DATA SHEETS FOR ELECTRICAL CABLES

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

NC-200 ERAWIN FIELD EPF PHASE- I (PLAN B)

CONTRACT NO: ENG052-20ERW

SUPPLIER DOCUMENT COVER SHEET

Supplier Name: Turk Prysmian Kablo ve Sistemleri A.S.


Purchase Order Number: JI2047-PPFE005
Purchase Order Title: Supply of MV, LV CABLES AND EARTHING CABLES &
INSTRUMENT CABLES
Equipment/Tag Number: NA
SDRL Code: D09
Supplier’s Document number: PRY-ENG052-20ERW-PPFE005-D09-0001

Document Total Pages : 16

Document Title: DATA SHEETS FOR ELECTRICAL CABLES

Document No: ENG052-20ERW-PPFE005-D09-0001

SUPPLIER DOCUMENT REVIEW

Purchaser’s review of this document does not relieve Seller of the responsibility for correctness under the purchase order
or contract. Permission to proceed does not constitute acceptance of design, detail and calculations, test methods or
materials developed or selected by the Seller and does not relieve the Seller from full compliance with the purchase order,
contract or any other obligations, nor detract from any of the Purchaser’s rights.

Reviewer Signature Date

CODE A Final: No Comment, document accepted. Do not re‐submit, except modified.


Revise and Re-issue. Work may not Proceed
CODE B
Revise and Re‐issue: Returned with comment, incorporate comments and re‐issue for review.
• Revise document to address comments and issue as final. Work may Proceed
No re-submittal for review required if SUPPLIER agrees with and makes indicated document
CODE C
changes. CONTRACTOR to resolve with Project Team if disagreement on making changes to address
comments
• Review not Required. Work may Proceed
CODE D
Incorporate comments and proceed. Do not re-issue for review, issue for Final Submission.
• Rejected. Work may not Proceed
CODE R
Incorporate comments and re-issue for review. Work may NOT proceed.

Issue Record

02 Issued for Review 17.06.2022 B.UNVER E.AKARSU G.KECECI

01 Issued for Review 25.05.2022 B.UNVER E.AKARSU G.KECECI

Rev Purpose Date Prepared Checked Approved


NC-200 ERAWIN FIELD EPF PHASE-
I (PLAN B)
CONTRACT NO: ENG052-20ERW

Revision No. Date Author Scope / Remarks


01 25.05.2022 B.UNVER Issued for Review
02 17.06.2022 B.UNVER Issued for Review

Holds List

S. No Reference Clause Remarks


NC-200 ERAWIN FIELD EPF PHASE- I (PLAN B

VENDOR COMMENTS RESPONSE SHEET

Document No. ENG052-20ERW-PPFE005-D09-0001 Rev No. ZLOG Transmittal No. Date

PFML Transmittal 02 17/06/22

SL Page PETROFAC STATUS


VENDOR RESPONSE REMARKS
No. No. COMMENTS By ( O\C)
1. 1
Mohammed Drum weight and size information have
. 4 drum weight and size shall be given
Metfah been provided.

2. Mohammed Drum weight and size information have


6 drum weight and size shall be given
Metfah been provided.
3. Mohammed
6 fault curent of armour for 1 sec is required Provided information.
Metfah
general comment for all LV cables :
4. Mohammed
7 details shall be given in data sheet even for cables Details have been given.
Metfah
which have not been ordered
5. earthing cables data sheets are missing . Prysmian Mohammed
3 Earthing cables are already provided.
can use their data sheet format for earthing cables Metfah
PFML Representative Vendor Representative
Name Name Beyza Ünver

Signature Signature

Date Date 17/ JUN / 22

Legend (Status O\C) : O - Open / C – Closed Page 1 of 1


NC200 Erawin Field Development Rev : 02
Doc. No.: ENG052-20ERW-000-EL-DAS-0010-000 Page : 3 of 16

DATA SHEET - HV CABLES

Tag No. : Not Applicable Inq/PO No:ENG052-20ERW-000-EL-REQ-0005-000 Date : 27/01/2022


GENERAL INFORMATION
Name of Manufacturer PRYSMIAN Country of Manufacture TURKEY
SERVICE CONDITIONS
Onshore, Outdoor, Under ground/Above
Maximum ambient temperature 50 ºC Installation
ground
Minimum ambient temperature -2 ºC
BASIC DESIGN DATA
3.6/6 (7.2) kV for 6.6 kV system Three core : Red, Yellow, Blue color
Voltage grade Core identification
strips

Cu/XLPE/CTS/PVC/AWA/PVC (For Single Core Non-hygroscopic extruded filler over the


Cable type Fillers
Cable) assembly

Flame Retardant-Category A (IEC60332-3-22, IEC


Outer sheath Binding tape NA
60332-1-2)
Ref. Standard IEC 60502-2 Lead Sheath No

Max. operating / SC temp. 90 ºC 250 ºC Inner sheath material Extruded PVC, Class : ST2

Conductor Copper Armour material Single Layer of SWA for three core cable

Conductor shape Circular Annealed Stranded Outer sheath material Extruded PVC, Class : ST2
Flexibility class (IEC 60228) Class 2 Outer sheath Colour Red

Material-conductor screen Extruded semi-conducting compound (bonded) Embossing on outer sheath Every 1 meter (meter is inkjet)

Material of insulation XLPE (Cross Linked Polyethylene) Embossing details PRYSMIAN 2XSEYRY 3x185/25 3,6/6 kV
Extruded semi-conducting compound (Cold CU/XLPE/CTS/PVC/SWA/PVC IEC 60502-2
Material-insulation screen Year Meter
Strippable)
Metallic Screen Copper Tape Special requirement UV resistant outer sheath (as per ISO 4892-
Copper screen fault rating 4,90 kA for 1 sec (6.6kV System) 2)

Minimum Design Life 30 Years


INSPECTION AND TESTS
Required Witness Required Witness
Routine tests per IEC and requisition YES YES Type tests per IEC & requisition (As required) NO NO
Sample tests per IEC YES YES
(Sample as per IEC OR as per requisition)
NOTES AND REMARKS
* data to be furnished by Manufacturer ** TBA-To be Advised Later
1) In general, all Cables shall comply to Technical specification- HV & LV Cables, Doc. No. ENG052-20ERW-000-EL-SPC-0010-000 and relevant IEC Standards
2) Furnish data for all cables sizes as per the requisition
3) Current de-rating factors applicable for different laying conditions shall be furnished by the Supplier.
4) Technical catalogue of the offered cables meeting to the specification & data sheet requirement to be furnished by cable Supplier.
CABLE CHARACTERISTICS UNIT CABLE SIZES (REFER NOTE-2 ABOVE)
ITEM 3Cx95 3Cx120 3Cx150 3Cx185 3Cx240
1) CONDUCTOR
Diameter of conductor (Nominal) mm * * * 11,3 12,73 14,05 15,67 18,1
No. of conductor wires (minimum) No. * * * 19x2,62 24x2,62 30x2,62 37x2,62 48x2,62
2) CONDUCTOR SCREEN
Conductor Screen Thickness (Approx) mm * * * 0,5 0,5 0,5 0,5 0,5
3) INSULATION
Insulation thickness (nominal) mm * * * 2,5 2,5 2,5 2,5 2,6
Insulation thickness (minimum) mm * * * 2,15 2,15 2,15 2,15 2,24
Diameter over laid assembly (multi-core) mm * * * 17,0 18,4 19,8 21,3 24
4) INSULATION SCREEN
Insulation Screen Thickness (Approx) mm * * * 0,5 0,5 0,5 0,5 0,5
5) METALLIC SCREEN
Copper screen area (nominal) mm2 * * * 16 16 25 25 25
Diameter over screen (Core Diameter) mm * * * 19 20,5 21,8 23,4 25,8
Dia. over laid assembly (multi-core) mm * * * 41 44 46,9 50,4 55,6
NC200 Erawin Field Development Rev : 02
Doc. No.: ENG044-20ERW-000-EL-DAS-0010-000 Page : 4 of 16

TITLE: DATA SHEET - HV CABLES

6) BEDDING (INNER SHEATH)


Inner sheath thickness (nominal) mm * * * 1,4 1,5 1,6 1,6 1,7
Inner sheath thickness (minimum) mm * * * 0,92 1 1,08 1,08 1,16
Diameter over Bedding mm * * * 45,5 49,2 52 55,5 61
7) ARMOUR
Armour wire dia. mm * * * 2,5 2,5 2,5 2,5 3,15
No. of armour wires (approx.) No. * * * 47 51 53 57 49
Diameter over armour mm * * * 50,5 51,2 57 60,5 67,3
8) OUTER SHEATH
Outer sheath thickness (nominal) mm * * * 2,8 2,9 3 3,1 3,3
Outer sheath thickness (minimum) mm * * * 2,04 2,12 2,2 2,28 2,44
OVERALL DIAMETER mm * * * 56 60 63 66 73,5
Tolerance on O.D. of cable mm ± ± ± +3,-2 +3,-2 +3,-2 +3,-2 +3,-2
9) PACKING
Maximum cable Drum length metres * * * 1000 1000 1000 1000 500
Positive Tolerance on drum cable length % 2% 2% 2% 2% 2% 2% 2% 2%
Cable Weight kG/km * * * 6900 8090 9235 10635 13595
Drum Weight kG * * * 1100 1400 1650 1650 1100
284 x 170 x 304 x 170 324 x 180 x 324 x 180 x 284 x 170 x
Size of Drum (H x W) mm * * *
284 x 304 324 324 284
Minimum Pulling tension kG * * * 14250 18000 22500 27750 36000
Min. Bending Radius (No. x Diameter) No. * * * 840 900 945 990 1102,5
10) ELECTRICAL PARAMETERS
Max. DC resistance at 20ºC ohm/km * * * 0,193 0,153 0,124 0,0991 0,0754
Max. DC resistance at 90ºC ohm/km * * * 0,246 0,195 0,158 0,126 0,096
Approx. AC resistance at 90ºC ohm/km * * * 0,246 0,195 0,158 0,126 0,096
Approx. Reactance at 50Hz ohm/km * * * 0,084
Approx. impedance at 50Hz ohm/km * * * 0,246 0,195 0,158 0,151 0,096
Approx. capacitance µF/km * * * 0,620
Cable charging current at nom. V & Hz A/km * * * 0,000 0,000 0,000 0,117 0,000
DC resistance of armour at 20ºC ohm/km * * * 0,832 0,766 0,737 0,686 0,686
AC resistance of armour at 80ºC ohm/km * * * 1,027 0,946 0,911 0,847 0,847
11) CURRENT RATING (Metallic layer bonded at both Ends)
Buried 0.8m at ground temperature Amps * * * 188 213 238 268 309
of 30ºC, g=3.3ºCm/W, single cable
In Duct at 0.8m, ground temperature Amps * * * 179 204 228 259 299
of 30ºC, g=3.3ºCm/W, single cable
Cable laid in Air, at ambient temperature Amps * * * 252 289 326 371 434
of 50ºC, Single cable
Short circuit rating for 1 sec. Amps * * * 13,59 17,16 21,45 26,46 34,32
Fault current rating of armour-1 sec. Amps * * * 11,3 12,3 12,7 13,7 18,7
Fault current rating of screen-1 sec. Amps * * * 3,1 3,1 4,9 4,9 4,9
NC200 Erawin Field Development Rev : 02
Doc. No.: ENG052-20ERW-000-EL-DAS-0010-000 Page : 5 of 16

DATA SHEET - LV CABLES

Tag No. : Not Applicable Inq/PO No:ENG052-20ERW-000-EL-REQ-0005-000 Date : 27/01/2022


GENERAL INFORMATION
Name of Manufacturer PRYSMIAN Country of Manufacture TURKEY
SERVICE CONDITIONS
Onshore, Outdoor/Indoor, Under
Maximum ambient temperature 50 ºC Installation
ground/Above ground
Minimum ambient temperature -2 ºC
BASIC DESIGN DATA
Voltage grade 0.6/1.0 (1.2) kV Fillers NA

Flame Retardant: Non-hygroscopic poly


Cable type Binding tape
Cu/XLPE/PVC/AWA/PVC (Single Core Cable) propylene/polyester tape

Flame Retardant-Category A (IEC60332-3-


Outer sheath
22)

Ref. Standard IEC 60502-1 Lead Sheath No

Max. operating / SC temp. 90 ºC 250 ºC Inner sheath material Extruded PVC, Class : ST2

Conductor Copper Armour material Single Layer of AWA for single-core

Conductor shape Circular Annealed Stranded Outer sheath material Extruded PVC, Class : ST2
Flexibility class (IEC 60228) Class 2 Outer sheath Colour Black
XLPE (Cross Linked Polyethylene)

Material of insulation Embossing on outer sheath Every 1 meter (meter is inkjet)

PRYSMIAN 2XR(A)Y 1x300 0,6/1 kV


Black
Core Identification Embossing details CU/XLPE/PVC/AWA/PVC IEC 60502-1
Year Meter

Minimum Design Life 30 Years Screening requirement No


UV resistant outer sheath (as per ISO
VFD Cable (Special Requirement) No Special requirement
4892-2)
INSPECTION AND TESTS
Required Witness Required Witness
Routine tests per IEC and requisition YES YES Type tests per IEC & requisition (As required) NO NO
Sample tests per IEC YES YES
(Sample as per IEC OR as per requisition)
NOTES AND REMARKS
* data to be furnished by Manufacturer
1) In general, all Cables shall comply to Technical specification- HV & LV Cables, Doc. No. ENG052-20ERW-000-EL-SPC-0010-000 and relevant IEC Standards
2) Furnish data for all cables sizes as per the requisition
3) Current de-rating factors applicable for different laying conditions shall be furnished by the Supplier.
4) Technical catalogue of the offered cables meeting to the specification & data sheet requirement to be furnished by cable Supplier.
CABLE CHARACTERISTICS UNIT CABLE SIZES (REFER NOTE-2 ABOVE)
ITEM 1Cx300 1Cx630
1) CONDUCTOR
Diameter of Main conductor (Nominal) mm 20,3 29,4 * * * * * *
No. of conductor wires Main (minimum) No. 59x2,62 61x3,82 * * * * * *
Diameter of Earth conductor (Nominal) mm * * * * * * * *
No. of conductor wires - Earth(minimum) No. * * * * * * * *
2) INSULATION
Insulation thickness (nominal) mm 1,8 2,4 * * * * * *
Insulation thickness (minimum) mm 1,52 2,06 * * * * * *
Diameter over laid assembly (multi-core) mm * * * * * * * *
3) BINDER TAPE
Approximate thickness (nominal) mm * * * * * * * *
Diameter over Binder Tape mm * * * * * * * *
4) BEDDING (INNER SHEATH)
Inner sheath thickness (nominal) mm 1 1 * * * * * *
Inner sheath thickness (minimum) mm 0,75 0,75 * * * * * *

Diameter over Bedding mm 26,3 36,6 * * * * * *

NC200 Erawin Field Development Rev : 02


Doc. No.: ENG044-20ERW-000-EL-DAS-0010-000 Page : 6 of 16

TITLE: DATA SHEET - LV CABLES

5) ARMOUR
Armour wire dia. mm 1,6 2 * * * * * *
No. of armour wires (approx.) "As per
Table 54.3 of IEC 60364-5-54 if armour is No. 43 47 * * * * * *
used as PE"
Diameter over armour mm 29,6 40,6 * * * * * *
6) OUTER SHEATH
Outer sheath thickness (nominal) mm 1,9 2,3 * * * * * *
Outer sheath thickness (minimum) mm 1,32 1,64 * * * * * *
OVERALL DIAMETER mm 33 45 * * * * * *
Tolerance on O.D. of cable mm +3,-2 +3,-2 ± ± ± ± ± ±
7) PACKING
Maximum cable Drum length metres 1000 1000 * * * * * *
Positive Tolerance on drum cable length % 2% 2% 2% 2% 2% 2% 2% 2%
Cable Weight kG/km 3340 6815 * * * * * *
Drum Weight kG 315 1100 * * * * * *

184 x 113 284 x 170 x


Size of Drum (H x W) mm * * * * * *
x 184 284

Minimum Pulling tension kG 15000 31500 * * * * * *


Min. Bending Radius (No. x Diameter) No. 495 675 * * * * * *
8) ELECTRICAL PARAMETERS
Max. DC resistance at 20ºC ohm/km 0,0601 0,0283
Max. DC resistance at 90ºC ohm/km 0,077 0,036
Approx. AC resistance at 90ºC ohm/km 0,077 0,036
Approx. Reactance at 50Hz ohm/km 0,089 0,085
Approx. impedance at 50Hz ohm/km 0,118 0,092
Approx. capacitance µF/km 0,855 0,936
Cable charging current at nom. V & Hz A/km 0,161 0,176
DC resistance of armour at 20ºC ohm/km 0,387 0,227
AC resistance of armour at 80ºC ohm/km 0,478 0,280
9) CURRENT RATING (Metallic layer bonded at both Ends)
Buried 0.8m at ground temperature Amps 467 536 * * * * * *
of 30ºC, g=2.5ºCm/W, single cable
In Duct at 0.8m, ground temperature Amps 415 * * * * * * *
of 30ºC, g=2.5ºCm/W, single cable
Cable laid in Air, at ambient temperature Amps 604 1192 * * * * * *
of 50ºC, Single cable
Short circuit rating for 1 sec. Amps 42,9 90,09 * * * * *
Fault current rating of armour-1 sec. Amps 4,2 7,2 * * * * * *
NC200 Erawin Field Development Rev : 02
Doc. No.: ENG052-20ERW-000-EL-DAS-0010-000 Page : 7 of 16

DATA SHEET - LV CABLES

Tag No. : Not Applicable Inq/PO No:ENG052-20ERW-000-EL-REQ-0005-000 Date : 27/01/2022


GENERAL INFORMATION
Name of Manufacturer PRYSMIAN Country of Manufacture TURKEY
SERVICE CONDITIONS
Onshore, Outdoor/Indoor, Under
Maximum ambient temperature 50 ºC Installation
ground/Above ground
Minimum ambient temperature -2 ºC
BASIC DESIGN DATA
Non-hygroscopic extruded filler over
Voltage grade 0.6/1.0 (1.2) kV Fillers
the assembly

Non-hygroscopic poly
Flame Retardant:
propylene/polyester tape for small
Cable type Cu/XLPE/PVC/SWA/PVC Binding tape
cross sections,
kraft paper for bigger cross sections

Flame Retardant-Category A (IEC60332-3-


Outer sheath
22)

Ref. Standard IEC 60502-1 Lead Sheath No

Max. operating / SC temp. 90 ºC 250 ºC Inner sheath material Extruded PVC, Class : ST2

Conductor Copper Armour material Single Layer of SWA

Conductor shape Circular Annealed Stranded Outer sheath material Extruded PVC, Class : ST2
Flexibility class (IEC 60228) Class 2 Outer sheath Colour Black
XLPE (Cross Linked Polyethylene)

Material of insulation Embossing on outer sheath Every 1 meter (meter is inkjet)

PRYSMIAN 2XRY 3x2,5 0,6/1 kV


2x.. white and black ( Dc voltage )
Core Identification Embossing details CU/XLPE/PVC/SWA/PVC IEC 60502-1
3x.. Red,Yellow,Blue
Year Meter

Minimum Design Life 30 Years Screening requirement No


UV resistant outer sheath (as per ISO
VFD Cable (Special Requirement) No Special requirement
4892-2)
INSPECTION AND TESTS
Required Witness Required Witness
Routine tests per IEC and requisition YES YES Type tests per IEC & requisition (As required) NO NO
Sample tests per IEC YES YES
(Sample as per IEC OR as per requisition)
NOTES AND REMARKS
* data to be furnished by Manufacturer
1) In general, all Cables shall comply to Technical specification- HV & LV Cables, Doc. No. ENG052-20ERW-000-EL-SPC-0010-000 and relevant IEC Standards
2) Furnish data for all cables sizes as per the requisition
3) Current de-rating factors applicable for different laying conditions shall be furnished by the Supplier.
4) Technical catalogue of the offered cables meeting to the specification & data sheet requirement to be furnished by cable Supplier.
CABLE CHARACTERISTICS UNIT CABLE SIZES (REFER NOTE-2 ABOVE)
ITEM 2Cx70 3Cx4 3Cx6 3Cx25 3Cx50 3Cx70 3Cx95
1) CONDUCTOR
Diameter of Main conductor (Nominal) mm 9,62 * 2,49 3,06 5,9 7,98 9,62 11,3
No. of conductor wires Main (minimum) No. 14x2,62 * 7x0,83 7x1,02 7x2,22 10x2,62 14x2,62 19x2,62
Diameter of Earth conductor (Nominal) mm * * * * * * * *
No. of conductor wires - Earth(minimum) No. * * * * * * * *
2) INSULATION
Insulation thickness (nominal) mm 1,1 * 0,7 0,7 0,9 1,0 1,1 1,1
Insulation thickness (minimum) mm 0,89 * 0,53 0,53 0,71 0,8 0,89 0,89
Diameter over laid assembly (multi-core) mm 23,8 * 8,3 9,5 16,7 21,6 25,6 29,2
3) BINDER TAPE
Approximate thickness (nominal) mm * * * * * * * *
Diameter over Binder Tape mm * * * * * * * *
4) BEDDING (INNER SHEATH)
Inner sheath thickness (nominal) mm 1 * 0,6 0,6 1 1 1 1
Inner sheath thickness (minimum) mm 0,75 * 0,41 0,41 0,75 0,75 0,75 0,75

Diameter over Bedding mm 27,3 * 10,2 11,4 20,2 25,1 29,1 32,3

NC200 Erawin Field Development Rev : 02


Doc. No.: ENG044-20ERW-000-EL-DAS-0010-000 Page : 8of 16

TITLE: DATA SHEET - LV CABLES

5) ARMOUR
Armour wire dia. mm 1,6 * 0,8 0,8 1,6 1,6 2 2
No. of armour wires (approx.) "As per
Table 54.3 of IEC 60364-5-54 if armour is No. 44 * 34 38 34 41 38 43
used as PE"
Diameter over armour mm 30,5 * 11,8 13 23,4 28,3 33,1 36,7
6) OUTER SHEATH
Outer sheath thickness (nominal) mm 2 * 1,8 1,8 1,8 1,9 2 2,2
Outer sheath thickness (minimum) mm 1,4 * 1,24 1,24 1,24 1,32 1,4 1,56
OVERALL DIAMETER mm 34 * 15 16 27 32 37 40,8
Tolerance on O.D. of cable mm +3,-2 * +2-1 +2-1 +3,-2 +3,-2 +3,-2 +3,-2
7) PACKING
Maximum cable Drum length metres 1000 * 1000 1000 1000 1000 1000 1000
Positive Tolerance on drum cable length % 2% * 2% 2% 2% 2% 2% 2%
Cable Weight kG/km 2850 * 435 535 1730 2620 3655 4680
Drum Weight kG 426 * 55 55 220 315 473 625

204 x 113 104 x 69 x 104 x 69 x 154 x 112 184 x 113 x 224 x 137 x 244 x 138 x
Size of Drum (H x W) mm *
x 204 104 104 x 154 184 224 244

Minimum Pulling tension kG 7000 * 600 900 3750 7500 10500 14250
Min. Bending Radius (No. x Diameter) No. 408 * 180 192 319 380 444 490
8) ELECTRICAL PARAMETERS
Max. DC resistance at 20ºC ohm/km 0,268 * 4,61 3,08 0,727 0,387 0,268 0,193
Max. DC resistance at 90ºC ohm/km 0,341 * 5,873 3,924 0,926 0,493 0,341 0,246
Approx. AC resistance at 90ºC ohm/km 0,342 * 5,878 3,927 0,927 0,493 0,342 0,246
Approx. Reactance at 50Hz ohm/km 0,074 * 0,093 0,089 0,081 0,078 0,074 0,072
Approx. impedance at 50Hz ohm/km 0,350 * 5,879 3,928 0,931 0,499 0,350 0,256
Approx. capacitance µF/km 0,758 * 0,281 0,330 0,484 0,585 0,633 0,731
Cable charging current at nom. V & Hz A/km 0,143 * 0,053 0,062 0,091 0,110 0,119 0,138
DC resistance of armour at 20ºC ohm/km 2,168 * 11,127 9,956 2,806 2,327 1,607 1,420
AC resistance of armour at 80ºC ohm/km 2,678 * 13,742 12,296 3,466 2,874 1,985 1,754
9) CURRENT RATING (Metallic layer bonded at both Ends)
Buried 0.8m at ground temperature Amps 209 * 36 46 100 142 175 210
of 30ºC, g=2.5ºCm/W, single cable *
In Duct at 0.8m, ground temperature Amps 189 * 33 41 89 126 155 183
of 30ºC, g=2.5ºCm/W, single cable *
Cable laid in Air, at ambient temperature Amps 237 * 34 44 104 157 202 244
of 50ºC, Single cable *
Short circuit rating for 1 sec. Amps 10,01 * 0,572 0,858 3,575 7,15 10,01 13,59
Fault current rating of armour-1 sec. Amps * * 0,8 0,9 3,3 4 5,8 6,6
NC200 Erawin Field Development Rev : 02
Doc. No.: ENG052-20ERW-000-EL-DAS-0010-000 Page : 9 of 16

DATA SHEET - LV CABLES

Tag No. : Not Applicable Inq/PO No:ENG052-20ERW-000-EL-REQ-0005-000 Date : 27/01/2022


GENERAL INFORMATION
Name of Manufacturer PRYSMIAN Country of Manufacture TURKEY
SERVICE CONDITIONS
Onshore, Outdoor/Indoor, Under
Maximum ambient temperature 50 ºC Installation
ground/Above ground
Minimum ambient temperature -2 ºC
BASIC DESIGN DATA
Non-hygroscopic extruded filler over
Voltage grade 0.6/1.0 (1.2) kV Fillers
the assembly

Non-hygroscopic poly
Flame Retardant:
propylene/polyester tape for small
Cable type Cu/XLPE/PVC/SWA/PVC Binding tape
cross sections,
kraft paper for bigger cross sections

Flame Retardant-Category A (IEC60332-3-


Outer sheath
22)

Ref. Standard IEC 60502-1 Lead Sheath No

Max. operating / SC temp. 90 ºC 250 ºC Inner sheath material Extruded PVC, Class : ST2

Conductor Copper Armour material Single Layer of SWA

Conductor shape Circular Annealed Stranded Outer sheath material Extruded PVC, Class : ST2
Flexibility class (IEC 60228) Class 2 Outer sheath Colour Black
XLPE (Cross Linked Polyethylene)

Material of insulation Embossing on outer sheath Every 1 meter (meter is inkjet)

PRYSMIAN 2XRY 3x2,5 0,6/1 kV


Core Identification 3x.. Red,Black,Yellow/Green Embossing details CU/XLPE/PVC/SWA/PVC IEC 60502-1
Year Meter

Minimum Design Life 30 Years Screening requirement No


UV resistant outer sheath (as per ISO
VFD Cable (Special Requirement) No Special requirement
4892-2)
INSPECTION AND TESTS
Required Witness Required Witness
Routine tests per IEC and requisition YES YES Type tests per IEC & requisition (As required) NO NO
Sample tests per IEC YES YES
(Sample as per IEC OR as per requisition)
NOTES AND REMARKS
* data to be furnished by Manufacturer
1) In general, all Cables shall comply to Technical specification- HV & LV Cables, Doc. No. ENG052-20ERW-000-EL-SPC-0010-000 and relevant IEC Standards
2) Furnish data for all cables sizes as per the requisition
3) Current de-rating factors applicable for different laying conditions shall be furnished by the Supplier.
4) Technical catalogue of the offered cables meeting to the specification & data sheet requirement to be furnished by cable Supplier.
CABLE CHARACTERISTICS UNIT CABLE SIZES (REFER NOTE-2 ABOVE)
ITEM 3Cx2,5 3Cx4
1) CONDUCTOR
Diameter of Main conductor (Nominal) mm * 1,98 2,49 * * * * *
No. of conductor wires Main (minimum) No. * 7x0,66 7x0,83 * * * * *
Diameter of Earth conductor (Nominal) mm * * * * * * * *
No. of conductor wires - Earth(minimum) No. * * * * * * * *
2) INSULATION
Insulation thickness (nominal) mm * 0,7 0,7 * * * * *
Insulation thickness (minimum) mm * 0,53 0,53 * * * * *
Diameter over laid assembly (multi-core) mm * 7,2 8,3 * * * * *
3) BINDER TAPE
Approximate thickness (nominal) mm * * * * * * * *
Diameter over Binder Tape mm * * * * * * * *
4) BEDDING (INNER SHEATH)
Inner sheath thickness (nominal) mm * 0,6 0,6 * * * * *
Inner sheath thickness (minimum) mm * 0,41 0,41 * * * * *

Diameter over Bedding mm * 9,1 10,2 * * * * *

NC200 Erawin Field Development Rev : 02


Doc. No.: ENG044-20ERW-000-EL-DAS-0010-000 Page : 10 of 16

TITLE: DATA SHEET - LV CABLES

5) ARMOUR
Armour wire dia. mm * 0,8 0,8 * * * * *
No. of armour wires (approx.) "As per
Table 54.3 of IEC 60364-5-54 if armour is No. * 31 34 * * * * *
used as PE"
Diameter over armour mm * 10,7 11,8 * * * * *
6) OUTER SHEATH
Outer sheath thickness (nominal) mm * 1,8 1,8 * * * * *
Outer sheath thickness (minimum) mm * 1,24 1,24 * * * * *
OVERALL DIAMETER mm * 14 15 * * * * *
Tolerance on O.D. of cable mm * +2-1 +2-1 * ± ± ± ±
7) PACKING
Maximum cable Drum length metres * 1000 1000 * * * * *
Positive Tolerance on drum cable length % * 2% 2% * 2% 2% 2% 2%
Cable Weight kG/km * 360 435 * * * * *
Drum Weight kG * 55 55 * * * * *

104 x 69 x 104 x 69 x
Size of Drum (H x W) mm * * * * * *
104 104

Minimum Pulling tension kG * 375 600 * * * * *


Min. Bending Radius (No. x Diameter) No. * 168 180 * * * * *
8) ELECTRICAL PARAMETERS
Max. DC resistance at 20ºC ohm/km * 7,41 4,61 * * * * *
Max. DC resistance at 90ºC ohm/km * 9,440 5,873 *
Approx. AC resistance at 90ºC ohm/km * 9,448 5,878 *
Approx. Reactance at 50Hz ohm/km * 0,099 0,093 *
Approx. impedance at 50Hz ohm/km * 9,449 5,879 *
Approx. capacitance µF/km * 0,238 0,281 *
Cable charging current at nom. V & Hz A/km * 0,045 0,053 *
DC resistance of armour at 20ºC ohm/km * 12,204 11,127 *
AC resistance of armour at 80ºC ohm/km * 15,072 13,742 *
9) CURRENT RATING (Metallic layer bonded at both Ends)
Buried 0.8m at ground temperature Amps * 28 36 * * * * *
of 30ºC, g=2.5ºCm/W, single cable * *
In Duct at 0.8m, ground temperature Amps * 26 33 * * * * *
of 30ºC, g=2.5ºCm/W, single cable * *
Cable laid in Air, at ambient temperature Amps * 26 34 * * * * *
of 50ºC, Single cable * *
Short circuit rating for 1 sec. Amps * 0,358 0,572 * * * * *
Fault current rating of armour-1 sec. Amps * 0,8 0,8 * * * * *
NC200 Erawin Field Development Rev : 02
Doc. No.: ENG052-20ERW-000-EL-DAS-0010-000 Page : 11 of 16

DATA SHEET - LV CABLES

Tag No. : Not Applicable Inq/PO No:ENG052-20ERW-000-EL-REQ-0005-000 Date : 27/01/2022


GENERAL INFORMATION
Name of Manufacturer PRYSMIAN Country of Manufacture TURKEY
SERVICE CONDITIONS
Onshore, Outdoor/Indoor, Under
Maximum ambient temperature 50 ºC Installation
ground/Above ground
Minimum ambient temperature -2 ºC
BASIC DESIGN DATA

Non-hygroscopic extruded filler over the


Voltage grade 0.6/1.0 (1.2) kV Fillers
assembly

Non-hygroscopic poly
Flame Retardant: propylene/polyester tape for small cross
Cable type Binding tape
Cu/XLPE/PVC/SWA/PVC sections,
kraft paper for bigger cross sections

Outer sheath Flame Retardant-Category A (IEC60332-3-22)

Ref. Standard IEC 60502-1 Lead Sheath No

Max. operating / SC temp. 90 ºC 250 ºC Inner sheath material Extruded PVC, Class : ST2

Conductor Copper Armour material Single Layer of SWA

Conductor shape Circular Annealed Stranded Outer sheath material Extruded PVC, Class : ST2
Flexibility class (IEC 60228) Class 2 Outer sheath Colour Black
XLPE (Cross Linked Polyethylene)

Material of insulation Embossing on outer sheath Every 1 meter (meter is inkjet)

PRYSMIAN 2XRY 4x4 0,6/1 kV


Core Identification 4x.. Red,Yellow,Blue,Black Embossing details CU/XLPE/PVC/SWA/PVC IEC 60502-1
Year Meter

Minimum Design Life 30 Years Screening requirement No


UV resistant outer sheath (as per ISO
VFD Cable (Special Requirement) No Special requirement
4892-2)
INSPECTION AND TESTS
Required Witness Required Witness
Routine tests per IEC and requisition YES YES Type tests per IEC & requisition (As required) NO NO
Sample tests per IEC YES YES
(Sample as per IEC OR as per requisition)
NOTES AND REMARKS
* data to be furnished by Manufacturer
1) In general, all Cables shall comply to Technical specification- HV & LV Cables, Doc. No. ENG052-20ERW-000-EL-SPC-0010-000 and relevant IEC Standards
2) Furnish data for all cables sizes as per the requisition
3) Current de-rating factors applicable for different laying conditions shall be furnished by the Supplier.
4) Technical catalogue of the offered cables meeting to the specification & data sheet requirement to be furnished by cable Supplier.
CABLE CHARACTERISTICS UNIT CABLE SIZES (REFER NOTE-2 ABOVE)
ITEM 4Cx4 4Cx6 4Cx10 4Cx25 4Cx185 4Cx240 2Cx16 4Cx2.5
1) CONDUCTOR
Diameter of Main conductor (Nominal) mm 2,49 3,06 3,7 5,9 15,67 18,1 4,7 1,98
No. of conductor wires Main (minimum) No. 7x0,83 7x1,02 7x1,36 7x2,22 37x2,62 48x2,62 7x1,75 7x0,66
Diameter of Earth conductor (Nominal) mm * * * * * * * *
No. of conductor wires - Earth(minimum) No. * * * * * * * *
2) INSULATION
Insulation thickness (nominal) mm 0,7 0,7 0,7 0,9 1,6 1,7 0,7 0,7
Insulation thickness (minimum) mm 0,53 0,53 0,53 0,71 1,34 1,43 0,53 0,53
Diameter over laid assembly (multi-core) mm 9,2 10,6 12,2 18,7 45,8 52,2 12,1 8,0
3) BINDER TAPE
Approximate thickness (nominal) mm * * * * * * * *
Diameter over Binder Tape mm * * * * * * * *
4) BEDDING (INNER SHEATH)
Inner sheath thickness (nominal) mm 0,6 0,6 0,6 1 1 1 0,6 0,6
Inner sheath thickness (minimum) mm 0,41 0,41 0,41 0,75 0,75 0,75 0,41 0,41

Diameter over Bedding mm 11,2 12,5 14,1 22,3 49,5 55,7 14,1 9,9

NC200 Erawin Field Development Rev : 02


Doc. No.: ENG044-20ERW-000-EL-DAS-0010-000 Page : 12 of 16

TITLE: DATA SHEET - LV CABLES

5) ARMOUR
Armour wire dia. mm 0,8 1,25 1,25 1,6 2,5 2,5 1,25 0,8
No. of armour wires (approx.) "As per Table
54.3 of IEC 60364-5-54 if armour is used as No. 37 27 31 37 51 57 30 33
PE"
Diameter over armour mm 12,8 15 16,8 25,5 54,3 60,7 16,6 11,5
6) OUTER SHEATH
Outer sheath thickness (nominal) mm 1,8 1,8 1,8 1,8 2,8 3 1,8 1,8
Outer sheath thickness (minimum) mm 1,24 1,24 1,24 1,24 2,04 2,2 1,24 1,24
OVERALL DIAMETER mm 16 18,2 20 29 60 66,5 19,7 14,7
Tolerance on O.D. of cable mm +2-1 ± +3,-2 +3,-2 +3,-2 +3,-2 +2-1 +2-1
7) PACKING
Maximum cable Drum length metres 1000 1000 1000 1000 750 500 1000 1000
Positive Tolerance on drum cable length % 2% 2% 2% 2% 2% 2% 2% 2%
Cable Weight kG/km 500 715 930 2070 10620 13415 885 400
Drum Weight kG 55 63 102 220 650 1100 102 55
104 x 69 x 114 x 69 x 154 x 112 x 244 x 138 284 x 170 x 124 x 83 x
Size of Drum (H x W) mm 124 x 83 x 124 104 x 69 x 104
104 114 154 x 244 284 124
Minimum Pulling tension kG 800 1200 2000 5000 37000 48000 1600 500
Min. Bending Radius (No. x Diameter) No. 192 218 240 348 720 798 236 176
8) ELECTRICAL PARAMETERS
Max. DC resistance at 20ºC ohm/km 4,61 3,08 1,83 0,727 0,0991 0,0754 1,15 7,41
Max. DC resistance at 90ºC ohm/km 5,873 3,924 2,331 0,926 0,126 0,096 1,465 9,440
Approx. AC resistance at 90ºC ohm/km 5,878 3,927 2,333 0,927 0,126 0,096 1,466 9,448
Approx. Reactance at 50Hz ohm/km 0,093 0,089 0,084 0,081 0,072 0,071 0,081 0,099
Approx. impedance at 50Hz ohm/km 5,879 3,928 2,335 0,931 0,145 0,119 1,468 9,449
Approx. capacitance µF/km 0,281 0,330 0,405 0,484 0,706 0,757 0,554 0,238
Cable charging current at nom. V & Hz A/km 0,053 0,062 0,076 0,091 0,133 0,143 0,104 0,045
DC resistance of armour at 20ºC ohm/km 10,225 5,739 4,999 2,579 0,766 0,686 5,165 11,465
AC resistance of armour at 80ºC ohm/km 12,628 7,088 6,174 3,185 0,946 0,847 6,379 14,159
9) CURRENT RATING (Metallic layer bonded at both Ends)
Buried 0.8m at ground temperature Amps 36 46 60 100 301 349 93 28
of 30ºC, g=2.5ºCm/W, single cable
In Duct at 0.8m, ground temperature Amps 33 41 54 89 261 301 85 26
of 30ºC, g=2.5ºCm/W, single cable
Cable laid in Air, at ambient temperature Amps 34 44 62 104 374 441 94 26
of 50ºC, Single cable
Short circuit rating for 1 sec. Amps 0,572 0,858 1,43 3,575 26,46 34,32 2,29 0,358
Fault current rating of armour-1 sec. Amps 0,9 1,6 1,9 3,6 12,3 13,7 1,8 0,8
NC200 Erawin Field Development Rev : 02
Doc. No.: ENG052-20ERW-000-EL-DAS-0010-000 Page : 13 of 16

DATA SHEET - LV CABLES

Tag No. : Not Applicable Inq/PO No:ENG052-20ERW-000-EL-REQ-0005-000 Date : 27/01/2022


GENERAL INFORMATION
Name of Manufacturer PRYSMIAN Country of Manufacture TURKEY
SERVICE CONDITIONS
Onshore, Outdoor/Indoor, Under
Maximum ambient temperature 50 ºC Installation
ground/Above ground
Minimum ambient temperature -2 ºC
BASIC DESIGN DATA

Non-hygroscopic extruded filler over


Voltage grade 0.6/1.0 (1.2) kV Fillers (bet. Cores & in centre) the assembly for 2, 3, 4, 5 cores
NA for above 5 cores

Flame Retardant: Non-hygroscopic poly


Cu/XLPE/PVC/SWA/PVC propylene/polyester tape for small
Cable type Binding tape
Fire Resistant: cross sections,
Cu/MGT/XLPE/LSZH/SWA/PVC kraft paper for bigger cross sections

Flame Retardant-Category A (IEC60332-3-22) or Fire


Outer sheath Resistance (IEC 60331-11& IEC 60331-21) (As per
specification)

Ref. Standard IEC 60502-1 Lead Sheath No

Extruded PVC, Class : ST2 for flame


retardant cables
Max. operating / SC temp. 90 ºC 250 ºC Inner sheath material
Extruded LSZH, Class : ST8 for fire
resistant cables

Single Layer of SWA (AWA for single-


Conductor Copper Armour material
core)
Conductor shape Circular Annealed Stranded Outer sheath material Extruded PVC, Class : ST2
Flexibility class (IEC 60228) Class 2 Outer sheath Colour Black
XLPE (Cross Linked Polyethylene) or Mineral
Ceramic (Mica/Glass Fire Resistant) Tape (For Fire
Material of insulation Resistance Cable-As per specification) Embossing on outer sheath Every 1 meter (meter is inkjet)

3x.. Red,Black,Yellow/Green PRYSMIAN 2XRY 5x2,5 0,6/1 kV


Core Identification 5x.. Red 1,Black 1,Red 2,Black 2,Yellow/Green Embossing details CU/XLPE/PVC/SWA/PVC IEC 60502-1
>5x.. Black numbered on White cores Year Meter

Minimum Design Life 30 Years Screening requirement No


UV resistant outer sheath (as per ISO
VFD Cable (Special Requirement) No Special requirement
4892-2)
INSPECTION AND TESTS
Required Witness Required Witness
Routine tests per IEC and requisition YES YES Type tests per IEC & requisition (As required) NO NO
Sample tests per IEC YES YES
(Sample as per IEC OR as per requisition)
NOTES AND REMARKS
* data to be furnished by Manufacturer
1) In general, all Cables shall comply to Technical specification- HV & LV Cables, Doc. No. ENG052-20ERW-000-EL-SPC-0010-000 and relevant IEC Standards
2) Furnish data for all cables sizes as per the requisition
3) Current de-rating factors applicable for different laying conditions shall be furnished by the Supplier.
4) Technical catalogue of the offered cables meeting to the specification & data sheet requirement to be furnished by cable Supplier.
CABLE CHARACTERISTICS UNIT CABLE SIZES (REFER NOTE-2 ABOVE)
ITEM 5Cx2.5 7Cx2.5 12Cx2.5 2Cx6 (FR) 2Cx16 (FR) 2Cx25 (FR) 2Cx95 (FR) 3Cx4 (FR)
1) CONDUCTOR
Diameter of Main conductor (Nominal) mm 1,98 1,98 1,98 3,06 4,71 5,9 11,3 2,49
No. of conductor wires Main (minimum) No. 7x0,66 7x0,66 7x0,66 7x1,02 7x1,75 7x2,22 19x2,62 7x0,83
Diameter of Earth conductor (Nominal) mm * * * * * * * *
No. of conductor wires - Earth(minimum) No. * * * * * * * *
2) INSULATION
Insulation thickness (nominal) mm 0,7 0,7 0,7 0,7 0,7 0,9 1,1 0,7
Insulation thickness (minimum) mm 0,53 0,53 0,53 0,53 0,53 0,71 0,89 0,53
Diameter over laid assembly (multi-core) mm 9,7 10,3 13,8 10,4 13,7 16,3 27,9 10
3) BINDER TAPE
Approximate thickness (nominal) mm * * * * * * * *
Diameter over Binder Tape mm * * * * * * * *
4) BEDDING (INNER SHEATH)
Inner sheath thickness (nominal) mm 0,6 0,6 0,6 0,8 0,8 1,2 1,2 0,8
Inner sheath thickness (minimum) mm 0,41 0,41 0,41 0,58 0,58 0,92 0,92 0,58

Diameter over Bedding mm 12,1 11,6 15,4 12,7 16 20,2 31,8 12,3

NC200 Erawin Field Development Rev : 02


Doc. No.: ENG044-20ERW-000-EL-DAS-0010-000 Page : 14 of 16

TITLE: DATA SHEET - LV CABLES

5) ARMOUR
Armour wire dia. mm 0,8 1,25 1,25 0,8 1,25 1,6 2 0,8
No. of armour wires (approx.) "As per
Table 54.3 of IEC 60364-5-54 if armour is No. 40 26 33 38 34 34 42 36
used as PE"
Diameter over armour mm 13,7 14,1 17,9 14,5 18,5 23,4 35,8 14,1
6) OUTER SHEATH
Outer sheath thickness (nominal) mm 1,8 1,8 1,8 1,8 1,8 1,8 2,1 1,8
Outer sheath thickness (minimum) mm 1,24 1,24 1,24 1,24 1,24 1,24 1,48 1,24
OVERALL DIAMETER mm 17 18 21 18 22 27 40 18
Tolerance on O.D. of cable mm +2-1 +2-1 +3-2 +2-1 +3-2 +3-2 +3-2 +2-1
7) PACKING
Maximum cable Drum length metres 1000 1000 1000 1000 1000 1000 1000 1000
Positive Tolerance on drum cable length % 2% 2% 2% 2% 2% 2% 2% 2%
Cable Weight kG/km 500 590 830 585 1015 1575 3960 550
Drum Weight kG 63 63 102 63 115 220 473 63

124 x 83 x 134 x 89 x 154 x 112 x 224 x 137 x 114 x 69 x


Size of Drum (H x W) mm 114 x 69 x 114 114 x 69 x 114 124 x 83 x 124
124 134 154 224 114

Minimum Pulling tension kG 750 1050 1800 600 1600 2500 9500 600
Min. Bending Radius (No. x Diameter) No. 204 216 252 216 261,6 324 480 216
8) ELECTRICAL PARAMETERS
Max. DC resistance at 20ºC ohm/km 7,41 7,41 7,41 3,08 1,15 0,727 0,193 4,61
Max. DC resistance at 90ºC ohm/km 9,440 9,440 9,440 3,924 1,465 0,926 0,246 5,873
Approx. AC resistance at 90ºC ohm/km 9,448 9,448 9,448 3,927 1,466 0,927 0,246 5,878
Approx. Reactance at 50Hz ohm/km 0,099 0,099 0,099 0,089 0,081 0,081 0,072 0,093
Approx. impedance at 50Hz ohm/km 9,449 9,449 9,449 3,928 1,468 0,931 0,256 5,879
Approx. capacitance µF/km 0,268 0,268 0,268 0,382 0,554 0,484 0,88 0,281
Cable charging current at nom. V & Hz A/km 0,051 0,051 0,051 0,072 0,104 0,091 0,166 0,053
DC resistance of armour at 20ºC ohm/km 9,458 5,960 4,696 7,867 4,558 2,806 1,454 8,304
AC resistance of armour at 80ºC ohm/km 11,681 7,361 5,799 9,715 5,629 3,466 1,796 10,255
9) CURRENT RATING (Metallic layer bonded at both Ends)
Buried 0.8m at ground temperature Amps 28 28 28 54 93 120 251 36
of 30ºC, g=2.5ºCm/W, single cable
In Duct at 0.8m, ground temperature Amps 26 26 26 49 85 108 222 33
of 30ºC, g=2.5ºCm/W, single cable
Cable laid in Air, at ambient temperature Amps 26 26 26 52 94 122 289 34
of 50ºC, Single cable
Short circuit rating for 1 sec. Amps 0,358 0,358 0,358 0,858 2,288 3,575 13,585 0,572
Fault current rating of armour-1 sec. Amps 1,4 2,2 2,7 0,9 2 3,3 6,5 0,9
Earthing Cables
NC200 Erawin Field Development Rev : 02
Doc. No.: ENG052-20ERW-000-EL-DAS-0010-000 Page : 15 of 16

DATA SHEET - EARTHING WIRES CABLES

Tag No. : Not Applicable Inq/PO No:ENG052-20ERW-000-EL-REQ-0005-000 Date : 27/01/2022


GENERAL INFORMATION
Name of Manufacturer PRYSMIAN Country of Manufacture TURKEY
SERVICE CONDITIONS
Onshore, Outdoor/Indoor, Under
Maximum ambient temperature 50 ºC Installation
ground/Above ground
Minimum ambient temperature -2 ºC
BASIC DESIGN DATA

Voltage grade 450/750 V

Cable type Cu/PVC

Flame Retardant-Category A (IEC60332-3-


Outer sheath
22)

Ref. Standard IEC 60227-3

Max. operating / SC temp. 70 ºC 160 ºC

Conductor Copper

Conductor shape Circular Annealed Stranded


Flexibility class (IEC 60228) Class 2
Extruded PVC
Material of insulation Embossing on outer sheath Every 1 meter (meter is inkjet)

PRYSMIAN H07V-R 120 mm² CU/PVC


Core Identification GREEN/YELLOW Embossing details
IEC 60227-3 Year Meter

Minimum Design Life 30 Years Screening requirement No


UV resistant outer sheath (as per ISO
VFD Cable (Special Requirement) No Special requirement
4892-2)
INSPECTION AND TESTS
Required Witness Required Witness
Routine tests per IEC and requisition YES YES Type tests per IEC & requisition (As required) NO NO
Sample tests per IEC YES YES
(Sample as per IEC OR as per requisition)
NOTES AND REMARKS
* data to be furnished by Manufacturer
1) In general, all Cables shall comply to Technical specification- HV & LV Cables, Doc. No. ENG052-20ERW-000-EL-SPC-0010-000 and relevant IEC Standards
2) Furnish data for all cables sizes as per the requisition
3) Current de-rating factors applicable for different laying conditions shall be furnished by the Supplier.
4) Technical catalogue of the offered cables meeting to the specification & data sheet requirement to be furnished by cable Supplier.
CABLE CHARACTERISTICS UNIT CABLE SIZES (REFER NOTE-2 ABOVE)
ITEM 1C6 1C16 1C25 1C50 1C70 1C120 1C300
1) CONDUCTOR
Diameter of Main conductor (Nominal) mm 3,06 4,71 5,9 7,98 9,62 12,73 20,3 *
No. of conductor wires Main (minimum) No. 7x1,02 7x1,75 7x2,22 10x2,62 14x2,62 24x2,62 59x2,62 *
Diameter of Earth conductor (Nominal) mm * * * * * * * *
No. of conductor wires - Earth(minimum) No. * * * * * * * *
2) INSULATION
Insulation thickness (nominal) mm 0,8 1,0 1,2 1,4 1,4 1,6 2,4 *
Insulation thickness (minimum) mm 0,62 0,8 0,98 1,16 1,16 1,34 2,06 *
Diameter over laid assembly (multi-core) mm * * * * * * * *
3) BINDER TAPE
Approximate thickness (nominal) mm * * * * * * * *
Diameter over Binder Tape mm * * * * * * * *
4) BEDDING (INNER SHEATH)
Inner sheath thickness (nominal) mm * * * * * * * *
Inner sheath thickness (minimum) mm * * * * * * * *

Diameter over Bedding mm * * * * * * * *

NC200 Erawin Field Development Rev : 02


Doc. No.: ENG044-20ERW-000-EL-DAS-0010-000 Page : 16 of 16

TITLE: DATA SHEET - LV CABLES

5) ARMOUR
Armour wire dia. mm * * * * * * * *
No. of armour wires (approx.) "As per
Table 54.3 of IEC 60364-5-54 if armour is No. * * * * * * * *
used as PE"
Diameter over armour mm * * * * * * * *
6) OUTER SHEATH
Outer sheath thickness (nominal) mm * * * * * * * *
Outer sheath thickness (minimum) mm * * * * * * * *
Min.4,3 Min.6,4 Min.8,1 Min.8,9 Min.12,1 Min.15,6 Min.24,5
OVERALL DIAMETER mm *
Max.5,2 Max.7,8 Max.9,7 Max.12,3 Max.14,6 Max.18,8 Max.29,6
Tolerance on O.D. of cable mm ± ± ± ± ± ± ± ±
7) PACKING
Maximum cable Drum length metres 1000 1000 1000 1000 1000 1000 1000 *
Positive Tolerance on drum cable length % 2% 2% 2% 2% 2% 2% 2% 2%
Cable Weight kG/km 67 165 260 470 660 1140 2850 *
Drum Weight kG 12 25 25 55 55 115 315 *
56 x 40 x 104 x 69 x 104 x 69 x 134 x 89 x 184 x 113 x
Size of Drum (H x W) mm 74 x 49 x 74 74 x 49 x 74 *
56 104 104 134 184
Minimum Pulling tension kG 90 240 375 750 1050 1800 4500 *
Min. Bending Radius (No. x Diameter) No. 62,4 93,6 116,4 147,6 87,6 112,8 177,6 *
8) ELECTRICAL PARAMETERS
Max. DC resistance at 20ºC ohm/km 3,08 1,15 0,727 0,387 0,268 0,153 0,0601 *
Max. DC resistance at 90ºC ohm/km * * * * * * * *
Approx. AC resistance at 90ºC ohm/km 3,927 1,466 0,927 0,493 0,342 0,195 0,077 *
Approx. Reactance at 50Hz ohm/km * * * * * * * *
Approx. impedance at 50Hz ohm/km * * * * * * * *
Approx. capacitance µF/km * * * * * * * *
Cable charging current at nom. V & Hz A/km * * * * * * *
DC resistance of armour at 20ºC ohm/km * * * * * * * *
AC resistance of armour at 80ºC ohm/km * * * * * * * *
9) CURRENT RATING (Metallic layer bonded at both Ends)
Buried 0.8m at ground temperature Amps * * * * * * * *
of 30ºC, g=2.5ºCm/W, single cable
In Duct at 0.8m, ground temperature Amps * * * * * * * *
of 30ºC, g=2.5ºCm/W, single cable
Cable laid in Air, at ambient temperature Amps 36 67 84 128 165 233 421 *
of 50ºC, Single cable
Short circuit rating for 1 sec. Amps 0,858 2,288 3,575 7,150 10,010 17,160 42,900 *
Fault current rating of armour-1 sec. Amps * * * * * * * *