1714560 CT - 01SP

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Unit arrangement Site Preparations - Floor Electrical Site Preparations - Concrete fill up

Fixpoints Notes on preparations for installation


IK 10*5 cm Fixpoint Components
To Pull Box Contracts for performing and supervising on-site installation preparations should be concluded with technically
350 167 400 competent companies by the customer. The customer is responsible for timely and proper completion and
123 25 CT P.D.B Pb 2mm Lead lining for all walls,frames and doors GR Gantry (incl. REPO contact)
AFFL140 cm. in accordance to the national regulation supervision of all preparations for installation at the construction site in observance of all applicable legal regulations
(e.g. X-ray regulations, radiation protection regulations) and all applicable general recognized rules of technology
Operating console (controlbox, monitor, keyboard)
(e.g. VDE regulations, DIN standards).

10
1.05 Execution and supervision of installation preparations at the construction site and later observance of the standard
1 UPS P.D.B Wireless Access Point
AFFL140 cm. operating conditions are not included in our duties. The customer is responsible for checking the static calculations

Battery
X1 Grounded socket for Wireless Access Point and, where applicable, the air conditioning in the building to be equipped.
Pull Box

128
20*20*10 cm. 42
IM Interventional monitor
1.02

250
UPS

250
MD MEDRAD Injector Room dimensioning
MEDRAD Injector Control panel The indicated room dimensions have to be checked on site. The planning department has to be informed about
UPS Room 10 possible deviations. Otherwise we cannot assume any guarantee for the accurate implementation of the dimensions
1.01 X2 Grounded socket for control unit MEDRAD injector indicated in the planning documents.

10
2 P.V.C Pipes AT Emergency off button with locking mechanism

544
D=4'' UFFL

50
1 67 90 On-off button with pilot lamp Room lighting

25
10 SW Radiation warning lamp Ambient lighting in rooms with diagnostics or with workstations must comply with the respective local and national
1.02 1.01 regulations.
P.V.C Pipes Radiation ready indicator
D=4'' UFFL General requirements like the needed intensity of illumination - adjustable, reproducible, flicker-free or a limitation of
Examination Room

25
P.V.C Pipe AT dazzlings and reflections etc. have to be observed (EN 12464-1, DIN 5035-7).
D=4'' UFFL
Electrical outlet Electrical outlet
aABGD PVC pipe D= 32 mm aABGD Electrical outlet Available cable sets

120
130
180 cm AFFL aABGD
1.04 To Floor duct in control room Display screen workstations
pipe connected to CT PDB
Cable set
For setting up display screen workstations, take account of the guidelines in the Display Screen Workstation
15 m directive as well as any national regulations (e.g. EN ISO 9241-5).
1.03
180 cm AFFL 80 60 100 100 140 30 m
pipe connected to CT PDB 53 30 70 10
1.06 25 25 25 10 * *For the shown installation the selected option has to be used. Safety distances

220
1.07
1.08 FK 20 x10 cm Legend Distances from moving parts of the medical device to walls, furniture and other equipment have to be kept to avoid
Control Room
Control Room X-ray warning lamp injuries by crushing in compliance with local regulations, e.g. a minimum distance of 50 cm according to EN 349.
above door frame

80
pipes routed to gantry cut-out, LxW (i. e. in FK or raised floor) It is the customer's responsibility to ensure the above requirements are followed.
through the CT PDB This is to avoid the risk of injury.
cut-out, Ø in mm (i.e. in suspended ceiling)

10
If safety distances are not maintained appropriate on-site safety measures have to be put in place.
350 188 KB core hole, Ø in mm (minimum inner clearance required) Clear visible markings according to national guidelines, e.g. crushing warning signs, hazard warning
tape, hazard area cordon, safety mats, may be required.
BD floor opening, top view LxW (break-throughs and openings, which delimit the
fireproof area, must be closed on site after the installation is finished).
DD ceiling opening in ceiling above LxW (break-throughs and openings, which
delimite the fireproof area, must be closed on site after the installation is finished).
Concrete Fill-up Dimensions WD wall break WxH (break-throughs and openings, which delimit the Dimensioning
fireproof area, must be closed on site after the installation is finished).
All installation measurements apply to finished wall/floor/ceiling and are to be checked prior to assembling the unit.
110 110 name of a fixpoint or a connection point
SOMATOM go.All - Equipment Legend cm mm
cable fixing point
Weight (kg), Heat dissipation to the air (W)
Access hatch in suspended ceiling not required if the ceiling tiles are easily removable Orientation point = reference point of the Siemens unit for planning and installation
Pos. Description kg W Remark

65
Size and position depending on structural conditions on site.
1.01 Gantry with tablet, remote control, computer and UPS 1306 6800 #1

100
1.02 Patient table Vario RT (1600 mm scannable range) 338 300
switch, installation according to national guidelines

35
35 20 45
1.03 Control unit with TFT monitor, control box, keyboard 9 75 Notes
1.04 Wireless Access Point 3 grounded socket, installation according to national guidelines

245
#1 2250 W in stand-by mode, isocentre at 985 mm 15
grounded socket, switchable, installation according to national guidelines

145
TP telephone socket warning lamp / indicator,
Examination Room Examination Room ceiling mounted, wall mounted
RJ45 network socket
PVC pipe D= 32 mm
70 80 70 UK bottom edge OK top edge
To Floor duct on control room
Radiation protection in doors 220
Electrical outlet bottom edge suspended ceiling OK FFL top edge finished floor
180 cm AFFL aABGD UK ABGD
Milled lead inlay in doors pipe connected to CT PDB
bottom edge bare ceiling OK RFB top edge unfinished floor
The radiation protection must be well overlapped, especially UPS Room UK RHD
on doors and windows. door leaf RHD bare ceiling RFB unfinished floor level

milled lead door frame suspended Ceiling suspended Ceiling ABGD suspended ceiling FFL finished floor level
suspended Ceiling
Suspended Ceiling
aABGD above suspended ceiling AFFL above finished floor level
Examination
Control Room room aD on ceiling / suspended ceiling aFFL on finished floor / raised floor
Examination Room
BRH parapet height UZ downstand beam
CT- P.D.B CT- P.D.B
AFFL140 cm. AFFL140 cm.
FK cable duct WxD (minimum inner clearance required), accessible flush floor trunking system,
moisture-proof, grounded
IK cable trunking WxD, surface mounted

180
Examination
room
BK parapet channel WxD, surface mounted (for power and network sockets, etc.)
On/Off Switchs

80
30
KW cable tray WxD (i. e. in ceiling void)

140
LR ductwork, Ø in mm (minimum inner clearance required)
NOTE : ALL DOORS SYMBOLS MEAN CLEAR DOOR OPENING
NOT WALL OPENING FK 20 x10 cm The installations for cable routing depicted in the drawing need to be reserved for the exclusive
P.V.C Pipes use by SIEMENS Healthineers.
D=4'' UFFL
FK 20/10

Control Room
Cable lead-in and floor mounting - Gantry with Patient table not to scale
180 cm AFFL
pipe connected to CT PDB
Floor requirements: Gantry and patient table
1037 - The floor construction has to be performed solid and free of vibration, e.g. concrete flooring C20/25 to C50/60 corresponding
suspended Ceiling to DIN EN 206-1, according to the maximum values as specified in the text block “Floor and building vibrations”.
912 930 ESD flooring is not required for CT systems and CT options.
4) - NOTE: A solid and vibration-free floor is needed to avoid a negative influence on the vibration characteristic of the gantry. An
Wooden frame
incorrect vibration characteristic of the gantry can cause problems with balancing and image quality.
105 x 85 cm.
1) 1) - Level in the area of the gantry and the table base. Permissible tolerance in levelness max. 10 mm referenced to the length of
the gantry base.
- On-site subconstructions have to fulfil the flooring conditions

510
510

115

180
3)
- It is recommended to test the weight capacity of the concrete or composite flooring by a stress analyst.
X1 X1

TP
RJ45
RJ45
Floor- and building vibrations - Flooring in the area around the contact surfaces of the gantry and the patient table must be removed in the area around

100
the patient table and gantry.

146
Floor- and building vibrations can reduce image quality! 1) 1)

30
Permissable continuous floor vibrations
- Floor mounting, as well as principally every kind of CT system component mounting, must be performed in accordance with
Sources that produce vibrations are, e.g.:
1054 country-specific guidelines in countries prone to earthquakes.
Railroad routes, subways, roads, road works and construction

806
sites, hospital power plants, mines, open-cast minings, quarries - The gantry and the patient table have to be on the same (isocentric) plane.
(explosions), ferry moorings, any other sources of striking FK
20*10 cm 230 - Cables should be routed to the gantry through the cable inlet in the right stand of the gantry.
vibrations. Any transient vibration has to be less than 0.5 m/s² 1) Adjustable feet and drill holes: List of Documents
peak-to-peak in the time domain. The vibrations have to be drilling Ø 17 mm for attaching to

26
measured with a sampling rate of 1000 Hz. floor via adjustable feet; Floor mounting Gantry No. Document No. Document
Transport not to scale
bearing area Ø 54 mm - Not required for system operation. Possible by anchoring/screw connections at the 4 adjustable feet. Only required according Site Preparations
The CT system is not sensitive to common vibrations. If the CT is 01 112332-1714560-01SP
The transport route (doors and hallways) needs sufficient dimensions for the following parts! 2) 2) to the currently valid country guidelines, e.g. in countries prone to earthquakes. Technical details
away from vibrational sources, or the CT is replacing a CT system 2) Two sets of drilling holes:
that to date has not shown image quality problems due to Ø 25 mm (standard), Installation material has to be provided on-site.
vibrations, it is usually not necessary to execute vibrational 1 10 100 Gantry with transport device Ø 25 mm (alternatively) - Subgrade: Basically only concrete flooring/composite flooring; on-site mounting frame
Frequency [Hz]
measurements.

808
756
for mounting the patient table
Transport rollers swiveled out Transport rollers swiveled in - Stands on 4 adjustable feet. Levelling with 4 adjustable feet.
It is the customer's responsibility to contract a qualified specialist. to floor via mounting plate
ca. 2748 x 1631 x 1864* mm ( L x W x H ) ca. 3449 x 1040 x 1864* mm ( L x W x H ) Basics of Planning
The specialist must implement site modifications to meet the specific 3) Standard cable inlet 90 x 160 mm
limits, and to design structural solutions in case of deviations.
Floor mounting patient table No. Document No. from Document
2748
4) Alternative cable inlet 85 x 45 mm - As a rule, floor mounting of the patient table is required by the manufacturer. Add compensating plates (included in delivery
If there are any doubts, the following thresholds have to be verified by measurement: 3449 01 C2-081.891.01.09.02 04.19 PG SOMATOM go.
in Gantry rear volume). Installation material for floor mounting on concrete and a drilling template are included in delivery volume.
In the three spatial directions, acceleration in vibrations at the mounting points of the computer tomograph (Gantry and
250 02 CT00-000.891.04.19.02 03.19 PG Common CT Basic
Patient Handling System PHS) must not exceed the thresholds as described in the above shown diagram. - Subgrade: Basically only concrete flooring / composite flooring ≥ 140 mm; composite flooring up to max. 125 mm strength;
Floating screed with sub-construction only; on-site mounting frame; Access floor with sub-construction only 03 CT00-000.891.03.42.02 10.18 PG Common CT Options
330
- Required concrete thickness: min. 140 mm (when using the delivered HILTI anchors)

Statics not to scale - Required extraction force min. 4.2 kN per fastening point. According to IEC 60601-1, a factor of 4 safety margin is mandatory.
- Positioning and levelling as given on table base.
4 The floor construction has to be performed solid and free of vibration,
3
e.g. concrete flooring C20/25 to C50/60 corresponding to DIN EN 206-1,
according to the maximum values as specified in the textblock Power supply SOMATOM go.All
“Floor and building vibrations”. Mains TN-S 3/N/PE AC 50/60 Hz ± 2Hz Line impedance ≤ 110 mΩ Power consumption
It is recommended to test the weight capacity of the concrete or composite * The transport device with the gantry can be lowered to a ground clearance of 7 mm.
Voltage 400 V ± 10 % On site circuit breaker 100 A System
flooring by a stress analyst. ** The Gantry can be moved through the entrance < 1000 mm, when the transport adapter is partially removed.
Only copper cables are allowed Connection value 69,2 kVA Stand-by ≤ 3 kVA
Fastening the gantry on the floor is possible but only necessary in TIPPING HAZARD ! Transport with the rollers swivelled in is permissible only in narrow passages! Cable cross section is to be determined by national regulations. System off 0 kVA Room height finished floor to
1 2 countries prone to earthquakes or according to local regulations. As soon as the system has passed through narrow passages, the transport rollers Size of connector terminals in Gantry is 25 bis 95 mm². for time up to 4 s 115 kVA
Securing the patient table to the floor is mandatory. have to be swivelled out again. Suspended available Suspended required, min.
PE N L1 L2 L3 Electrical installation according to IEC 60364-7-710, national guidelines must be observed Location Concrete
Total weight of Gantry: 1295 kg Total static load (center of gravity ): Fstat total = 12.95 kN Gantry with transport device 1500 kg, transport device 220 kg. Additional electrical connectivity for the customer in Power supply EXAMINATION ROOM 345 cm. N.A 250 cm.
for CT System Minimum requirement for the on site
The maximum possible floor load (2-point load) per roller may be reached during gantry transport.
Partial load on gantry foot number 1 2 3 4 SIEMENS Customer Power distributor electrical installation
If necessary, cover the transport route with metal sheets to distribute the load. Healthineers
PE
Nominal static load after levelling Fstat nom [kN] 2.66 3.16 4.43 2.70 The door must have a final clearance of 1250 mm if bed entrance to the CT examination room is requested. +
2 3.3 min. 18
Maximum dynamic load (amplitude) during gantry rotation ± 0.3 ± 0.3 ± 0.3 ± 0.3 intern 1m
Fdyn max [kN] PHS Vario1 / RT Weight 570 kg 2574 x 824 x 1517 mm ( L x W x H ) max. 2,5 mm² flexible 16 □ 1.4 13 13 13 21 T1 T2 T3
T3
max. 3.4 Cu 15 80% 20% 5%
Outer diameter gantry foot [mm] 54 54 54 54 250 VAC / 2 A
K2 K3 K1 K1
PHS Vario2 Weight 592 kg 2574 x 824 x 1517 mm ( L x W x H ) 10s 1s 10s
24 VDC / 2 A PA 1.1 14 14 14 22 K K B
AUX 3 VA

1
Floor contact area gantry foot [cm²] 16 16 16 16 12 6 33
18 43
9 10 17
K4 Site Preparations
K1
L1
L2
L3
PE

During gantry installation and leveling, the maximum possible load on one gantry foot can be 7.76 kN (the gantry is 2 3.1 K5 2 T2 K1
Environment intern 1m 11 34
standing on two diagonal feet). Design access floors for a weight capacity of min. 400 kg per slab/plate. During max. 2,5 mm² flexible 5 15 44
18 Technical details
max. 3.2 ~
gantry transport, the load may be higher at certain individual points (3-point load, e.g. due to uneven flooring). All CT components Temperature 18 to 30 °C 250 VAC / 2 A T1
Relative humidity 20 to 75 % 24 VDC / 2 A 15
18
Absolute humidity max. 30 g/m³
6A A1 B1 A1 4 3 A1 A1 B1 F1 E1 Abdelrahman Gamal Karem Zakaria Abdelrahman Gamal
Barometric pressure 800 to 1060 hPa 5 Priority 1
2 1.1 Q1 T3 K5 MODE 1
M 3VA <U T1 T2 K2 K3 ZE + ZA K4 K1 5/1/2024 5/1/2024 5/1/2024
Temperature gradient 6 K/h intern 1m A2 E2
max. 2,5 mm² flexible 4 100A A2 A2 7
17 7 8 9 10 12 13 16 Edited Checked Released
not to scale max. 1.2 -
On-site cooling requirements Transport / storage Temperature -20 to 50 °C 3e
250 VAC / 2 A
Relative humidity 10 to 95 % 24 VDC / 2 A Siemens Healthcare GmbH
Workload CT-system [%] 100 (maximum power) 0 (stand-by) 2 3R Planning department
Absolute humidity max. 30 g/m³
Barometric pressure 700 to 1060 hPa Gantry outlet for Power Distribution System (PDS) Hartmannstrasse 16
Heat dissapation to ambient air 7.1 kW 2.25 kW 34 78 6 21 5 EXAMINA-
Temperature gradient 1 TION D-91052 Erlangen
10° K/h ROOM
Air temperature (air intake) 18 °C to 30 °C Maximum storage period 2 months Radiation ready indicator 2
1 Floating ground contact 250 VAC / 2 A or 24 VDC / 2 A. by customer L
DELTA UNIVERSITY HOSPITAL
max. ± 1 K/min; max. < 6 K/h; If it is not possible to maintain these ranges, an air conditioning system with or without humidifier / dehumidifier L
Temperature gradient (air intake) The need for the installation has to be clarified with the local authorities.
max. ± 4 K/h in 24 h 1 should be installed. By intake of outside air it is recommended to install air filters (Class EU3 to EU4)
International Coastal Rd,
CONTROL CONTROL
ROOM ROOM
for filtering dust particles of > 10 µm (DIN EN 779). Radiation warning indicator IEC 60601-2-44 and CFR 21 Al Hafir WA Al Amal
Humidity (air intake) 20 % to 75 % RE AR Floating ground contact 250 VAC / 2 A or 24 VDC / 2 A. [0.7m] RADIOLOGY
The need for the installation has to be clarified with the local authorities. X20.1-3
Air flow rate (through the Gantry) 1800 m³/h to 2200 m³/h 1) air intake 2) exhaust air PE L1/L2/L3/N
SIEMENS REPO
Door switchlock for blocking radiation 25 to GROUND FLOOR
X22.3
X22.4
X22.7
X22.8
X22.6
X22.2
X22.1
X22.5

Healthineers X20.1-4
Structural room conditions (e.g. windows, large glass areas, building and room thermal insulation, room size and 95 mm² 0m 1m 2m
Room height Floating ground contact 250 VAC / 2 A or 24 VDC / 2 A. CT System Multi Modality
volume...) influences the climatic room conditions for the air-cooled gantry and other air-cooled CT-system
The need for the installation has to be clarified with the local authorities.
components in general. These climatic influences must be taken into account by the Project Manager when Technically required minimum room height 2100 mm (with injector arm: 2300 mm).
dimensioning a new or checking an existing on-site room air condition. Measured from the highest point of the finished floor (with covering) to the lowest point of the ceiling. Project File Revision Page Size Scale
112332 1714560 01 01 of 01 A0 1:50
© Siemens Healthcare GmbH created by Sales CAD

You might also like