Professional Documents
Culture Documents
Cgat Series
Cgat Series
Operation
Maintenance
Models;
CGAT 065 D, CGAT 135 D
CGAT 085 D, CGAT 175 D
CGAT 105 D, CGAT 215 D
C G A T 0 6 5 D 0 0 0 0 A A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
DIGIT 1,2,3 - MODEL IDENTIFIER
CGA = COLD GENERATOR, AIR-COOLED
Model Nomenclature 2
General Information 4
General Data 5
Installation 6
Electrical 8
Typical Wiring Diagram 9
Trouble Shooting 10
Dimensional Data 12
CGAT-IOM01-EN 3
General Information
Corner Weight-Kgs
Shipping Maximum Net maximum
Model Kgs Lbs Kgs Lbs #1 #2 #3 #4
CGAT065 201 442.2 181 398.2 67.5 38.1 44.0 31.4
CGAT085 224 492.8 204 448.8 76.1 42.9 49.6 35.4
CGAT105 270 594.0 250 550.0 100.4 38.2 91.0 20.4
CGAT135 441 970.2 406 893.2 107.3 97.8 95.8 105.3
CGAT175 487 1071.4 452 994.4 119.5 108.5 106.5 117.5
CGAT215 507 1115.4 472 1038.4 125.0 113.0 111.0 123.0
4 CGAT-IOM01-EN
General Data
CGAT-IOM01-EN 5
Installation
6 CGAT-IOM01-EN
Installation
Unions
Vibration
Eliminators
Thermometers
Shutoff
Valves
Water Strainer
Reeturn Line
(Inlet)
(See Note 1)
Flow Switch
Gate Valves
(See Note 2
Balancing Valve
100.00
10.00
1.00
10.0 100.0
Water flowrate, gpm
CGAT-IOM01-EN 7
Electrical
8 CGAT-IOM01-EN
Control Panel
Compressor on/off
LED Display for water
display status
temperature and errors
Water Freeze
Leaving Water Temp
Sensor#2 display status
status display
Up/Down button
use to select which
sensor temperature or Power on/off button
settings to be shown on
LED display
CGAT-IOM01-EN 11
Pre-Start Procedure
Once the unit is installed, follow the Measure each leg of supply voltage
steps below to ensure the installation (3-phase) at all ling voltage disconnect
procedure is complete. When all are switches. Readings must fall within
accomplished, the unit is ready for the voltage utilization range shown on
operation. the unit nameplate.
WARNING : More than one discon- 4. Fill the chilled water circuit, leaving Voltage Imbalance
nect switch may be required to the system air vents open. Close Excessive voltage imbalance between
de-energize unit for servicing. Refer to vent after filling. phase will cause motors to overheat
unit schematic and open all electrical 5. Start the chilled water pump. With and eventually fail. Maximum allow-
disconnects to prevent injury or death water circulating through the chilled able imbalance is 2%
due to electrical shock. water system, inspect all piping
connections for leaks and make % Voltage Imbalance = 100 x [VA -VD]
1. Inspect all wiring connections; any necessary repairs. VA
electrical connections should be 6. Adjust the water flow rate through where VA is the average voltage and
clean and tight. the chilled water circuit, and check VD is the ling voltage that deviates
the water pressure drop through farthest from VA
WARNING : Use extreme care the evaporator. Refer to water
when electrically troubleshooting pressure drop data on page 8. 11. Establish a balanced water flow
compressors. If electrical power is 7. Ensure flow switch is installed and through the evaporator.
applied to a damaged fusite terminal, wired to the control panel. Adjust 12. Measure the water pressure drop
a fire or explosion could occur, the flow switch to provide proper through the evaporator at the
resulting in injury or death. operation. pressure gauge(s) on the system
water piping. Pressure drop
CAUTION : Check tightness of all NOTE : Withe the water pump readings at the gauges should
connections in the compressor power operating, throttle the water flow to approximate those indicated by
circuit (disconnects, terminal block, approximately 50 percent of the full the pressure drop charts (figure 2)
contactors, compressor junction box flow rate. Following the manufacturer’s on page 8
terminals, etc.) to prevent overheating instruction adjust the flow switch
at connections and under voltage contacts to open at this point. Use NOTE : Be sure to account for piping/
conditions at the motor. an Ohmmeter to verify opening and fittings that will create additional
closure of the switch contacts. pressure drop between the unit and
2. Check power supply voltage to the pressure gauge locations.
the unit at the main power fused 8. Stop the chilled water pump.
disconnect switch; the voltage 9. Open all fused disconnect
reading should be within the switches.
utilization range shown in Table 2
on page 9. Also, Voltage imbalance WARNING : Use extreme care when
must not exceed 2%. (Refer to item checking voltage at live terminals to
10 Unit voltage and amperage avoid serious injury or death due to
checks ) electrical shock.
3. Check the condenser fan
assemblies; the fan blades should 10. Unit Voltage and Amperage
rotate freely in the fan orifice, and Checks Voltage supply
be securely attached to the fan
shaft.
12 CGAT-IOM01-EN
Operation
CGAT-IOM01-EN 13
Operation
14 CGAT-IOM01-EN
Trouble Shouting
CGAT-IOM01-EN 15
Trouble Shouting
16 CGAT-IOM01-EN
Note
CGAT-IOM01-EN 19
Trane Thailand Literature Order Number: CGAT-IOM01-EN0303
7th Floor, Ploenchit Center Building
New
2 Sukhumvit Road, Klongtoey
Bangkok 10110 Stocking Location: Bangkok, Thailand
Amair Limited
35 Mu 8, Poochaosamingprai Road ∫√‘…—∑ ·Õ¡·Õ√å ®”°—¥ 35 À¡Ÿà 8 ∂.ªŸÉ‡®â“ ¡‘ßæ√“¬ µ. ”‚√ß„µâ Õ.æ√–ª√–·¥ß ®. ¡ÿ∑√ª√“°“√ 10130
Samrong Tai, Samutprakarn 10130
http://www.trane.com Since The Trane Company has a policy of continuous product and product data improvement,
An American Standard Company it reserves the right to change design and specifications without notice.