Professional Documents
Culture Documents
1714802 2
1714802 2
9 13
1 3 1 2 3
2 5 5
1 10
2 5 3
25
25
Pb 2mm Lead lining for all walls,frames and doors 4
in accordance to the national regulation . 11
95
10 11 8
400 88 35 35 166 4
7 14
≥ 140
12
≥ 140
18
1.05 Pb 6
1.03 ≥ 140
6
60
6
80
Pb
1.02
30 20 30
134
SID = 115
1 Base plate of unit 2 Shim(s) 3 Floor covering 4 tfix-mark
25
5 Seal all around with hygienic-grad silicon
567
Examination room Concrete filling with reinforcement of grade min. C20/25, with force-fit connection to 6 if there is
170
1.04 7
a risk of tilting; min. thickness 140 mm for 11 below t fix mark
Pb
8 Concrete filling/bonded screed of grade min. C20/25 9 Screed 10 Insulation
1.01 Examination Room 52
In Shipment: Mungo HL-B M10 / 25 expansion bolts with t fix= 25 mm (maximum thickness for fixing parts)
50 80 202 11
Please observe the manufacturer's installation instructions.
Alternative: Mungo HL-B M10 / 95 expansion bolts (with t fix= 95 mm); not in shipment
16 12 Please observe the manufacturer's installation instructions.
185
13 Tiles of raised floor 14 Subconstruction of raised floor / free space
Pb
199
1.08 Solid surface with sufficient load capacity is required, e.g. structural concrete/reinforced concrete.
Control Room The concrete quality in the setup and installation area of the units must be at least C20/25 with a characteristic
Control Room cylinder compressive strength of 2.0 kN/cm².
Other floor types without sufficient load bearing capacity and floor coverings must be removed first.
A floor unevenness of max. 5 mm/m is permitted in the footprint area of all components.
188 Min. thickness of structural concrete slab = 140 mm plus remaining thickness of fixture.
In shipment: Mungo HL-B M10 / 25 expansion bolts
With the heavy duty anchor in shipment only parts with thickness up to 25 mm can be fixed in structural ceiling
concrete. Therefore anchors in shipment are applicable only in case the fixation is realized directly on structural
concrete ceiling.
For other conditions the fixation requires other solutions as exemplarily described:
- Fixation on concrete filling with thickness up to 80 mm → Mungo HL-B M10 / 95 - not in shipment
- Fixation on concrete filling as replacement of raised floor, thickness > 160 mm → Concrete filling need to be
executed as reinforced concrete member with grade C20/25 and this member - if there is a risk of tilting - needs
to be fixed force-fit to the structural concrete ceiling below. Then the heavy duty anchor in shipment can be used.
For this example a structural engineer is mandatory!
The supplied drilling templates must be used.
Please observe the manufacturer's installation instructions.
Mounting table base not to scale Concrete fill-up min. C20/25 1:20 Conrete fill-up min. C20/25 not to scale
800
2500
1397 400 400
668 668
1 613 613 1
500
850
2 2
252
241
550
100
Radiation protection in doors
1700
Milled lead inlay in doors
Room height finished floor to
65
241
252
2 The radiation protection must be well overlapped, especially Location Concrete Suspending Ceiling Suspended required, min.
2 on doors and windows. door leaf
600
EXAMINATION ROOM 325 cm. N.A 250 cm.
850
milled lead door frame
1 1
3
250
1
1 Fixing holes, max. tensile force per anchor 1.5 kN; max. compressive force 4.2 kN
Basics of Planning
2 No. Document No. from Document
2 Alternative fixing holes 3 User side
01 XPB1-200.891.01.01.02 01 / 2019 PG Multix Impact
300 200 300
Mounting Bucky Wall Stand 1:10 1 Recess for cable duct, width depending on cable duct 2 Cable duct 200x60 mm NOTE : ALL DOORS SYMBOLS MEAN CLEAR DOOR OPENING
NOT WALL OPENING
45
1
102
1 Abdelrahman Gamal Karem Zakaria Abdelrahman Gamal
5/1/2024 5/1/2024 5/1/2024
168
311
Edited Checked Released
168
2 2 Siemens Healthcare GmbH
98
Planning department
41
Hartmannstrasse 16
1 1
62.5 343 62.5 D-91052 Erlangen