DEPYM_A6V10859655
DEPYM_A6V10859655
DEPYM
IG-100, FK-5-1-12, HFC 227ea, CO2
Functions
The actuator activates the automatic gas extinguishing system manually, either
pneumatically and automatically or manually.
Manual actuation
The user removes the safety axis pin and lowers the actuation lever firmly:
● The actuator pusher presses on the PIST actuation piston which perforates the sealing
disc (VS12-, VR12- and VSB33-type cylinder valves, and MAVADI distribution matrices),
● The actuator pusher activates the shaft on a VFR300-S type cylinder valve.
Type summary
2
Smart Infrastructure A6V10859655_en--_g
Building Products 2023-07-05
Equipment combinations
Product documentation
Notes
Safety
This product may only be installed by Siemens-authorized specialized installers, with
experience in the design, installation, and maintenance of automatic extinguishing systems.
During installation, it must be ensured that:
● this product is installed in compliance with the accident prevention regulations and
national regulations in force,
● this product is used as intended,
● any danger is avoided,
● Siemens requirements are met (assembly instructions, technical instructions,
commissioning, and operating instructions),
● the operators have received and understood the information related to this product.
At commissioning, ensure compliance with the legislation in force, technical regulations and
safety instructions.
Failure to comply with Siemens' instructions may result in serious bodily injury or significant
property damage, for which Siemens cannot be held liable.
Siemens reserves the right to make technical modifications and/or improvements at any
time.
3
Smart Infrastructure A6V10859655_en--_g
Building Products 2023-07-05
Mounting
All cylinder valves (except VFR300-S) and distribution matrix
● Apply fluorosilicone grease sparingly to the O-ring of the PIST piston.
● Check that the spring of the PIST piston is correctly positioned, its wide base towards the
tip of the needle.
● Position the PIST equipped with its spring gently in the valve port, without pressing on
the O-ring: the O-ring must remain visible.
Storage
● Store in its original packaging, protected from shocks.
● Storage time: maximum 10 years (observe ISO 2230 guidelines).
After an actuation
All cylinder valves (except VFR300-S) and distribution matrix
● Remove the actuator from the cylinder to be replaced, or from the related zone port on
the distribution matrix.
● Remove the used PIST piston and dispose of it.
● Apply grease to a new PIST and position it into the actuation port of the cylinder valve,
on the new cylinder, or in the zone port of the distribution matrix.
● Screw the pre-sealed actuator.
VFR300-S cylinder valve
● Screw the pre-sealed actuator.
4
Smart Infrastructure A6V10859655_en--_g
Building Products 2023-07-05
Technical data
Technical data
Actuation pressure
minimum 9 bar
maximum 100 bar
Thread M24x1.5
Weight 0.46 kg
Marking
070793
Ind: revision
WW / YY (week / year)
5
Smart Infrastructure A6V10859655_en--_g
Building Products 2023-07-05
Dimensions
Dimensions in mm
Issued by
© Siemens 2023
Siemens SAS
Technical specifications and availability subject to change without notice.
Smart Infrastructure
15-17, avenue Morane-Saulnier
FR-78140 VELIZY-VILLACOUBLAY
+33 1 85 57 01 00
www.siemens.com/buildingtechnologies
Document ID A6V10859655_en--_g
Edition 2023-07-05