STREAM-A
1 Proper earthing is not provided in any motors and o.p. pannels , So its very necessary.
2 Cable routing, adderssing and dressing is not properly .
3 Automation work is whole pending yet, all electricals motors are running under manual.
4 In APFC , auto mode is not working .
5 The temperary arrangement of VFD near buffer tank for Extruction screw is in under observation. But
that should be install in proper location.
6 The temperary arrangement of VFD in MCC Panel room for Marut Drum is in under observation. But
that should be install in proper location also.
7 Ceiling fan is required in MCC panel, Not a moveble fan.
8 In RO- plant , earthing is not provided in all equipment and electricals pannels.
9 All blowers for matchuration in Bio compost shed , electrical connection found wrong then in future all motors can be
10 Nuematic exhaust fan is more riquired on top roof of the shed.
STREAM-B
bservation. But