OWNER’S RESPONSIBILITY
• PERIODIC TRAINING IN HEALTH & SAFETY TO ALL SUPERVISORS AND WORKMEN.
• PERIODIC AUDIT AND ENFORCEMENT OF ALL PROCEDURES AND SYSTEMS.
Page 1 of 8
ELECTRICAL SAFETY SYSTEM
Page 2 of 8
ELECTRICAL SAFETY SYSTEM
THE TERM INTERIOR LIGHTING COVERS THOSE PARTS OF STRUCTURES WHICH MAY
NOT HAVE CLADDING DURING ERECTION, BUT WHICH WILL BECOME INTERIORS WHEN
THE WORK IS FINISHED.
Page 3 of 8
ELECTRICAL SAFETY SYSTEM
IDENTIFICATION COLOURS
Page 4 of 8
ELECTRICAL SAFETY SYSTEM
TRANSFORMERS
WHERE HV SWITCHGEAR AND TRANSFORMER ARE IN TWO DIFFERENT BUILDINGS FAR
AWAY, A LOAD BREAK SWITCH WITHIN 15m DISTANCE OF TRANSFORMER IS
RECOMMENDED
MOTORS
ALL MOTORS SHALL HAVE LOAD BREAK POWER ISOLATOR CLOSE TO MOTOR WITHIN
VISIBLE DISTANCE
SWITCHYARD EQUIPMENT
CIRCUIT BREAKER SHALL HAVE ISOLATOR ON EITHER SIDE FOR CIRCUIT BREAKER &
CT MAINTENANCE. PT's SHALL HAVE ISOLATORS OR DROPOUT FUSE FOR THEIR
MAINTENANCE.
OVERHEAD LINES
ALL OVERHEAD LINES SHALL HAVE ISOLATOR ON BOTH ENDS FOR THEIR
MAINTENANCE.
Page 5 of 8
ELECTRICAL SAFETY SYSTEM
MEGGER TEST
CONTINUITY TEST
DUCTOR TEST ( FOR JOINTS )
FUNCTIONAL TEST
EMERGENCY SWITCHING
HV / LV CIRCUIT BREAKERS
SHALL HAVE MECHANICAL AS WELL AS ELECTRICAL TRIP PBs IN PANEL
HV / LV ISOLATORS
INCOMER ISOLATOR FEEDER SHALL HAVE ELECTRICAL TRIP PB FOR TRIPPING SENDING
END CIRCUIT BREAKER OR MCCB
MOTORS
• LOCAL ISOLATORS SHALL BE OF LOAD BREAK TYPE.
• TRIP PUSH BUTTON SHALL ALSO BE PROVIDED.
• THE ABOVE WILL CATER FOR EITHER SWITCH OR CONTACTOR CONTACT WELDING.
TRANSFORMER
A TRIP PUSH BUTTON OUTSIDE THE TRANSFORMER ROOM SHALL BE PROVIDED FOR
EMERGENCY TRIP OF SENDING END BREAKER.
Page 6 of 8
ELECTRICAL SAFETY SYSTEM
GUARD
TYPE FUNCTION
PREVENTS ACCESS TO DANGEROUS
FIXED GUARDS
PARTS
MOVE IN ADVANCE OF EACH
AUTOMATIC GUARDS OPERATION OR STROKE TO SWEEP OR
PUSH OPERATORS ARM
MUST BE IN CORRECT ADJUSTMENT
INTERLOCKED GUARDS BEFORE DANGEROUS OPERATION CAN
COMMENCE
STOPS THE MACHINE AUTOMATICALLY
TRIP GUARDS WHEN DANGER ARISES (SIMPLE LIMIT
SWITCHES)
ANOTHER FORM OF FIXED GUARD
POSITIONAL GUARDS WHERE OPERATOR IS KEPT AT SAFE
DISTANCE
GUARDS OPERATING ON
LIGHT BEAM &
PHOTOELECTRIC OR
ELECTRICAL INDUCTION
PROXIMITY EFFECT TO PREVENT
GUARDS
OPERATION OR TRIP THE MACHINE
INTERLOCKS
SEQUENCE
FOR MATERIAL HANDLING SERVICES (LIKE COAL HANDLING PLANT).
• START - LAST CONVEYOR FIRST / FIRST CONVEYOR LAST.
• STOP - FIRST CONVEYOR FIRST / LAST CONVEYOR LAST.
GENERATOR
• NO. OF GENERATORS OPERATE IN PARALLES IN SOLIDLY EARTHED SYSTEM.
• ENSURE EARTHING ISOLATOR CLOSED AND MORE THAN ONE ISOLATOR ARE NOT
CLOSED (RELAY LOGIC OR CASTLE KEY INTERLOCKS).
Page 7 of 8
ELECTRICAL SAFETY SYSTEM
TRANSFORMER
HT BREAKER TRIP TO TRIP LT BREAKER. LT BREAKER CLOSES ONLY ON HT BREAKER
CLOSING.
FEEDER
FOR UNIDIRECTIONAL POWER FLOW - DOWN STREAM BREAKER INTERLOCK WITH
UPSTREAM BREAKER FOR CLOSE AND TRIP.
SWITCHGEAR
• EARTHING TRUCK CAN BE INSERTED IF ASSOCIATED BUS OR CABLE DEAD BREAKER
CAN BE CLOSED IF ASSOCIATED EARTH TRUCK NOT INSERTED.
• ENSURE TWO ASYNCHRONOUS SOURCES ARE NOT PARALLELED.
INCOMER TO CLOSE IF OTHER(S) OPEN OR SHORT TIME PARALLELING THROUGH
SYNCHRO CHECK FACILITY.
• CHANGEOVER OF SUPPLY BREAKER ON U / V; FIRST BREAKER OPENS AND SECOND
BREAKER CLOSES IF SOURCE VOLTAGE PRESENT.
• ON BUS U / V, TRIP MOTOR FEEDERS.
MOTOR
• START / TRIP INTERLOCK WITH GUARD LOCAL ISOLATOR.
• PROVIDE SPEED SWITCH IF START TIME MORE THAN LOCKED ROTOR WITHSTAND
• TIME (NORMAL FOR HIGH INERTIA MOTORS).
BKR - ISOLATOR
• BREAKER TO CLOSE ONLY IF ISOLATOR IS CLOSED.
• ISOLATOR TO CLOSE OR OPEN ONLY IF BREAKER IS OPEN.
GENERAL
PROVIDE HAND RESET TYPE LOCKOUT RELAY. BREAKER TO CLOSE ONLY IF LOCK OUT
RELAY IS RESET.