PENGUJIAN TAHANAN ISOLASI TRAVO

1. SPESIFIKASI
OPERATION TYPE FREQUENCY (HZ)
COOLING RATED POWER (kVA)
HIGH VOLTAGE (V) HV CURRENT (A)
LOW VOLTAGE (V) LV CURRENT (A)
IMPEDANCE 75°C (%) AMBIENT TEMP (°C)
B.I.L (kV) TEMP. RISE (°C)
TOTAL WEIGHT (kG) OIL VOLUME (L)
SERIAL NO. MFG.DATE
TAP CHANGER
1
2
3 PT.TRAFINDO PRIMA PERKASA
4 MADE IN INDONESIA
5

2. HASIL PENGUKURAN TAHANAN ISOLASI


PRIMER ( Low voltage ) SEKUNDER ( hight voltage )
R-G S-G T-G U-G V-G W-G

PRIMER –SEKUNDER ( Hight voltage – low voltage)


R- U S - V T - W

TESTED BY CHECKED BY APPROVE BY

(TEAM DES)
PENGUKURAN TAHANAN ISOLASI
PENGUKURAN SISI PRIMER LV ( TAP 2 : 20500)
PENGUKURAN DENGAN MULTITESTER PENGUKURAN DENGAN MERGER
PHASA R-S PHASA R-T PHASA S-T PHASA T-G PHASA S-G PHASA R-G

PENGUKURAN SISI SEKUNDER HV ( TAP 2 : 20500)


PENGUKURAN DENGAN MULTITESTER PENGUKURAN DENGAN MERGER
PHASA W-V PHASA W-U PHASA V-U PHASA W-G PHASA V-G PHASA U-G

PENGUKURAN SISI PRIMER-SEKUNDER (TAP 2 : 20500)


PHASA T-W PHASA S-V PHASA R-U

KESIMPULAN :

Referensi petunjuk standart nilai tahanan isolasi dan pengencangan baut


Pengukuran tahan isolasi Nilai yang diizinkan
Terminal HV- LV
1.2 KV Maks : alat 1000 VDC, hasil min 32 M Ω
2.5 KV Alat 5000 VDC, hasil min 80 M Ω
5 KV Alat 5000 VDC, hasil min 135 M Ω
8.7 KV Alat 5000 VDC, hasil min 230 M Ω
15 KV Alat 5000 VDC, hasil min 410 M Ω
25 KV Alat 5000 VDC, hasil min 670 M Ω
Kekencangan baut pada conector Bushing
M–8 10 Nm
M – 12 20 Nm