Professional Documents
Culture Documents
06 Earth Fault Loop Impedence
06 Earth Fault Loop Impedence
AS3000 1.5.5.3
(b) Touch-voltage limits In the event of a fault between a live part and an exposed
conductive part that could give rise to a prospective touch voltage exceeding 50 V a.c.
or 120 V ripple-free d.c., a protective device shall automatically disconnect the
supply to the circuit or electrical equipment concerned.
NOTE: Lower touch-voltage limits are required for special electrical installations or
locations by the relevant clauses of Sections 6 and 7.
(c) Earthing system impedance (earth fault-loop impedance) The characteristics of
protective devices and the earthing system impedance shall be such that, if a fault of
negligible impedance occurs anywhere in the electrical installation between an active
conductor and a protective earthing conductor or exposed conductive part, automatic
disconnection of the supply will occur within the specified time.
NOTES:
1 Clause 5.7 contains further requirements and Appendix B provides guidance
regarding earth fault-loop impedance.
2 Refer to Appendix B, Table B 1, for comparison of circuit route length based on
impedance and various voltage drops.
(d) Disconnection times The maximum disconnection time for 230/400 V supply voltage
shall not exceed the following:
(i) 0.4 s for final subcircuits that supply-
(A) socket-outlets having rated currents not exceeding 63 A
(B) hand-held Class I equipment; or
(C) portable equipment intended for manual movement during use.
(ii) 5 s for other circuits including submains and final subcircuits supplying fixed or
stationary equipment.
NOTE: Maximum disconnection times will vary for other voltages and installation
conditions. Appendix B provides further guidance regarding disconnection times.
Example 1
A three phase 400V three phase circuit, protected by a 30A C-type circuit breaker , using 6mm2
thermoplastic-insulated unsheathed V90 copper cable in PVC conduit. Allowable voltage drop in circuit is
3.5%.
A) What is the Max. Permissible route length satisfying 3.5% VD
B) What is the Max. Permissible route length satisfying Earth fault loop impedence
Lmax = 65.67m
It is clear that permissible length of EFLI is less then permittted length using CVD consideratio. To
satisfay safe operation of system, increase diameter of protective earthing conductor, lets say 4mm2
Example 2
A three phase 400V
A three core 4mm2 V75 thermoplastic insulated sheathed cable supplies three phase 400v 19A notor in a
factory.Protection is by 20A D type circuit breaker. Allowable Vd is 18V.
C) What is the Max. Permissible route length satisfying 18V Vd
D) What is the Max. Permissible route length satisfying Earth fault loop impedence
Lmax = 21.8m
It is assumed that it is existing facility, and much can not be done to meet the safe operation of
circuit breaker. It is clear EFLI length requirements is not satisfied and breaker probably will not
trip within safe limits, one solution is to install RCD
Method 2
Formula
Z(fault) = Zph + Zearth …………………(1)
I(fault) = 80% Voltage(PN)/Z(fault)…(2)
V(touch) = I(fault) X Z(earth)…………(3)
Example
A 250m, 50mm2 V90 multicore cable conductor is connected to a load and is protected by 100A fuse.
Assuming length of earthing conductor is also 250m, Determine permissible earth conductor size for
A. Circuit breaker having disconnection time of 0.4sec
B. Circuit breaker having disconnection time of 5sec
Solution:
FOR 0.4Sec:
For 250m, 50mm2 copper conductor (refer table 35 AS3000)
R(Phase) = 0.494 * 0.25 = 0.1235
X(Phase) = 0.0751 * 0.2 = 0.0188
Z(Phase) = 0.125 Ohm
From table 8.1, AS3000, Allowable impedence for 100A fuse for 0.4sec is 0.27, I.e Z(fault)<0.27
Refer equation 1
Z(fault) = Z(Phase) + Z(Earth)
Z(earth) < Z(fault) - Z(Phase)
< 0.27 - 0.125 = 0.145
Option 1
Now we need to find earth having impedence <=0.145
From table 5.1, minimum earth conductor size of 50mm2 copper cable is 16mm2,
From table 35, AS3000 impedence/meter of 16mm2 V90 cable = 1.47 = 1.47*0.25 = 0.3675
This value is way higher then allowable earth impedence value of 0.145 Ohms
Option 2:
Consider earth conductor size of 50mm2,
From table 35, AS3000 impedence/meter of 50mm2 V90 cable Z(earth) = 0.494 = 0.494*0.25 = 0.1235
Which is less then 0.145 ohms
From graph below it is clear that for 94V touch voltage, Disconnection time is 0.6sec,it is pretty
close to our requirements.
Therefore, we are going top use 0.4sec fuse with earth conductor size of 50mm2 for safe operation
of system