequential operation tests.
Page 21 of 21