Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Anderson, Loren Runar et al "APPLICATION OF FINITE ELEMENT ANALYSIS TO A BURIED PIPE"

Structural Mechanics of Buried Pipes


Boca Raton: CRC Press LLC,2000
CHAPTER 29 APPLICATION OF FINITE ELEMENT ANALYSIS TO A BURIED PIPE

Introduction four soils that were used in the soil box be tested for
engineering properties, including triaxial testing at
As discussed in Chapter 28, the finite-element several densities for evaluation of the hyperbolic
analysis of buried flexible pipes requires capabilities parameters for the Duncan soil model. Results from
generally not included in most finite-element analysis the tests are described by Sharp et al. (1984). In the
applications. Many types of buried pipes (such as following discussion, only the results of the
fiberglas-reinforced plastic pipe) are very flexible, applications of the finite-element program to the
thus, requiring a finite-element analysis of the installation conditions for silty sand are presented.
system to accommodate large deflections. The results of the remaining applications are
included in the report by Sharp et al. (1984).
The sensitivity of the pipe and the soil properties to
compaction loading may be an important
consideration. The stress history of each soil Determination of Duncan Soil Parameters
element should be monitored at each loading
increment to determine whether the element is in a The silty sand that was used in the soil-box tests is
state of primary loading, unloading or reloading, and characterized as a nonplastic material with about
then appropriate parameters need to be used for 40% passing the 0.075-mm sieve and about 10%
each increment of the analysis. clay-size particles. Maximum dry density is 124.7
lb/ft3 and the optimum water content is 9.5 % based
Properly accounting for all elements of the soil on AASHTO T-99 compaction.
structure system makes the finite-element method a
useful tool for the analysis of buried flexible pipes Triaxial shear tests on the silty sand were performed
when subjected to various installation conditions, by using samples compacted at water contents
backfill material types, surcharge loadings, and similar to those used in soil-box tests. Figure 29-1 is
internal pressurization. the sketch of a "soil box." Elastic modulus and bulk
modulus parameters are required in the FEA for
This chapter illustrates the application of the finite- each density. Testing of the clean granular
element method to the solution of a soil structure materials (washed sand and gravel) was performed
interaction problem. The response as computed by by using saturated samples, and the volume change
a finite-element analysis (FEA) of a buried flexible was monitored by measuring the volume of water
fiberglas-reinforced plastic (FRP) pipe, when extruded or imbibed in the samples during drained
subjected to various installation and static loading shear.
conditions, was compared with measured strains and
deflections taken from physical tests in a soil box at Because the stress-strain and strength properties of
the Buried Structures Laboratory at Utah State the silty sand and clay are dependent on drainage,
University, Sharp et al. (1985). The FEA modeled density, compaction water content, and water
the actual soil box installation conditions. content at shear, it was necessary for the soil
parameters to represent field conditions as much as
The approach that was taken in the study was to possible. Therefore, the silty sand and the clay were
simulate the backfill and loading conditions that had tested by using unsaturated undrained conditions.
been used in the soil-box tests in order to compare The triaxial device was not equipped to
the predicted response of the pipe from FEA results
with the measured response. This required that the

©2000 CRC Press LLC


Figure 29-1 Sketch of the large USU soil cell (soil box) for investigating pipe-soil interaction of buried pipes.
The cell is an elliptical steel cylinder with horizontal radius of curvature at the spring lines equal to three times
the vertical radius at the invert. The ellipse reduces boundary effects by simulating a one-third ratio of
horizontal to vertical soil stresses as load is applied. Boundary effects are negligible for pipes up to about 60
inches (1.5 m) in diameter. The cell is 15 ft (4.6 m) wide, 18 ft (5.5 m) high to the hydraulic cylinders, and
22 ft (6.7 m) long. Vertical pressure is applied by 50 hydraulic cylinders on ten beams. The beams are
pinned at one end such that they can be tilted up out of the way for installing pipes. This is the larger of two
soil cells used, primarily, for investigating performance of pipes under high soil pressures, and for comparison
with finite element analyses.

©2000 CRC Press LLC


measure volumetric strain of undrained samples. complete description of sensitivity is contained in the
Therefore, bulk modulus parameters were not report by Sharp et al. (1984).
measured for the fine-grained soils (silty sand and
clay). Finite-Element Modeling

Triaxial testing was performed on the silty sand at The modeling of the fiberglass pipe performance in
three different densities (95%, 80%, and 77% silty sand consisted of several installation conditions
relative compaction based on Standard Proctor). and 10 and 100 psi pipe stiffnesses (ASTM D-
Stress-strain curves were obtained for three 2412). Installation conditions included homogeneous
confining pressures within the range used in the soil- compaction at 90 and 80% relative compaction, poor
box tests for each density. The triaxial testing haunches, and soft crown. In general the poor-
procedure involved preparing the sample with haunch and soft-crown conditions were obtained by
compaction techniques similar to those in the field not compacting the soil in those areas. Figure 29-2
and by applying the deviator by initial loading, shows the finite-element mesh and soil materials or
unloading, and reloading to failure. This resulted in types that were used in this study. The poor-haunch
data that were interpreted with procedures outlined condition used 90% relative compaction for all soil
by Duncan et al. (1980) for determination of shear types except that in the haunches (soil type 6). The
strength and the hyperbolic parameters for the soft-crown condition used 90% relative compaction
elastic moduli. for all soil types except that in the area from the
shoulders to the crown of the pipe, shown in Figure
The unloading and reloading data were also 29-2 as soil type 7. Thes e installation conditions
evaluated to obtain the rebound parameters for each were used because of the way in which materials
density. were placed around the pipe during installation.
When the pipe has low stiffness, it is difficult to
Because data were not obtained for the hyperbolic compact the fill material over the crown until
bulk modulus parameters, an FEA sensitivity study sufficient cover has been placed. Also, extra effort
was performed using soil-box test results to calibrate is required to compact the soil in the haunches, so it
the silty-sand data using 90 and 80% relative was desired to model installation conditions in which
compaction. The elastic modulii for the 90% relative there was loose material in the haunches. The other
c ompaction were obtained by interpolating the soil types that are shown were included to
measured values from the 95%, 80%, and 77% investigate effects due to split installation, different
percent relative compaction data. Sensitivity studies foundation materials, and other types of installations.
were performed by using a 90% homogeneous
relative compaction and an 80% homogeneous
relative compaction in the finite-element mesh to The finite-element modeling scheme consisted of
determine the bulk modulus parameters. These two phases. The first modeled construction
sensitivity studies show that the shape of the load- increments without compaction simulation. Four
deflection curve can be adjusted by modifying the installation conditions were modeled for pipes with
bulk modulus exponent. Pipe strain plots can also be stiffnesses of 10 and 100 psi. The second
adjusted because of complex interrelationships incorporated a compaction simulation on each
between hyperbolic elastic and bulk modulus construction increment before the next construction
parameters in conjunction with the shear strength of increment was added. Three installation conditions
the soil. Table 29-1 shows the final values for the were modeled by using the compaction simulation.
soil parameters that were used for the silty sand at Table 29-2 shows the installation conditions that
90% and 80% relative compaction. A more were used for the silty sand and indicates those that
included compaction simulation.

©2000 CRC Press LLC


Table 29-1. Soil Parameters for Silty Sand
RC density ϕ ∆ c K n Rf Kb m Ko Kur nur
Stand lb/in3 deg deg psi

90% 0.065 30 0. 8.3 480 .44 .75 80 .38 .48 720 .44

80% 0.058 30 0. 3.5 350 .28 .89 15 .40 .37 525 .28
Note: New report in Duncan et al., 1998) for definition of parameter.

Figure 29-2 Finite-element mesh for buried pipe installation, including pipe coordinate system.

©2000 CRC Press LLC


TABLE 29-2. Installation Conditions for Silty Sand
Condition Pipe Stiffness Compaction
(psi) Simulation

1. 90% homogeneous 10. 100 yes

2. 90% backfill with soft top @ 80% RC 10. 100 yes

3. 90% backfill with soft top @ 99% RC 10 no

4. 90% backfill with haunches @ 80% RC 10. 100 yes

5. 90% backfill with haunches @ 79% RC 10 no

6. 90% backfill with haunches @ 77% RC 10 no

7. 90% backfill with top and haunches 10 no


@ 85% RC

8. 80% homogeneous 10. 100 no

Soil elements in the foundation and up to the spring appears to be in accordance with the actual
line (soil materials 1 through 3) were treated as installation conditions, in which it was found that
preexisting elements having stresses and strains effective soil compaction could not be performed
predefined at the time of program execution. In the over the pipe until sufficient cover had been placed.
construction sequence used in the first phase, Also, it was not possible to add compaction loads on
placement of the remainder of soil 3 and all of soils the soil before placement of the first increment.
4 and 7 was simulated as the first construction When loads were added adjacent to the spring line
increment. The second construction increment on soil material 3, pressures caused excessive
completed the mesh by placing soil material S. deformation of the pipe.

The second phase or the modeling incorporated For compaction simulation, a uniform static load of
compaction simulation after each construction 10 psi was used corresponding to the type of
sequence. The compaction simulation involved compaction equipment used in the soil-box test. A
addition and removal of compaction loads at the end more rigorous compaction sequence would have
of the first and second construction increments. The been to load each soil element individually with a
first compaction load was added to the first layer of larger pressure, which would result in a better
soil material 4. The second compaction loading was simulation of the compaction process. The load of
placed on the completed mesh over soil material 5. 10 psi was an equivalent surface pressure over a
It was found that the first loading sequence was large area. The compaction load was added in two
critical in inducing initial ovalization of the pipe. It increments of 5 psi each. After the compaction load
was not possible to load directly over the pipe (soil had been placed, a sequence of unloading was
material 7) without causing structural failure and followed. A series of unloading steps in small
large unrealistic deformation of the pipe and soil pressure increments was followed until the elements
because of an unstable condition. This result

©2000 CRC Press LLC


in the top row of the mesh approached a tension behavior in triaxial shear of saturated drained
condition with negative confining pressure. granular material for primary loading as well as
rebound loading. It was not possible to conclude
Small increments were used in the loading and how volumetric deformation behaves as a function
unloading sequence in order to assure that the soil of stress history for the coarse-grained material. In
elements were being evaluated correctly for either addition, the granular material exhibited dilation at a
the primary loading or rebound parameters. small strain (a response that cannot be
Magnitudes that were too large for compaction accommodated within the theory of elasticity).
loading might have caused poor convergence and
incorrect evaluation of the appropriate soil response RESULTS OF FEA MODELING
model. It was not possible with the silty sand to
remove the same load magnitude that was placed The results of the applications of FEA were
without causing tension failures in all elements in the compared with the measured response from the soil-
mesh. box tests. The comparisons that follow are for a
pipe with 10 psi pipe stiffness. Soil box compaction
This was not the case with the clay analysis, conditions that were used for comparisons were
however, because it was numerically possible to 90% relative compaction with homogeneous
remove the same quantity of compaction load that conditions, 90% relative compaction with poor
was placed. Although it may seem invalid to model haunches, and 80% relative compaction with
compaction loading without removing the same load homogeneous conditions. In the soilbox testing,
that was placed, it must be pointed out that the every attempt was made to achieve homogeneous
solution is an incremental loading procedure. The conditions.
total load vector is not evaluated at each iteration. However, as noted, the flexible nature of the pipe
Only the total stresses and strains in each element does not always allow for thorough compaction in
are evaluated. Thus although success at unloading the haunches and around the shoulders and crown of
the elements with the same compaction load the pipe. Therefore, for the homogeneous conditions
magnitude was not achieved, it was possible to that were attempted in the soil box there was
induce stress history in the soil due to compaction actually some variation in density. When the pipe
loads, which resulted in allowable soil stresses, was installed with poor haunches in the soil box, no
strains, and deformations. attempt was made to compact the soil. Finite-
element modeling of homogeneous and poor-haunch
The inability to unload the soil element completely conditions is better defined because, numerically, all
without complete tension failure might be attributed soil elements in a homogeneous condition have
to numerical approximations with the finite-element identical stress-strain properties.
technique. Problems arise in the soil model in Comparisons of the FEA results with those of the
evaluating Poisson's ratio when the soil is in the soil-box tests are made by using pipe-strain and
unloading and reloading range. Poisson's ratio is load-deflection results. The pipe-strain plots indicate
computed by using the theory of elasticity the bending strain in the outside fibers (tension is
relationships between bulk modulus and elastic positive) and thrust strain around the circumference
modulus. When the elastic modulus increases as in of the pipe for a given surcharge pressure. The
unloading and reloading, Poisson's ratio is computed load-deflection plots indicate the vertical and
at its minimum of 0.0 if the bulk modulus does not horizontal ring deflections (the ratios of change in
increase proportionately. vertical and horizontal diameters to initial diameter)
Behavior of the bulk modulus is difficult to determine versus surcharge pressure. In the soil-box tests, the
on unloading and reloading relative to primary load-deflection plots are referenced to the deformed
loading. Sharp et al. (1984) tested bulk modulus state of the pipe after

©2000 CRC Press LLC


Figure 29-3 Vertical soil pressure versus pipe deflection for (curve A) soil-box data. 90 percent relative
compaction, silty sand and (curve B) FEA, no compaction simulation.

Figure 29-4 Pipe strains as functions of circumferential position, conditions as in Figure 29-3.

©2000 CRC Press LLC


compaction. In the FEA plots, the reference of ring figures show a similarity in the general shape of the
deflection is based on the initial undeformed load-deflection curve. The pipe-strain plots in Figure
condition. Thus in the comparison of figures that 29-4 indicates that the magnitudes of pipe strain for
follow, the zero point of deflection should be this case at a surface pressure of 50.0 psi are
considered when direct comparisons of load comparable, but several maxima and points of
deflections between the FEA and the soil-box tests inflection are missing. The magnitude of ring
are performed. Pipe-strain plots for both soil-box deflection at the 50 psi surface pressure is also
and FEA results are referenced from the same comparable within one-half of 1% of the measured
unstrained condition. The pipe-strain plots show deflection.
bending and thrust strain versus position on the pipe.
Zero degrees on the pipe is at the invert, 90 degrees Figures 29-5 and 29-6 show the results of the FEA
is at the spring line, and 180 degrees is at the crown for the homogeneous dense soil condition with
as shown in Figures 29-2 and 29-3. The values for compaction simulation during construction. The
pipe strain from 180 to 360 degrees are symmetric physical pipe data are:
with 0 to 180 degrees for the FEA because the FEA
mesh presented here used an axis of symmetry for Curve
the analysis of symmetric bedding. Parameter A B
Stiffness (psi) 10 10
Thickness (in.) 0.285 0.300
Homogeneous Installation at 90% Relative Surface pressure (psi) 48.9 50.0
Compaction Vertical deflection (t) 5.53 5.42
Horizon. deflection (1) 3.74 3.14
Figures 29-3 and 29-4 show the soil-box test results
for a 10-psi pipe installed with homogeneous The load-deflection plot in Figure 29-5 has lost some
compaction at 90% of Standard Proctor maximum of the initial steepness, but the difference between
dry density. Physical pipe date are: vertical and horizontal deflection is maintained.
Compared to Figure 29-3, the magnitudes of
Curve deflection are similar. Figure 29-6 shows the pipe-
Parameter A B strain plots from the compaction simulation at a
Stiffness (psi) 10 10 surface pressure of 50.0 psi. Comparison of Figure
Thickness (in.) 0.285 0.300 29-6 with the measured values from the soil-box
Surface pressure (psi) 40.9 50.0 results in Figure 29-4 shows that compaction
Vertical deflection (t) 5.53 4.82 simulation improved correlation. In fact, the general
Horizontal deflection (1) 3.74 2.52 shape, maxima, and magnitudes all compare well.
This result is the best comparison between any soil-
Figure 29-3 shows the load-deflection curve and box test and FEA result.
Figure 29-4 shows pipe strain versus location on the
pipe for a surcharge pres sure of 48.9 psi. Additional comparisons included soft elements in the
Noteworthy features of these results are the shape shoulders of the pipe. Because techniques did not
of the load-deflection curve, relative magnitudes of allow compaction above the pipe, a theoretically
horizontal and vertical ring deflections, and the homogeneous installation would still have soil of a
shapes and magnitudes of bending and thrust strain. lesser density at the crown. FEA results for this
This condition was modeled with FEA in several condition included various degrees of compaction
ways. Figures 29-3 and 29-4 also show the results simulation. From additional load-deflection and pipe-
from the FEA using homogeneous 90% relative strain plots it is evident that with the soft-crown
compaction and no compaction simulations. These analyses the pipe strain at the

©2000 CRC Press LLC


Figure 29-5 Vertical soil pressure versus pipe deflection for (curve A) soil-box data, 90% relative
compaction, silty sand and (curve B) FEA with compaction simulation.

Figure 29-6 Pipe strains as functions of circumferential location, conditions as in Figure 29-5.

©2000 CRC Press LLC


135-degree location increases. See Figure 29-3. the pipe-strain plots from soil-box tests. Figures 29-
This is due to decreased stiffness of the soil in the 7 and 29-8 also show the FEA results for the poor-
shoulders which allows for more bending haunch condition without compaction simulation.
deformation in the pipe. Compaction simulation for The load-deflection plot shows similar behavior, yet
the soft-crown condition decreases the bending the deformations are larger in the FEA results. The
strains and ring deformations because the soil pipe-strain plot shows a peak of large strain at 45
responds initially in the rebound range and inhibits degrees and low strains from spring line to crown
deformation at the low pressures. Because that are similar to the soil-box results. Figures 29-9
compaction simulation does not include adding loads and 29-10 show the FEA results for poor haunches
directly over the pipe at the first construction with compaction simulation. The load-deflection
increment, a soft-crown condition is actually created plots show larger deflections and the pipe-strain
in the homogeneous case. The soil at the crown is plots show larger strains from spring line to cro w n
uncompacted and does not respond to the stiffer than in Figure 28-8. However, strain at the invert of
rebound modulus at the lower pressure ranges as the pipe with compaction simulation was closer to
does the surrounding soil elements that receive the measured results than to the FEA results that did
compaction loads directly. not include compaction simulation. The physical
pipe data for Figures 29-9 and 29-10 are:

Poor-Haunch Installation at 90% Relative Curve


Compaction Parameter A B
Stiffness (psi) 10 10
Figures 29-7 and 29-8 show the results for the poor- Thickness (in.) 0.285 0.300
haunch installation with the silty sand in the soil-box Surface pressure (psi) 35.5 30.0
tests. The physical pipe data are: Vertical deflection (%) 3.14 5.14
Horizontal deflection (%) 1.30 2.92
Curve
Parameter A B
Stiffness (psi) 10 10 Homogeneous Installation with 80% Relative
Thickness (in.) 0.285 0.300 Relative Compaction
Surface pressure (psi) 35.5 30.0
Vertical deflection (%) 3.14 2.21 Figures 29-11 and 29-12 show the soil-box results
Horizontal deflection (%) 1.30 1.09 for 80% relative compaction homogeneous installa-
tion. The physical pipe data are:

Figure 29-7 shows the load-deflection response and Curve


Figure 29-8 shows the pipe strain around the pipe for Parameter A B
a surface pressure of 35.5 psi. Again the initial Stiffness (psi) 10 10
steepness of the load-deflection curve, the relative Thickness (in.) 0.285 0.300
magnitudes between the vertical and horizontal Surface pressure (psi) 14.6 15.0
deflections, and the shapes and magnitude of the Vertical deflection (%) 8.78 3.85
strain plots are noteworthy. The bending strains are Horizontal deflection (%) 7.87 2.06
higher at the 30 to 45 degree locations on the pipe
because of the lack of support in the haunch area. The vertical and horizontal deflections are similar
Also, a comparison of the homogeneous installation throughout the test, which includes elliptical
and the poor-haunch installation in Figures 29-6 and deformation as shown in Figure 29-11. Figures 29-
29-8, respectively, shows noticeable differences in 11 and 29-12 also show the results from the FEA

©2000 CRC Press LLC


Figure 29-7 Vertical soil pressure versus pipe deflection for (curve A) soil-box data, 90% relative
compaction, silty sand, and poor haunch support; and (curve B) FEA, no compaction simulation, and poor
haunch support.

Figure 29-8 Pipe strains as functions of circumferential location, conditions as in Figure 29-7.

©2000 CRC Press LLC


Figure 29-9 Vertical soil pressure versus pipe deflection for (curve A) soil-box data, 90% relative compaction,
silty sand, and poor haunch support; and (curve B) FEA with compaction simulation and poor haunch support.

Figure 29-10 Pipe strains as functions of circumferential location, conditions as in Figure 29-9.

©2000 CRC Press LLC


Figure 29-11 Vertical soil pressure versus pipe deflection for (curve A) soil-box data, 80% relative
compaction and (curve B) FEA, no compaction simulation.

Figure 29-12 Pipe strains as functions of circumferential location, conditions as in Figure 29-11.

©2000 CRC Press LLC


for the 80% relative compaction homogeneous deflections of around 8%. However, for the other
condition. Although the load-deflection curve shows types of loading conditions (such as rerounding), the
more deformation with the loose material than with formulation of the stiffness matrix must reflect the
the dense material, the actual comparison of soil-box shape of the pipe.
tests with FEA tests shows that the FEA does not
compare as well for the looser soil condition. The
pipe-strain plots in Figure 29-12 also confirm the
poorer comparison. In terms of magnitude of the SUMMARY AND CONCLUSIONS
maximum strain, there is correlation, but the overall
shape of the pipe-strain plots do not match measured Good correlation of finite-element modeling of
values as well as the analyses with 90% density. flexible pipes with test data requires modeling
c apabilities not readily available in most computer
programs. Such capabilities include analysis of the
DISCUSSION OF RESULTS stress history of the soil elements to determine
whether each element is in primary loading or in
Soil compaction simulation for the FEA response of unloading and reloading, modification of the iteration
the FRP pipe improves the comparison with soil-box scheme to better model the soil response when there
tests for homogeneous soil. For nonhomogeneous is a change from one stress condition to another, and
soil installation conditions, compaction simulation did large-deflection theory by modifying nodal
not improve the comparison of FEA with soil-box coordinates after each load increment. In addition,
tests enough to justify the additional computational postprocessing plotting routines are needed to
effort required. graphically analyze the pipe response to each loading
condition. The development of these features
The FEA results were generally better for dense soil makes possible the analysis of flexible pipe under
installation conditions than for loose soil conditions. compaction simulation, surcharge pressures,
This is due to a combination of numerical difficulties rerounding caused by internal pressure, and various
with the finite-element method and lack of similitude installation conditions. The results of analyses for
in the soil-box model that arises with loose soil various installation conditions show the effects of
conditions. Entries in the stiffness matrix become shoulder and haunch support on the pipe and suggest
s ensitive to the magnitudes of the elastic and bulk that these conditions can be considered in FEA
moduli at low soil stiffness. In order to achieve analysis of pipe and installation conditions.
larger deflections, lower values of the bulk modulus
are required. This, however, can result in singular The results of the USU study of four soil types and
matrix warnings, which indicates that entries in the various loading conditions, show a good correlation
stiffness matrix will not produce reliable results. between FEA results and the measured responses
from physical model tests in a soil-box. The finite-
The geometric nonlinear analysis (wherein the element method can be used for analyzing
formulation of the stiffness matrix accounts for the performance of buried flexible pipes with various
nodal deflections at each loading increment) does installation conditions, soil types and densities,
not significantly change the results for installation loading conditions, and pipe sizes and stiffnesses.
condition modeling. The inclusion of the geometric T he cost of FEA is less than physical testing.
nonlinear analysis would generally predict higher However, calibration of the FEA requires results
deflections. For example, an analysis that did not from physical tests. The two techniques used
include geometric nonlinearities might predict a together are applicable and cost effective for
vertical ring deflection of 7%. The same conditions analyzing buried flexible pipe performance.
including geometric nonlinearities would predict ring

©2000 CRC Press LLC


REFERENCES Medrano, (1984), A. P.Moser, and O.K.Shupe.
Performance of fiberglass reinforced plastic pipe to
Duncan, J.M. (1979). Behavior and design of long- various soil loads and conditions. Buried Structures
span metal culverts. Journal of Geotechnical Laboratory, Utah State University, Logan, 1094.
Engineering, ASCE, Vol. 105, No. GT3, March
1979. Nyby, D.W. (1981). Finite element analysis of soil-
structure interaction. Ph.D. dissertation, Utah State
Duncan, J.M. (1980), P. Byrne, K.S.Wong, and University, Logan, 1981.
P.Mabry. Strength, stress-strain and bulk modulus
parameters for finite element analyses of stresses Ozawa, Y. (1973),and J.M.Duncan. ISBILD: A
and movements in soil masses. Geotechnical computer program for analysis of static stresses and
Engineering Report UCB/GT/80-81. University of movements in embankments. Geotechnical
California, Berkeley, 1980. Engineering Report, University of California,
Berkeley, 1973.
Katona, M.G. (1976), J.B.Forrest, R.J.Odello, and
J.R.Allgood. CANDE—A modern approach for the Sharp, K.D. (1984), F.W.Kiefer, L.R.Anderson, and
structural design and analysis of buried culverts. E.Jones. Soils testing report for applications of finite
Report FHWA-RD-77-5, FHWA, U.S.Department element analysis of FRP pipe performance. Soils
of Transportation, 1976. Testing Report, Buried Structures Laboratory, Utah
State University, Logan, 1984.
Katona, M.G. (1982). Effects of frictional slippage
of soil-structure interfaces of buried culverts. In Sharp, K.D. (1984), L.R.Anderson, A.P.Moser, and
Transportation Research Record 878, TRB, National M.J.Warner. Applications of finite element analysis
Research Council, Washington, D.C., 1982, pp 8-10. of FRP pipe performance. Buried Structures
Laboratory, Utah State University, Logan, 1984.
Knight, G.K. (1983), and A.P.Moser. The structural
response of fiberglass reinforced plastic pipe under Sharp, K.B. (1985), L.R.Anderson, A.P.Moser, and
earth loadings. Buried Structures Laboratory, Utah R.R.Bishop. Finite element analysis applied to the
State University, Logan, 1983. response of buried FRP pipe under various
installation conditions. In Transportation Research
Kulhawy, F.N. (1969), J.M.Duncan, and H.B.Seed.
Finite element analysis of stresses and movements Record 1008, Transportation Research Board,
in embankments during construction. Geotechnical National Research Council, pp 63-72, 1985.
Engineering Report TE-69-4. University of
California, Berkeley, 1969. Wilson, E.L. (1963). Finite element analysis of two-
dimensional structures. Ph.D. dissertation,
Leonards, G.A. (1982), T.H.Wu, and C.H.Juang. University of California, Berkeley 1963.
Predic ting performance of buried conduits. Report
FHWA/IN/JHRP-81/3. FHWA, U.S. Department
of Transportation, 1982.

©2000 CRC Press LLC

You might also like