INSTALLATION NOTES:

1. ALL ELECTRICAL WORKS MUST CONFORM TO THE PROVISIONS OF PEC 2017, THE RULES & REGULATIONS OF ALL LOCAL & NATIONAL AUTHORITIES
CONCERNED IN THE PRACTICE OF ELECTRICAL ENGINEERING AND SHALL BE IN ACCORDANCE WITH THE POLICY OF THE LOCAL UTILITY COMPANY.
2. SERVICE VOLTAGE TO THE BUILDING SHALL BE 23OV, SINGLE PHASE, TO BE SERVE THRU A 60 AT ACB WITH 2 NO. 14 SQ. MM THHN WIRE IN 25 MM DIA. RSC
PLUS 1 – 8.0 SQ. MM THHN WIRE, GEC.
3. ALL BRANCH CIRCUITS INSTALLATION SHALL BE IN RIGID uPVC SCHED.40, COMPLETE WITH PROPER FITTINGS.
4. MINIMUN SIZE OF CONDUCTOR SHALL BE 3.5 SQ. MM TYPE THW/THHN COPPER WIRE, WITH INSULATIONS GOOD FOR 600 VOLTS, AND CONDUIT SHALL BE RUN
20MM NOMINAL DIAMETER.
5. ALL GROUNDING CONDUCTORS SHALL BE PROPERLY IDENTIFIED USING GREEN COLORED INSULATION OF WIRES, AND IN NO OTHER PURPOSE SHALL GREEN
COLORED CONDUCTOR BE USED IN THE ENTIRE INSTALLATION.
6. ALL LIGHT CONTROL SWICHES FOR LIGHTING SHALL BE RATED 15A, 220V, AC.
7. ALL CONVENIENCE OUTLETS FOR GENERAL USE SHALL BE GROUNDING TYPE, RATED 15A, 220V, THREE WIRES.
8. ALL FLUORESCENT FIXTURES SHALL BE EQUIPPED WITH RAPID START, HIGH POWER FACTOR BALLAST & SHALL USE HIGH QUALITY POLYCARBONATE LAMP
HOLDER & END CAPS.
9. ALL ELECTRICAL EQUIPMENTS SHALL BE EQUIPPED WITH PROPER GROUNDING WITH CONNECTIONS HAVING HIGHER FAULT CURRENT CAPACITY THAN THE
CONDUCTOR.
10. ALL WIRING MATERIALS TO BE USED SHALL BE NEW AND OF APPROVED TYPE AS TO BOTH PURPOSE & LOCATION INTENDED.
11. BRANCH CIRCUITS PROTECTION AND CONDCUTOR SHALL BE RATED AS INDICATED ON THE SINGLE LINE WIRING DIAGRAM.
12. THE PLANS DRAWN ARE DIAGRAMMATIC AND DO NOT NECESSARILY PIT FOR PROJECT CONDITONS. ANY CONCERN AS WITH REGARDS TO THE ABOVE SHALL
BE REFERRED TO THE ARCHITECT, THE DESIGNER OR THE ON SITE OWNER’S REPRESENTATIVE FOR CONFIRMATION.
13. ALL ELECTRICAL WORKS SHALL BE DONE WORKMANLIKE EMPLOYING ONLY SKILLED & QUALIFIED ELECTRICIANS UNDER THE SUPERVISION OF A DULY
LICENSED ELECTRICAL ENGINEER OR RME.
14. ALL METAL FRAMES & ENCLOSURES SHALL BE PROPERLY BONDED TO THE BUILDING GROUNDING SYSTEM.