1. SPESIFIKASI
OPERATION TYPE - FREQUENCY (HZ) 50
COOLING ONAN RATED POWER (kVA) 3150
HIGH VOLTAGE (V) 20000 HV CURRENT (A) 90.93
LOW VOLTAGE (V) LV CURRENT (A) 4546.63
400
IMPEDANCE 75°C (%) 7.5 AMBIENT TEMP (°C) -
B.I.L (kV) L1 125 AC 50/L1-AC 3 TEMP. RISE (°C) 60/65
TOTAL WEIGHT (kG) 6100 OIL VOLUME (L) 1605
SERIAL NO. MFG.DATE 2014
TAP CHANGER
1 21000
2 20500
3 20000 PT.TRAFINDO PRIMA PERKASA
4 19500 MADE IN INDONESIA
5 19000
(TEAM)
PENGUKURAN TAHANAN ISOLASI
PENGUKURAN SISI PRIMER LV ( TAP 1 : 21000)
PENGUKURAN DENGAN MULTITESTER PENGUKURAN DENGAN MERGER
PHASA R-S PHASA R-T PHASA S-T PHASA T-G PHASA S-G PHASA R-G
0.1 Ω 0.1 Ω 0.1 Ω 5.60 G Ω 5.44 G Ω 5.14 G Ω
PENGUKURAN SISI SEKUNDER HV ( TAP 1 : 21000)
PENGUKURAN DENGAN MULTITESTER PENGUKURAN DENGAN MERGER
PHASA W-V PHASA W-U PHASA V-U PHASA W-G PHASA V-G PHASA U-G
3.5 Ω 2.2 Ω 2.8 Ω 5.38 G Ω 5.75 G Ω 5.87 G Ω
PENGUKURAN SISI PRIMER-SEKUNDER (TAP 2 : 20500)
PHASA T-W PHASA S-V PHASA R-U
1.93 G Ω 1.86 G Ω 1.69 G Ω
NOTE :
Dilakukan perbaikan pin insulator travo sisi high voltage yang stud bolt bengkok
Dari hasil pengujian tahanan isolasi dapat dinyatakan kondisi bagus