Bus ducts
Bus ducts
Bus ducts
BUS DUCTS
THEORY
APPLICATION
CLASSIFICATION
CONSTRUCTIONAL FEATURES
TESTS
SAMPLE DESIGN CALCULATIONS
THEORY
A) NON SEGREGATED / SEGREGATED PHASE BUSDUCTS
RATED CURRENT CARRYING CAPACITY:
A FUNCTION OF
MATERIAL COMPOSITION (CONDUCTIVITY) OF BUSBAR (D50SWP / CISM)
(P=2.88 / 3.13)
SHAPE
- SKIN EFFECT (RATIO OF AC TO DC RESISTANCE)
- COOLING SURFACE
AMBIENT TEMPERATURE
FINAL PERMISSIBLE TEMPERATURE (GENERALLY 85° TO 95° C
NO. OF BUSBARS IN PARALLEL- PROXIMITY EFFECT (GROUP DERATING)
COOLING EFFECT (ENCLOSURE)
- NATURAL COOLED
- FORCED COOLED
MOUNTING OF BUSBAR - VERTICAL / HORIZONTAL
FINISH COLOUR – EMISSIVITY (BLACK UPRATES CURRENT RATING BY 20%)
TABLE OF CURRENT RATINGS TO BE FOLLOWED AS GIVEN BY BUSBAR
MANUFACTURER. DERATING TO BE APPLIED TO OBTAIN SITE RATINGS .
INTERLEAVED BUSBAR DESIGN IS DONE TO IMPROVE CURRENT RATINGS.
Page 1 of 23
BUSDUCT
CONDUCTOR RESISTANCE
Rdcc= ρL / Ac
Racc = Rdcc * SKIN EFFECT FACTOR
CONDUCTOR CURRENT = Ic
A CURRENT IS INDUCED IN THE ENCLOSURE EQUAL AND OPPOSITE TO CONDUCTOR
CURRENT
Page 2 of 23
BUSDUCT
ENCLOSURE CURRENT = Ie
Page 3 of 23
BUSDUCT
FIBRE STRESS
NATURAL FREQUENCY OF OSCILLATION
IPBD PHILOSOPHY
TRANSFERS BUS CONDUCTOR FORCES TO ENCLOSURE
INCREASES BUS SUPPORT DISTANCE TO MINIMISE CREEPAGE PATH
ELIMINATES PHASE TO PHASE FAULT
CONDUCTOR CURRENT (Ic) WHICH INDUCES A CURRENT Ie IN ENCLOSURE WHICH
OPPOSES Ic
THE RESIDUAL CURRENT Ir IS VECTOR SUM OF Ic & Ie AND CARRIES FLUX EXTERNAL
TO ENCLOSURE. CURRENT Ir WILL RESULT IN HEATING OF SUPPORT BEAMS DUE TO
HYSTERESIS LOSSES IN STEEL. COPPER BANDS ARE USED ON THE BEAMS TO MINIMISE
THE SAME.
APPLICATION
OPEN BUSBARS
RECTIFIER TRANSFORMER TO ARC FURNACES
NON-SEGREGATED BUSDUCT
APPLICATIONS UPTO 1.1 kV (LV & MV)
TRANSFORMER TO PCC
PCC TO PCC
GENSETS TO PCC
Page 4 of 23
BUSDUCT
SEGREGATED BUSDUCT
APPLICATIONS IN HV 3.3kV / 6.6kV / 11kV
SWITCHGEAR TO SWITCHGEAR
SWITCHGEAR TO TRANSFORMER
GENERATOR TO TRANSFORMER
GENERATOR TO SWITCHGEAR
CABLES
COST OF CABLES, LAYING, GLANDS, LUGS, TERMINATION, STRUCTURAL STEEL, CABLE
TRAYS AND CIVIL WORKS.
BUSDUCTS
COST OF STRAIGHT RUN, BENDS, END ADAPTOR BOXES, FLEXIBLES AND JOINTING,
STRUCTURAL STEEL SUPPORTS
NON-SEGREGATED TYPE
VOLTAGES - 415V AC
CURRENT - 1000-4000A
SC LEVEL - 80kA
Page 5 of 23
BUSDUCT
SEGREGATED TYPE
VOLTAGES - 3.6 kV/7.2 kV/12 kV/17.5 kV/24 kV/36 kV
CURRENTS – 500 TO 4000A
SC LEVEL - 40kA
TYPE OF ENCLOSURE
OPEN BUSBAR
NON-PHASE SEGREGATED
PHASE SEGREGATED
PHASE ISOLATED
- DISCONTINUOUS
- CONTINUOUSLY BONDED
Page 6 of 23
BUSDUCT
TYPE OF APPLICATION
LOW REACTANCE
HIGH REACTANCE
VOLTAGE RATING
LOW VOLTAGE
MEDIUM VOLTAGE
HIGH VOLTAGE
CONSTRUCTIONAL FEATURES
A) MAIN COMPONENTS OF NSPBD / SPBD
BUSBAR
BUS ENCLOSURE
BUS SUPPORT INSULATOR
WALL FRAME ASSEMBLY
ENCLOSURE SUPPORT
ACCESORIES
BUSBARS:
ELECTROLYTIC GRADE ALUMINIUM OR COPPER
RECTANGULAR BARS - SINGLE OR MULTIPLE
ROLLED SECTION – ANGLES / CHANNEL / TEE - SINGLE OR MULTIPLE
BARE OR SLEEVED (NSPBD/SPBD)
BLACK MATT PAINTED
BUSBAR JOINTS:
BOLTED
RIGID
EXPANSION
FLEXIBLE
DISCONNECTING LINKS
Page 7 of 23
BUSDUCT
BUS ENCLOSURE:
ENCLOSURE
MS SHEET FOR SEG & NON-SEG PH BUS DUCTS UPTO 3150A
ALUMINIUM SHEET FOR RATINGS 4000A & ABOVE
PHASE BARRIERS - USED ONLY FOR SPBD
MS SHEET / AL / INSULATING MATERIAL
DIMENSIONS SHALL ALLOW SUFFICIENT PH-PH & PH-EARTH CLEARANCES BETWEEN
BUSBAR AND ENCLOSURE FOR NSPBD AND PH-EARTH FOR SPBD
BLACK MATT PAINTED INSIDE, GREY OUTSIDE
ENCLOSURE JOINTS
FLANGED BOLTED JOINTS BETWEEN TRANSPORT SECTIONS
RUBBER BELLOW JOINTS AT TERMINAL EQPT
RUBBER BELLOW IN THE RUN OF THE BUSDUCT TO TAKE CARE OF EXPANSION AND
ALIGNMENTS
Page 8 of 23
BUSDUCT
COMPONENTS
ALUMINIUM ANGLE FRAME WORK EMBEDDED IN WALL
AN ALUMINIUM SHEET FIXED TO THE FRAME
THROUGH BUSHING WITH CENTRE FIXING ARRANGEMENT WITH EMBEDDED COPPER
BAR
THE BUS ENCLOSURE IS TERMINATED ON THE SHEET ON BOTH SIDES
THE BUS BARS ARE TERMINATED ON BUSHING BAR ON EITHER SIDE
BUSHINGS SHALL HAVE SUFFICIENT MECHANICAL AND ELECTRICAL STRENGTH
ENCLOSURE SUPPORT
FLOOR SUPPORT
CEILING SUPPORT
GALVANISED STRUCTURAL FRAMEWORK
SHALL WITHSTAND WIND LOAD, FORCES DUE TO SHORT CIRCUIT AND SEISMIC
ACCELERATION
ACCESSORIES
INSPECTION COVERS NEAR JOINTS / INSULATORS
DRAIN PLUGS AND VENTS
GASKETS
RAIN COVER
BREATHER
SPACE HEATERS
EARTH BUSBARS
Page 9 of 23
BUSDUCT
B-1) IPBD
MAIN COMPONENTS
BUSBAR
BUS ENCLOSURE
BUS SUPPORT INSULATOR
WALL FRAME ASSEMBLY
ENCLOSURE SUPPORT
ACCESORIES
(ABOVE ARE COMMON FOR SPBD / IPBD)
BUSBARS:
ELECTROLYTIC GRADE ALUMINIUM OR COPPER
RECTANGULAR BARS - SINGLE OR MULTIPLE
ROLLED SECTION
ANGLES / CHANNEL / TEE - SINGLE OR MULTIPLE
FORMED SECTIONS - CIRCULAR / POLYGON
BLACK MATT PAINTED
BUSBAR JOINTS:
WELDED
* RIGID * EXPANSION
BOLTED
* RIGID * EXPANSION
* FLEXIBLE * DISCONNECTING LINKS
Page 10 of 23
BUSDUCT
BUS ENCLOSURE:
ENCLOSURE
ALUMINIUM SHEET
DIMENSIONS SHALL ALLOW SUFFICIENT PH - EARTH CLEARANCES BETWEEN BUSBAR
AND ENCLOSURE
BLACK MATT PAINTED INSIDE, GREY OUTSIDE
ENCLOSURE JOINTS
BONDING ENCLOSURE
RUBBER BELOW JOINTS AT TERMINAL EQPT
FLEXIBLE EXPANSION JOINTS IN THE RUN OF BUS DUCT
METALLIC BELLOW OR RUBBER BELLOW WITH COPPER FLEXIBLE PARALLEL LINKS
Page 11 of 23
BUSDUCT
PREVENTS MIXING OF AIR WITHIN DUCT AT TWO DIFF TEMP IN INDOOR AND OUTDOOR
COMPONENTS
ALUMINIUM ANGLE FRAME WORK EMBEDDED IN WALL.
AN ALUMINIUM SHEET FIXED TO THE FRAME.
THROUGH BUSHING WITH CENTRE EMBEDDED COPPER BAR FIXING ARRANGEMENT
WITH EMBEDDED COPPER BAR.
THE BUS ENCLOSURE IS TERMINATED ON THE SHEET ON BOTH SIDES.
THE BUS BARS ARE TERMINATED ON BUSHING BAR ON EITHER SIDE.
BUSHINGS SHALL HAVE SUFFICIENT MECHANICAL AND ELECTRICAL STRENGTH.
ENCLOSURE SUPPORT
CHANNEL RING AND BRACKETS
TRANSFER BEAMS
INSULATOR SUPPORT
STRUCTURAL SUPPORT
FLOOR SUPPORT
CEILING SUPPORT
GALVANISED STRUCTURAL FRAMEWORK
SHALL WITHSTAND WIND LOAD, FORCES DUE TO SHORT CIRCUIT AND SEISMIC
ACCELERATION
ACCESSORIES
INSPECTION COVERS NEAR JOINTS/INSULATORS
DRAIN PLUGS AND VENTS
GASKETS
RAIN COVER
BREATHER
EARTH BUSBARS
COOLING SYSTEM
ONCE THROUGH SYSTEM
RECIRCULATING TYPE
Page 12 of 23
BUSDUCT
HEAT EXCHANGERS
AIR TO AIR
AIR TO WATER
INSTRUMENTATION CONTROL PANEL
PRESSURIZATION SYSTEM
COMPRESSORS
DRYER
VALVES & REDUCERS
COPPER TUBINGS
INSTRUMENTATION
CONTROL PANEL
HOT AIR BLOWING SYSTEM (USED DURING STARTUP ONLY TO IMPROVE MEGGAR
VALUE OF INSULATORS)
PORTABLE TROLLEY COMPRISING
COMPRESSORS
HEATERS
VALVES
INSTRUMENTATION & CONTROL PANEL
AIR DUCTS
BLANK FLANGES
LAVT CUBICLE
DRAW-OUT VT MODULE WITH HV & LV FUSES (FOR METERING, PROTECTION & AVR)
SURGE ARRESTORS
CAPACITORS
SET OF BUSBARS
MALE / FEMALE CONTACTS FOR PRIMARY & SECONDARY SIDE
EARTHING SYSTEM FOR VT
MARSHALLING BOX
Page 13 of 23
BUSDUCT
TYPE TESTS:
ONE MINUTE POWER FREQUENCY WITHSTAND VOLTAGE
IMPULSE WITHSTAND
TEMPERATURE RISE
DYNAMIC WITHSTAND
WATER TIGHTNESS
AIR TIGHTNESS
ROUTINE TESTS:
ONE MINUTE POWER FREQ WITHSTAND VOLTAGE
WATER TIGHTNESS
AIR TIGHTNESS
Page 14 of 23
BUSDUCT
CORRECTION FACTORS
MATERIAL COMPOSITION (K1)
D50 SWP SPECIFIC RES 3.166 K1=1.00
CISM SPECIFIC RES 2.860 K1=1.03
Page 15 of 23
BUSDUCT
Page 16 of 23
BUSDUCT
Page 17 of 23
BUSDUCT
Page 18 of 23
BUSDUCT
V CONCLUSION
1 Ambient Temperature (TA) (deg.C) : 40.00
2 Enclosure Temperature (T2) (deg.C) : 52.85
3 Busbar Temperature (T1) (deg.C) : 68.85
Page 19 of 23
BUSDUCT
Page 20 of 23
BUSDUCT
V CONCLUSION
1 Ambient Temperature (TA) (deg.C) : 40.00
2 Enclosure Temperature (T2) (deg.C) : 41.25
3 Busbar Temperature (T1) (deg.C) : 46.25
Page 21 of 23
BUSDUCT
c. Main Busduct
1 Short Circuit Current RMS sym (Amps) : 100000
2 Phase Spacing (Meter) : 1.2
3 Multiplication Factor : 2.94
4 Force along Centerline of Busbar
without Enclosure (Kg/mtr) : 793.8
5 Shielding Factor : 0.05
6 Force on Shielded Busbar (Kg/mtr) : 39.69
7 Cantilever Strength of Insulator (Kg) : 2750
8 Compression Strength of Insulator (Kg) : 10000
9 Factor of Safety : 2.5
10 Average span of Support Insulator
based on Cantilever Strength (Meter) : 55
11 Average span of support Insulator
based on compression Strength (Meter) : 116
12 Adopted span (Meter) : 3.8
Page 22 of 23
BUSDUCT
Page 23 of 23