PENGUJIAN TAHANAN ISOLASI TRAVO

1. SPESIFIKASI
OPERATION TYPE - FREQUENCY (HZ) 50
COOLING ONAN RATED POWER (kVA) 3150
HIGH VOLTAGE (V) 20000 HV CURRENT (A) 90.93
LOW VOLTAGE (V) LV CURRENT (A) 4546.63
400
IMPEDANCE 75°C (%) 7.5 AMBIENT TEMP (°C) -
B.I.L (kV) L1 125 AC 50/L1-AC 3 TEMP. RISE (°C) 60/65
TOTAL WEIGHT (kG) 6100 OIL VOLUME (L) 1605
SERIAL NO. 143305773 MFG.DATE 2014
TAP CHANGER
1 21000
2 20500
3 20000 PT.TRAFINDO PRIMA PERKASA
4 19500 MADE IN INDONESIA
5 19000

2. HASIL PENGUKURAN TAHANAN ISOLASI


PRIMER ( Low voltage ) SEKUNDER ( hight voltage )
R-G S-G T-G U-G V-G W-G
66.6 G Ω 73 G Ω 77.4 G Ω 73.1 G Ω 94.7 G Ω 101 G Ω

PRIMER –SEKUNDER ( Hight voltage – low voltage)


R- U S - V T - W
55.6 G Ω 76 G Ω 88.3 Ω
TESTED BY CHECKED BY APPROVE BY

(TEAM)
PENGUKURAN TAHANAN ISOLASI
PENGUKURAN SISI PRIMER LV ( TAP 2 : 20500)
PENGUKURAN DENGAN MULTITESTER PENGUKURAN DENGAN MERGER
PHASA R-S PHASA R-T PHASA S-T PHASA T-G PHASA S-G PHASA R-G
0.1 Ω 0.1 Ω 0.1 Ω 77.4 G Ω 73 G Ω 66.6 G Ω
PENGUKURAN SISI SEKUNDER HV ( TAP 2 : 20500)
PENGUKURAN DENGAN MULTITESTER PENGUKURAN DENGAN MERGER
PHASA W-V PHASA W-U PHASA V-U PHASA W-G PHASA V-G PHASA U-G
1.8 Ω 1.5 Ω 2Ω 101 G Ω 94.7 G Ω 73.1 G Ω
PENGUKURAN SISI PRIMER-SEKUNDER (TAP 2 : 20500)
PHASA T-W PHASA S-V PHASA R-U
88.3 G Ω 76 G Ω 55.6 G Ω

NOTE :
 Dilakukan perbaikan seal rubber sisi high voltage yang mengalami kebocoran
 Dari hasil pengujian tahanan isolasi dapat dinyatakan kondisi bagus

Referensi petunjuk standart nilai tahanan isolasi dan pengencangan baut


Pengukuran tahan isolasi Nilai yang diizinkan
Terminal HV- LV
1.2 KV Maks : alat 1000 VDC, hasil min 32 M Ω
2.5 KV Alat 5000 VDC, hasil min 80 M Ω
5 KV Alat 5000 VDC, hasil min 135 M Ω
8.7 KV Alat 5000 VDC, hasil min 230 M Ω
15 KV Alat 5000 VDC, hasil min 410 M Ω
25 KV Alat 5000 VDC, hasil min 670 M Ω
Kekencangan baut pada conector Bushing
M–8 10 Nm
M – 12 20 Nm