Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Sinorix™

CP16
IG-100, FK-5-1-12, HFC 227ea, CO2

Pneumatic actuator
● Compatible with all Siemens cylinder valves
● Compatible with MAVADI distribution matrices

Product code: FR2:LB700060008

A6V10756550_en--_f Smart Infrastructure


2023-07-05 Building Products
Use
This product is used in fixed Sinorix™ automatic extinguishing systems based on inert gases
and fire-inhibiting gases.

Functions
When the system is actuated, pressurized gas activates the actuator and opens the cylinder
valve:
● by perforating the sealing plug of a VS12-, VR12- and VSB33-type cylinder valve, or a
MAVADI distribution matrix,
● by activating the shaft of a VFR300-S type cylinder valve.

Type summary

Item Description Item Description

1 Actuator body 2 Single-use PIST actuation piston

Equipment combinations

Reference Description Product code

PIST Actuation piston FR2:LB700950008

UNJIC Union fitting FR2:LB703410008

RENJIC Tee fitting with external thread FR2:LB704290008

EQJIC Elbow fitting FR2:LB703400008

TEJIC Tee fitting FR2:LB703390008

2
Smart Infrastructure A6V10756550_en--_f
Building Products 2023-07-05
Product documentation

Type Title Document ref.

Installation, Sinorix™ CDT-V A6V10780127


Commissioning, Fixed gas automatic extinguishing systems
Maintenance

Installation, Sinorix™ fixed automatic extinguishing systems based on A6V10780132


Commissioning, fire-inhibiting gases
Maintenance

Installation, Sinorix™ CO2 APEXT range


Commissioning, Fixed gas automatic extinguishing systems
Maintenance

Notes
Safety
This product may only be installed by Siemens-authorized specialized installers, with
experience in the design, installation and maintenance of automatic extinguishing systems.
During installation, it must be ensured that:
● this product is installed in compliance with the accident prevention regulations and
national regulations in force,
● this product is used as intended,
● any danger is avoided,
● Siemens requirements are met (assembly instructions, technical instructions,
commissioning, and operating instructions),
● the operators have received and understood the information related to this product.
At commissioning, ensure compliance with the legislation in force, technical regulations and
safety instructions.
Failure to comply with Siemens' instructions may result in serious bodily injury or significant
property damage, for which Siemens cannot be held liable.
Siemens reserves the right to make technical modifications and/or improvements at any
time.
Mounting
All cylinder valves (except VFR300-S) and distribution matrix
● Apply fluorosilicone grease sparingly to the O-ring of the PIST piston.
● Check that the spring of the PIST piston is correctly positioned, its wide base towards the
tip of the needle.
● Position the PIST equipped with its spring gently in the valve port, without pressing on
the O-ring: the O-ring must remain visible.

Fig. 1: Mounting example: on a VS12F cylinder valve

● Apply fluorosilicone grease sparingly to the O-ring of the actuator.


● Screw the actuator by hand to the stop onto the actuation port.
● Tighten with an open-end wrench without forcing.
VFR300-S cylinder valve
● Apply fluorosilicone grease sparingly to the O-ring of the actuator.
● Screw the actuator by hand to the stop onto the actuation port of the cylinder valve.
● Tighten with an open-end wrench without forcing.

3
Smart Infrastructure A6V10756550_en--_f
Building Products 2023-07-05
Maintenance

Storage
● Store in its original packaging, protected from shocks.
● Storage time: maximum 10 years (observe ISO 2230 guidelines).
● Check that the product is in good condition.
● Check that the product is properly tightened. Re-tighten if necessary.

After an actuation
All cylinder valves (except VFR300-S) and distribution matrix
● Disassemble the actuator.
● Remove the used PIST piston.
● Insert a new PIST in the actuation port.
● Reassemble the actuator.

Only use actuators in good condition.

VFR300-S cylinder valve


No PIST is used with the CP16. There is no replacement procedure.

4
Smart Infrastructure A6V10756550_en--_f
Building Products 2023-07-05
Technical data

Technical data

Operating pressure 190 bar

Minimum actuation pressure 9 bar*

Maximum actuation pressure 100 bar

Thread 1/8’’ NPT M24x1.5

Materials Brass, elastomer

Operating temperature -20 °C to +50 °C

Weight 0.085 kg

* Refer to the Standards paragraph for additional information.

Marking

CP16
070006 Index
WW / YY (week/year)
SIEMENS
PS220B
VdS 100 bar

Standards, directives and authorizations Actuation pressure

minimum nominal maximum

305/2011/EU (CPR) With the following cylinder valves:

VR12C, VR12CB 1116-CPR-019 15 bar / /

VS12F, VS12F KVP 1116-CPR-021 9 bar / /

VSB33 1116-CPR-020 9 bar / /

VFR300-S 1116-CPR-024 9 bar / /

VdS Approved when associated with

VS12F, VS12F KVP G303010 9 bar 42 bar 53 bar

VSB33 G303009 9 bar 42 bar 53 bar

VFR300-S G308008 9 bar 60 bar 100 bar

5
Smart Infrastructure A6V10756550_en--_f
Building Products 2023-07-05
Dimensions

Dimensions in mm

Issued by
© Siemens 2023
Siemens SAS
Technical specifications and availability subject to change without notice.
Smart Infrastructure
15-17, avenue Morane-Saulnier
FR-78140 VELIZY-VILLACOUBLAY
+33 1 85 57 01 00
www.siemens.com/buildingtechnologies

Document ID A6V10756550_en--_f
Edition 2023-07-05

You might also like